HP (Hewlett-Packard) 6269b User Manual

TM 11-6625-2958-14&P
TECHNICAL MANUAL
OPERATOR’S, ORGANIZATIONAL,
DIRECT SUPPORT AND GENERAL SUPPORT
MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS
AND SPECIAL TOOLS LIST)
FOR
(HEWLETT-PACKARD MODEL 6269B)
(NSN 6130-00-148-1796)
HEADQUARTERS, DEPARTMENT OF THE ARMY
21 AUGUST 1980
SAFETY STEPS TO FOLLOW IF SOMEONE
IS THE VICTIM OF ELECTRICAL SHOCK
DO NOT TRY TO PULL OR GRAB THE INDIVIDUAL
IF POSSIBLE , TURN OFF THE ELECTRICAL POWER
IF YOU CANNOT TURN OFF THE ELECTRICAL POWER, PULL, PUSH, OR LIFT THE PERSON TO
SAFETY USING A WOODEN POLE OR A ROPE OR
SOME OTHER INSULATING MATERIAL
SEND FOR HELP AS SOON AS POSSIBLE
AFTER THE INJURED PERSON IS FREE OF
CONTACT
WITH THE SOURCE OF ELECTRICAL
SHOCK, MOVE THE PERSON A SHORT DISTANCE AWAY AND IMMEDIATELY START ARTIFICIAL
RESUSCITATION
This manual includes copyright material reproduced by permission of the HEWLETT-PACKARD Company.
TM 11-6625-2958-14&P
TECHNICAL MANUAL No. 11-6625-2958-14&P
DEPARTMENT OF THE ARMY
Washington DC, 21 August 1980
HEADQUARTERS
OPERATOR’S, ORGANIZATIONAL, DIRECT SUPPORT AND
GENERAL SUPPORT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LISTS)
FOR
DC POWER SUPPLY PP-7545/U
(HEWLETT-PACKARD MODEL 6269B)
(NSN 6130-00-148-1796)
FOR SERIALS 1027A00101 AND ABOVE*
REPORTING OF ERRORS
You can improve this manual by recommending improvements using DA Form 2028-2 located in the back of the manual. Simply tear out the self-addressed form, fill it out as shown on the sam­ple, fold it where shown, and drop it in the mail.
If there are no blank DA Forms 2028-2 in the back of your manual, use the standard DA Form 2028 (Recommended Changes to Publications and Blank Forms) and forward to Commander, US Army Communications and Electronics Materiel Readiness Command, ATTN: DRSEL-ME-MQ, Fort Monmouth, NJ 07703.
In either case a reply will be forwarded direct to y
OU.
This manual is an authentication of the manufacturer's commercial literature which, through usage, has been found to cover the data required to operate and maintain this equipment. Since the manual was not prepared0 in accordance with military specifications and AR 310-3, the format has not been structured to consider Ievels of maintenance.
i
TABLE OF CONTENTS
Section
0
INSTRUCTIONS
0-1 Scope 0-2 Indexes of Publications
0-3 Forms and Records 0-4 Reporting Equipment Im-
provement Recom­mendations (EIR) 0-1
0-5 Administrative Storage 0-6 Destruction of Army
Electronics Materiel 0-1
I GENERAL INFORMATION. . . . . . . . 1-1
1-1 Description 1-7 Specifications 1-9 Options 1-11 Instrument/Manual
Identification
1-14 Ordering Additional Manuals 1-3
II INSTALLATION . . . . . . . . 2-1
2-1
Initial Inspection
2-3
Mechanical Check
2-5
Electrical Check
2-7
Installation Data
2-9
Location
2-11
Outline Diagram
2-13
Rack Mounting
2-15
Input Power Requirements
2-17
Connections for 208 Volt
Operation (Model 6259B, 6261B, or 6268B)
2-19
Connections for 208 Volt
Operation (Model 6260B and 6269B)
2-21
Connections for 115 Volt
Operation (Model 6259B,
6261B, and 6268B)
2-23
Connections for 115 Volt
Operation (Model 6260B)
2-25
Connections for 50Hz
Operation
2-27
Power Cable
2-29
Repackaging for Shipment
III OPERATING INSTRUCTIONS . . . . . . . .3-1
3-1 Turn-On Checkout Procecdure 3-1 3-3 Operating Modes
3-5 Normal Operating Mode 3-7 Constant Voltage 3-9 Constant Current 3-11 Overvoltage Trip
Point Adjustment 3-14 Connecting Load 3-18 No Load Operation 3-20 Operation Beyond
Rated Output
. . . . . . . . . . . . . . .
