Recommended Installation, Maintenance and
MODEL 5827
Inspection Instructions
Balance Vapor Recovery Flo-Equalizer™
Important safety InstructIons - save these InstructIons In a readIly accessIble locatIon.
WARNING Designed for use at motor fuel dispensing facilities only.
INSTALLATION INSTRUCTIONS
1. Turn off dispenser and relieve line pressure.
2. Apply anti-seize (not Teon tape or any other type of
pipe sealant) thinly to threads of Flo-Equalizer™.
4. Tighten rmly but do not overtighten. Refer to UL 567
for details.
5. Lubricate the o-rings on the fuel hose.
6. Insert the hose into the Flo-Equalizer™ and
tighten rmly.
5. Conrm nozzle is properly installed, pressurize the
system and check for leaks.
6. Test nozzle for proper automatic shut off between 5 10 gpm / 18.9 - 37.9 Lpm.
INSTALL DIRECTLY TO THE DISPENSER.
DO NOT OVERTIGHTEN.
DO NOT WRENCH ACROSS COUPLING.
IF DRIVE OFF OCCURS
• Inspect the entire dispensing system for damage.
• Check for leaks.
• Test nozzle for proper automatic shut off between 5 -
10 gpm / 18.9 - 37.9 Lpm.
• Check for electrical conductivity.
TROUBLESHOOTING GUIDE
Nozzle keeps shutting off or won't dispense... 1. Make sure dispenser is on and activated.
2. Check for blocked lter.
3. Reset the nozzle.
Low ow rate... 1. Check for blocked lter.
2. Remove Flo-Equalizer™ and recheck ow rate.
3. Verify dispenser is not in slow ow rate mode.
4. Check for leak detection failures.
Flow rate above 10 gpm / 37.9 Lpm... 1. Verify Flo-Equalizer™ is being used - either inside
2. Check the Flo-Equalizer™ for debris.
or outside dispenser.
TESTING / MAINTENANCE / INSPECTION
FUEL DISPENSER FLOW RATE TEST PROCEDURE
(For 10 gpm / 37.9 Lpm maximum ow rate standard)
***Any volume listed in the chart below may be used:
Gallons / Liters Minimum Time
2.0 gal / 7.6 L 11.8 seconds
3.0 gal / 11.4 L 17.7 seconds
4.0 gal / 15.1 L 23.6 seconds
5.0 gal / 18.9 L 29.5 seconds
1. Observe a vehicle that is being fueled at the
dispenser's maximum ow rate. Start the stopwatch
when the dispenser indicates 1 gal / 3.8 L dispensed.
2. Carefully measure the time that it takes to dispense
exactly 2*** gal / 7.6 L of fuel.
3. If the time is greater than 11.8*** seconds there is not
a violation.
4. If the time is less than or equal to 11.8*** seconds,
repeat the test for another 2*** gal / 7.6 L into the
same vehicle (if possible). If the second test time
is also less than or equal to 11.8*** seconds, use a
calibrated fuel container to verify the accuracy of the
dispenser meter.
5. When the dispenser meter shows 5 gal / 18.9 L
and the volume dispensed is more than 6 cubic
inches over or under the 5 gal / 18.9 L mark on the
calibrated fuel container, note the amount in the
comment area of the fuels inspection form.
5a. If the volume in the calibrated fuel container is 5
gal / 18.9 L or greater, record the two test times
and note as a violation.
Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
5b. If the volume in the calibrated fuel container is
less than 5 gal / 18.9 L by more than 6 cubic
inches, conduct the test on another dispenser.
6. Dispose of the fuel following city, state, or federal
regulations.
Daily
• Check for leaks / stains.
Monthly
• Check nozzle auto shut off between 5 -
10 gpm / 18.9 - 37.9 Lpm.
• Check "remove after" date.
Annually
• Check for electrical conductivity.
• All drive aways, maintenance and inspection activities
must be logged using the serial number of the
individual product.
• Apply city, state, or federal testing regulations as
appropriate.
ANY TEST / INSPECTION FAILURE REQUIRES
IMMEDIATE EQUIPMENT REPLACEMENT OR
REMOVAL FROM SERVICE.
