DANGERWILL cause DEATH, SEVERE INJURY or substantial
•
WARNING CAN cause DEATH, SEVERE INJURY or substantial
•
CAUTIONWILL or CAN cause MINOR INJURY or property
•
GENERAL SAFETY PRECAUTIONS ____________________
DANGERINTAKE AIR. Can contain carbon monoxide or other
•
• WARNING HAZARDOUS VOLTAGE. Can cause serious injury
•
CAUTIONRISK OF BURSTING. Use only suitable air handling
property damage.
property damage.
damage.
contaminants. Will cause serious injury or death.
Ingersoll-Rand air compressors are not designed,
intended or approved for breathing air. Compressed
air should not be used for breathing air applications
unless treated in accordance with all applicable
codes and regulations.
or death. Disconnect power and bleed pressure
from the tank before servicing. Lockout/Tagout
machine. Compressor must be connected to
properly grounded circuit. See grounding
instructions in manual. Do not operate compressor
in wet conditions. Store indoors.
MOVING PARTS. Can cause serious injury. Do not
operate with guards removed. Machine may start
automatically. Disconnect power before servicing.
Lockout/Tagout machine.
HOT SURFACES. Can cause serious injury. Do not
touch. Allow to cool before servicing. Do not touch
hot compressor or tubing.
HIGH PRESSURE AIR. Bypassing, modifying or
removing safety/relief valves can cause serious
injury or death. Do not bypass, modify or remove
safety/relief valves. Do not direct air stream at body.
Rusted tanks can cause explosion and severe injury
or death. Drain tank daily or after each use. Drain
valve located at bottom of tank.
parts acceptable for pressure of not less than the
maximum allowable working pressure of the
machine.
This manual provides safe and reliable instructions for the
installation, operation and maintenance of your Ingersoll-Rand air
compressor. Carefully read this manual before attempting to
operate or perform any maintenance. If you are uncertain about any
of the instructions or procedures provided in this manual, contact
Ingersoll-Rand. We recommend you retain this manual, and all
publications provided with your air compressor, in a location which
is accessible to all personnel who operate and service your
compressed air equipment.
Ingersoll-Rand’s standard two-stage lubricated air compressors are
single-acting, air-cooled machines. Typical compressors are
furnished as compact, self-contained, air receiver tank mounted
units that are automatically regulated and driven by an electric
motor or gasoline engine. An air-cooled aftercooler, low oil level
shutdown switch and automatic drain valve are among the optional
accessories that can be furnished. Bare compressor pumps and
baseplate-mounted units are also available.
These compressors may be used for a variety of compressed air
application up to 250 PSIG (17.5 kg/cm²). Application of these
compressors as either a primary or supplementary source of air is
virtually unlimited in industrial plants, service stations and auto
repair shops. Supplementary service includes such uses as
furnishing air at pressure not carried in regular shop lines, air at
isolated locations, and standby service for air when larger
compressors are shut down.
TWO-STAGE OPERATION_____________________________
Two-stage compressors consist of one or two first-stage cylinders
with the same bore size and one second-stage cylinder with a
smaller bore size.
The basic principle of operation is as follows: On the suction stroke
of the first-stage piston(s), air at atmospheric pressure enters the
cylinders through the inlet filter(s) and then the inlet valves located
in the head. On the compression stroke of the first-stage piston(s),
the air is compressed to an intermediate pressure and discharged
through the discharge valves(s) into common manifold(s). From the
manifold(s) the air passes through the intercooler tubes, where the
heat of first-stage compression is removed. On the suction stroke of
the second-stage piston this cooled air enters the second-stage
cylinder through the inlet valve. The compression stroke of the
second-stage piston compresses the air to the final discharge
pressure and forces it out through the discharge valve into the
receiver tank or system. If cooling of the discharge air is required,
an air-cooled aftercooler should be installed between the
compressor discharge and the receiver tank or system.
For maintaining the receiver tank or system air pressure within
predetermined limits, the compressor may be operated with
automatic start & stop control or constant speed control regulation.
The type of regulation used depends upon the application.
ADDITIONAL REFERENCES___________________________
Unless otherwise stated, dimensions, weights and measurements
are provided in standard U.S. measure followed in parentheses by
the metric conversion. Any torque values given are stated in inch or
foot pounds followed by the Newton-meter equivalent in
parentheses. Electrical characteristics are given in
voltage-phase-hertz.
RECEIPT & INSPECTION
Ensure adequate lifting equipment is available for unloading and
moving the unit to the installation site.
NOTELifting equipment must be properly rated for the
• CAUTIONLift the unit by the shipping skid only. Do not use
•
CAUTION! Do not work on or walk under the unit while it is
Before signing the delivery receipt, inspect for damage and missing
parts. If damage or missing parts are apparent, make the
appropriate notation on the delivery receipt, then sign the receipt.
Immediately contact the carrier for an inspection.
All material must be held in the receiving location for the carrier’s
inspection.
Delivery receipts that have been signed without a notation of
damage or missing parts are considered to be delivered “clear.”
Subsequent claims are then considered to be concealed damage
claims. Settle damage claims directly with the transportation
company.
If you discover damage after receiving the unit (concealed damage),
the carrier must be notified within 15 days of receipt and an
inspection must be requested by telephone with confirmation in
writing. On concealed damage claims, the burden of establishing
that the unit was damaged in transit reverts back to the claimant.
Read the unit nameplate to verify it is the model ordered, and read
the motor nameplate to verify it is compatible with your electrical
conditions. Make sure electrical enclosures and components are
appropriate for the installation environment.
weight of the unit.
the motor lifting eye to lift the entire unit. The motor
lifting eye is for removing the motor from the unit
only.
suspended.