Page No.
6-1 0-1
0-1
0-1
0-1
1-1 1-2 1-2
1-2
2-1 2-1
2-1 2-1 2-1 2-1 2-1 2-1
2-1
2-2
2-3 2-3 2-4
2-4 2-4
3-1
3-1 3-2 3-2
3-2 3-2 3-2
3-3
iii
Section
3-22
Optional Operating Modes
3-23
Remote Programming,
3-32
3-41 3-46 3-50 3-55 3-59
3-60
3-62 3-65
3-67
IV PRINCIPLES OF OPERATION.. . . . ...4-1
4-1
4-16 4-17 4-27 4-29 4-31
4-38 4-43 4-46 4-50
4-56
4-59 4-64 4-68
v
MAINTENANCE . . . . . . . . . . . . . . . . . .. 5-1
5-1 5-3 5-5
5-7 5-40 5-51
5-56 5-62
5-71 5-73 5-75
5-77 5-79
5-81 5-90 .5-99
5-101 Ripple Imbalance 150 and
Constant Voltage
Remote Programming,
Constant Current
Remote Sensing Auto-Parallel Operation Auto-Series Operation
Auto-Tracking Operation
Special Operating
Considerations
Pulse Loading
Output Capacitance
Reverse Voltage Loading Reverse Current Loading
Overall BIock Diagram
Discussion Detailed Circuit Analysis Preregulator Control Circuit Series Regulator and Driver
Short Circuit Protection Constant Voltage Comparator Constant Current Comparator
Voltage Clamp Circuit
Mixer and Error Amplifiers
Overvoltage Protection
Crowbar
Turn-On Control Circuit Reference Regulator Meter Circuit
Additional Protection Features
Introduction
Test Equipment Required
performance Test Constant Voltage Tests Constant Current Tests
Troubles hooting
Overall Troubleshooting
Procedure
Disassembly Procedures
Repair and Replacement Adjustment and Calibration Meter Zero Voltmeter Calibration
Ammeter Calibration
Constant Voltage
Programming Current
Constant Current
Programming Current
Transient Recovery Time
60Hz Operation)
Page No.
3-3 3-3
3-4 3-5 3-6 3-7
3-8 3-8
3-8
3-9 3-9
3-9
4-1 4-3 4-3
4-4 4-4 4-5
4-5 4-6 4-6
4-6 4-7
4-7 4-7 4-8
5-l 5-1
5-2 5-2 5-7 5-9
5-10
5-15 5-16 5-18 5-18 5-18
5-18 5-19
5-20 5-20
5-20
Section
V MAINTANCE . . Continued
5-103 Preregulator Tracking (5 O and
60Hz Operation) 5-105 50Hz Operation (Option 005) 5-21 5-107 Crowbar Trip Voltage 5-109 Maximum Crowbar
Trip Voltage
TABLE OF CONTENTS (Continued)
Page No.
5-21 VI REPLACEABLE PARTS . . . . . . . . . . . ...6-1
5-21 6-4 Ordering Information 5-22 VII CIRCUIT DIAGRAMS & COMPONENT
Section
5-111 Crowbar Disablement
6-1 Introduction
LOCATION DIAGRAMS . . . . . . . . . . . 7-1
Page No.
5-22
6-1 6-1
APPENDIX
Section
APPENDIX
Section
Table
1-1 5-1
5-2 5-3 5-4 5-5 5-6 5-7 5-8 6-1 6-2 6-3 6-4
6-5
A.
B.
I.
II.
III. c. D.
I.
II.
111. Iv.
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test Equipment Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference and Bias Voltages. . Overall Troubleshooting Feedback Loop Isolation . .