MADE IN THE USA
Page 1 009038-3 1/2013
5827
ALWAYS ADHERE TO INSTALLATION / USAGE INSTRUCTIONS AND WARNINGS.
Improper use may result in injury, damage, or hazardous spill.
GENERAL WARNINGS / INSTRUCTIONS PERTAINING TO A RISK OF FIRE, ELECTRIC
SHOCK OR INJURY TO PERSONS:
• Use of equipment is at individuals’ own risk.
• Always abide and adhere to city, state, and
federal regulations regarding use and
installation of dispensing equipment.
• Always follow the product manufacturer’s
installation and maintenance instructions.
• Always turn off all power to dispenser
during maintenance and inspection activities.
• Always close the shear valves during
maintenance and inspection activities.
• Always relieve pressure from system prior
to performing maintenance activities.
• Always check continuity after installation
using a megohmeter (Refer to PEI RP 400
for details).
• Always replace or remove from service
damaged or leaking dispensing equipment
immediately.
• Always report leaks / spills / accidents
to appropriate authorities.
• Always wear appropriate safety equipment
during maintenance activities.
• Always have appropriate re extinguishing
equipment within 5 ft / 1.5 m of dispensers.
• Always use pipe sealant approved for
gasoline service.
• Always place containers on the ground
before lling.
• Always discharge static electricity before
using or servicing equipment by touching
a metal part of the dispenser before and
after fueling vehicle.
• Never smoke within 20 ft / 6.1 m of dispensers.
• Never keep in service past recommended life.
• Never leave the nozzle unattended while
dispensing fuel.
• Never use sparking or aming devices within 20
ft / 6.1 m of dispensers.
• Never use power tools near dispensers or
to aid in the installation process.
• Never use cell phone within 20 ft / 6.1 m
of dispensers.
• Never reenter car when fueling vehicle.
• Never allow gasoline to touch eyes or skin.
• Never use at ow rates in excess of
regulatory guidelines.
• Never use at ow rates less than 5 gpm /
18.9 Lpm.
• Never dispense ammable material into
unapproved containers.
• Never dispense fuel without a valid
driver’s license.
NOTE: In the event of pressure differential in excess of 25 psi / 1.7 bar across the Flo-
Equalizer™ or the presence of debris obstructing movement of internal components, the
Flo-Equalizer™ output may exceed 10 gpm / 38 Lpm.
Important safety InstructIons - save these InstructIons In a readIly accessIble locatIon.
WARRANTY
VAPOR PRODUCTS – Husky Corporation will, at its option, repair, replace, or credit the purchase price of any Husky
manufactured product which proves upon examination by Husky, to be defective in material and/or workmanship for a period of one (1)
year of installation or fteen (15) months from the manufacture date of shipment by Husky, whichever occurs rst. The warranty period on
repaired or replacement vapor recovery products is only for the remainder of the warranty period of the defective product.
CONVENTIONAL PRODUCTS – Husky Corporation will, at its option, repair, replace, or credit the purchase price of any Husky
manufactured product which proves upon examination by Husky, to be defective in material and/or workmanship for a period of one (1)
year from the manufacture date of shipment by Husky.
Buyer must return the products to Husky, transportation charges prepaid. This Warranty excludes the replaceable bellows,
bellows spring assembly, spout assembly and scuff guard, unless (i) damage is obvious when the product is removed from shipping carton
and (ii) the defective product is returned to Husky prior to use. This warranty does not apply to equipment or parts which have been installed
improperly, damaged by misuse, improper operation or maintenance, or which are altered or repaired in any way.
The warranty provisions contained herein apply only to original purchasers who use the equipment for commercial or
industrial purposes. There are no other warranties of merchantability, tness for a particular purpose, or otherwise, and any other such
warranties are hereby specically disclaimed.
Husky assumes no liability for labor charges or other costs incurred by Buyer incidental to the service, adjustment, repair, return,
removal or replacement of products. Husky assumes no liability for any incidental, consequential, or other damages under any warranty,
express or implied, and all such liability is hereby expressly excluded.
Husky reserves the right to change or improve the design of any Husky fuel dispensing equipment without assuming any
obligations to modify any fuel dispensing equipment previously manufactured.
Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 2 009038-3 1/2013