INSTALLATION
SELECTING A LOCATION_____________________________
ELECTRIC MOTOR UNITS. For most electric motor units, select a
relatively clean and dry well-lighted indoor area with plenty of space
for proper ventilation, cooling air flow and accessibility. Provide
1,000 cubic feet of fresh air per 5 horsepower. Locate the unit at
least 15 inches (38 cm) from walls, and make sure the main power
supply is clearly identified and accessible.
Unless the electrical components of the unit are specially protected
for outdoor use, do not install an electric motor unit outdoors or in
an area that will expose the electrical components to rain, snow or
sources of appreciable moisture.
WARNING FOR UNITS EQUIPPED
WITH ELECTRIC DRAIN VALVE
WARNING The electric drain valve incorporates arcing or
•
GASOLINE ENGINE UNITS. For gasoline engine units, keep the
engine at least 3 feet (1 m) away from building walls and other
equipment. Install the unit in a location with plenty of space for
proper ventilation, cooling air flow and accessibility. Do not install or
operate a gasoline engine unit in a confined area.
AMBIENT TEMPERATURE CONSIDERATIONS. Ideal operating
temperatures are between 32°F and 100°F (0°C and 37.8°C). If
temperatures consistently drop below 32°F (0°C), install the
compressor in a heated area. If this is not possible, you must
protect safety/relief valves and drain valves from freezing. If
temperatures are consistently below 40°F (4.4°C), consider
installing an external crankcase heater kit, especially if the
compressor has difficulty starting.
•
CAUTIONNever operate the compressor in temperatures
HUMID AREAS. In frequently humid areas, moisture may form in
the pump and produce sludge in the lubricant, causing running parts
to wear out prematurely. Excessive moisture is especially likely to
occur if the unit is located in an unheated area that is subject to
large temperature changes.
Two signs of excessive humidity are external condensation on the
pump when it cools down and a “milky” appearance in petroleum
lubricant.
You may be able to prevent moisture from forming in the pump by
increasing ventilation, operating for longer intervals or installing an
external crankcase heater kit.
NOISE CONSIDERATIONS. Consult local officials for information
regarding acceptable noise levels in your area. To reduce excessive
noise, use vibration isolator pads or intake silencers, relocate the
unit or construct total enclosures or baffle walls.
sparking parts, such as snap switches, receptacles
and the like that tend to produce arcs or sparks
and, therefore, when located in a garage, the
compressor should be in a room or enclosure
provided for the purpose, or the electric drain
valve should be 18 inches (457 mm) or more above
the floor.
WARNING Remove the unit from the skid before mounting.
•
ELECTRIC MOTOR UNITS. Bolt the unit to a firm, level foundation
(such as a concrete floor). Do not bolt uneven feet tightly to the
foundation, as this will cause excessive stress on the receiver tank.
Use metal shims under the “short” feet if necessary.
GASOLINE ENGINE UNITS. Bolt the unit to a firm, level
foundation. Do not bolt uneven feet tightly to the foundation, as this
will cause excessive stress on the receiver tank. Use metal shims
under the “short” feet if necessary. Gasoline engine units mounted
on truck beds must be fastened securely without applying excessive
stress on the receiver tank. We recommend installing a vibration
isolator kit with gasoline engine models.
INSTALLING REMOTE AIR INLET PIPING _______________
• CAUTIONDo not operate the unit without air inlet filtration.
If the air around the unit is relatively free of dirt, install the air inlet
filter at the inlet connection at the pump. If the air is dirty, pipe the
filter to a source of clean air. Use PVC plastic tubes for remote inlet
piping. Do not use black pipe or galvanized pipe, as these promote
sweating and rust. Consider installing an in-line type filter for ease
of cleaning and replacement. Make the line as short and direct as
possible and as large, or larger, than the diameter of the inlet
connection on the pump. Do not install piping with a diameter lower
than that of the pump intake.
Increase the pipe diameter one size for every 10 feet (3 m) of length
or every 90° bend. Make sure the piping is adequately braced.
If you pipe the filter outdoors, cover it with a hood to prevent the
entrance of rain or snow.
Heavy duty filter elements and filtration equipment are available for
fine airborne dust, such as cement and rock dust.
Typical Remote Air Inlet Piping.
HOOD
ELBOW
Direct to compressor
air intake (if distance
is less than 6 feet)
INTAKE HOSE
SUPPORT
PIPE
SUPPORT
TEE
HOSE
FITTING
BUSHINGS
DRAIN VALVE
AIR INLET
FILTER
OUTSIDE
WALL
INSTALLING DISCHARGE PIPING______________________
WARNING Do not use plastic pipe, soldered copper fittings,
•
• CAUTION! If you will be using synthetic compressor lubricant,
SUITABLE
Viton®, Teflon®, Epoxy (Glass Filled), Oil Resistant Alkyd, Fluorosilicone,
Fluorocarbon, Polysulfide, 2-Component Urethane, Nylon, Delrin®,
Celcon®, High Nitrile Rubber (Buna N. NBR more than 36% Acrylonitrile),
Polyurethane, Polyethylene, Epichlorohydrin, Polyacrylate, Melamine,
Polypropylene, Baked Phenolics, Epoxy, Modified Alkyds
(® indicates trademark of DuPont Corporation)
rubber hose, or lead-tin soldered joints anywhere in
the compressed air system.
all downstream piping material and system
components must be compatible. Refer to the
following material compatibility list. If there are
incompatible materials present in your system, or if
there are materials not included in the list, contact
Ingersoll-Rand for recommendations.
SYNTHETIC COMPRESSOR LUBRICANT
MATERIAL COMPATIBILITY LIST
NOTEAll compressed air systems generate condensate
which accumulates in any drain point (e.g. tanks,
filters, drip legs, aftercoolers, dryers). This
condensate contains lubricating oil and/or
substances which may be regulated and must be
disposed of in accordance with local, state, and
federal laws and regulations.