Series Regulator Troubleshooting, High Voltage Condition . . . . . . . . . . . . . . . . ...5-13
Series Regulator Troubleshooting, Low Voltage Condition. . . . . . . . . . . . . . . . . ...5-13
Preregulator Troubleshooting
Checks and Adjustments After Replacement of Semiconductor Devices . . . . . . . . .5-17
Reference Designators. . .
Description Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...6-1
Code List of Manufacturers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replaceable Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part Number-National Stock Number Cross Reference Index . . . . . . . 6-12
References Components of End Item List
Introduction
Integral Components of End Item Basic Issue Items Additional Authorization List (N/A) Maintenance Allocation Chart
Introduction Maintenance Allocation Chart Tools and Test Equipment Required
Remarks
LIST OF TABLES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page No.
A-1
D-1 D-1
D-3
D-4 D-5
Page No
1-3 5-1 5-10 5-10 5-12
5-14 6-1 6-2
6-5
MANUAL CHANGES
Check the serial number of your power supply. Then refer to the manual changes at the rear
of this technical manual and make changes as required so that your power supply can be correctly serviced.
iv
LIST OF ILLUSTRATIONS
Figure
1-1 DC Power Supply, Model 6259B, 6260B, 6261B, 6268B, or 6269B . . . . . . . . . . . .. l-l
2-1 Outline Diagram . . . . . . . . . . .
2-2 Bias Transformer Primary Connections for 208Vac and 115Vac Operation . . . . . . .2-2
2-3
Power Transformer Primary Connections for 208Vac and 115Vac Operation . . . ...2-2
2-4 Power Transformer T1 Primary Connections for 208Vac Operation. . . . . . . . . . . . .. 2-3
2-5 RF I Choke (A2L1A/A2L1B) Connections for 115Vac Operation . . . . . . . . . . . . . . ...2-3
3-1 Front Panel Controls and Indicators
3-2 Normal Strapping Pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...3-2
3-3 Remote Resistance Programming (Constant Voltage) . . . . . . . . . . . . . . . . . . . . . . ...3-3
3-4 Remote Voltage Programming, Unity Gain (Constant Voltage) . . . . . . . . . . . . . . ...3-3
3-5 Remote Voltage Programming, Non-Unity Gain (Constant Voltage). . . . . . . . . . ...3-4
3-6 Remote Resistance Programming (Constant Current) . . . . . . . . . . . . . . . . . . . . . . ...3-4
3-7 Remote Voltage Programming, Unity Gain (Constant Current) . . . . . . . . . . . . . . ...3-5
3-8 Remote Voltage Programming, Non-Unity Gain (Constant Current). . . . . . . . . . ...3-5
3-9 Remote Sensing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-10 Auto-Parallel Operation, Two and Three Units . . . . . . . . . . . . . . . . . . . . . . . . . . ...3-6
3-11 Auto-Series Operation, Two and Three Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...3-7
3-12 Auto-Tracking, Two and Three Units
4-1 Overall Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4-1
4-2 Operating Locus of a CV/CC Power Supply
4-3 Triac Phase Control Over AC Input Amplitude . . . . . . . . . . . . . . . . . . . . . . . . . . . ...4-3
4-4 Preregulator Control Circuit Waveforms . . . .
5-1 Differential Voltmeter Substitute Test Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Constant Voltage Load Regulation Test Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Ripple Test Setup
5-4 Noise Spike Measurement Test Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...5-5
Transient Recovery Time Test Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...5-6
5-5
5-6 Transient Recovery Time Waveforms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...5-6
5-7 Current Sampling Resistor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...5-8
5-8 Constant Current Load Regulation Test Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . ...5-8
5-9 Constant Current Ripple and Noise Test Setup . . . . . . . . . . . . . . . . . . . . . . . . . . ...5-9
5-10 “ZERO ADJUST’’ Section of Main Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . ...5-19
7-1 A2 RFI Assembly Component Location Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . ...7-2
7-2 A3 Interconnection Circuit Board Assembly Component Location Diagram. . . . ...7-2
7-3 Top Front Chassis Assembly Component Location Diagram . . . . . . . . . . . . . . . . . . . . 7-3
7-4 Bottom Front Chassis Assembly Component Location Diagram . . . . . . . . . . . . . ...7-4
7-5 Bottom Rear Chassis Assembly Component Location Diagram . . . . . . . . . . . . . . ...7-5
7-6 Series Regulator Emitter Resistor Assembly Component Location Diagram . . . ...7-6
7-7 A4 Heat Sink Assembly Component Location Diagram (Top View) . . . . . . . . . . . ...7-6
7-8 A4 Heat Sink Assembly Component Location Diagram (End View) . . . . . . . . . . . ...7-7
7-9 Preregulator Control Circuit Waveforms
7-10 A1 Main Printed Circuit Board Component Location Diagram. . . . . . . . . . . . . . . ...7-8
7-11 Schematic Diagram . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page No.
