HPE P9R55A Getting Started Guide

QuickSpecs
HPE G2 Metered Power Distribution Units

Overview

Page 1
Setting new standards for reliable power distribution and metering
HPE Advanced Series G2 Metered PDUs are designed to work precisely with HPE Infrastructure and Compute solutions, providing a highly accurate (billing grade accuracy) power distribution Standard, Advanced, and Enterprise racks (and compatible with other industry guarant t
A major concern for IT administrators and facility managers is their ability to quic in their IT racks
this problem by, first, offering a wide range of models and mounting options that promote flexible power configuration in efficiently utilize rack space while placing access to power where you need it most in the rack with features such as color power cables in the rear of the rack
HPE G2 Metered PDU features to maintain older switch solution configurations that provide up to 48 power outlets while minimizing physical cable solution for monitoring the environmental elements (temperature, humidity, and leakage)
HPE IEC Locking Power Cords are
provide secure cable retention to both the PDU and target device are not dislodged during a service ev issues that lead to power
Why
that promote efficient use of space in the rack and provide flexibility in how
and metering solution for your racks. Designed for use with HPE
-standard server racks), HPE G2 Metered PDUs
ee a compatible fit and reliable operation backed by a 3 year warranty. HPE G2 Metered PDUs are also rated for operating
emperatures up to 60°C, adding an increased level of operational reliability for power distribution in IT racks.
kly diagnose and service power related problems
. The HPE G2 PDU portfolio addresses
IT racks. Vertical, Horizontal, and True 0U mounting, give you the flexibility to
. Serviceability is further enhanced
-coded outlets and low-profile form factors, allowing for simple and quick access to IT equipment and .
are also directly focused on other pain points in the data center. 1Gb Ethernet alleviates the need
s that have been traditionally required for PDU network connectivity. High-density outlet
in a full-height vertical form factor allow for simple access to power in the rack
requirements. Support for up to eight sensors per PDU provides a cost-effective and exhaustive
in both the front and rear of the rack.
a new supported option available for most HPE G2 PDUs. The IEC Locking Power Cords
HPE Metered PDUs?
HPE Foundation Care services purchased for server and storage products, such as extended warranties and premium
support services, extend to our PDU products free of charge when purchased together.
HPE guarantees 100% compatibility between its Rack and Power Infrastructure products and its industry-standard
compute, storage, and networking solutions, backed with a 3-year warranty for all G2 Metered PDU models.
HPE offers multiple Metered PDU form factors
each PDU can be mounted and configured with cables.
-related downtime.
ent. HPE’s IEC Locking Power Cords provide a safe and secure solution against the common
, protecting against vibration during shipping and ensuring that cables
QuickSpecs
HPE G2 Metered Power Distribution Units

Models

Page 2
100-120V Input, Single Phase, North America/Japan
HPE G2 Metered 1.9 kVA/IEC C20 Detachable 16A/120V Outlets (8) 5-20R/1U Horizontal NA/JP PDU
P9R45A
HPE G2 Metered 1.9kVA/IEC C20 Detachable 16A/120V Outlets (16) 5-20R/Vertical NA/JP PDU
P9R46A
HPE G2 Metered 2.8kVA/L5-30P 24A/120V Outlets (24) 5-20R/Vertical NA/JP PDU
P9R48A
HPE G2 Metered 2.8kVA/L5-30P 24A/120V Outlets (16) 5-20R/2U Horizontal NA/JP PDU
P9R49A
NOTE: Models P9R45A and P9R46A include a C19 to NEMA 5-15 detachable input power cord.
100-240V Input, Single Phase, Worldwide
HPE G2 Metered 3.6kVA/IEC C20 Detachable 16A/100-240V Outlets (12) C13/1U Horizontal WW PDU
P9R50A
NOTE: Worldwide models do not include an input power cord. Please go to the Related Options section and select the appropriate input power cord for your geographic location.