GENERAL REQUIREMENTS. The piping, fittings, air receiver tank,
etc. must be certified safe for at least the maximum working
pressure of the unit. Use hard-welded or threaded steel or copper
pipes and cast iron fittings that are certified safe for the unit’s
discharge pressure and temperature. DO NOT USE PVC PLASTIC
IN THE COMPRESSED AIR DISCHARGE LINE. Use pipe thread
sealant on all threads, and make up joints tightly to prevent air
leaks.
4
http://air.irco.com
CONDENSATE DISCHARGE PIPING. If installing a condensate
discharge line, the piping must be at least one size larger than the
connection, as short and direct as possible, secured tightly and
routed to a suitable drain point or waste container. Condensate
must be disposed of in accordance with local, state, and federal
laws and regulations.
WARNING If an aftercooler, check valve, block valve, or any
•
other restriction is added to the compressor
discharge, install a properly-sized ASME approved
safety/relief valve between the compressor
discharge and the restriction.
INSTALLING ELECTRICAL WIRING (ELECTRIC MOTOR
UNITS) _____________________________________________
WARNING Electrical installation and service should be
•
GENERAL. The motor rating, as shown on the motor nameplate,
and the power supply must have compatible voltage, phase and
hertz characteristics.
WIRE SIZE. The electrical wiring between the power supply and
electric motor varies according to motor horsepower and other
factors. Install adequately sized power leads to protect against
excessive voltage drop during start-up. Refer to the National
Electric Code (NEC) for information on selecting the proper wire
size and securing electrical connections. If you connect additional
electrical equipment to the same circuit, consider the total electrical
load when selecting the proper wire size. DO NOT USE
UNDERSIZE WIRE.
If wire size information is not available, the wire sizes shown in the
following wire selection chart can be used as a safe guide, if the
distance does not exceed 50 feet (15.3 m). For longer distances,
consult and electrical contractor or the local electric company for
recommendations.
performed by a qualified electrician who is familiar
with all applicable local, state and federal laws and
regulations.
PRESSURE SWITCH. On units without a factory-installed pressure
switch, wire a pressure switch in accordance with the appropriate
wiring schematic in the DIAGRAMS section of this manual. Mount
the pressure switch in accordance with the manufacturer’s
recommendations. The connecting line to the receiver tank must be
as short and direct as possible, and certified safe for at least the
maximum working pressure of the unit.
CONNECTING A BATTERY (GASOLINE ENGINE UNITS) __
NOTEIf you will be making connections to a remote
BATTERY. A 12 volt battery with a minimum current rating of 250
CCA (cold cranking amps) and minimum ampere-hour rating of 24
Ah should be sufficient for cranking most electric start engines.
BATTERY CABLES. Refer to the following table for size and length
recommendations.
CONNECTION PROCEDURES:
1. Connect the battery positive (+) cable (A) to the starter solenoid
terminal (B).
battery, the engine on the compressor unit must be
equipped with an alternator.
MAGNETIC STARTER. If the motor installed on your unit has a
motor reset button, it does not require a magnetic starter. If the
motor does not have this button and the unit does not have a
factory-installed starter, install a magnetic starter with thermal
overload protection. Follow the manufacturer’s instructions for
installation. Ingersoll-Rand cannot accept responsibility for
damages arising from failure to provide adequate motor protection.
FUSES. Refer to the NEC to determine the proper fuse or circuit
breaker rating required. When selecting fuses, remember the
momentary starting current of an electric motor is greater than its
full load current. Time-delay or “slow-blow” fuses are recommended.
2. Connect the battery negative (-) cable (C) to the bolt shown in the
following illustration. Secure the wire in place by screwing a
suitably-sized nut onto the bolt and down onto the terminal.
KohlerHonda
KawasakiIngersoll-Rand
3. Connect the battery positive (+) cable (A) to the battery positive (+)
terminal.
4. Connect the battery negative (-) cable to the battery negative (-)
terminal.
5. Coat the terminals and cable ends with corrosion-preventive grease.
WARNING Remove the cable from the negative (-) side of the
http://air.irco.com
•
battery before servicing.
Refer to the engine manufacturer’s instructions for more
information.
FUEL PUMP INSTALLATION (GASOLINE ENGINE UNITS) _
Some engines use an optional fuel pump to supply gasoline to the
engine directly from a vehicle’s onboard fuel system. Install the fuel
pump within 12 inches (30 cm) of the bottom surface of the vehicle’s
fuel tank. Protect the pump from contamination by installing a fuel
isolation valve and an inline filter between the pump fuel system.
COMPRESSOR LUBRICATION_________________________
CAUTIONDo not operate without lubricant or with inadequate
•
SYNTHETIC COMPRESSOR LUBRICANT. Ingersoll-Rand
recommends All Season Select synthetic lubricant from start-up.
See the WARRANTY section for extended warranty information.
ALTERNATE LUBRICANTS. You may use XL-300 or a comparable
petroleum-based lubricant that is premium quality, does not contain
detergents, contains only anti-rust, anti-oxidation, and anti-foam
agents as additives, has a flashpoint of 440°F (227°C) or higher,
and has an auto-ignition point of 650°F (343°C) or higher.
See the petroleum lubricant viscosity table below. The table is
intended as a general guide only. Heavy duty operating conditions
require heavier viscosities. Refer specific operating conditions to
Ingersoll-Rand for recommendations.
Temperature Around
Compressor
°F°CSUSCentistokesISOSAE
< 40< 4.4150323210
40-804.4-26.750011010030
80-12526.7-51.075016515040
If you use a petroleum-based compressor lubricant at start-up and
decide to convert to All Season Select later on, the pump must be
decarbonized and flushed before conversion. Contact
Ingersoll-Rand for more information.
