Ingersoll Rand System Automation VSD B Box or VSD mA Box MODBUS RTU User Manual

Before installing or starting this unit for the first time, this manual should be studied carefully to obtain a working knowledge of the unit and/or the duties to be performed while operating and maintaining the unit. RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the unit at all times.
More Than Air Answers.
Online answers: http://www.air.irco.com
Ingersoll Rand
System Automation
VSD B Box or VSD mA Box
MODBUS RTU User’s Manual
C.C.N. : 80445000 REV. B DATE: JUNE 2009
2
SECTION 1 – TABLE OF CONTENTS
SECTION 1 – TABLE OF CONTENTS .................................................................................................................... 3
SECTION 2 - INTRODUCTION ................................................................................................................................ 4
SECTION 3 - SAFETY PRECAUTIONS .................................................................................................................. 4
SECTION 4 - MODBUS RTU ................................................................................................................................... 6
MODBUS TABLE(S) ............................................................................................................................................. 6
MODBUS RTU ...................................................................................................................................................... 6 U
COMMUNICATION LINK ...................................................................................................................................... 6
RS485 SERIAL DATA FORMAT ........................................................................................................................... 6
MESSAGE DATA FORMAT ................................................................................................................................. 6
SLAVE RESPONSE TIMEOUT ............................................................................................................................ 8
MESSAGE ANSWER FROM SLAVE TO MASTER .............................................................................................. 8
EXCEPTION RESPONSE .................................................................................................................................... 9
TROUBLESHOOTING ......................................................................................................................................... 9
SECTION 5 - MODBUS TABLE DESCRIPTION ................................................................................................... 10
TABLE ITEM FORMAT ....................................................................................................................................... 10
NAME AND FUNCTION ..................................................................................................................................... 10
CODING ............................................................................................................................................................. 10
MENU REFERENCE .......................................................................................................................................... 11
‘ADV’ ADVISE FUNCTION ................................................................................................................................. 11
‘ADV’ ADVISE FUNCTION SINGLE ITEM FORMAT OPTION ........................................................................ 11
‘CMD’ COMMAND FUNCTION ........................................................................................................................... 13
‘GET’ FUNCTION ............................................................................................................................................... 14
‘SET’ FUNCTION ................................................................................................................................................ 14
DATA CODING DEFINITIONS: .......................................................................................................................... 15
DATA TYPES ...................................................................................................................................................... 15
DATA UNITS ....................................................................................................................................................... 16
SECTION 6 - X-SERIES AIR SYSTEM .................................................................................................................. 18
SMG BOX ........................................................................................................................................................... 19
GENERAL X-SERIES SYSTEM COMPONENTS .............................................................................................. 19
X-SERIES NETWORK ADDRESSES................................................................................................................. 20
COMMUNICATION LINK .................................................................................................................................... 20
MODBUS TIMING............................................................................................................................................... 20
RS485 MODBUS SERIAL DATA FORMAT ........................................................................................................ 20
SECTION 7 – VSD B BOX OR VSD MA BOX MODBUS RTU DEFINITIONS ..................................................... 21
3
SECTION 2 - INTRODUCTION
System MODBUS Gateway (SMG Box) communication is RS485, RTU, Master-Slave configuration. The SMG Box acts as a transparent interface to enable a remote ‘master’ device to be able to communicate with the X-Series Units and th e Intellisys Controllers via the ir485 network ‘slave’ device(s). The MODBUS RTU data construction and formatting for a ‘master’ device is the subject of this document. This information is intended for a systems integrator to facilitate set-up of a ‘master’ device in order to communicate successfully with the X-Series Units and the Intellisys Controllers through a SMG Box.
SECTION 3 - SAFETY PRECAUTIONS
WARNING :
!
WARNING :
WARNING :
!
WARNING :
Before installing or operating the SYSTEM MODBUS GATEWAY (SMG) BOX, take time to carefully read all the instructions contained in this manual, all compressor manuals, and all manuals of any other peripheral devices that may be installed or connected to the unit.
Electricity and compressed air have the potential to cause severe personal injury or property damage.
The operator should use common sense and good working practices while operating and maintaining this system. All applicable codes should be strictly adhered to.
Maintenance must be performed by adequately qualified personnel that are equipped with the proper tools.
INSTALLATION
Installation work must only be carried out by a competent person under qualified supervision.
A fused isolation switch must be fitted between the main power supply and the SYSTEM MODBUS GATEWAY (SMG) BOX.
The SYSTEM MODBUS GATEWAY (SMG) BOX should be mounted in such a location as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times.
If raised platforms are required to provide access to the SYSTEM MODBUS GATEWAY (SMG) BOX, they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides.
Risk of Danger
Risk of Electric Shock
Risk of High Pressure
Consult Manual
OPERATION
The SYSTEM MODBUS GATEWAY (SMG) BOX must only be operated by competent personnel under qualified supervision.
Never remove or tamper with safety devices, guards or insulation materials fitted to the SYSTEM MODBUS GATEWAY (SMG) BOX.
The SYSTEM MODBUS GATEWAY (SMG) BOX must only be operated at the supply voltage and frequency for which it is designed.
When main power is switched on, lethal voltages are present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit.
Do not open access panels or touch electrical components while voltage is applied unless it is necessary for measurements, tests or adjustments. Such work should be carried out only by a qualified electrician equipped with the correct tools and wearing appropriate protection against electrical hazards.
All air compressors and/or other equipment connected to the unit should have a warning sign attached stating “THIS UNIT MAY START WITHOUT WARNING” next to the display panel.
If an air compressor and/or other equipment connected to the unit is to be started remotely, attach two warning signs to the equipment stating “THIS UNIT CAN BE STARTED REMOTELY”. Attach one sign in a prominent location on the outside of the equipment, and the other sign inside the equipment control compartment.
4
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must only be carried out by competent personnel under qualified supervision.
If replacement parts are required, use only genuine parts from the original equipment manufacturer, or an alternative approved source.
Carry out the following operations before opening or removing any access panels or carrying out any work on the SYSTEM MODBUS GATEWAY (SMG) BOX:
i. Isolate the SYSTEM MODBUS
GATEWAY (SMG) BOX from the main electrical power supply. Lock the isolator in the “OFF” position and remove the fuses.
ii. Attach labels to the isolator
switch and to the unit stating “WORK IN PROGRESS - DO NOT APPLY VOLTAGE”. Do not switch on electrical power or attempt to start the SYSTEM MODBUS GATEWAY (SMG) BOX if such a warning label is attached.
Make sure that all instructions concerning operation and maintenance are strictly followed and that the complete unit, with all accessories and safety devices, is kept in good working order.
The accuracy of sensor devices must be checked on a regular basis. They must be calibrated when acceptable tolerances are exceeded. Always ensure any pressure within the compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device.
The SYSTEM MODBUS GATEWAY (SMG) BOX must only be cleaned with a damp cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis.
Do not paint the control faceplate or obscure any indicators, controls, instructions or warnings
5
SECTION 4 - MODBUS RTU
MODBUS TABLE(S)
This document discusses generic MODBUS communications and how to implement the software specific ‘MODBUS Table’ information. MODBUS communication formatting may differ from controller to controller and you may require more than one ‘MODBUS Table’.
Always check the software variant identification and version number for a controller or unit with the variant and version of the ‘MODBUS Table’ supplied. In some instances the information contained in a ‘MODBUS Table’ may not be ap plicable to a controller or unit installed with the same software variant but a different version number.
MODBUS RTU
MODBUS RTU (Remote Terminal Unit) is a master-slave type protocol. An X-Series Automation System Controller or Intellisys Controller functions as the slave device. Information requests or commands are communicated from master to slave only through a System Modbus Gateway Box (SMG). The SMG Box will always respond to communications from a remote master device in accordance with the MODBUS RTU protocol standard.
The MODBUS protocol is used to communicate with personal computers (PC), Programmable Logic Controllers (PLC’s), or Distributed Control Systems (DCS) over the Network port. The SMG Box only responds to three MODBUS commands, Read Holding Register 03 (03 Hex), Preset Single Register 06 (06 Hex), and Preset Multip le Registers command 16 (10 Hex) (See Modicon MODBUS Protocol Reference Guide, PI-MBUS-300 Rev. J, for more details on MODBUS).
