Ingersoll-Rand 1100, 1200, 1300, 1000, 1600 Operator's Manual

...
NIRVANA CYCLING REFRIGERATED DRYER
MODELS 1000-1600
OPERATORS MANUAL
C.C.N. : 80442791 DATE : DECEMBER 2006 REV. : A
Ensure that the operator reads and understands the decals and consults the manuals before maintenance or operation.
Ensure that the Operation and Maintenance manual is not removed permanently from the machine.
Ensure that maintenance personnel are adequately trained, competent and have read the Maintenance Manuals.
a
1
Nirvana Cycling Refrigerated Dryer Models 1000-1600
http://air.irco.com
CONTENTS PAGE
1.0 CONTENTS 1
2.0 INTRODUCTION 2
3.0 WARRANTY 2
4.0 REFRIGERATED DRYER NOMENCLATURE 2
5.0 RECEIVING AND INSPECTION 3
5.1 INSPECTIONS
5.2 UNPACKING AND HANDLING
6.0 SAFETY AND OPERATION PRECAUTIONS 3
7.0 PRINCIPLES OF OPERATION 5
7.1 INTRODUCTION
7.2 AIR SYSTEM
7.3 MOISTURE REMOVAL SYSTEM
7.4 REFRIGERATION SYSTEM
7.5 THERMAL MASS CIRCULATING SYSTEM
7.6 CONTROLS
7.6.1 BASIC USER INTERFACE
7.6.2 DISPLAY PARAMETERS
7.6.3 DRYER SET POINTS AND ALARMS
7.6.4 ADJUSTING SET POINTS
7.6.5 ALARMS AND THEIR FUNCTIONS
7.6.6 START MODES
7.6.6.1 Manual Mode
7.6.6.2 Auto Restart Mode
7.6.6.3 Remote Automatic Mode
CONTENTS PAGE
8.0 INSTALLATION AND INITIAL START-UP 9
8.1 LOCATION AND MOUNTING
8.2 PIPING AND VALVES
8.3 FILTRATION
8.4 ELECTRICAL CONNECTION
8.5 INITIAL START-UP
8.5.1 START- UP SEQUENCE
9.0 SCHEDULED MAINTENANCE 12
9.1 INTRODUCTION
9.2 REFRIGERANT CONDENSER
9.3 CONDENSATE DISCHARGE SYSTEM
9.4 PREFILTERS AND AFTERFILTERS
9.4.1 THREADED FILTERS
9.4.2 FLANGED FILTERS
10.0 TECHNICIAN MODE 16
11.0 TROUBLESHOOTING 18
11.1 INTRODUCTION
11.2 PROBLEM / ACTION GUIDE
12.0 WIRING DIAGRAMS 20
13.0 GENERAL ARRANGEMENT 21
14.0 REPLACEMENT PARTS 22
15.0 ENGINEERING SPECIFICATIONS 23
CONTENTS
The Ingersoll Rand Nirvana Cycling refrigerated air dryer removes moisture, oil vapor, and other contaminants from compressed air. These contaminants are detrimental to pneumatically operated appliances, controls, instruments, machinery and tools. This is accomplished by cooling the air with a refrigeration unit to a temperature at which moisture in the air is condensed and separated from the airstream. The temperature the air is cooled to, normally between 36 and 40°F, is known as dew point. This dryer can be easily installed into various
2
Nirvana Cycling Refrigerated Dryer Models 1000-1600
http://air.irco.com
pneumatic systems in which dry air is required or desired. Please refer to Principles of Operation for complete operating details.
• For warning label information with French translations, refer to pages
5 and 6.
• Pur obtenir l’informatione des etiquettes dangereuses avec la
traductione en francais, s’il vous plait consul ter les pages 5 and 6.
The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in material and workmanship for a period of twelve months from the date of placing the Equipment in operation or eighteen months from the date of shipment from the factory, whichever shall first occur. The Purchaser shall be obligated to promptly report any failure to conform to this warranty, in writing to the Company in said period, whereupon the Company shall, at its option, correct such nonconformity, by suitable repair to such equipment or, furnish a replacement part F.O.B. point of shipment, provided the Purchaser has stored, installed, maintained and operated such Equipment in accordance with good industry practices and has complied with specific recommendations of the Company. Accessories or equipment furnished by the Company, but manufactured by others, shall carry whatever warranty the manufactures have conveyed to the Company and which can be passed on to the Purchaser. The Company shall not be liable for any repairs, replacements, or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company's prior written approval.