200-208V Input, Single Phase, North America/Japan
HPE G2 Metered Modular 4.9kVA/L6-30P 24A/208V Outlets (6) IEC C19/1U Horizontal NA/JP PDU
P9R51A
HPE G2 Metered 4.9kVA/L6-30P 24A/208V Outlets (12) C13, (4) C19/2U Horizontal NA/JP PDU
P9R52A
HPE G2 Metered 4.9kVA/L6-30P 24A/208V Outlets (32) C13, (6) C19/Vertical NA/JP PDU
P9R53A
HPE G2 Metered 8.3kVA/CS8265C 40A/208V Outlets (30) C13, (6) C19/Vertical NA/JP PDU
P9R57A
HPE G2 Metered Modular 8.3kVA/CS8265C 40A/208V Outlets (6) C19/1U Horizontal NA/JP PDU
P9R77A
200-208V Input, Three Phase, North America/Japan
HPE G2 Metered 3Ph 8.6kVA/L15-30P 24A/208V Outlets (18) C13, (6) C19/Vertical NA/JP PDU
P9R58A
HPE G2 Metered 3Ph 8.6kVA/L21-30P 24A/208V Outlets (30) C13, (6) C19, (2) 5-20R/Vertical NA/JP PDU
P9R59A
HPE G2 Metered Modular 3Ph 8.6kVA/L15-30P 24A/208V Outlets (6) C19/1U Horizontal NA/JP PDU
P9R78A
HPE G2 Metered 3Ph 10kVA/CS8365C 35A/208V Outlets (30) C13, (6) C19/Vertical NA/JP PDU
P9R60A
HPE G2 Metered Modular 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (6) C19/1U Horizontal NA/JP PDU
P9R80A
HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (18) C13, (6) C19/Vertical NA/JP PDU
P9R82A
HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (36) C13, (12) C19/Vertical NA/JP PDU
P9R83A
HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (12) C13 (12) C19/Vertical NA/JP PDU
P9R86A
NOTE: Models P9R82A and P9R83A are high density models that have circuit breakers on the back side of the unit.
220-240V Input, Single Phase, International
HPE G2 Metered Modular 7.3kVA/60309 3-Wire 32A/230V Outlets (6) C19/1U Horizontal INTL PDU
P9R54A
HPE G2 Metered 7.3kVA/60309 3-Wire 32A/230V Outlets (12) C13, (4) C19/2U Horizontal INTL PDU
P9R55A
HPE G2 Metered 7.3kVA/60309 3-Wire 32A/230V Outlets (32) C13, (6) C19/Vertical INTL PDU
P9R56A
220-240V Input, Three Phase, International
HPE G2 Metered 3Ph 11kVA/60309 5-Wire 16A/230V Outlets (36) C13, (6) C19/Vertical INTL PDU
P9R61A
HPE G2 Metered Modular 3Ph 11kVA/60309 5-Wire 16A/230V Outlets (6) C19/1U Horizontal INTL PDU
P9R79A
HPE G2 Metered Modular 3Ph 22kVA/60309 5-Wire 32A/230V Outlets (6) C19/1U Horizontal INTL PDU
P9R81A
HPE G2 Metered 3Ph 22kVA/60309 5-Wire 32A/230V Outlets (18) C13, (6) C19/Vertical INTL PDU
P9R84A
HPE G2 Metered 3Ph 22kVA/60309 5-Wire 32A/230V Outlets (36) C13, (12) C19/Vertical INTL PDU
P9R85A
HPE G2 Metered 3Ph 22kVA/60309 5-Wire 32A/230V Outlets (12) C13 (12) C19/Vertical INTL PDU
P9R87A
NOTE: Models P9R84A and P9R85A are high density models that have circuit breakers on the back side of the unit.