2-1
3-1
3-5
3-8 4-2 4-4
5-2 5-3 5-4
7-7
Foldout
v
SECTION O
INTRODUCTION
TM 11-6625-2958-14&P
0-1. SCOPE.
a. This manual describes DC Power
Supply PP-7545/U (fig. l-l) and
provides maintenance instructions. Throughout this manual, PP-7545/U is referred to as the Hewlett-Pack-
4430.3E
and DSAR 4140.55.
c. Discrepancy in Shipment Report (DISREP)
(SF 361). Fill out and forward Discrepancy in
Shipment Report (DISREP) (SF 361) as prescribed in AR 55-38/NAVSUPlNST 4610.33B/AFR 75-
18\MCO P4610.19C and DLAR 4500.15. ard (HP) Model 6269B DC Power supply.
0-4. REPORTING EQUIPMENT
IMPROVEMENT
RECOMMENDATIONS (EIR).
0-2. INDEXES OF PUBLICATIONS.
a. DA Pam 310-4. Refer to the latest issue of DA Pam 310-4 to determine whether there are new editions, changes, additional publications per-
.
taining to the equipment.
b. DA Pam 310-7: Refer to DA Pam 310-7 to determine whether there are modification work orders (MWO’s) pertaining to the equipment.
0-3. FORMS AND RECORDS.
a. Reports of Maintenance and Unsatisfactory Equipment. Maintenance forms, records, and reports which are to be used by maintenance per-
EIR’s will be prepared using SF 368 (Quality Defi­ciency Report). Instructions for preparing EIR’s are provided in TM 38-750, the Army Mainten­ance Management System. El R’s should be mailed direct to Commander, US Army Communication and Electronics Materiel Readiness Command, ATTN: DRSEL-ME-MQ, Fort Monmouth, NJ
07703. A reply will be furnished direct to you. 0-5. ADMINISTRATIVE STORAGE.
Administrative storage of equipment issued to and used by Army activities shall be in accordance with
TM 740-90-1 and paragraph 2-8.
sonnel at all maintenance levels are listed in and
SCribed by TM 38-750.
pre
b. Report of Packaging and Handling Deficien­ties. FiII out and forward DD Form 6 (Packaging Improvement Report) as prescribed in AR 735-11
-2/NAVUPINST4440.127E/AFR 400-54/MCO
0-6. DESTRUCTION OF ARMY
ELECTRONICS MATERIEL.
Destruction of Army electronics materiel to pre­vent enemy use shall be in accordance with TM 750-244-2.
SAFETY PRECAUTIONS.
A periodic review of safety precautions in TB 385-4 is
recommended.
When the equipment is operated with covers
removed while performing maintenance, DO NOT TOUCH ex­posed connections or compments. MAKE CERTAIN you are not grounded when making connections or adjusting com­ponents inside the power supply.
WARNING
HIGH VOLTAGE is used during the “performance of maintenance as instructed in this manual. DEATH ON CONTACT may result if personnel fail to observe safety precautions.
0-1

SECTION I

GENERAL INFORMATION
TM 11-6625-2958-14&P
Figure 1-1.