The effects of corrosion, erosion and normal wear and tear are specifically excluded. Performance warranties are limited to those specifically stated within the Company's proposal. Unless responsibility for meeting such performance warranties are limited to specified tests, the Company's obligation shall be to correct in the manner and for the period of time provided above.
THE COMAPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HERBY DISCLAIMED.
Correction by the Company of nonconformities whether patent or latent, in the manner and for the period of time provided above, shall constitute fulfillment of all liabilities of the Company for such nonconformities whether based on contract, warranty negligence, indemnity, strict liability or otherwise with respect to or arising out of such Equipment.
The Purchaser shall not operate Equipment which is considered to be defective, without first notifying the Company in writing of its intention to do so. Any such use of Equipment will be at Purchaser's sole risk and liability.
Note that this is Ingersoll Rand standard warranty. Any warranty in force at the time of purchase of the equipment or negotiated as part of the purchase order may take precedence over this warranty.
2.0 INTRODUCTION
3.0 WARRANTY
4.0 REFRIGERATED DRYER NOMENCLATURE
NOMINAL*
FLOW CONDENSER PREFIX (SCFM) TYPE RATING POWER NVC 1000-1600 A = AIR (BLANK) = NEMA 1 (BLANK) = 460-3-60
W = WATER N4 = NEMA 4 230-3-60
575-3-60 380-3-50 220-3-50
* Nominal Flows indicated are for 100°F inlet temperature, 100°F ambient temperature and 100 psig compressed air pressure.
3
Nirvana Cycling Refrigerated Dryer Models 1000-1600
http://air.irco.com
5.1 INSPECTION
Upon receiving your Ingersoll Rand air dryer, please inspect the unit closely. If rough handling has been detected, please note it on your delivery receipt, especially if the dryer will not be immediately uncrated. Obtaining the delivery person's signed agreement to any noted damages will facilitate any insurance claims
5.2 UNPACKING AND HANDLING
a
WARNING
Under no circumstances should any person attempt to lift heavy objects without proper lifting equipment (i.e., crane, hoist, slings or fork truck). Lifting any unit without proper lifting equipment, can cause serious injury.
5.0 RECEIVING AND INSPECTION
All dryer packages have been mounted on a base which provides for forklifting between the two base channels to facilitate handling during shipment. Forks should extend all the way through forklift channels to reduce unnecessary forces to the dryer during moving. Slings can be used to lift the crates, but spreader bars must be used to prevent the slings from exerting a force against the sides of the crates.
6.0 SAFETY AND OPERATION PRECAUTIONS
Because an air dryer is pressurized and contains rotating parts, the same precautions should be observed as with any piece of machinery of this type where carelessness in operation or maintenance could be hazardous to personnel. In addition to obvious safety rules that should be followed with this type of machinery, safety precautions as listed below must be observed:
1. Only qualified personnel shall be permitted to adjust, perform maintenance or repair this air dryer.
2. Read all instructions completely before operating unit.
3. Pull main electrical disconnect switch and disconnect any separate control lines, if used, before attempting to work or perform maintenance on the unit.
4. Do not attempt to service any part while machine is in an operational mode.
5. Do not attempt to remove any parts without first relieving the entire air system of pressure.
6. Do not attempt to remove any part of the refrigeration system without removing and containing refrigerant in accordance with the EPA and local regulations.
7. Do not operate the dryer at pressures in excess of its rating.
8. Do not operate the dryer without guards, shields and screen in place.
9. Inspect unit daily to observe and correct any unsafe operating conditions.
OSHA
Heading Descriptions
a
WARNING
“Warning” is used to indicate a hazardous situation which has some probability of death or severe injury. Warning should not be considered for property damage accidents unless personal injury risk is present.
a
CAUTION
“Caution” is used to indicate a hazardous situation which may result in minor or moderate injury.
a
NOTICE
“Notice” is used to indicate a statement of company policy as the message relates directly or indirectly to the safety of personnel or protection of property. Notice should not be associated directly with a hazard or hazardous situation and must not be used in place of “Danger,” “Warning,” or “Caution.”
a
NOTICE
The user of any air dryer manufactured by Ingersoll Rand, is hereby warned that failure to follow the above Safety and Operation Precautions may result in personal injury or equipment damage. However, Ingersoll Rand does not state as fact, nor does it mean to imply, that the preceding list of Safety and Operating Precautions is all inclusive, and further, that the observance of this list will prevent all personal injury or equipment damage.