QuickSpecs
HPE G2 Metered Power Distribution Units
Models
Page 3
Horizontal Form Factors
1U Horizontal WW Model (P9R50A)
1U Horizontal 120V Model (P9R45A)
QuickSpecs
HPE G2 Metered Power Distribution Units
Models
Page 4
1U Three-Phase Horizontal Model (P9R80A)
Vertical Form Factors
Vertical 120V Model (P9R46A)
Vertical Single Phase Model with 100-240V Output (P9R59A)
QuickSpecs
HPE G2 Metered Power Distribution Units

Key Features

Page 5
Power Metering and Management
All G2 HPE Metered PDUs meet IEC 62053-21, Class 1 standards for ±1% or better accuracy in power
o Kilowatts per hour
An OLED display provides local monitoring and alert indications
CLI, and third-party software applications supporting SNMP
Compatibility
Designed specifically for use with HPE rack enclosures, but compatible with most 3rd party IT racks
Integrated web-based user interface compatible with IPv4/IPv6 and SNMPv1/SNMPv3
Usability
Wide range of mounting options including vertical, 1U/2U horizontal, and True 0U (between the RETMA
Local and remote firmware updates
Security
Local and LDAP security with multiple access levels
Optional dual-locking power cords securing both power connections
HPE G2 Metered PDUs support multiple features that are unique to HPE and help to provide the best user experience. Information on these features is summarized below with additional information found online in HPE G2 Metered PDU User’s Guide.
Rated for High Operating Temperatures
Increasing IT densities and escalating operating costs have created a need for rack infrastructure that can operate reliably at higher operating temperatures rated premium components and construction that support increased reliability levels at elevated temperatures HPE G2 PDUs are rated for operation in temperatures up to 60°C (or 140°F) in the rear of the rack.
IEC Locking Power Cords
HPE G2 PDU models support optional IEC Locking Power Cords with an integrated locking technology on both ends of the cable multiple cable length options, and can be purchased in single or six been included with each PDU model that supports either a C13 and/or C19 outlet.
High-Density Vertical PDU Models
High-density Vertical PDU models provide 24 outlets in a half-height (22U) form factor and 48 outlets in a full­height (42U) form factor access to the circuit breakers on the opposite side without significantly impacting the height (profile) of the PDU. See the Model Matrix section for more information on high-density Vertical PDU models.
Color-Coded Outlets
All HPE G2 PDU models now include color-coded outlets which are highly visible from the rear of the rack. The color configuring your IT equipment.
1Gb Ethernet Support
HPE is the first IT solutions company to standardize on 1Gb Ethernet for PDU network connectivity. This eliminates the need to maintain older switching solutions needed for the 10/100 connectivity provided by most other PDU manufacturers.
metering of:
o Amperage o Voltage o Wattage
Remote PDU management and power monitoring supported through integrated web-based user interface,
rails) configurations
Low-profile PDU form factors ensure integrity of rear-rack keep-out zone for IT maintenance Color-coded receptacles to easily distinguish between the different load segments/phases Integrated cord retention on all IEC C19 and C13 receptacles (does not require any additional brackets)
Support for HTTP, HTTPS, SSH protocols Configurable alarm thresholds for both power and environmental monitoring
. HPE G2 PDUs have been designed with high temperature-
. HPE Locking Power Cord are available for both C13/14 and C19/20 power receptacles in
.
-pack kits. One IEC Locking Power Cord has
. This density is achieved by placing the power receptacles on one side of the PDU and
-coding helps to easily and clearly identify outlets to simplify cabling and power phase balancing when
QuickSpecs
HPE G2 Metered Power Distribution Units
Key Features
Page 6
Environmental Senso
HPE G2 Metered PDU models include two environmental sensor ports (can be upgraded to six ports with the addition of up to two
. Multiple senor options are available prov intrusion for each rack. Please review the Related Options section for a list of the options available.