COMMUNICATION LINK
MODBUS is implemented using a two-wire RS485 industry standard communications link operating in master-slave mode.
Polarity of the two RS485 wires (L1+ and L2-) is important; reversal will disrupt communications.
RS485 SERIAL DATA FORMAT
The RS485 MODBUS port is a 2-wire operating with an asynchronous serial data format: 8 data bits / no parity / 1 stop - (8,N, 1) - transmitted at 9600 baud.
MESSAGE DATA FORMAT
The bytes of the MODBUS RTU message must be sent in one message package. The RTU protocol allows for a maximum pause of 1.5 byte-times between 2 consecutive bytes of a message.
A pause longer than 1.5 byte-times will render the message invalid and it will be ignored.
Message data format is dependant on function and will consist of a combination of the following elements:
1) Destination address (slave network address)
2) Function Code
3) Data start address (slave register start address)
4) Number of registers, number of bytes of data
5) Message data
6) CRC checksum
Message Destination Address
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
The ‘destination address’ must be correct for the ‘slave’ controller device for which the message is inten ded. An address can be from 01Hex to EFHex. The SMG Box is transparent and addresses must be for the destination ‘slave’ controller or unit. Each controller or unit must be set with a unique address.
6
Message Function Codes
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
The message function code defines the required data processing operation of the slave controller. Although several types of message function codes are defined by the MODBUS standard, only the message function code types working directl y with registers are implemented on controller units:
03H Read Holding Register(s) – Get (Get Data) or Adv (Advise Data) (X-Series) and Read (Intellisys) 06H Preset Single Register - Write (Intellisys Only) 10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series only)
Any other message function code type will result in an EXCEPTION response.
Message Data Start Address
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
The message data start address (16bit word) designates the initial register address location in the contr oller from which the data is processed. Start address information is contained in the ‘MODBUS Table’.
Note: high-byte transmitted first followed by low-byte.
Message Data
The message data content depends on the message function code type.
03H Read Holding Register(s) – Get (Get Data), Adv (Advise Data) (X-Series) or Read (Intellisys)
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
Slave address + function code ’03 Hex’ + start address of registers in slave memory + 16bit integer value that determines the size (in 16bit ‘word’ registers) of the message data being requested (00 02 = 2 registers of data). This is the number of 16bit registers to read. A maximum of 32 registers can be read at one time. This information is contained in the ‘MODBUS Table’.
06H Preset Single Register - Write (Intellisys Only)
Slave
Address
Function
Code
Start
Address
DATA
byte 0 byte 1
CRC Check
Sum
01 06 00 6F 00 5F FE BC
Slave address + function code ’06 Hex’ + start address of register(s) in slave memory to be set then the ‘data’ itself. This information is contained in the ‘MODBUS Table’.
10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series only)
Slave
Address
Function
Code
Start
Address
Number of
Registers To
Be Set
Number of
Bytes of
Data
DATA
1st Register
byte 0 byte 1
DATA 2nd Register byte 2 byte 3
CRC Check
Sum
01 10 40 18 00 02 04 00 00 1B 5F 88 0E
Slave address + function code ’10 Hex’ + start address of register(s) in slave memory to be set + 16bit (integer valve of the number of registers to be set) + 8bit ‘byte’ (integer value for the number of following data bytes) then the ‘data’ itself. This information is contained in the ‘MODBUS Table’.
Note: A function ’10 Hex’ Set message also requires an additional byte defining the number of ‘data’ bytes in the data message. This will always be the number of ‘registers’ multiplied by 2 as each ‘data’ register consists of 2 bytes (if number of ‘data’ registers = 2 then number of ‘data’ bytes = 4).
7
Message CRC Checksum
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
The CRC (Cyclical Redundancy Check) is a check-sum generated by means of ‘A001H polynomial’. The CRC is two bytes containing a 16-bit binary value (word). The CRC value is calculated by the transmitting device that
appends the CRC to the end of the message. The receiving device recalculates the CRC value prior to processing of a received message and compares the result to the actual CRC value appended to the message. If the two values do n ot match the message is regarded as invalid. The CRC is initiated by first preloading a 16bit register to all 1's (FFFF Hex). Then a process begins of applying each consecutive 8bit byte of the message to the register contents us ing an exclusive ‘OR’ calculation. The result is shifted one bit in the direction of the least significant bit (LSB), with the most significant bit (MSB) set at ‘0’. The LSB is then examined; if ‘1’ the register content is applied to the polynomial value ‘A001’ Hex (101 0 0000 0000 0001) using an exclusive ‘OR’ calculation - if ‘0’ no exclusive OR takes place. This process is repeated until eight ‘bit’ shifts have been performed. After the eighth bit shift, the next 8bit message byte is applied to the register contents using an exclusive ‘OR’ calculation. The bit shift and re-calculation process is then repeated again. When all message bytes have been processed the final content of the 16bit register is the message CRC value.
Only the 8bits of ‘data’ in each message character is used for generating the CRC; start, stop and parity bits are ignored. Note: When the 16bit CRC value is appended to a message, the low order byte must be transmitted first followed by the high order byte. An incorrect or byte reversed check sum will render the message invalid and it will be ignored.
SLAVE RESPONSE TIMEOUT
A slave controller may not answer immediately. Ensure the ‘slave timeout’ setting of the ‘master’ device is set to a value no less than 500ms. If the ‘slave’ device fails to receive a valid message due to a communication disruption, parity error, CRC error or other reasons, no response is given and the master must process a timeout condition in this instance. If the ‘slave’ receives a valid message that cannot be processed an exception response will be returned.
MESSAGE ANSWER FROM SLAVE TO MASTER
The format of the ‘slave’ controller answer is similar to the original master request format; the message data content depends on the message function code type.
The ‘address’ and ‘code’ of the slave answer is identical to the original request message; the address is the ‘slave’ device address and the ‘code’ is a repeat of received function code type from the master. The remainder of the message is dependant on the requested function code type. The CRC checksum is re-calculated for the answer message character s using the specified CRC process.
03Hex – Get: read from register (or ‘Adv’ Advise)
Slave
Address
Function
Code
Start
Address
Number of
Bytes of
Data
DATA
1st Register
byte 0 byte 1
DATA 2nd Register byte 2 byte 3
CRC Check
Sum
01 03 40 18 04 00 00 1B 5F BE 61
1) slave address 1byte
2) function code 1byte
3) bytes of data 1byte (number of bytes in ‘data’ answer)
4) data (high byte of each register transmitted first)
5) CRC checksum 2bytes (low byte first followed by high byte)
06Hex - Preset Single Register: write to single register
Slave Address Function Code Start Address
DATA
byte 0 byte 1
CRC Check Sum
01 06 00 6F 00 5F FE BC
1) slave address 1byte
2) function code 1byte
3) bytes of data 1byte (number of bytes in ‘data’ answer)
4) data (high byte of each register transmitted first)
5) CRC checksum 2bytes (low byte first followed by high byte)
8
10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series only)
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 10 40 18 00 02 D4 0F
1) slave address 1byte
2) function code 1byte
3) number of registers set 2 bytes
4) CRC checksum 2 Bytes (low byte first followed by high byte)
EXCEPTION RESPONSE
If the ‘slave’ device receives a request that cannot be processed an ‘exception response’ is given. An exception response message consists of the following elements:
1) Slave Network Address (1 byte): Slave address identification
2) Function Code (1 byte): In a normal response, the slave repeats the function code of the original master request. All function codes have an MSB (most significant bit) of 0 (values are all below 80 hexadecimal). In an exception response, the slave sets the MSB of the function ‘code’ to 1. This makes the ‘code’ value 80 Hex greater than the received ‘code’ value from the master.
3) Data (1 byte): The ‘data’ response will contain a ‘1 byte’ value exception code.
4) CRC Checksum (2 byte).
CRC Check SumSlave Address Function Code Error Code
01 90 04 4D C3
Exception Codes:
01H Illegal Function Code
The requested ‘code’ function is not supported.
02H Illegal Data Address
The requested ‘data start address’ is not supported.
03H Illegal Data Value
The requested ‘data’ value is not supported.
04H Function Error
The slave cannot execute the request or the request type is inhibited.