FILLING PROCEDURES:
1. Unscrew and remove the oil fill plug.
2. Fill the crankcase with lubricant.
3. Replace the oil fill plug HAND TIGHT ONLY.
•
CAUTIONDo not remove the oil fill plug while the compressor
lubricant. Ingersoll-Rand is not responsible for
compressor failure caused by inadequate
lubrication.
Viscosity @ 100°F
(37.8°C)
Viscosity Grade
is running.
5
Refer to the following table for crankcase capacity.
ModelCrankcase Capacity
234028 oz. (827 ml.)
247541 oz. (1212 ml.)
254573 oz. (2158 ml.)
710080 oz. (2365 ml.)
15T, 3000144 oz. (4258 ml.)
Use one of the following methods illustrated to determine when the
crankcase is full.
A = FULL level at bottom thread of oil fill opening on units without
sight glass or dipstick.
B = ADD level below bottom thread of oil fill opening on units
without sight glass or dipstick.
A float activated low oil level switch may be installed to protect your
unit against damage due to insufficient compressor oil level. Low oil
level in the compressor crankcase causes the switch contacts to
open, thus shutting the unit down until the proper oil level has been
restored.
Proper protection against low oil level depends on proper
adjustment of the low oil level switch. During the initial run, stop the
unit and drain one quart of oil from the compressor crankcase into a
suitable clean container. Listen for the switch to click or check the
switch with a continuity tester.
The float sometimes gets cocked or stuck during shipping. If the
float is cocked or stuck, open the disconnect switch, drain the
remaining oil, remove the crankcase cover and then free the float.
Reassemble and then reuse the same oil.
NOTEIf the float is cocked in the low position, the unit
cannot start.
6
http://air.irco.com
OPERATION
INTERMITTENT DUTY FORMULA ______________________
Units operating above 200 PSIG are to be operated according to the
"Intermittent Duty Formula."
INTERMITTENT DUTY FORMULA
Pump-up time should not ordinarily exceed thirty (30)
minutes or be less than ten (10) minutes. Shutdown
periods between cycles of operation should be at least
equal to the pump-up time. Note: When the compressor
is regulated by constant speed control, the shutdown
period is the time the compressor is operating
unloaded.
A pump-up time limit with the following cool-down period is
recommended to protect the valves and heads against stabilized
high operating temperatures, which could rapidly build up carbon in
these areas.
All inquiries for high-pressure compressor application where the
"use" cycle differs from the "Intermittent Duty Formula" should be
referred to Ingersoll-Rand.
START-UP (ELECTRIC MOTOR DRIVEN MODELS) _______
1. Close the service valve.
2. Release any remaining tank pressure by slowly opening the manual
drain valve.
3. Close the manual drain valve and apply power to the compressor. If
the pressure switch is equipped with an “ON/AUTO-OFF” lever, flip
the switch to the “ON/AUTO” position. If the unit is equipped with a
control panel “ON/OFF” switch, move the switch to the “ON”
position.
Typical Pressure Switch Lever (If Equipped)
4. Slowly open the service valve.
Typical Service Valve (A = Open, B = Closed)
•
CAUTIONUnusual noise or vibration indicates a problem. Do
NOTEEnsure the direction of rotation is correct per the
not continue to operate until you identify and
correct the source of the problem.
arrow on the motor. If the rotation is incorrect on
three-phase units, interchange any two of the three
leads.
5-8 break-in hours of operation before reaching full
capacity and speed.
COMPRESSOR CONTROLS ___________________________
AUTOMATIC START & STOP CONTROL. This type of control
applies to electric motor driven models under 10 horsepower.
NOTEAutomatic Start & Stop Control is intended for use
When the receiver tank pressure reaches the factory pre-set
maximum pressure (usually 175 PSIG), the pressure switch stops
the unit. When the receiver tank pressure drops below the factory
pre-set minimum (usually 135 PSIG), the pressure switch resets
and restarts the unit.
CONSTANT SPEED CONTROL. This type of control applies to
gasoline engine units.
When the receiver tank pressure reaches the factory pre-set
maximum pressure (usually 175 PSIG), the unloader slows down
the engine and the unit stops pumping. When the receiver tank
pressure drops to the factory pre-set minimum (usually 145 PSIG),
the unloader resets, the engine returns to full speed, and the unit
resumes pumping.
DUAL CONTROL. This type of control applies to electric motor
units over 10 horsepower. Select either automatic start and stop
control or constant speed control by adjusting the knob on the
auxiliary valve. For automatic start and stop control, turn the knob
on the auxiliary valve fully clockwise to disable the auxiliary valve.
The pressure switch will then start and stop the unit.
NOTEFor dual control models, automatic start and stop is
when the motor will start no more than 6 times per
hour.
preferred.
7
http://air.irco.com
Auxiliary Valve.
Select constant speed control if the unit restarts in less than 10
minute intervals or runs more than 40 minutes per hour. Turn the
knob fully counterclockwise to run the unit continually. When the
receiver tank pressure reaches 170 PSIG, the unit runs but does not
pump.
NOTEThe auxiliary valve is factory pre-set at 5 PSIG lower
CAUTIONRunning unloaded for more than 20 minutes per
•
than the factory pressure switch setting.
hour or more than 15 minutes continually with the
use of constant speed control will cause oil
pumping and should be avoided.
PRESSURE SWITCH ADJUSTMENT ____________________
WARNING High voltage is present at the pressure switch
•
• CAUTIONDo not adjust the pressure switch to exceed the
NOTEAdjust the pressure switch only if adjustments are
CUT-IN & CUT-OUT. The cut-out (compressor shut-down) is the
pressure at which the switch contacts open, and the cut-in
(compressor restart) is the pressure at which the switch contacts
close. See COMPRESSOR CONTROLS.