Flexible Mounting
Most vertical HPE G2 PDU models support mounting on the back and both sides of the PDU using a button and keyhole mounting system for easy drop power cables to be configured toward the front, middle, or rear of the rack, allowing users to c cable management strategy specifically for each rack.
True 0U Mounting
HPE Horizontal PDUs have a unique design specifically for data center customers who want to maximize space efficiencies in the rack. installed in the 0U space between the RETMA rails on HPE Advanced and Enterprise Series racks below).
HPE PDU Extension Bar Option
HPE PDU extension bar options help expand the availability of power in the rear of the rack. Each extension bar includes a locking input power cord that connects to the PDU and supports HPE’s new IEC Locking Power Cords for C13/C14 and C19/C20 outlets models the rack the flexibility of placing access to power where it is options are available to help you customize the outlet configurations you require compatib
C20 outlets (locking feature only supported on new
G2 PDU models). See the Related Options section for more information on G2 Extension Bar models.
3-Year Warranty
HPE G2 Metered PDU models are supported with a 3-year warranty. Additionally, the HPE Foundation Care Extension program provides additional support and services for your PDU models when purchased with HPE servers, storage, and networking solutions at no additional charge Additional informati
http://h17007.www1.hpe.com/us/en/enterprise/servers/warranty/index.aspx#.V-10xE3rvbq
rs
G2 PDU Sensor Port Hubs) that can monitor and record up to eight sensor measurements
iding the ability to monitor temperature, humidity, water leakage, and
-in installation. This provides a flexible mounting capability that allows ustomize their
All HPE 1U Horizontal PDUs can be installed in any U position in your rack or can be
(see figure
s
. HPE PDU extension bars can be added to Horizontal and Vertical PDU
, with available C19 outlets, to add additional power outlets and expand access to power in the back of
when needed. Extension Bars mount directly to the frame of the rack in multiple locations allowing you
needed most (see figure above). Multiple extension bar
extension bars are also
le with previous generation PDU models that offer
on regarding worldwide limited warranty and technical support is available at:
.
QuickSpecs
HPE G2 Metered Power Distribution Units

Related Options

Page 7
Related Options
Extension Bars
HPE G2 IEC C20 Input/(8) C13 Expansion Outlets/PDU Extension Bar Kit
P9Q66A
HPE G2 IEC C20 Input/(4) C13 (2) C19 Expansion Outlets/PDU Extension Bar Kit
P9Q67A
HPE G2 IEC C20 Input/(7) 5-20R Expansion Outlets/PDU Extension Bar Kit
P9Q68A
NOTE: All kits include 2 extension bars with a locking C19 input power cord (1.8m).
IEC Locking Power Cords
HPE C13 - C14 WW 250V 10Amp 0.7m Black Locking Power Cord
Q0P67A
HPE C13 - C14 WW 250V 10Amp 0.7m Black 6-pack Locking Power Cord
Q0Q02A
HPE C13 - C14 WW 250V 10Amp 1.4m Black Locking Power Cord
Q0P68A
HPE C13 - C14 WW 250V 10Amp 1.4m Black 6-pack Locking Power Cord
Q0Q03A
HPE C13 - C14 WW 250V 10Amp 2m Black Locking Power Cord
Q0P69A
HPE C13 - C14 WW 250V 10Amp 2m Black 6-pack Locking Power Cord
Q0Q04A
HPE C13 - C14 WW 250V 10Amp 3m Black Locking Power Cord
Q0P70A
HPE C13 - C14 WW 250V 10Amp 3m Black 6-pack Locking Power Cord
Q0Q05A
HPE C19 - C20 WW 250V 16Amp 0.7m Black Locking Power Cord
Q0R19A
HPE C19 - C20 WW 250V 16Amp 0.7m 6-pack Black Locking Power Cord
Q0R15A
HPE C19 - C20 WW 250V 16Amp 1.2m Black Locking Power Cord
Q0P71A
HPE C19 - C20 WW 250V 16Amp 1.2m 6-pack Black Locking Power Cord
Q0R16A
HPE C19 - C20 WW 250V 16Amp 2m Black Locking Power Cord
Q0P72A
HPE C19 - C20 WW 250V 16Amp 2m 6-pack Black Locking Power Cord
Q0R17A
HPE C19 - C20 WW 250V 16Amp 2.5m Black Locking Power Cord
Q0P73A
HPE C19 - C20 WW 250V 16Amp 2.5m 6-pack Black Locking Power Cord
Q0R18A
NOTE: HPE Locking Power Cords are only supported on either C13/14 or C19/20 power
receptacles using HPE G2 PDUs.