TROUBLESHOOTING
Problem: No ‘slave’ response or corrupt MODBUS message Solution: Check that the ‘slave’ controller is set for the anticipated slave address
Check that all ‘slave’ controllers are set with a unique system address Check that the controller is set for MODBUS RTU mode (if applicable) Check that the ‘master’ is operating in MODBUS RTU mode Check that the ‘master’ baud rate, parity bit and number of s t op bits are correct Check that the ‘master ‘response timeout is set for a minimum of 500ms Check that the ‘master’ is implementing the specified CRC check sum process
Check RS485 wiring polarity and security of connections
Problem: Last character of MODBUS message is corrupted Solution: Add a delay of 2ms after last character received before releasing RTS signal
Problem: The MODBUS master message is reflected in the slave answer Solution: Inhibit RX/TX echo on ‘master’ device communications port
9
SECTION 5 - MODBUS TABLE DESCRIPTION
A ‘MODBUS table’ describes the “items” used to access information in the memory registers of different types of controller, or similar controllers using different application software variants or versions. The MODBUS Table will contain the valid message items (“Name”) together with the Function Code (Function), Register Start Address (“Register Address”), Register Size (“Register Length”) and a definition for coding and decoding the item data (“Coding”). A ‘MODBUS Table’ order form, detailing the required order information, can be found on the last page of this document.
TABLE ITEM FORMAT
Each ‘item’ of a ‘MODBUS Table’ will define the massage format to read or set the information contained in the slave controller register(s):-
Name
Descriptive ‘name’ or ‘item tag’ for the data item. The ‘Name’ is not used in code or message formatting and serves only as a reference for the defined item.
Function
The Hex code required that instructs the slave (Intellisys controller) to perform a GET, ADV (Advise), CMD (command) or SET function.
Register Address Register Length Coding Menu
The slave controller register start address for the defined processing function. The number of registers to be processed. How to construct or interpret the data elements of a message. Controller menu item reference.
Note: see “MODBUS RTU” for a detailed description of ‘Function’, ‘Register Address’ and ‘Register Length’ formats.
NAME AND FUNCTION
The ‘name’ for each table item will always start with 3 characters that describe the function type:
Adv Advise Function (03Hex) – same format as a Get function, see ‘Advise Function’. Get Read from register (03Hex) Set Write to registe r (10Hex) Cmd Command (10Hex) – same format as a Set function; will instruct the slave to perform a defined action or
process
CODING
Item coding definitions specify the ‘number of data bytes’ and the ‘data conversion type’. In some instances a data message may contain multiple sets of data items; an ‘Advise’ message for example. In this instance the ‘start location of data’ within the message is also specified to enable extraction of the required data item from the entire message data.
Number of data bytes:
This specifies the length of the item data in bytes (6 = 6 bytes (3 registers) of data)
Start location of data bytes:
Number of Data Bytes to Follow
DATA
1st Register byte
0 byte 1
DATA 2nd Register byte 2 byte 3
DATA
3rd Register byte
4 byte 5
CRC Check SumSlave Address Function Code
01 03 06 09 00 00 65 00 A8 30 4D
If a data message consists of more than one set of data items (multiple item data message) the ‘start location’ specifies where the first byte of the data associated with in item begins. If, for example, a 6 byte (3 register) answer is returned that consists of three different ‘2 byte’ item data values, a ‘start location of data bytes’ = ‘2’ indicates that the item data starts with the 3rd byte (byte 2) of the data message. The 1st byte of a data message is regarded as byte 0(zero). In this instance the ‘number of data bytes’ will be ‘2’ indicating that the data associated with the item is 2 bytes of data in length. A ‘start location’ of byte ‘2’ and register length of ‘1’ (register = 2 bytes) means the data is contained in the 3rd and 4th bytes of the data message. If no ‘start location’ is specified then data associated with the item will start with the first byte (byte 0) of the message data.
Data Conversion Type:
This specifies how to interpret the data; refer to the ‘Data Conversion Type’ list in the Modbus Table. For example: If the ‘Data Conversion Type’ = CODED, STATUS then the decimal integer value of the data has a defined meaning; refer to the ‘STATUS’ Coded data list in the ‘MODBUS Table’ for definitions. If the ‘Data Conversion Type’ = PSI then the decimal integer value of the data is ‘pressure’ in ‘psi’ units.
10
MENU REFERENCE
The menu structure of a controller has menu pages that contain a number of menu page ‘items’.
example menu and items For example: menu pages P00, P01, P02 > P’n’. Menu page P00 is the normal running list of display items that can be accessed and viewed on the controller displ ay without
access code. These items are ‘read only’ and consist of status, hours run and other general control or monitoring value (s). Menu pages other than P00 are setup and configuration items that require an ‘access code’ when accessing the items on
the controller display. Each menu page has a list of items that are referenced ‘1, 2, 3 > ‘n’.
a b c
P01
For example, a menu reference of P01.02 “AB” refers to menu item ‘2’ of menu page P01. Each menu page item reference also has a two or three alphanumeric character item identification that is displayed by the
controller. With a menu reference the controller manual can be examined to determine the exact function, definition, scope and limits for the specified item value.
Items that do not have a ‘Menu’ reference are general controller status or menu page P00 items.
‘ADV’ ADVISE FUNCTION
The ‘Advise’ function is a special type of ‘Get’ function. Each ‘Advise’ function item has an equivale nt ‘Get’ function; both functions will provide a similar result.
Controllers on a Multi485 network will routinely broadcast key value and status specific data to all other controllers on the network. This information is used, for example, by a system management unit for systems monitoring and control functions. A SMG Box will automatically capture, store and continuously update these information items for each controller on the network. Adv are Routine network broadcasts that occur every 2 seconds. Th transmission of this data consumes no network bandwidth. (The maximum recommended request rate is 1 request every 2 seconds.)
This facility provides a method of retrieving ‘Adv’ data items directly from the SMG Box resulting in a faster response time for information requests from a master. The method also has the advantage of reducing the amount of data traffic on the Multi485 network enabling system management controllers to perform there functions without potential communication delays. For this reason MODBUS ‘Adv’ functions are preferable to ‘Get’ functions when implemented on a Multi485 network that consists of a system management controller with multiple machine controllers.
‘ADV’ ADVISE FUNCTION – SINGLE ITEM FORMAT OPTION
Controllers or units on a Multi485 network routinely broadcast general status and key per formance information. The SMG Box will capture and store each ‘Broadcast’ detected. The Gateway ‘Broadcast’ registers will always contain the latest ‘broadcast’ information for each controller or unit on the Multi485 network. When a Modbus ‘Adv’ request is made the SMG Box will respond immediately with information from it’s own ‘Broadcast’ registers for the unit addr ess specified. This function reduces network activity and enables a faster Modbus response to commonly requested data.
A standard ‘Advise’ function defined in the ‘MODBUS Table’ will show the entire ‘broadcast’ being returned as a response. The table will define for each ‘name’ item where in the returned data message the actual requ ested data can be found. The ‘master’ must then extract the required data from the returned data message. This method is very efficient as the master can extract all ‘broadcast’ data from the single returned data message without the need to perform multiple requests for each individual data item contained in a single slave controller ‘broadcast’ message.
01.02 AB
11
Some ‘master’ devices may not be equipped with the necessary data message memory to handle a large message of many bytes or have the ability to extract multiple data items from a single data message item. In this instance an alternativ e ‘Advise’ function request method can be implemented.If the ‘Advise’ items of a ‘MODBUS Table’ are examined it will be seen that the ‘Register Address’ for each individual ‘Advise’ item contained in a single slave controller ‘broadcast’ message will have the same start address (Register Address). If the entire ‘broadcast’ data message is 7 registers (14 bytes) in length and only the 2nd register (2 bytes) of item data is required, it is possible to specify a ‘Register Address’ that is 2 bytes higher (skip the first 2 bytes of the broadcast data message) with a ‘Register Length’ that is consistent with the required item data length. This will instruct the MODBUS Gateway to extract the 2 bytes of required item data from the entire broadcast data message and only return the required 2 bytes of data as a response. Using this method an ‘Advise’ fu nction can be handled by a ‘master’ in exactly the same way as a ‘Get’ function.