ADJUSTMENT CONTROLS. All pressure switches have a range
adjustment control (A). Some pressure switches also have a
differential adjustment (B) control. On switches without a differential
adjustment control, the span between cut-in and cut-out pressure
levels switches is factory set for 40 ± 4 PSIG and cannot be
adjusted.
NOTESome pressure switches are equipped with an
ADJUSTMENT PROCEDURES (SWITCHES WITHOUT
DIFFERENTIAL ADJUSTMENT CONTROL):
1. Remove the pressure switch cover.
2. Adjust the range by turning the range adjustment screw clockwise
(in) to increase the cut-out point or counter-clockwise (out) to
decrease the cut-out point.
NOTE:One full turn changes the setting approximately 2
3. Replace cover, reconnect power supply and start the compressor.
4. Note the pressure gauge reading at which the compressor cuts out.
5. Repeat adjustment procedure if necessary.
contacts when the power supply is connected.
Disconnect, lock and tag main power supply before
making adjustments.
maximum discharge pressure of the unit.
absolutely necessary.
on-off lever used to open and close the electrical
contacts inside the switch. THIS LEVER IS NOT A
DIFFERENTIAL ADJUSTMENT CONTROL. The
pressure switches with the on-off lever do not have
a differential adjustment control.
PSIG.
Pressure Switch Range Adjustment.
ADJUSTMENT PROCEDURES (SWITCHES WITH DIFFERENTIAL
ADJUSTMENT CONTROL):
1. Remove the pressure switch cover.
2. Set the cut-in pressure with the range adjustment nut. Turn the nut
clockwise (in) to increase the pressure or counter-clockwise (out) to
decrease the pressure.
NOTE:One full turn changes the setting approximately 2
PSIG.
3. Set the cut-out pressure with the differential adjustment. Turn the
differential adjustment nut clockwise (in) to increase the pressure or
counter-clockwise (out) to decrease the pressure.
NOTE:One full turn changes the setting approximately 2
PSIG.
4. Replace the cover, reconnect the power supply and start the unit.
5. Note the pressure gauge reading at which the unit cuts out.
6. Repeat the adjustment procedure if necessary.
The minimum possible differential is approximately 20% of cutout
pressure. It is advisable to have as wide a differential as possible to
avoid frequent starting and stopping of the unit. Note the pressure
gauge reading at which the unit cuts-out and re-establish this point
if necessary.
Note the interaction between the range and differential adjustments,
i.e., if the cut-out is increased, the differential will also increase, or
if the differential is narrowed, the cut-out will be reduced, etc. These
factors must be considered when adjusting the switch and
compensated for accordingly.
STARTING UNLOADING SYSTEM ______________________
The starting unloading feature exists on certain models. The
purpose of the system is to relieve cylinder pressure when the unit
stops, permitting it to start against a light load. A light load
increases the life of the driver and belts and also reduces the
possibility of tripping the overload relay. The system operates in the
following manner:
The centrifugal unloader is attached to the end of the crankshaft as
shown in the following illustrations.
When the unit starts, centrifugal force acts upon the unloader
weights and they swing outward. This permits the plunger and thrust
pin to move inward and the pilot valve to close. The escape path to
atmosphere for the cylinder pressure is now closed and the
compressor pumps air in a normal manner.
When the unit stops, the weights retract, permitting the thrust pin
spring to move the plunger and thrust pin outward. The thrust pin
opens the pilot valve and the trapped air pressure escapes from the
cylinder and intercooler through a passage in the frame end cover,
through the unloader tube and to atmosphere through the inlet
filter/silencer.
8
http://air.irco.com
Position of weight and thrust pin when unit is operating.
Position of weight and thrust pin when unit is stopped.
BREATHER/UNLOADER BY-PASS _____________________
The breather/unloader by-pass tube lines eliminates air pressure
build-up in the compressor frame by providing a passage for the air
to escape through the inlet unloader (if opened) or (if closed)
through the check valve, therefore, by-passing the inlet unloader
and escaping to atmosphere through the inlet filter/silencer.
OIL CONSUMPTION CHECK___________________________
A rule of thumb in determining a "passing grade" for oil consumption
is to consider consumption at or above 50 horsepower-hours per
ounce to be acceptable.
The formula is as follows:
HorsepowerX
Ounces of Oil Used
Hours of Operation
To apply this formula, consider the size of the machine. In the
following example, a 5 horsepower compressor uses 2 ounces of oil
every 20 hours of operation.
5 HorsepowerX20 Hours of
2 Ounces of Oil Used
Operation
The compressor in the example passes the oil consumption test.
NOTENew or rebuilt compressor pumps will discharge
higher than normal amounts of oil until the piston
rings are seated (approximately 100 operating
hours).
=Horsepower Hours
per Ounce
=50 Horsepower
Hours per Ounce
PILOT VALVE ADJUSTMENT __________________________
If the pilot valve tube line is excessively hot, it is a good indication
that the pilot valve is leaking and adjustment is required.
To adjust the pilot valve, proceed as follows:
1. Stop the unit and disconnect and tag the electrical supply main
switch to prevent accidental start-up.
2. Remove the pilot valve tube and the tube fittings.
3. Remove the pilot valve body and all existing shims.
4. Screw the pilot valve body back into the frame end cover (without
any shims) until contact with the thrust pin is felt. Advance the pilot
valve body 1/4 to 1/2 turn more.
If contact with the thrust pin cannot be felt, the following steps may
be necessary to locate the contact point:
1. Insert a small instrument (punch, rod, nail, etc.) into the end of the
pilot valve until it contacts the valve stem.
2. While still inserted in the pilot valve, make a mark on the instrument
even with the outside edge of the pilot valve body.
3. Keeping the instrument pressed lightly against the valve stem, screw
the pilot valve body into the frame end cover. When the mark on the
instrument starts moving out away from the edge of the pilot valve
body, contact has been made with the thrust pin.