1-1 DESCRIPTION
1-2 This power supply, Figure 1-1, is completely transistorized and suitable for either bench or relay rack operation. It is a well-regulated, constant voltage/constant current supply that will furnish full rated output voltage at the maximum rated out­put current or can be continuously adjusted through­out the output range. The front panel CURRENT con­trols can be used to establish the output current limit (overload or short circuit) when the supply is used as a constant voltage source and the VOLTAGE controls can be used to establish the voltage limit
(ceiling) when the supply is used as a constant cur­rent source. The supply will automatically cross over from constant voltage to constant current oper-
ation and vice versa if the output current or voltage exceeds these preset limits.
1-3 The power supply contains an added feature for protection of delicate loads. A limit can be set on the output voltage. If this limit is exceeded the output will automatically be shorted.
DC Power Supply, Model 6259B, 6260B, 6261B, 6268B, or 6269B
1-4 The power supply has rear output terminals. Either the positive or negative output terminal may be grounded or the power supply can be operated floating at up to a maximum of 300 volts above ground.
1-5 Output voltage and current are continuously monitored on two front panel meters.
1-6 TerminaIs located at the rear of the unit allow access to various control points within the unit to expand the operating capabilities of the power sup­ply. A brief description of these capabilities is
given below:
a. Remote Programming. The power supply output voltage or current may be programmed (con- trolled) from a remote location by means of an ex­ternal voltage source or resistarice.
b. Remote-Sensing. The degradation in regu­lation which occurs at the load due to voltage drop in the load leads can be reduced by using the pow­er supply in the remote sensing mode of operation.
c. Auto-Series Operation. Power supplies
1-1
TM 11-6625-2958-14&P may be used in series when a higher output voltage is required in the constant voltage mode of opera-
t ion or when greater voltage compliance is required
in the constant current mode of operation. Auto­Series operation permits one-knob control of the
total output voltage from a “master” supply.
d. Auto-Parallel Operation. The power sup-
ply may be operated in parallel with a similar unit when greater output current capability is required. Auto-Parallel operation permits one-knob control of the total output current from a “master” supply.
e. Auto-Tracking. The power supply may be
used as a “master” supply controlling one or more
“slave” supplies furnishing various voltages for a
system.
1-7 SPECIFICATIONS
1-8 Detailed specifications for the power supply
are given in Table 1-1 on Page 1-3.
1-9 OPTIONS
1-10 Options are customer-requested factory mod­ifications of a standard instrument. options are available for the instrument covered by this manual. Where necessary, detailed coverage of the options is included throughout the manual.
Option No.
005
007
008
009
010
013
50Hz Regulator Realignment: Stand-
ard instruments are designed for 57 to
63 Hz operation. Option 005 (factory
realignment) is necessary when the
instrument is to be operated from a
50Hz ac source. The option consists
of changing a resistor in the preregu -
lator circuit and adjusting the prereg­ulator tracking.
Ten-Turn Output Voltage Control:
A single control that replaces the
coarse voltage control and allows
greater resolution in setting the out-
put voltage.
Ten-Turn Output Current Control:
A single control that replaces the
coarse current control and allows greater resolution in setting the out­put current.
Ten-Turn Output Voltage and Current Controls: Options 007 and 008 on the same instrument.
Chassis Slides: Enables convenient access to power supply interior for maintenance purposes.
Three Digit Graduated Decadial Voltage Control: A single control that replaces the coarse voltage control and allows accurate resetting of the output voltage.
Description
The following
Option No.
014
020
021
022
027
1-11 lNSTRUMENT/MANUAL IDENTIFICATION
1-12 Hewlett-Packard power supplies are identified by a two-part serial number. The first part is the serial number prefix, a number-letter combination
that denotes the date of a significant design change and the country of manufacture. The first two digits
indicate the year (10= 1970, 11= 1971, etc.), the second two digits indicate the week, and the letter “A” designates the U.S.A. as the country of manu-
facture. The second part is the power supply serial number; to each power supply, starting with 00101.
1-13 If the serial number on your instrument does not agree with those on the title page of the manual, Change Sheets supplied with the manual or Manual Backdating Changes in Appendix A define the dif­ferences between your instrument and the instru­ment described by this manual.
a different sequential number is assigned
Three Digit Graduated Decadial Cur­rent Control: replaces the coarse current control and allows accurate resetting of the output current.