IEC Standard Power Cords
HP C13 - C14 WW 250V 10A Gray 0.7m Jumper Cord
A0K03A
HP C13 - C14 WW 250V 10Amp 0.7m Jumper Cord
142257-B28
HP C13 - C14 WW 250V 10Amp 1.4m Jumper Cord
142257-006
HP C13 - C14 WW 250V 10A Gray 1.37m Jumper Cord
A0K04A
HP C13 - C14 WW 250V 10Amp 1.4m 15 pc Jumper Cord
142257-007
HP C13 - C14 WW 250V 10Amp 2.0m Jumper Cord
A0K02A
HP C13 - C14 WW 250V 10Amp Flint Gray 2.0m Jumper Cord
AF573A
HP C13 - C14 WW 250V 10Amp 2.5m Jumper Cord
142257-002
HP C13 - C14 WW 250V 10Amp 3.0m Jumper Cord
142257-003
HP C13 - C14 WW 250V 10A Gray 3.0m Jumper Cord
A0K06A
HP C20 - C13 WW 250V 15Amp 2.0m Jumper Cord
AF590A
HP C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord
AF575A
HP C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord
AF574A
HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord
295633-B22
HP 200-250V 10A C15 to C14 .76m Jumper Cable
E7807A
Country Powe
HP C13 - NEMA 5-15P US/CA 110V 10Amp 1.83m Power Cord
AF556A
HP C19 - NEMA L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord
AF593A
HP C19 - NBR-14136 BR 250V 16Amp 2.5m Power Cord
AF592A
HP C19 - GB-1002 CN 250V 16Amp 2.5m Power Cord
AF584A
HP C19 - IS-1293 IN/PK/BD 250V 16Amp 2.5m Power Cord
AF582A
HP C19 - ISI-32 IL 250V 16Amp 2.5m Power Cord
AF583A
HP C19 - AS3112-3 AU/NZ 250V 15Amp 3.6m Power Cord
AF577A
-Specific
r Cords
QuickSpecs
HPE G2 Metered Power Distribution Units
Related Options
Page 8
HP C19 - IEC-309 DK/SE/AR 250V 16Amp 3.6m Power Cord
AF581A
HP C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord
AF576A
HP C19 - CEI-23-50 IT/CL 250V 16Amp 3.6m Power Cord
AF580A
HP C19 - SABS-164 ZA 250V 16Amp 3.6m Power Cord
AF579A
HP C19 - BS-1363/A UK/HK/SG 250V 13Amp 3.6m Power Cord
359615-031
HP 240 VAC 4.5M Unterminated End NA Power Cord
E7806A
HPE Mounting Brackets
HPE Vertical PDU 10K G2 Mounting Kit
H6L32A
NOTE: This kit allows for vertical HPE G2 PDU models to be mounted in HPE 10000 G2 series racks and in the HPE Standard Series rack.
Environmental Sen
HPE G2 Metered PDUs include 2 physical sensor ports and can monitor and record up to eight sensor measurements. Data collected by each sensor can be viewed and managed through the integrated graphical user interface (GUI), or by third supported API software applications.
HPE G2 PDU Environmental Temperature Sensor
NOTE: Requires one input port and monitor/records one sensor measurement.