4. Advance the pilot valve body 1/4 to 1/2 turn more and proceed with
step five.
5. Measure the gap between the pilot valve body and the frame end
cover.
6. Remove the pilot valve body and add enough shims to fill the gap
measured in step five.
7. Screw the pilot valve body back into the frame end cover until the
body is tight on the shims.
8. Reconnect the pilot valve tube and tube fittings.
MAINTENANCE
• WARNING Before performing maintenance, release air
pressure from the system and disconnect, lock and
tag the main power supply or disconnect the wire
from the engine spark plug.
NOTEAll compressed air systems contain maintenance
parts (e.g. lubricating oil, filters, separators) which
are periodically replaced. These used parts may be,
or may contain, substances that are regulated and
must be disposed of in accordance with local, state,
and federal laws and regulations.
NOTETake note of the positions and locations of parts
during disassembly to make reassembly easier. The
assembly sequences and parts illustrated may differ
for your particular unit.
NOTEAny service operations not explained in this manual
should be performed by an authorized service
representative.
NOTEReference the engine owner's manual for engine
care information.
NOTEThe following maintenance schedule has been
developed for typical applications. Maintenance
intervals should be shortened in harsher
environments.
9
http://air.irco.com
MAINTENANCE SCHEDULE
Check for oil leaks.
Daily or Before
Each
Operation
CHECKING BELT TENSION. Check belt tension should be
occasionally, especially if looseness is suspected. New belts must
also be properly tensioned upon installation.
TENSIONING BELTS. Belt tensioning can be achieved by
loosening the motor or engine anchor screws, pushing the motor or
engine away from the pump, and retightening the motor or engine
anchor screws. Some units are equipped with a belt tensioning bolt
that, when turned, pulls the motor or engine away from the pump.
Otherwise, the motor can be easily moved by placing a prying tool
beneath it. A commercially available spreader or other belt
tensioning device can also be helpful.
Follow the procedures outlined below to correctly set and measure
belt tension on electric motor and gas engine models including
2340, 2475, and 2545 (with "A" belt type only). Refer to the
following illustration for a visual representation.
FILTER INSPECTION & CLEANING_____________________
1. Unscrew and remove the wing nut (A) securing the filter housing (B)
to its base (C).
2. Remove the filter housing and withdraw the old filter element (D).
Clean the element with a jet of air or vacuum.
3. Replace the filter element and housing, securing it in place with the
1. Remove the oil drain plug (A) and allow the lubricant to drain into a
suitable container.
2. Replace the oil drain plug.
3. Follow the filling procedures in OPERATION section.
1. Lay a straight edge across the top outer surface of the belt drive
from pulley to sheave.
2. At the center of the span, perpendicular to the belt, apply pressure
to the outer surface of the belt with a tension gauge. Force the belt
to the deflection indicated in the BELT TENSION TABLE in the
DIAGRAMS & TABLES section. Compare the reading on the tension
gauge to the table.
Follow the procedures outlined below to correctly set and measure
tension on 7.5 through 30 horsepower models 2545, 7100, 15T and
3000 with "B" and "C" belt types.
1. Measure the span length (t) of the drive.
2. Determine the amount of deflection (in inches) required to measure
deflection force (in pounds) by multiplying the span length (t) by
1/64. For example, a 32” span length multiplied by 1/64 equals 1/2”
of deflection required to measure deflection force.
3. Lay a straight edge across the top outer surface of the belt drive
from pulley to sheave.
4. At the center of the span, perpendicular to the belt, apply pressure
to the outer surface of the belt with a tension gauge. Force the belt
to the predetermined deflection calculated in step 2. Compare the
reading on the tension gauge to the BELT TENSION TABLE in the
DIAGRAMS & TABLES section.
10
http://air.irco.com
Ensure the pulley and sheave are properly aligned and the motor
anchor screws are adequately retightened prior to restarting the
compressor.
CAUTIONImproper pulley/sheave alignment and belt tension
•
To prevent these problems from occurring, ensure the pulley and
sheave are aligned and belt tension is satisfactory after installing
new belts or tensioning existing belts.
can result in motor overload, excessive vibration,
and premature belt and/or bearing failure.
ELECTRIC DRAIN MAINTENANCE _____________________
NOTEThe following maintenance schedule has been
DAILYTest the valve for proper
MONTHLY (EVERY 30 DAYS)Clean the filter screen.
To clean the filter screen, perform the following steps:
1. Close the strainer ball valve completely to isolate it from the air
receiver tank.
2. Press the TEST button on the timer to vent the pressure remaining
in the valve. Repeat until all pressure is removed.
• CAUTIONHigh pressure air can cause injury from flying
3. Remove the plug from the strainer with a suitable wrench. If you
hear air escaping from the cleaning port, STOP IMMEDIATELY and
repeat steps 1 and 2.
4. Remove the stainless steel filter screen and clean it. Remove any
debris that may be in the strainer body before replacing the filter
screen.
developed for typical applications. Maintenance
intervals should beshortened in harsher
environments.
DRAIN VALVE MAINTENANCE SCHEDULE
operation. Clean the filter screen
if needed.
debris. Ensure the strainer ball valve is completely
closed and pressure is released from the valve prior
to cleaning.
5. Replace plug and tighten with wrench.
Position of weight and thrust pin when unit is operating.
6. When putting the EDV-2000 back into service, press the TEST
button to confirm proper function.
TANK INSPECTION __________________________________
The life of an air receiver tank is dependent upon several factors
including, but not limited to, operating conditions, ambient
environments, and the level of maintenance. The exact effect of
these factors on tank life is difficult to predict; therefore,
Ingersoll-Rand recommends that you schedule a certified tank
inspection within the first five years of compressor service. To
arrange a tank inspection, contact Ingersoll-Rand.