Rewire for 115Vac Input (6260B only): Consists of replacing the input power transformer and circuit breaker, and reconnecting the bias transformer, RFI choke, and fans for 115Vac operation.
Voltage Programming Adjustment: Two rear panel mounted, screwdriver­adjustable controls that allow accu-
rately setting the zero volt output and the constant voltage programming co­efficient.
Current Programming Adjustment:
Two rear panel mounted, screwdriver­adjustable controls that allow accu­rately setting the zero current output and the constant current programming coefficient.
Voltage and Current Programming
Adjustments: Options 020 and 021 on the same instrument.
Rewire for 115Vac Input (6259B,
6261B, and 6268B only): Consists of replacing the line circuit breaker, and reconnecting the input power transfor­mer, bias transformer, RF I choke, and fans for 115Vac operation.
Rewire for 208Vac Input: Consists of reconnecting the input power trans­former and bias transformer for 208V ac operation.
Description
A single control that
1-2
1-14 ORDERING ADDITIONAL MANUALS
1-15 One manual is shipped with each power sup-
ply. Additional manuals may be purchased from
Table 1-1. Specifications
TM 11-6625-2958-14&P your local Hewlett-Packard field office (see list at rear of this manual for addresses). Specify the model number, serial number prefix, and HP part number shown on the title page.
INPUT:
230Vac *10%, single phase, 57-63 Hz, 18A,
2500W @ 230V.
OUTPUT :
0-40 volts @ 0-50 amperes.
LOAD REGULATION:
Constant Voltage - Less than 0.01% plus 200µV for a load current change equal to the current rating of the supply.
Constant Current - Less than 0.02% plus 2mA for a load voltage change equal to the voltage rating of the supply.
LINE REGULATION :
Constant Voltage - Less than 0.01% plus 200µV
for a change in line voltage from 207 to 253 volts
at any output voltage and current within rating.
Constant Current - Less than 0.02% plus 2mA for a change in line voltage from 207 to 253 volts at any output voltage and current within rating.
RIPPLE AND NOISE:
Constant Voltage - Less than 1mV rms, 5mV P-P (dc to 20MHz).
Constant Current - Less than 25mA rms. TEMPERATURE RATINGS:
Operating: O to 55°C. Storage: -40 to +75°C.
TEMPERATURE COEFFICIENT:
Constant Voltage - Less than O .01% plus 200µV
change in output per degree Centigrade change in
ambient following 30 minutes warm-up.
Constant Current - Less than 0.01% plus 4mA change in output per degree Centigrade change in ambient following 30 minutes warm-up.
STABILITY :
Constant Voltage - Less than O .03% plus 2mV total drift for 8 hours following 30 minutes warm­up under constant ambient conditions.
Constant Current- Less than 0.03% plus 10mA total drift for 8 hours following 30 minutes warm­up under constant ambient conditions.
TRANSIENT RECOVERY TIME:
Less than 50µsec is required for output voltage
recovery (in constant voltage operation) to within
10mV of the nominal output voltage following a S ampere change in output current.
METERS:
A front panel voltmeter (0-50V) and ammeter
(0-60A) is provided.
scale. )
OUTPUT CONTROLS:
Single-turn coarse and fine voltage and current
controls are included on the front panel.
OUTPUT TERMINALS:
Output bus bars are located on the rear of the chassis. Both bus bars are isolated from the chassis and either the positive or negative bus bar may be connected to the chassis through a separate, adjacent ground terminal.
REMOTE VOLTAGE PROGRAMMING:
All programming terminals are on a rear barrier strip.
Constant Voltage -
Constant Current ­REMOTE RESISTANCE PROGRAMMING:
All programming terminals are on a rear
barrier strip.
Constant Voltage -200 ohms/volt (Accuracy:
1%).
Constant Current -4 ohms/ampere (Accuracy
10%).
OVERVOLTAGE PROTECTION CROWBAR:
The minimum crowbar trip setting above the desired operating output voltage” to prevent false crowbar tripping is 5% of output voltage setting plus 2 volts. Range is 4 to 45Vdc.