For Example: (AdvDeliveryPressure): The ‘broadcast’ of an example slave controller may be 6 bytes of data (3 registers) in length starting at register address
location ‘F000’ Hex. The 1st byte (byte 0) is 8bits coded status, the 2nd byte (byte 1) is 8bits status flags which together form a single 16bit status register (1st register). The 3rd and 4th bytes (byte 2 and byte 3) are a single16bit register (2nd register) containing a ‘delivery pressure’ value. The 5th and 6th b ytes (byte 4 and byte 5) are a single 16bit register (3rd register) containing a ‘delivery temperature’ value. From an example ‘MODBUS Table’ it may be seen that the ‘Register Address’ for all four of these separate ‘Adv’ items is ‘F000 Hex’ (the start address of the entire ‘Broadcast’ message that contains the data specified).
An entire ‘Broadcast’ message may, for example, contain 3 registers (6 bytes) of data. For a particular item the ‘Modbus Table’ may show the ‘start address’ for the entire broadcast to be ‘F000’ with a length of 3 registers (6 bytes). The Modbus Table will indicate that the required data is 2 bytes long (number of data bytes) starting at the 2nd byte of data in the entire broadcast (start location of data bytes).
Name AdvDeliveryPressure Modbus Function 03 Modbus Register Address F000 (start address of entire Broadcast message) Modbus Register Length 0003 (length of entire Broadcast message) Coding Number of data bytes = 2 (length of AdvDeliveryPressure data)
Start location of data bytes = 2 (the 2 data bytes of the AdvDeliveryPressure data item start at byte 2 in the Broadcast message = bytes 2 and 3 of the message) Data Conversion Type = PSI
Master Request Message “01 03 F000 00 03 36CB” (36CB = CRC check sum) Slave Answer Message “01 03 06 09 00 00 65 00 A8 304D” (304D = CRC) Coding = PSI ‘00 65’Hex = 101 decimal = 101 psi
Register addresses shown are examples only
Status Register
Delivery
Pressure
Delivery
Temperature
Slave Address Function Code
Number of Data Bytes to Follow
DATA
1st Register byte
0 byte 1
DATA 2nd Register byte 2 byte 3
DATA
3rd Register byte
4 byte 5
CRC Check Sum
01 03 06 09 00 00 65 00 A8 30 4D
F000 F001 F002
Message Data
12
If only the ‘delivery pressure’ (AdvDeliveryPressure) data value is required a new ‘Advise’ req uest message format can be constructed from the Modbus Table definition:
Name AdvDeliveryPressure Modbus Function 03 Modbus Register Address F001 (start at the second regi ster, byte 2, of the Broadcast) Modbus Register Length 0001 (only return one register, 2 bytes, of data)
Using the new ‘Advise’ message format the SMG Box will return only the 2nd Broadcast message register (2 bytes) containing the ‘delivery pressure’ data value.
Master Request Message “01 03 F001 0001 E6CA” (E6CA = CRC check sum) Slave Answer Message “01 03 02 00 65 786F” (786F = CRC check sum) Coding = PSI ’00 6 5’Hex = 101 decimal = 101 psi
Status Register
Delivery
Pressure
Delivery
Temperature
Modbus Register Address F000 Modbus Register Length 0003
Slave Address Function Code
Number of Data Bytes to Follow
DATA
1st Register byte
0 byte 1
01 03 06 09 00 00 65 00 A8 30 4D
DATA 2nd Register byte 2 byte 3
DATA
3rd Register byte
4 byte 5
CRC Check Sum
F000 F001 F002
Number of Data Bytes to Follow
Modbus Register Address F001 Modbus Register Length 0001
Slave Address Function Code
01 03 02 00 65 78 6F
It is only possible to manipulate a Modbus message format using ‘registers’ (1 register = 2 bytes = 1 word = 16bits); it is not possible to manipulate addresses or register lengths to a single byte of data. At least one register (2 bytes) of data must be specified even if only one byte of information is required. The ‘master’ must extract the required byte of data from the returned message.
The data type (the definition of the returned data) may be different when using an ‘Advise’ function than it is when using a ‘Get’ function for the same information. The ‘delivery pressure’ returned by an ‘Advise’ function will be 2 bytes in length and will represent pressure as an integer value in ‘psi’ units (PSI). The ‘delivery pressure’ returned by a ‘Get’ function may, for example, be 4 bytes (2 registers) in length and represent a 32bit signed integer value in miliBar units (mBAR). Always check the item ‘Coding’ definition to establish the data definition type.
Register addresses shown are examples only
‘CMD’ COMMAND FUNCTION
A ‘Command’ function will instruct the ‘slave’ controller or unit to execute a pre-defined action or process. With a command type message the content of the ‘message data’ from the ‘master’ must always be the same value as the ‘lower byte’ of the command register address. For example: if the command item ‘Register Address’ = 3302 then the ‘data’ value must be ’00 02’ Hex.
Slave Address Function Code Start Address
Number of
Registers To Be
Set
Number of Bytes
of Data
DATA
DATA 2nd Register byte 2 byte 3
CRC Check Sum
CRC Check Sum
01 10 33 02 00 01 02 00 02 25 70
It is the act of setting the specified register in the ‘slave’ controller with the defined ‘data’ value that initiates the action or process. An incorrect ‘data’ value will result in an exception response. If the ‘command’ is accepted the ‘slave’ will answer with a normal ‘Set’ register response. If the slave is unable to execute the command it will give a code ‘04’ exception response.
13
Example: Using a command function item to set the specified item register to the correct value, the ‘slave’ controller is instructed to perform the defined action or process. In the case of a ‘CmdStart’ item, for example, the ‘slave’ controller is instructed to start the machine. The implementation of a ‘Cmd’ function message by the ‘master’ is identical to a ‘Set’ function message; both operations use function code ‘10 Hex’ to write data to a slave controller register.
Name CmdStart Modbus Function 10 Modbus Register Address 3300 Modbus Register Length 0001 Coding Number of data bytes = 1
CmdStart (to slave at address ‘01’ Hex) Master Command Message “01 10 3300 0001 02 0000 A553” (A553 = CRC check sum)
Slave Answer Message “01 10 3300 0001 0E8D” if start command executed or “01 90 04 4D C3” exception
response if not executed, ‘90’ = repeat of ‘10’ function code with MSB set to ‘1’ and ‘04’ = exception error code.
Register addresses shown are examples only
Names that begin with CMD are Non-routine. This data must be written to the device. (The maximum recommended
request rate is 2 requests per second up to 32 words per request.)
‘GET’ FUNCTION
Using the MODBUS Table a read data (Get) function message can be constructed: Name GetDeliveryPressure Modbus
Function 03 Modbus Register Address 4006 Modbus Register Length 0002 Coding Number of data bytes = 4
Data Conversion Type = mBAR GetDeliveryPressure (request to slave at address ‘01’ Hex) Master Request Message “01 03 400 6 0002 31CA” (31CA = CRC check sum)
Slave Answer Message “01 03 04 00 00 1B 58 F139” (F139 = CRC check sum) Coding = mBAR 1B 58Hex = 7000 decimal = 7000 miliBar (7.0 bar)
Register addresses shown are examples only Note: Names that begin with Get are Non-routine. This data must be requested from the device. (The maximum recommended request rate is 2 requests per second up to 32 words per request.)
‘SET’ FUNCTION
Using the MODBUS Table a write data (Set) function message can be constructed: Name SetLoadPressure Modbus
Function 10 Modbus Register Address 4018 Modbus Register Length 0002 Coding Number of data bytes = 4
SetLoadPressure (to slave at address ‘01’ Hex) Master Write Message “01 10 4018 0002 04 0000 1B58 C9CC” (C9CC = CRC)
Slave Answer Message “01 10 4018 0002 D40F” (D40F = CRC check sum) Coding = mBAR 0000 1B58Hex = 7000 decimal = 7000 miliBar (7.0 bar)
Register addresses shown are examples only Names that begin with Set are Non-routine. This data must be written to the device. (The maximum recommended
request rate is 2 requests per second up to 32 words per request.)
Data Conversion Type = mBAR
14
DATA CODING DEFINITIONS:
Definitions for ‘data units’ and ‘data conversion types’ are listed for each ‘item’ in the “MODBUS Table” document. All ‘data’ values are ‘whole’ numbers (integers); decimal places are not permitted in MODBUS data messages. All ‘data’ values are unsigned (always positive) unless otherwise stated. Values specified as ‘SIGNED’ in the MODBUS
Table can be negative in accordance to the standard data conventio n for ‘sign ed’ number values.