Nirvana Cycling Refrigerated Dryer Models 1000-1600
http://air.irco.com
4
6.0 SAFETY AND OPERATION PRECAUTIONS
ELECTRICAL CONNECTION BOX
CONTAINS HIGH VOLTAGE
• Turn Off Power And Lock Out At ALL Sources Before Opening To Perform Service.
• Remote Alarm Contact Wiring Has Control Power From Separate Source.
READ TECHNICAL MANUAL
Air Under Pressure Will Cause Injury, Death Or Property Damage.
• Do Not Exceed Pressure Rating.
• Relieve Press. Before Servicing.
• Do Not Modify/Repair/Rework ASME Coded Pressure Vessels As Insurance Rating Affected.
READ TECHNICAL MANUAL
Removing fuses will not disconnect power from dryer. Always disconnect power from ALL sources before performing service.
READ TECHNICAL MANUAL
FAN MAY AUTOMATICALLY
START AT ANY TIME
ELECTRICAL CONNECTION BOX
All Customer Connections To Be Made At This Location.
See Terminal Connection Diagrams, below.
Be Certain To Follow All NEC, State, Local and Other Applicable
Codes During Installation.
FACTORY
WIRING
GRN
WHT
BLK
100-125VAC / 1 PH
1
2
G
3
N
4
L1
5
6
INCOMING
LINE VOLTAGE
100-125VAC 1PH/50-60HZ
(BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
FACTORY
WIRING
Air Under Pressure Will Cause Injury, Death Or Property Damage.
• Relieve Press. Before Servicing.
• Condensate Drain Discharges Under Pressure.
• Drain Requires Periodic Cleaning (Service).
READ TECHNICAL MANUAL
GRN
BLK
RED
200-240VAC / 1 PH
1
2
G
3
4
L1
5
L2
6
INCOMING
LINE VOLTAGE
200-240VAC 1PH/50-60HZ (BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
FACTORY
WIRING
GRN
RED
WHT
BLK
200-575VAC / 3 PH
1
2
G
3
L1
4
L2
5
L3
6
INCOMING
LINE VOLTAGE
200-575VAC 3PH/50-60HZ (BY OTHERS)
(REFER TO UNIT
NAMEPLATE FOR
POWER
REQUIREMENTS)
This unit is charged with
refrigerant under high pressure.
HIGH VOLTAGE
5
7.1 INTRODUCTION
Ingersoll Rand Nirvana Cycling™ dryers remove moisture from compressed air by cooling the air temperature to between 36° and 40°F (2 and 4°C). This causes vapors to condense into liquid droplets which can then be easily removed from the air. The major systems of the dryer which contribute to its operation are the Air System, the Moisture Removal System, the Refrigeration System, the Thermal Mass Circulating System and the Controls. The following paragraphs describe each of the systems in greater detail.
7.2 AIR SYSTEM
The air system consists of the dryer components which are in contact with the compressed air. Referring to Figure 1 and following the bold
7.0 PRINCIPLES OF OPERATION
AIR FLOW,” hot saturated air from the compressor enters the precooler/reheater where the air temperature is reduced prior to entering the chiller by the cool air exiting the air/moisture separator. This precooling allows for the use of a smaller refrigeration system. The air then goes into the chiller section where it is further cooled to the desired dew point by a thermal mass fluid. The temperature of the thermal mass fluid is maintained by the refrigeration circuit and controls. The air continues to the separator where moisture is removed, thereby, allowing the cool, dry air to return back to the precooler/reheater to be heated by the incoming moist hot air. The air exiting the “reheater” portion of the dryer should be approximately 15°- 20°F lower than the inlet air temperature based on standard conditions at full rated flow.
FIGURE 1
FLOW DIAGRAM
7.3 MOISTURE REMOVAL SYSTEM
Ingersoll Rand condensate drains discharge condensed moisture and lubricants (condensate) from compressed air equipment. The condensate drain operates as a zero-air-loss drain, returning air that is displaced in the drain bowl back into the compressed air system. Consistent discharging of condensate from compressed air equipment is essential for proper equipment operation and performance.
The condensate drain uses a unique sensing method to determine the level of condensate in the drain bowl. A transducer located in the drain bowl continuously sends out a signal 50 times per second. Once the transducer determines that the level of condensate has reached a predetermined level within the drain bowl, a signal is sent to the no-loss drain valve to open. This operation permits removal of condensate of up to 80 gallons per hour.