P9T00A
HPE G2 PDU Environmental Temperature and Humidity Sensor
NOTE:
P9T01A
HPE G2 PDU Environmental 3-Temperature and 1-Humidty Sensor
NOTE:
P9T02A
HPE G2 PDU Open/Close Door Sensor
NOTE: Requires two input ports and monitors/records two sensor measurements.
P9T03A
HPE G2 PDU Leak Detection Sensor
NOTE:
covers up to six linear meters and can be expanded to cover up to thirty linear meters with the addition of up to four HPE G2 PDU Leak Detection Sensor Extension Kits (P9T08A).
P9T04A
HPE G2 PDU Sensor Port Hub
NOTE:
sensor ports.
P9T07A
HPE G2 PDU Leak Detection Sensor Extension Kit
NOTE:
conjunction with this kit. Up to four Extension Kits can be added to a single Leak Detection Sensor to cover up to a maximum of thirty linear meters.
P9T08A
sors
-party applications that communicate through SNMP or through a Redfish
. Consult the HPE G2 Metered PDU User Guide for more information on use with third-party
Requires one input port and monitors/records two sensor measurements.
Requires one input port and monitors/records four sensor measurements.
Requires one input port and monitors/records one sensor measurement. Kit
This is an adapter that expands a single physical sensor port into three physical
Leak Detection Sensor (P9T04A) must be purchased separately to use in
QuickSpecs
HPE G2 Metered Power Distribution Units
Model Matrix
– Input Power
Page 9
Mounting options for Horizontal 1U and 2U PDU models
W x H x D
(inches)
Unit Weight
(lbs.)
Horizontal
Mounting
P9R45A
17.461 x 1.713 x 10.62
8.4
1U
P9R49A
17.461 x 3.425 x 10.62
14.2
2U
-
P9R50A
17.461 x 1.713 x 10.62
8.6
1U
17.461 x 1.713 x 10.62
1U
-
P9R54A
17.461 x 1.713 x 10.62
12.3
1U
P9R55A
17.461 x 3.425 x 10.62
13.8
2U
-
P9R77A
17.461 x 1.713 x 10.62
16.5
1U
P9R78A
17.461 x 1.713 x 10.62
16.0
1U
P9R79A
17.461 x 1.713 x 10.62
12.0
1U
P9R80A
17.461 x 1.713 x 10.62
22.9
1U
P9R81A
17.461 x 1.713 x 10.62
15.5
1U
Mounting options for Vertical PDU models in HPE Advanced and Enterprise racks (1075mm depth)
W x H x D
Unit Weight
Maximum PDUs per Side of Rack
22U
36U
42U
48U
P9R46A
2.047 x 32.165 x 2.087
8.3
Half-Height
2 2 4
4
P9R48A
2.047 x 58.661 x 2.087
14.1
Mid-Height
- 2 2
2
P9R53A
2.047 x 68.898 x 2.087
16.0
Full-Height
- - 2
2
P9R56A
2.047 x 68.898 x 2.087
14.4
Full-Height
- - 2
2
P9R57A
2.047 x 68.898 x 2.953
17.6
Full-Height
- - 2
2
P9R58A
2.047 x 58.661 x 2.953
14.5
Mid-Height
- 2 2
2
P9R59A
2.047 x 68.898 x 2.953
17.2
Full-Height
- - 2
2
P9R60A
2.047 x 68.898 x 2.953
18.0
Full-Height
- - 2
2
P9R61A
2.047 x 68.898 x 2.087
12.5
Full-Height
- - 2
2
P9R82A*
2.047 x 36.024 x 4.409
23.8
Half-Height
1 1 2
2
P9R83A*
2.047 x 71.654 x 4.409
31.0
Full-Height
- - 1
1
P9R84A*
2.047 x 36.024 x 4.409
14.2
Half-Height
1 1 2
2
P9R85A*
2.047 x 71.654 x 4.409
23.6
Full-Height
- - 1
1
P9R86A
2.047 x 68.898 x 2.953
24.8
Full-Height
- - 2
2
P9R87A
2.047 x 68.898 x 2.953
16.2
Full-Height
- - 2
2
*HPE high density model mounts on its side with outlets facing the back of the rack
NOTE: HPE G2 Advanced and Enterprise 1200mm deep racks include an extra set (2) of PDU trays in the rear of the rack enabling support of up to 2x the number of PDUs listed above for 1075mm deep racks.