DATA TYPES
Each standard definition will start with a “key” word that defines the data type:-
The following are selected examples; data types not included below are detaile d in individual ‘Modbus Tables’
Type Description
Coded a decimal value that has a defined definition; see the ‘Coded’ lists in the ‘MODBUS Table’ for value definitions Value a ‘whole’ number or value in the specified units Pressure a ‘whole’ number defining a pressure in the specified units Temperature a ‘whole’ number defining a temperature in the specified units Time a ‘whole’ number defining a time period in the specified units Electrical a ‘whole’ number defining a volt, amp, power, or speed value in the specified units Clock Clock values are relevant to real time clock functions; for example pressure schedules. These ‘whole number’ unsigned values are ‘packaged’ multiple values and must be interpreted as follows.
Clock Data Type Coding
HH_MM 1) Divide the value by 60 = Hours (0 to 23)
2) The remainder (modulus) = Minutes (0 to 59)
Example for a value of ‘1050’ Hours = 1050 / 60 = 17.5 = 17 Hours Minutes = remainder = 30 = 30 Minutes Time = 17:30 (5:30pm)
D_HH_MM 1) Divide the value by 10000 = Day (1 = Monday, 7 = Sunday)
2) Divide the remainder (modulus) by 60 = Hours (0 to 23)
3) The remainder (modulus) = Minutes
Example for a value of ‘31050’ Day = 31050 / 10000 = 3.105 = 3 = Wednesday Hours = = remainder / 60 = 17.5 = 17 Hours Minutes = remainder = 30 = 30 Minutes Day/Time = Wednesday 17:30 (5:30pm)
YYYY_DD_MO 1) Divide the value by 10000 = Year
2) Divide the remainder (modulus) by 100 = Day (1 to 31)
3) The remainder (modulus) = Month (1 to 12)
Example for a value of ‘20051605’ Year = 20051605 / 10000 = 2005.1605 = Year 2005 Day = remainder / 100 = 16.05 = Day 16 Month = remainder = 5 = Month 5 Date = 16th May 2005
15
DATA UNITS
The ‘MODBUS Table’ will define the ‘data units’ for each item. Data unit definitions are specified in the ‘M ODBUS Table’ as a separate list; for example:
The following are selected examples; data types not included below are detailed in the ‘Modbus Tables’
Value The engineering units will differ dependant on unit set-up or item definition.
PSI BAR FAH CEL HRS % BOOLEAN BINARY
The value must be interpreted in terms of each ‘bit’ as a set of sixteen Boolean (0 or 1) flags. These values are compressor related or I/O Box Input related. For compressor related items the least significant bit (Bit 0) represents compressor 1. For unit inputs the least significant bit (Bit 0) generally represents input 1.
The number is the value in the specified engineering units
Pressure in ‘psi’ Pressure in ‘Bar’ Temperature in oF Temperature in oC Hours Percentage 0 to 100 The number will be 0 or greater than 0, (Boolean: 0 = False, 1 = True) The number represents a 16bit (two byte) binary value of 16bit flags.
16 bit Register
1st Byte (byte 0) 2nd Byte (byte 1)
15141312111098 76543210
Bit
MSB
The example illustrates the bit pattern for a value of ’00 81 Hex’. This value is interpr eted as a ‘true’ condition with respect to the item definition for compressors 1 and 8. If the ‘item’ definition is ‘Compressors Running’ then com pressors 1 and 8 are in a ‘running’ condition.
00000000 10000001
Compressor 8 Compressor 1
LSB
16
The example illustrates the bit pattern for a value of "1A 04 C2 01" Hex. A reference to ‘Bit 18’ equates to bit ‘2’ of byte ‘1’ in the answer data message. If the ‘bit’ is ‘1’ then the condition is ‘TRUE’.
2nd Register1st Register
1st Byte (byte 0) 2nd Byte (byte 1) 3rd Byte (byte 2) 4th Byte (byte 3)
3130292827262524 2322212019181716 15141312111098 76543210
Bit
00011010 00000100 11000010 00000000
MSB
BIT ‘n’
Note: The LSB (least significant bit) of a register or byte is regarded as Bit 0(zero)
A Boolean (true/false) can be established from examining the specified ‘bit’ of the 16bit register. If the item specifies ‘Bit 4’ then the 4th bit should be examined:
LSB
16 bit Register
1st Byte (byte 0) 2nd Byte (by te 1)
15141312111098 76543210
Bit
MSB
00011010 10010001
LSB
AND
00000000 00010000
EQUALS
00000000 00010000
= 16 Decimal (Condition is TRUE) The 4th bit of a register can be extracted by ‘masking’ the register content with “10 Hex”; if the resulting value is greater than
0(zero) then the condition is ‘True’, if the result is 0(zero) then the condition is ‘False’.
Decimal Places:
Numbers with decimal places (eg 20.55) are not permissible in MODBUS data transfer – all numbers must be integer ‘whole’ numbers. To provide ‘decimal place’ accuracy some data values are multiplied by 10, 100 or 1000 and transmitted as a ‘whole’ number (integer). In this instance the ‘Data Units’ will specify that the number represe nts a value to one or more decimal places.
For example: PERCENT_DP2 = Percent to 2 decimal places
“2055” divided by 100 = 20.55%
If the ‘Data Units’ specifies “to 1 decimal place”, divide the number by 10 to convert to the correct engineering units. If the ‘Data Units’ specifies “to 2 decimal places”, divide the number by 100; if 3 decimal places divide by 1000.
17
SECTION 6 - X-SERIES AIR SYSTEM
Note: example only; systems will differ from installation to installation
18
SMG BOX
For Remote Monitoring/Control of X-Series Units and Boxes. The SMG Box provides a RS485 Modbus connection to the X8I Automation System. A system will only contain one SMG Box.
GENERAL X-SERIES SYSTEM COMPONENTS
The following Components can be monitored by the SMG Box. X8I Series Controller or X12I Series Controller: Automation System Unit
Monitors and controls the air compressors, all general system and air compressor related information is governed and available from this unit. A system will only contain one X-Series Automation System controller.
EX Box: Extension to the X-Series Unit For connection to remote compressor(s) or other specialized compressor integration. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple EX Boxes.
I/O Box: Monitoring/Control of Auxiliary Equipment and/or Sensors For monitoring and/or control of auxiliary compressed air equipment (for exam ple: dryer, auto drain, filtration differential, isolation valves, cooling water towers/pumps, ventilation) or sensors (for example: pressure, pressure differential, dewpoint, air flow, temperature). A system may contain multiple IO Boxes.
VSD Box: Extension to the X-Series Unit For connection to variable speed compressor(s) or other specialized compressor integration. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple VSD Boxes.
CX Box: Extension to the X-Series Unit For connection to non-Ingersoll Rand air compressors that are not equipped with any accessible means of remote connectivity. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple CX Boxes.
DX Box: Extension to the X-Series Unit For connection to two fixed speed online/offline air compressors to be seen as one compressor by the X8I or X12I. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple DX Boxes.
ir-485 Gateway / irV-485 Gateway
For connection to all Ingersoll Rand Intellisys based compressors. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple Gateways.
ir-485 Direct
For connection to all Ingersoll Rand R Series (S3) based compressors. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple R series compressors.
19
X-SERIES NETWORK ADDRESSES
UNIT X8I or X12I EX, VSD B / mA / V, CX, DX, ir485 / irV485, S3
(As It Relates To The Compressor Number Assigned) Compressor 1 1 (01) Compressor 2 2 (02) Compressor 3 3 (03) Compressor 4 4 (04) Compressor 5 5 (05) Compressor 6 6 (06) Compressor 7 7 (07) Compressor 8 8 (08) Compressor 9 9 (09) X12I ONLY Compressor 10 10 (0A) X12I ONLY Compressor 11 11 (0B) X12I ONLY Compressor 12 12 (0C) X12I ONLY
I/O
I/O Box 1 105(69) I/O Box 2 112(70) I/O Box 3 106(6A) X12I ONLY I/O Box 4 107(6B) X12I ONLY I/O Box 5 108(6C) X12I ONLY I/O Box 6 109(6D) X12I ONLY I/O Box 7 110(6E) X12I ONLY I/O Box 8 111(6F) X12I ONLY I/O Box 9 113(71) X12I ONLY I/O Box 10 114(72) X12I ONLY I/O Box 11 115(73) X12I ONLY I/O Box 12 116(74) X12I ONLY
Note: I/O Unit 2 address (70Hex) is intentionally out of sequence; this is not a print error.