The drain also features a test button that permits manual operation of the no-loss drain valve. Depressing the test button illuminates the LED and energizes the solenoid valve. The LED illuminates to indicate "POWER ON" and goes off when the no-loss drain valve is operated by the transducer or manual test button.
The condensate flows through the feed line into the drain unit and accumulates in the container. A capacitive sensor continuously registers the liquid level and passes a signal to the electronic control as soon as the container is filled. The pilot valve is then activated and the diaphragm opens the outlet line for discharging the condensate. When the drain unit has been emptied, the outlet line is closed again quickly and tightly without wasting compressed air.
Nirvana Cycling Refrigerated Dryer Models 1000-1600
http://air.irco.com
6
Nirvana Cycling Refrigerated Dryer Models 1000-1600
http://air.irco.com
7.0 PRINCIPLES OF OPERATION
7.4 REFRIGERATION SYSTEM
The Refrigeration System consists of all the components which handle R-22. This is a hermetically sealed closed-loop system. Referring to Figure 1 and following the phantom “
REFRIG
(R-22) FLOW,” refrigerant is shown leaving the evaporator section where, in the process of removing heat, it is changed from a low pressure liquid into a low pressure gas. This gas enters the suction side of the compressor where it is compressed into a high pressure gas. The high pressure gas is cooled in the air cooled or water cooled condenser section until it becomes a high pressure liquid. It then goes through a permanent filter dryer that ensures the refrigeration system is free of contaminants. A thermostatic expansion valve meters the refrigerant for introduction into the evaporator. The refrigerant pressure is reduced upon entering the evaporator where as it evaporates, heat is removed from the thermal mass fluid. A solenoid valve in the liquid line eliminates the possibility of flooded starts.
7.5 THERMAL MASS CIRCULATING SYSTEM
The thermal mass fluid in a Ingersoll Rand Nirvana Cycling™ dryer is continuously circulated in a closed pump loop system. Referring to Figure 1 and following the dashed “
THERMAL MASS FLUID” line, the heat is
removed from the fluid in the evaporator by the refrigeration system. The thermal mass reservoir is sized to minimize refrigeration cycles during reduced air load periods. The thermal mass fluid is pulled from the bottom of the reservoir and pumped through the chiller, removing heat from the air and returned to the evaporator. The pump utilized on Ingersoll Rand Nirvana Cycling™ dryer is a maintenance-free, quiet cartridge circulator pump similar to those used in residential water systems. While the refrigeration system cycles on and off based on loading conditions, the circulating pump runs continuously to maintain flow through the chiller at all times.
7.6 CONTROLS
Ingersoll Rand 1000-1600 Refrigerated Compressed Air Dryers are equipped with the Microprocessor Control. This advanced microprocessor-based controller has been engineered by Ingersoll Rand exclusively for use with Ingersoll Rand Compressed Air Dryers.
The Microprocessor Control cycles the refrigeration system based on the dryer's Chiller Temperature. A temperature sensor samples the thermal mass temperature as it enters the chiller exchanger. The Chiller Temperature Set point is a user adjustable set point that is used to set the Refrigeration Compressor Off temperature. Once the Chiller Temperature has fallen below the Chiller Temperature Set point, the refrigeration compressor will de-energize. The Operating Temperature Differential is factory set at 4°F above the Chiller Temperature Set point. Therefore, if a user adjusts the Chiller Temperature at 36°F, the Refrigeration Compressor On temperature will be 40°F.
In addition to the operation of the Nirvana Cycling™ dryers as described above, the Microprocessor Control permits monitoring of dryer parameters and enunciation of alarm conditions.
The list below summarize the features the Microprocessor Control:
• 2 X 16 Character Backlit LCD Display - Easy-to-read display provides
continuous indication of dryer default parameter. Standard backlight permits viewing of critical information in low light environments.
• Remote Start / Stop: Microprocessor Control-equipped dryers offer a
unique remote start / stop feature. This feature allows the dryer to be operated via a remote user-supplied switch.
• Remote Alarm Contact: Microprocessor Control-equipped dryers
include a remote alarm contact to provide indication of any of the dryers alarms described later in this manual. Contact rated for 2A / 120V max.
The Microprocessor Control features three levels of access. The default level CUSTOMER MODE permits adjustment of dryer parameters to address seasonal variations for drain timing and pressure dew point temperature. A password protected FACTORY MODE is also included for use with Ingersoll Rand Service Personnel for troubleshooting the dryer.