Model
P9R51A P9R52A
Model
17.461 x 3.425 x 10.62
(inches)
15.5
14.5
(lbs.)
U Height
2U
Vertical Height
True 0U Mounting
QuickSpecs
HPE G2 Metered Power Distribution Units
Model Matrix
Page 10
Phase & Input
Voltage
Input
Circuit
Circuit
Breakers
Input Plug
Type
Input Cord
Length
P9R45A
NA/JP
1-ph, 120V
16A
none
C20 Inlet
12' (detachable)
P9R46A
NA/JP
1-ph, 120V
16A
none
C20 Inlet
12' (detachable)
P9R48A
NA/JP
1-ph, 120V
24A
(2) 1-pole, 20A
L5-30P
10'
P9R49A
NA/JP
1-ph, 120V
24A
(2) 1-pole, 20A
L5-30P
12'
P9R50A
WW
1-ph, 100-240V
16A
none
C20 Inlet
Cord Not Included
P9R51A
NA/JP
1-ph, 208V
24A
(2) 2-pole 20A
L6-30P
12'
P9R52A
NA/JP
1-ph, 208V
24A
(2) 2-pole 20A
L6-30P
12'
P9R53A
NA/JP
1-ph, 208V
24A
(2) 2-pole 20A
L6-30P
10'
P9R54A
INTL
1-ph, 230V
32A
(2) 1-pole, 16A
IEC 32A, 1ph
12'
P9R55A
INTL
1-ph, 230V
32A
(2) 1-pole, 16A
IEC 32A, 1ph
12'
P9R56A
INTL
1-ph, 230V
32A
(2) 1-pole, 16A
IEC 32A, 1ph
10'
P9R57A
NA/JP
1-ph, 208V
40A
(3) 2-pole 20A
CS8265C
10'
P9R58A
NA/JP
3-ph, 208V
24A
(3) 2-pole 20A
L15-30P
10'
P9R59A
NA/JP
3-ph, 208V
24A
(3) 2-pole 20A
L21-30P
10'
P9R60A
NA/JP
3-ph, 208V
35A
(3) 2-pole 20A
CS8365C
10'
P9R61A
INTL
3-ph, 400V
16A
none
IEC 16A, 3ph
10'
P9R77A
NA/JP
1-ph, 208V
40A
(3) 2-pole 20A
CS8265C
12'
P9R78A
NA/JP
3-ph, 208V
24A
(3) 2-pole 20A
L15-30P
12'
P9R79A
INTL
3-ph, 400V
16A
none
IEC 16A, 3ph
12'
P9R80A
NA/JP
3-ph, 208V
48A
(6) 2-pole 20A
IEC 60A, 3ph
12'
P9R81A
INTL
3-ph, 400V
32A
(6) 1-pole, 16A
IEC 32A, 3ph
12'
P9R82A
NA/JP
3-ph, 208V
48A
(6) 2-pole 20A
IEC 60A, 3ph
10'
P9R83A
NA/JP
3-ph, 208V
48A
(6) 2-pole 20A
IEC 60A, 3ph
10'
P9R84A
INTL
3-ph, 400V
32A
(6) 1-pole, 16A
IEC 32A, 3ph
10'
P9R85A
INTL
3-ph, 400V
32A
(6) 1-pole, 16A
IEC 32A, 3ph
10'
P9R86A
NA/JP
3-ph, 208V
48A
(6) 2-pole 20A
IEC 60A, 3ph
10'
P9R87A
INTL
3-ph, 400V
32A
(6) 1-pole, 16A
IEC 32A, 3ph
10'
NOTE: All Input Circuit Ratings for NA/JP models have been de-rated according to NEC requirements.