DECIMAL (HEX) ADDRESS NOTES
101(65)
COMMUNICATION LINK
To Interface with a X-Series product that is equipped with a Multi485 enabled network port, or to interface with multiple X­Series products operating on a single Multi485 system network, a SMG Box unit is required. The SMG Box forms the interface between the Multi485 protocol and MODBUS RTU master/slave communications link.
SMG Box connectivity is implemented using a two-wire RS485 industry standard commun ications link operating in point-to­point, master-slave mode. In use the SMG Box is transparent and each X-Series system unit is accessible using individual system device addresses.
Polarity of the two MODBUS RS485 wires (L1+ or ‘A’ and L2- or ‘B’) is important; reversal will inhibit communications
and result in error.
MODBUS TIMING
The SMG will handle ONE (1) MODBUS request at a time from the customer’s port. The maximum recommended request rate is 2 requests per second. When a MODBUS request is received for any device connected to the XI Automation System, that request will be forwarded to the device between sequencer broadcasts and the response from the device will then be relayed back to the customer’s port. If a second MODBUS command is sent before the first command has been responded to, the second command will be ignored.
RS485 MODBUS SERIAL DATA FORMAT
The SMG supports only the RTU transmission mode. The user must configure their serial port communication parameters (baud rate, parity mode, etc.) during configuration to match those of the SMG Box. The SMG Box port operates with an asynchronous serial data format:
SMG Communication Parameters: Data Bits: 8 Parity: None Stop Bit: 1 Baud Rate: 9600
8-N-1-9600
20
SECTION 7 – VSD B BOX OR VSD MA BOX MODBUS RTU
DEFINITIONS
Name : AdvStatusRegister Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0003 Coding : Number of data bytes = 1 Data Conversion Type = CODED,STATUS Conversion table for CODED,STATUS can be found at the end of this document
Name : AdvStatusFlags Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0003 Coding : Number of data bytes = 1 : Start location of data bytes = 1
Name : AdvDeliveryPressure Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0003 Coding : Number of data bytes = 2 : Start location of data bytes = 2 Data Units = PSI
Name : AdvDeliveryAirTemperature Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0003 Coding : Number of data bytes = 2 : Start location of data bytes = 4 Data Units = FAH
21
Name : GetSoftwareVersionIdString Modbus Function : 03 Modbus Register Address : 3400 Modbus Register Length : 0003 Coding : Number of data bytes = 6 Data Conversion Type = STRING
Name : GetSoftwareVersionRevString Modbus Function : 03 Modbus Register Address : 3403 Modbus Register Length : 0003 Coding : Number of data bytes = 6 Data Conversion Type = STRING
Name : CmdStart Modbus Function : 10 Modbus Register Address : 3300 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : CmdStop Modbus Function : 10 Modbus Register Address : 3301 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : CmdLoad Modbus Function : 10 Modbus Register Address : 3304 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : CmdUnload Modbus Function : 10 Modbus Register Address : 3305 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : CmdReset Modbus Function : 10 Modbus Register Address : 3306 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : CmdClearLog Modbus Function : 10 Modbus Register Address : 3307 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : GetStatus Modbus Function : 03 Modbus Register Address : 3406 Modbus Register Length : 0003 Coding : Number of data bytes = 6 Data Conversion Type = CODED,STATUS Conversion table for CODED,STATUS can be found at the end of this document
22
Name : GetAnalogInput1 Modbus Function : 03 Modbus Register Address : 3100 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = ADSTEPS
Name : GetAnalogInput2 Modbus Function : 03 Modbus Register Address : 3101 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = ADSTEPS
Name : GetAnalogInput3 Modbus Function : 03 Modbus Register Address : 3102 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = ADSTEPS
Name : GetAnalogOutput1 Modbus Function : 03 Modbus Register Address : 310C Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = ADSTEPS
Name : GetDigitalInputs Modbus Function : 03 Modbus Register Address : 310E Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = BINARY bitvalue = 0 = digital input INACTIVE bitvalue = 1 = digital input ACTIVE bit = Name (Config, Delay in ms) 0 = EMERGENCY_STOP (Normal Closed, 0) 1 = READY_RUN (Pulsed, 0) 2 = SPARE_1 (Normal Open, 0) 3 = SPEED_DETECT (Normal Open, 100) 4 = SPARE_2 (Normal Open, 200) 5 = LOAD_MAINTENANCE (Pulsed, 0) 6 = AUXILIARY_ALARM (Pulsed, 0) 7 = AUXILIARY_TRIP (Normal Closed, 100)
Name : GetDigitalInputsConfiguration Modbus Function : 03 Modbus Register Address : 310F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = BINARY bitvalue = 0 = digital input NO bitvalue = 1 = digital input NC bit = Name 0 = EMERGENCY_STOP 1 = READY_RUN 2 = SPARE_1 3 = SPEED_DETECT 4 = SPARE_2 5 = LOAD_MAINTENANCE 6 = AUXILIARY_ALARM 7 = AUXILIARY_TRIP
23
Name : GetDigitalOutputs Modbus Function : 03 Modbus Register Address : 3110 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = BINARY bitvalue = 0 = digital output OFF bitvalue = 1 = digital output ON bit = Name 0 = RELAY_SEQUENCE 1 = RELAY_SPARE1 2 = RELAY_SPARE2 3 = RELAY_LOAD 4 = RELAY_FUNCTION_1 5 = RELAY_FUNCTION_2
Name : GetDeliveryPressure Modbus Function : 03 Modbus Register Address : 4004 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
Name : GetInternalPressure Modbus Function : 03 Modbus Register Address : 4006 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
Name : GetDiffPressure Modbus Function : 03 Modbus Register Address : 4008 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR
Name : GetRunningHours Modbus Function : 03 Modbus Register Address : 400A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.01 'H1' Menu = P10.06 'H1'
Name : GetLoadUnloadPressMinDiff Modbus Function : 03 Modbus Register Address : 400E Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
Name : SetLoadUnloadPressMinDiff Modbus Function : 10 Modbus Register Address : 400E Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
24
Name : GetParUnloadPressure Modbus Function : 03 Modbus Register Address : 4010 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P01.01 'Pu'
Name : SetParUnloadPressure Modbus Function : 10 Modbus Register Address : 4010 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P01.01 'Pu'
Name : GetParLoadPressure Modbus Function : 03 Modbus Register Address : 4012 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P01.03 'PL'
Name : SetParLoadPressure Modbus Function : 10 Modbus Register Address : 4012 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P01.03 'PL'
Name : GetPressureUnitsSel Modbus Function : 03 Modbus Register Address : 4014 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = CODED,P_UNIT Conversion table for CODED,P_UNIT can be found at the end of this document Data Units = LONG_VAL Menu = P03.01 'P>'
Name : SetPressureUnitsSel Modbus Function : 10 Modbus Register Address : 4014 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = CODED,P_UNIT Conversion table for CODED,P_UNIT can be found at the end of this document Data Units = LONG_VAL Menu = P03.01 'P>'
Name : GetFaultErrorLog1Fault Modbus Function : 03 Modbus Register Address : 4017 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.02 '01'
25
Name : GetFaultErrorLog1RunningHours Modbus Function : 03 Modbus Register Address : 4018 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.02 '01'
Name : GetFaultErrorLog2Fault Modbus Function : 03 Modbus Register Address : 401B Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.03 '02'
Name : GetFaultErrorLog2RunningHours Modbus Function : 03 Modbus Register Address : 401C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.03 '02'
Name : GetFaultErrorLog3Fault Modbus Function : 03 Modbus Register Address : 401F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.04 '03'
Name : GetFaultErrorLog3RunningHours Modbus Function : 03 Modbus Register Address : 4020 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.04 '03'
Name : GetFaultErrorLog4Fault Modbus Function : 03 Modbus Register Address : 4023 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.05 '04'
Name : GetFaultErrorLog4RunningHours Modbus Function : 03 Modbus Register Address : 4024 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.05 '04'