The Microprocessor Control includes a digital readout for monitoring the discharge pressure of the refrigerant gas exiting the compressor. This reading will vary dependent upon condenser type as indicated below:
• For air-cooled applications, condensing fans are cycled on and off by the Microprocessor Control based on the refrigerant discharge pressure. Primary fan(s) are cycled on at 235 psig and off at 195 psig. Should the discharge pressure continue to climb above 265 psig, the secondary condensing fans will cycle on. As discharge pressure is reduced below 210 psig, the secondary fan(s) will cycle off. On 1000 and 1200 models, two condensing fans are utilized. The 1600 has three condenser fans. For the 1600, the center fan is the primary controlled fan the outside fans are the secondary controlled fans.
• Water cooled condensers utilize a water regulating valve (Note Figure
2). The water regulating valve comes pre-adjusted from the factory at 250 psig discharge pressure. To compensate for water temperature variation, it may be necessary to adjust the water regulating valve to maintain a 250 psig discharge pressure. Adjustment can be done by rotating the adjusting screw counterclockwise for an increase in discharge pressure. For conditions where low water temperature and/or high water pressure are expected it is advisable to install a water pressure regulator ahead of the condenser.
ADJUSTMENT SCREW
FIGURE 2
WATER REGULATING VALVE
7.6.1 BASIC USER INTERFACE
The Microprocessor Control display provides the user with the operating parameters and their corresponding values. When power is supplied to the dryer, the Microprocessor Control will illuminate and default to the “Standby” mode, displaying the “Press ON” prompt.
The following illustration summarizes the keypad functions.
7
Nirvana Cycling Refrigerated Dryer Models 1000-1600
http://air.irco.com
7.0 PRINCIPLES OF OPERATION
7.6.2 DISPLAY PARAMETERS
The Microprocessor Control is capable of displaying a number of system parameters. The following summarizes the parameters that can be accessed by the user from the Microprocessor Control:
• Chiller Temperature (CHLLR TEMP): For Nirvana Cycling Dryers, the Chiller Temperature is the temperature, in degrees Fahrenheit, of the thermal mass fluid.
• Compressor Status (CMPRSSR): Displays whether the refrigeration compressor is “ON” or “OFF”.
• Discharge Pressure (P disch): Displays the discharge pressure of the refrigeration system.
• Suction Temperature (T suction): Displays the suction temperature, in deg. F, of the refrigeration system. This value is useful in determining superheat of the refrigerant.
• Suction Pressure (P suction): Displays the suction pressure, in psig, of the refrigeration system.
• Percent Savings (% SVGS): Displays the length of time the compressor has been operating versus the length of time the dryer has been on.
• Cumulative Dryer Hours (CUM DRYER HR): Displays the length of time, in hours, that the dryer has been operational.
• Cumulative Compressor Operating Hours (CUM CMP HR): Displays the length of time, in hours, that the refrigeration compressor has been energized.
Depressing the SELECT DISPLAY button repeatedly scrolls through the above non-adjustable displays. The Customer Set Points appear at the end of the list and may be adjusted by the end user to match seasonal refrigeration and drain operation. These settings are as follows:
• Chiller Temperature (CHLLR TEMP)
• Drain Interval (DRN INT)
CHLLR TEMP: 37
BUTTONS
• ON
Places the dryer "On Line"; Energizes glycol pump on Nirvana Cycling™ dryers. For Nirvana Cycling™ models, the compressor will operate based on temperature;
• OFF
Places the dryer "Off Line"; Stops all automatic functions, including circulating pump operation on Nirvana Cycling™ dryers.
• SELECT DISPLAY
Allows the user to cycle through the available displays. The last display selected will remain displayed as the default display.
• + / -
Allows user to increase set point values. Set point values cycle through a fixed range. Also allows entering negative numbers in FACTORY MODE.
• TEST
Allows user to manually activate the drain no-loss drain valve.
• RESET
Pressing once clears the local alarm indication and de-energizes the remote alarm contact. Should the alarm condition persist, the alarm will return after the alarm inhibit time has expired.
• SET
Permits the adjustment of parameters in TECHNICAN and FACTORY MODES. In CUSTOMER MODE, allows user to back through displays,
• ENTER
Used to accept changed parameters and set point values.
• i
Restricted Level access for factory use only. Not used for basic dryer functions. Not to be used by customer or service technician.
Loading...
+ 16 hidden pages