If the tank has not been inspected within the first 10 years of
compressor service, the receiver must be taken out of service until
it has passed inspection. Tanks that fail to meet requirements must
be replaced.
• WARNING Failure to replace a rusted air receiver tank could
result in air receiver tank rupture or explosion,
which could cause substantial property damage,
severe personal injury, or death. Never modify or
repair tank. Obtain replacement from service center.
11
http://air.irco.com
TROUBLESHOOTING
PROBLEMCHECK POINT
Abnormal piston, ring or cylinder wear4, 8, 9, 19, 28, 35
Air delivery drops off1, 6, 15, 16, 18, 19, 29
Automatic drain valve leaks or does not drain automatically16
Auxiliary valve chatters or leaks around stem23, 24
Broken intercooler or aftercooler tubes36
Compressor does not come up to speed2, 6, 12, 15, 21
Compressor is slow to come up to speed26, 27, 33, 34
Compressor runs excessively hot3, 14, 15, 22
Compressor will not unload cycle23, 24, 26
Compressor will not unload when stopped26, 33
Excessive noise during operation2, 6, 15, 16, 21, 27, 32
Excessive starting and stopping5, 11, 16, 32, 40
Knocks or rattles2, 15, 17, 19, 20, 21
Lights flicker or dim when running12, 13
Moisture in crankcase or “milky” appearance in petroleum lubricant or
rusting in cylinders
Motor overload trips or draws excessive current5, 6, 12, 13, 14, 15, 16, 19, 20, 21, 34
Oil in discharge air (oil pumping)4, 7, 9, 18, 19, 25, 35
Oil leaking from shaft seal25
Safety/relief valve “pops”1, 5, 29, 30
High interstage pressure30
Low interstage pressure31
Engine cranks slowly or will not start6, 14, 37, 38
Motor will not start12
Engine will not start39
Oil Leaks41
9, 10
ELECTRIC DRAIN TROUBLESHOOTING
TroubleCauseAction
Valve will not close.
Timer will not activate.
1. Debris in solenoid valve
prevents diaphragm from
seating.
2. Short in electrical component.
1. No electrical supply.
2. Timer malfunction
3. Clogged port.
4. Solenoid valve malfunction.
5. Clogged strainer.
1. Remove solenoid valve,
disassemble, clean and
reassemble.
2. Check and replace power cord
or timer as needed.
1. Apply power.
2. Replace timer.
3. Clean valve.
4. Replace solenoid valve.
5. Clean strainer.
12
http://air.irco.com
CHECK
POINT
1Clogged or dirty inlet and/or discharge line filter.Clean or replace.
2Loose beltwheel or motor pulley, excessive end play in motor
3Inadequate ventilation around beltwheel.Relocate compressor for better air flow.
4Lubricant viscosity too low.Drain existing lubricant and refill with proper lubricant.
5Air leaks in air discharge piping.Check tubing and connections. Tighten joints or replace as
6Lubricant viscosity too high.Drain existing lubricant and refill with proper lubricant.
7Lubricant level too high.Drain excess lubricant.
8Lubricant level too low.Add lubricant to crankcase to proper level.
9Detergent type lubricant being used.Drain existing lubricant and refill with proper lubricant.
10Extremely light duty cycles.Run compressor for longer duty cycles.
11Pressure switch differential too narrow.Adjust pressure switch to increase differential, if differential
12Improper line voltage.Check line voltage and upgrade lines as required. Contact
13Poor power regulation (unbalanced line).Contact power company.
14Drive belts too tight or misaligned.Adjust belts to proper tension and alignment.
15Compressor valves leaky, broken, carbonized or loose.Inspect valves. Clean or replace as required. Install Valve/Gasket
16Automatic drain valve clogged, leaking or defective.Inspect valve and clean, repair or replace as required.
17Carbon build-up on top of piston(s).Clean piston(s). Repair or replace as required.
18Piston rings damaged or worn (broken, rough or scratched).
19Cylinder(s) or piston(s) scratched, worn or scored.Repair or replace as required.
20Connecting rod, piston pin or crankpin bearings worn or scored.
21Defective ball bearings on crankshaft or motor shaft.Inspect bearings and replace if required. Install
22Wrong beltwheel direction of rotation.Check motor wiring for proper connections. Reverse two leads on
23Leaking, broken or worn inlet unloader parts.Inspect parts and replace as required.
24Auxiliary valve dirty or seats worn.Inspect parts. Clean, adjust or replace as required.
25Crankshaft seal worn or crankshaft scored.Replace seal. Install shaft sleeve if required. Install
26Leaking or maladjusted centrifugal pilot valve.Replace pilot valve o-ring. Adjust pilot valve.
27Leaking check valve or check valve seat blown out.Replace check valve.
28Extremely dusty atmosphere.Install remote air inlet piping and route to source of cleaner air.
29Defective safety/relief valve.Replace.
30High pressure inlet valve leaking.Inspect, clean or repair as required.
31Low pressure discharge valve leaking.Inspect, clean or repair as required.
32Automatic start and stop mode is not suitable for air demand.Adjust auxiliary valve for constant speed operation.
33Pressure switch unloader leaks or does not work.Realign stem or replace.
34Ambient temperature too low.Install crankcase heater kit. Convert to All Season Select
35Worn cylinder finish.Deglaze cylinder with 180 grit flex-hone.
36Beltwheel out of balance, tubes not braced or secured, wrong
37Engine not grounded properly.Ground battery to engine as recommended.
38Gasoline exceeds storage time or contains water.Replace gas, add fuel stabilizer.
39No fuel in tank.See manufacturer’s instructions for refueling.