26
Name : GetFaultErrorLog5Fault Modbus Function : 03 Modbus Register Address : 4027 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.06 '05'
Name : GetFaultErrorLog5RunningHours Modbus Function : 03 Modbus Register Address : 4028 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.06 '05'
Name : GetFaultErrorLog6Fault Modbus Function : 03 Modbus Register Address : 402B Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.07 '06'
Name : GetFaultErrorLog6RunningHours Modbus Function : 03 Modbus Register Address : 402C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.07 '06'
Name : GetFaultErrorLog7Fault Modbus Function : 03 Modbus Register Address : 402F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.08 '07'
Name : GetFaultErrorLog7RunningHours Modbus Function : 03 Modbus Register Address : 4030 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.08 '07'
Name : GetFaultErrorLog8Fault Modbus Function : 03 Modbus Register Address : 4033 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.09 '08'
27
Name : GetFaultErrorLog8RunningHours Modbus Function : 03 Modbus Register Address : 4034 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.09 '08'
Name : GetFaultErrorLog9Fault Modbus Function : 03 Modbus Register Address : 4037 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.10 '09'
Name : GetFaultErrorLog9RunningHours Modbus Function : 03 Modbus Register Address : 4038 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.10 '09'
Name : GetFaultErrorLog10Fault Modbus Function : 03 Modbus Register Address : 403B Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.11 '10'
Name : GetFaultErrorLog10RunningHours Modbus Function : 03 Modbus Register Address : 403C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.11 '10'
Name : GetFaultErrorLog11Fault Modbus Function : 03 Modbus Register Address : 403F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.12 '11'
Name : GetFaultErrorLog11RunningHours Modbus Function : 03 Modbus Register Address : 4040 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.12 '11'
28
Name : GetFaultErrorLog12Fault Modbus Function : 03 Modbus Register Address : 4043 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.13 '12'
Name : GetFaultErrorLog12RunningHours Modbus Function : 03 Modbus Register Address : 4044 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.13 '12'
Name : GetFaultErrorLog13Fault Modbus Function : 03 Modbus Register Address : 4047 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.14 '13'
Name : GetFaultErrorLog13RunningHours Modbus Function : 03 Modbus Register Address : 4048 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.14 '13'
Name : GetFaultErrorLog14Fault Modbus Function : 03 Modbus Register Address : 404B Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.15 '14'
Name : GetFaultErrorLog14RunningHours Modbus Function : 03 Modbus Register Address : 404C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.15 '14'
Name : GetFaultErrorLog15Fault Modbus Function : 03 Modbus Register Address : 404F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = P02.16 '15'
29
Name : GetFaultErrorLog15RunningHours Modbus Function : 03 Modbus Register Address : 4050 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HRS Menu = P02.16 '15'
Name : GetDeliveryPressureMaxLevel Modbus Function : 03 Modbus Register Address : 4052 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P03.05 'Dm'
Name : SetDeliveryPressureMaxLevel Modbus Function : 10 Modbus Register Address : 4052 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P03.05 'Dm'
Name : GetInternalPressureMaxLevel Modbus Function : 03 Modbus Register Address : 4054 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P03.06 'Im'
Name : SetInternalPressureMaxLevel Modbus Function : 10 Modbus Register Address : 4054 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P03.06 'Im'
Name : GetSelectedLoadEnable Modbus Function : 03 Modbus Register Address : 407A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetSelectedLoadEnable Modbus Function : 10 Modbus Register Address : 407A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetSelectedStartEnable Modbus Function : 03 Modbus Register Address : 407C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
30
Name : SetSelectedStartEnable Modbus Function : 10 Modbus Register Address : 407C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetConfigDigOut5 Modbus Function : 03 Modbus Register Address : 4080 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetConfigDigOut5 Modbus Function : 10 Modbus Register Address : 4080 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetConfigDigOut6 Modbus Function : 03 Modbus Register Address : 4082 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetConfigDigOut6 Modbus Function : 10 Modbus Register Address : 4082 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetIndicationFieldFunction Modbus Function : 03 Modbus Register Address : 4084 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetIndicationFieldFunction Modbus Function : 10 Modbus Register Address : 4084 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetAnalogOutputFunction Modbus Function : 03 Modbus Register Address : 4086 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.04 'Ao'
Name : SetAnalogOutputFunction Modbus Function : 10 Modbus Register Address : 4086 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.04 'Ao'
31
Name : GetFrequencyHighLimit Modbus Function : 03 Modbus Register Address : 4088 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HZ Menu = P08.02 'FH'
Name : SetFrequencyHighLimit Modbus Function : 10 Modbus Register Address : 4088 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HZ Menu = P08.02 'FH'
Name : GetFrequencyLowLimit Modbus Function : 03 Modbus Register Address : 408A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HZ Menu = P08.01 'FL'
Name : SetFrequencyLowLimit Modbus Function : 10 Modbus Register Address : 408A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = HZ Menu = P08.01 'FL'
Name : GetVsdSpeedPercentActual Modbus Function : 03 Modbus Register Address : 408C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT_DP2
Name : GetVsdControlPercentActual Modbus Function : 03 Modbus Register Address : 408E Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT_DP2 Menu = P08.03 'C>'
Name : GetDeliveryPressureOffset Modbus Function : 03 Modbus Register Address : 4090 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR Menu = P04.01 'do'
Name : SetDeliveryPressureOffset Modbus Function : 10 Modbus Register Address : 4090 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR Menu = P04.01 'do'
32
Name : GetDeliveryPressureRange Modbus Function : 03 Modbus Register Address : 4092 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P04.02 'dr'
Name : SetDeliveryPressureRange Modbus Function : 10 Modbus Register Address : 4092 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P04.02 'dr'
Name : GetInternalPressureOffset Modbus Function : 03 Modbus Register Address : 4094 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR Menu = P04.03 'Io'
Name : SetInternalPressureOffset Modbus Function : 10 Modbus Register Address : 4094 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR Menu = P04.03 'Io'
Name : GetInternalPressureRange Modbus Function : 03 Modbus Register Address : 4096 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P04.04 'Ir'
Name : SetInternalPressureRange Modbus Function : 10 Modbus Register Address : 4096 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P04.04 'Ir'
Name : GetErrorLogReset Modbus Function : 03 Modbus Register Address : 4098 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.05 'Er'
33
Name : SetErrorLogReset Modbus Function : 10 Modbus Register Address : 4098 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.05 'Er'
Name : GetInternalPressSensorUsed Modbus Function : 03 Modbus Register Address : 409A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetInternalPressSensorUsed Modbus Function : 10 Modbus Register Address : 409A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetVoltagePressSensorUsed Modbus Function : 03 Modbus Register Address : 409C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetVoltagePressSensorUsed Modbus Function : 10 Modbus Register Address : 409C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetDeliveryPressSensRange Modbus Function : 03 Modbus Register Address : 409E Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
Name : SetDeliveryPressSensRange Modbus Function : 10 Modbus Register Address : 409E Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