Nominal Input Voltage Ratings used for calculating output power are as follows:
Model Region
– Input Power
100 – 120V: 120V
200 – 208V: 208V
100 – 240V: 230V
220 – 240V: 230V
200 – 240V/346 – 415V: 230V
QuickSpecs
HPE G2 Metered Power Distribution Units
Model Matrix
– Output Power
Page 11
Output
Range
Support Extension
Power
P9R45A
NA/JP
1.9
100-125V
(8)5-20R
-
-
P9R46A
NA/JP
1.9
100-125V
(16)5-20R
-
-
P9R48A
NA/JP
2.8
100-125V
(24)5-20R
-
-
P9R49A
NA/JP
2.8
100-125V
(16)5-20R
-
-
P9R50A
WW
3.6
100-240V
(12)C13
-
P9R51A
NA/JP
4.9
200-240V
(6)C19
P9R52A
NA/JP
4.9
200-240V
(12)C13, (4)C19
P9R53A
NA/JP
4.9
200-240V
(32)C13, (6)C19
P9R54A
INTL
7.3
220-240V
(6)C19
P9R55A
INTL
7.3
220-240V
(12)C13, (4)C19
P9R56A
INTL
7.3
220-240V
(32)C13, (6)C19
P9R57A
NA/JP
8.3
200-240V
(30)C13, (6)C19
P9R58A
NA/JP
8.6
200-240V
(18)C13, (6)C19
P9R59A
NA/JP
8.6
100-240V
(30)C13, (6)C19, (2)5-20R
P9R60A
NA/JP
10
200-240V
(30)C13, (6)C19
P9R61A
INTL
11
220-240V
(36)C13, (6)C19
P9R77A
NA/JP
8.3
200-240V
(6)C19
P9R78A
NA/JP
8.6
200-240V
(6)C19
P9R79A
INTL
11
220-240V
(6)C19
P9R80A
NA/JP
17.3
200-240V
(6)C19
P9R81A
INTL
22
220-240V
(6)C19
200-240V
(18)C13, (6)C19
200-240V
(36)C13, (12)C19
220-240V
(18)C13, (6)C19
P9R85A
INTL
22
P9R86A
NA/JP
17.3
P9R87A
INTL
22
NOTE: For more information on Extension Bar and Power Cord options, please see the Related Options section.
Model Region
Nominal
Power (kVA)
Voltage
Output
Receptacles
Bar Options
Support Locking
Cord Options
P9R82A NA/JP 17.3 P9R83A NA/JP 17.3 P9R84A INTL 22
220-240V (36)C13, (12)C19 200-240V (12)C13, (12)C19 220-240V (12)C13, (12)C19
QuickSpecs
HPE G2 Metered Power Distribution Units

PDU Plugs

Page 12
Sample Plug Image
(color may vary by manufacturer)
Receptacle (R)
Plug (P)
3
Voltage Amps # Wires Plug Name
100-125 V
Single Phase
200-240 V
Single Phase
15 A 3 NEMA 5-15
20 A 3 NEMA 5-20
30 A 3 NEMA L5-30
20 A 3 IEC C20
30 A 3 NEMA L6-30
32 A 3 IEC 309 32A
50 A
CS8265C
63 A 3 IEC 309 63A
200 - 208 V
Three Phase
200 – 240 V 400 – 415 V
Three Phase
NA/JPN
INTL
30 A 5 NEMA L15-30
30 A 5 NEMA L21-30
50 A 4 CS8365C
60 A 4 IEC 309 60A
16 A 5 IEC 309 16 A
32 A 5 IEC 309 32 A