40Excessive condensate in receiver tank.Drain receiver tank with manual drain valve or install automatic
41Loose fittings/elbows/connectorsRe-torque fittings per specified torque requirements
POSSIBLE CAUSEPOSSIBLE SOLUTION
shaft or loose drive belts.
Compressor located in damp or humid location.Relocate compressor or install crankcase heater kit.
Wiring or electric service panel too small.Intall properly sized wire or service box. Contact electrician.
Poor contact on motor terminals or starter connections.Ensure good contact on motor terminals or starter connections.
Improper starter overload heaters.Install proper starter overload heaters. Contact electrician.
Excessive end gap or side clearance.
Piston rings not seated, are stuck in grooves or end gaps not
staggered.
ATo supply
CWiring for optional electric drain valve
EDVElectric drain valve
TSupply Line Terminal
LLoad Terminal
FUControl Circuit Fuse
HATSHigh Air Temperature Switch (#)
LOLSLow Oil Level Switch (#)
MMotor Starter Coil
OLMotor Starter Overload
PSPressure Switch
SSSelector Switch (#)
*Alternate wiring for converting 3 phase starter to 1
phase application
(#) = if provided
NOTEOn units requiring a starter, connect line power to the starter. do not connect
l
Connect ground wire to ground lug
l
L3 used for 3-phase motors & starters only
line power to the pressure switch.
Typical Baseplate Unit
http://air.irco.com
Typical Horizontal Simplex Unit
15
Typical Vertical Simplex Unit
http://air.irco.com
Typical Gasoline Engine Unit
16
Typical Duplex Unit
17
http://air.irco.com
WARRANTY
Ingersoll-Rand Company warrants that the Equipment manufactured by it and delivered hereunder shall be free of defects in material and
workmanship for a period of twelve (12) months from the date of placing the Equipment in operation or eighteen (18) months from the date
of shipment, whichever shall occur first. The foregoing warranty period shall apply to all Equipment, except for the following: (A)
Compressors that are operated solely on All Season Select synthetic compressor lubricant will have their bare compressor warranted for
the earlier of twenty-four (24) months from the date of initial operation or thirty (30) months from the date of shipment. (B) Replacement
parts will be warranted for six (6) months from the date of shipment. Should any failure to conform to this Warranty be reported in writing
to the Company within said period, the Company shall, at its option, correct such nonconformity by suitable repair to such Equipment, or
furnish a replacement part F.O.B. point of shipment, provided the purchaser has installed, maintained and operated such equipment in
accordance with good industry practices and has complied with specific recommendations of the Company. Accessories or equipment
furnished by the Company, but manufactured by others, shall carry whatever warranty the manufacturer conveyed to Ingersoll-Rand
Company and which can be passed on to the Purchaser. The Company shall not be liable for any repairs, replacements, or adjustments to
the Equipment or any costs of labor performed by the Purchaser without the Company’s prior written approval.
The Company makes no performance warranty unless specifically stated within its proposal and the effects of corrosion, erosion and
normal wear and tear are specifically excluded from the Company’s Warranty. In the event performance warranties are expressly included,
the Company’s obligation shall be to correct in the manner and for the period of time provided above.
THE COMPANY MAKES NO OTHER WARRANTY OF REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED,
EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE,
ARE HEREBY DISCLAIMED.
Correction by the Company of nonconformities, whether patent or latent, in the manner and for the period of time provided above, shall
constitute fulfillment of all liabilities of the Company and its Distributors for such nonconformities with respect to or arising out of such
Equipment.
LIMITATION OF LIABILITY
THE REMEDIES OF THE PURCHASER SET FORTH HEREIN ARE EXCLUSIVE, AND THE TOTAL LIABILITY OF THE COMPANY, ITS
DISTRIBUTORS AND SUPPLIERS WITH RESPECT TO CONTRACT OR THE E UIPMENT AND SERVICES FURNISHED, IN
CONNECTION WITH THE PERFORMANCE OR BREACH THEREOF, OR FROM THE MANUFACTURE, SALE, DELIVERY,
INSTALLATION, REPAIR OR TECHNICAL DIRECTION COVERED BY OR FURNISHED UNDER CONTRACT, WHETHER BASED ON
CONTRACT, WARRANTY, NEGLIGENCE, INDEMNITY, STRICT LIABILITY OR OTHERWISE SHALL NOT EXCEED THE PURCHASE
PRICE OF THE UNIT OF E UIPMENT UPON WHICH SUCH LIABILITY IS BASED.
THE COMPANY, ITS DISTRIBUTORS AND ITS SUPPLIERS SHALL IN NO EVENT BE LIABLE TO THE PURCHASER, ANY
SUCCESSORS IN INTEREST OR ANY BENEFICIARY OR ASSIGNEE OF THE CONTRACT FOR ANY CONSE UENTIAL, INCIDENTAL,
INDIRECT, SPECIAL OR PUNITIVE DAMAGES ARISING OUT OF THIS CONTRACT OR ANY BREACH THEREOF, OR ANY DEFECT IN,
OR FAILURE OF, OR MALFUNCTION OF THE E UIPMENT, WHETHER OR NOT BASED UPON LOSS OF USE, LOSS PROFITS OR
REVENUE, INTEREST, LOST GOODWILL, WORK STOPPAGE, IMPAIRMENT OF OTHER GOODS, LOSS BY REASON OF SHUTDOWN
OR NON-OPERATION, INCREASED EXPENSES OF OPERATION, COST OF PURCHASE OF REPLACEMENT POWER, OR CLAIMS OF
PURCHASER OR CUSTOMERS OF PURCHASER FOR SERVICE INTERRUPTION WHETHER OR NOT SUCH LOSS OR DAMAGE IS
BASED ON CONTRACT, WARRANTY, NEGLIGENCE, INDEMNITY, STRICT LIABILITY OR OTHERWISE.
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.