Name : GetInternalPressSensRange Modbus Function : 03 Modbus Register Address : 40A0 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
Name : SetInternalPressSensRange Modbus Function : 10 Modbus Register Address : 40A0 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
34
Name : GetDeliveryPressureOut Modbus Function : 03 Modbus Register Address : 40A4 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
Name : GetInternalPressureOut Modbus Function : 03 Modbus Register Address : 40A6 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR
Name : GetParSetpointPressure Modbus Function : 03 Modbus Register Address : 40A8 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P01.02 'Pt'
Name : SetParSetpointPressure Modbus Function : 10 Modbus Register Address : 40A8 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P01.02 'Pt'
Name : GetDeliveryOutputOffset Modbus Function : 03 Modbus Register Address : 40AA Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR Menu = P05.01 'do'
Name : SetDeliveryOutputOffset Modbus Function : 10 Modbus Register Address : 40AA Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR Menu = P05.01 'do'
Name : GetDeliveryOutputRange Modbus Function : 03 Modbus Register Address : 40AC Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P05.02 'dr'
Name : SetDeliveryOutputRange Modbus Function : 10 Modbus Register Address : 40AC Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P05.02 'dr'
35
Name : GetInternalOutputOffset Modbus Function : 03 Modbus Register Address : 40AE Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR Menu = P05.03 'Io'
Name : SetInternalOutputOffset Modbus Function : 10 Modbus Register Address : 40AE Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = SIGNED,NUMERIC Data Units = mBAR Menu = P05.03 'Io'
Name : GetInternalOutputRange Modbus Function : 03 Modbus Register Address : 40B0 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P05.04 'Ir'
Name : SetInternalOutputRange Modbus Function : 10 Modbus Register Address : 40B0 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P05.04 'Ir'
Name : GetAnalogueInputConfig Modbus Function : 03 Modbus Register Address : 40B2 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P03.04 'IC'
Name : SetAnalogueInputConfig Modbus Function : 10 Modbus Register Address : 40B2 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P03.04 'IC'
Name : GetConfigDigIn7 Modbus Function : 03 Modbus Register Address : 40B4 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.01 'D7'
36
Name : SetConfigDigIn7 Modbus Function : 10 Modbus Register Address : 40B4 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.01 'D7'
Name : GetConfigDigIn8 Modbus Function : 03 Modbus Register Address : 40B6 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.02 'D8'
Name : SetConfigDigIn8 Modbus Function : 10 Modbus Register Address : 40B6 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.02 'D8'
Name : GetHoldSeqControl Modbus Function : 03 Modbus Register Address : 40BA Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.03 'SQ'
Name : SetHoldSeqControl Modbus Function : 10 Modbus Register Address : 40BA Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P10.03 'SQ'
Name : GetVsdBoxType Modbus Function : 03 Modbus Register Address : 40C8 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = PCT.01 'CT'
Name : SetVsdBoxType Modbus Function : 10 Modbus Register Address : 40C8 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = PCT.01 'CT'
37
Name : GetFaultRegister Modbus Function : 03 Modbus Register Address : 3409 Modbus Register Length : 0003 Coding : Number of data bytes = 6 Data Units = BINARY bitvalue = 0 = fault INACTIVE bitvalue = 1 = fault ACTIVE bit = fault 40 = (E0010) Trip - Emergency Stop 41 = (E0020) Trip - Oil Filter 42 = (E0040) Trip - Air/Oil Separator High DP 43 = (E0080) Trip - Motor Overload 44 = (E0115) Trip - Delivery Pressure Sensor 45 = (E0119) Trip - Delivery Pressure High 46 = (E0125) Trip - Delivery Temperature Sensor 47 = (E0129) Trip - Delivery Temperature High 32 = (E0131) Trip - Internal Rotation Pressure Check 33 = (E0135) Trip - Internal Pressure Sensor 34 = (E0139) Trip - Internal Pressure High 35 = (E0506) Trip - Analog Input Short Circuit On Expansion Module Ai4-1 36 = (E0507) Trip - Analog Input Short Circuit On Expansion Module Ai4-2 37 = (E0508) Trip - Digital Input Short Circuit On Expansion Module Di8R4-1 38 = (E0509) Trip - Digital Input Short Circuit On Expansion Module Di8R4-2 39 = (E0809) Trip - Differential Pressure High 24 = (E0814) Trip - Blowdown Timeout 25 = (E0821) Trip - Short Circuit 26 = (E0836) Trip - PLL Unlocked Trip 27 = (E0840) Trip - Communication Error With Expansion Module 1 28 = (E0841) Trip - Communication Error With Expansion Module 2 29 = (E0842) Trip - Communication Error With Expansion Module 3 30 = (E0843) Trip - Communication Error With Expansion Module 4 31 = (E0844) Trip - Communication Error With Expansion Module 5 16 = (E0845) Trip - Communication Error With Expansion Module 6 17 = (E0846) Trip - Delivery Pressure Sensor Problem With Selected Model 18 = (E0856) Trip - Internal Pressure Sensor Problem With Selected Model 19 = (E5000) Trip - Parameter Table Index Corrupt 20 = (E5001) Trip - IO-Config Table Corrupt 21 = (A2070) Alarm - Auxiliary trip 22 = (A2118) Alarm - Delivery Pressure High 23 = (A2128) Alarm - Delivery Temperature High 8 = (A2138) Alarm - Internal Pressure High 9 = (A2808) Alarm - Differential Pressure High 10 = (A2816) Alarm - Power Failure 11 = (R3123) Run Inhibit - Delivery Temperature Low 12 = (R3137) Run Inhibit - Internal Pressure High 13 = (A4804) Service Alarm - Service Due 14 = ­ 15 = ­ 0 = ­ 1 = ­ 2 = ­ 3 = ­ 4 = ­ 5 = ­ 6 = ­ 7 = -
38
Table 1. Conversion table for 'Data Conversion Type = CODED,STATUS'
1 : Shutdown 2 : Initialising 3 : Ready to Start 4 : Standby 5 : Standby 6 : Standby 7 : Running 8 : Not responding 9 : On Load 10 : Operating state
Table 2. Conversion table for 'Data Conversion Type = CODED,P_UNIT'
0 : Bar 1 : PSI 2 : kPa
Table 3. Conversion table for 'Data Conversion Type = CODED,ERROR'
0 : No Error 10 : (E0010) Trip - Emergency Stop 20 : (E0020) Trip - Oil Filter 40 : (E0040) Trip - Air/Oil Separator High DP 80 : (E0080) Trip - Motor Overload 115 : (E0115) Trip - Delivery Pressure Sensor 119 : (E0119) Trip - Delivery Pressure High 125 : (E0125) Trip - Delivery Temperature Sensor 129 : (E0129) Trip - Delivery Temperature High 131 : (E0131) Trip - Internal Rotation Pressure Check 135 : (E0135) Trip - Internal Pressure Sensor 139 : (E0139) Trip - Internal Pressure High 809 : (E0809) Trip - Differential Pressure High 814 : (E0814) Trip - Blowdown Timeout 821 : (E0821) Trip – Short Circuit 836 : (E0836) Trip - PLL Unlocked Trip 846 : (E0846) Trip - Delivery Pressure Sensor Problem With Selected Model 856 : (E0856) Trip - Internal Pressure Sensor Problem With Selected Model 2070 : (A2070) Alarm - Auxiliary trip 2118 : (A2118) Alarm - Delivery Pressure High 2128 : (A2128) Alarm - Delivery Temperature High 2138 : (A2138) Alarm - Internal Pressure High 2808 : (A2808) Alarm - Differential Pressure High 2816 : (A2816) Alarm - Power Failure 3123 : (R3123) Run Inhibit - Delivery Temperature Low 3137 : (R3137) Run Inhibit - Internal Pressure High 4804 : (A4804) Service Alarm - Service Due 5000 : (E5000) Trip - Parameter Table Index Corrupt 5001 : (E5001) Trip - IO-config Table Corrupt 506 : (E0506) Trip - Analogue Input Short Circuit On Expansion Module Ai4-1 507 : (E0507) Trip - Analogue Input Short Circuit On Expansion Module Ai4-2 508 : (E0508) Trip - Digital Input Short Circuit On Expansion Module Di8R4-1 509 : (E0509) Trip - Digital Input Short Circuit On Expansion Module Di8R4-2 840 : (E0840) Trip - Communication Error With Expansion Module 1 841 : (E0841) Trip - Communication Error With Expansion Module 2 842 : (E0842) Trip - Communication Error With Expansion Module 3 843 : (E0843) Trip - Communication Error With Expansion Module 4 844 : (E0844) Trip - Communication Error With Expansion Module 5 845 : (E0845) Trip - Communication Error With Expansion Module 6
39
Data Conversion Type
STRING : String of ASCII characters (1 byte represents 1 ASCII character) SIGNED, NUMERIC : Value is signed numeric
Data Units
mBAR : Pressure in milliBar HRS : Time in Hours UCHAR_VAL : Value unsigned byte (8bit) LONG_VAL : Value signed long (32bit) ULONG_VAL : Value unsigned long (32bit) BINARY : Value bitwise represented PERCENT_DP2 : Percentage to 2 decimal places ADSTEPS : AD-steps HZ : Frequency in Hertz PSI : Pressure in PSI FAH : Temperature in Fahrenheit
40
Loading...