COOLING:
Forced air cooling is employed. The supply has
two cooling fans.
WEIGHT:
95 lbs. (43.0 kg.) net. 120 lbs. (54.5 kg.) shipping.
SIZE:
7.0“ (17.8cm) H x 17.511 (44.4cm) D x 19.0”
(48, 3 cm) W. The unit can be mounted in a
standard 19” rack panel. FINISH:
Light gray front panel with dark gray case.
(Accurate within 2% of full
1V/volt (accuracy: 1%). 10mV/amp (Accuracy 10%).
1-3

SECTION II

INSTALLATION
2-1 INITIAL INSPECTION
2-2 Before shipment, this instrument was inspect­ed and found to be free of mechanical and electri­cal defects. As soon as the instrument is unpacked, inspect for any damage that may have occurred in transit. Save all packing materials until the in­spection is completed. If damage is found, file a claim with the carrier immediately. Hewlett­Packard Sales and Service office should be notified.
TM 11-6625-2958-14&P
2-3 2-4 This check should confirm that there are no
broken knobs or connectors, that the cabinet and panel surfaces are free of dents and scratches, and that the meters are not scratched or cracked.
2-6 The instrument should be checked against its electrical specifications. Section V includes a n “in-cabinet” performance check to verify proper instrument operation.
operation. It is necessary only to connect the in­operation.
2-10 This instrument is fan cooled. Sufficient cooling air can reach the sides of the instrument
when it is in operation. It should be used in an area where the ambient temperature does not ex-
2-12 Figure 2-1 illustrates the outline shape and dimensions of Models 6259B, 6260B, 6261B, 6268B, and 6269B.
easily rack mounted in a conventional 19 inch rack
MECHANICAL CHECK
2-5 ELECTRICAL CHECK
2-7 INSTALLATION DATA
2-8 The instrument is shipped ready for bench strument to a source of power and it is ready for
.
2-9
LOCATION
space should be allotted so that a free flow of
ceed 55°C. 2-11 OUTLINE DIAGRAM
2-13 RACK MOUNTING 2-14 This instrument is full rack size and can be panel using standard mounting screws,
Figure 2-1.
2-15 INPUT POWER REQUIREMENTS
2-16 Model 6259B, 6260B, 6261B, or 6268B power
supply may be operated continuously from either a nominal 230 volt, 208 volt, or 115 volt 57-63Hz power source. a 230 volt or 208 volt, 57-63Hz power source only. The instrument as shipped from the factory is wired for 230 volt operation. The input power when oper­ated from a 230 volt power source at full load is:
Model 6259B 6260B 6261B 6268B 6269B
2-17 CONNECTIONS FOR 208 VOLT OPERATION
(Model 6259B, 6261B, or 6268B: Option 027)
2-18 To convert Model 6259B, 6261B, or 6268B to operation from a 208Vac source, taps on the power and bias transformers must be changed as follows:
a. Remove RFI assembly as described in Steps (a) through (c) of Paragraph 5-67. Access is now provided to bias transformer A3T2. (See Figure 7-2.)
Model 6269B may be operated from
Input Current
Outline Diagram
6A 12A 11A 11A 18A
Input Power
850W 1600W 1500W 1600W
2500W
2-1
TM 11-6625-2958-14&P
transformer (see Figure 2-2 B). Leave wire from fan B2 (not used in 62599) soldered to “230V” terminal.
c. Re-install RFI assembly by reversing pro-
cedure of Step (a).
d. Unsolder wire connected to terminal 5 of power transformer T1 (see Figure 7-4) and solder it instead to terminal 4 of transformer (see Figure
2-3 B).
Figure 2-2. Bias Transformer Primary Connections for 208Vac Operation (Model 6259B, 6260B, 6261B,
6268B, and 6269B) and 115Vac Operation
(Except Model 6269B)
b. Unsolder wire from circuit breaker A5CB1 connected to "230V" terminal of bias transformer A3T2 and solder it instead to "208V" terminal of
Figure 2-3.
Connections for 208Vac and 115Vac Operation
. (Model 6259B, 6261B, and 6268B)
2-19 CONNECTIONS FOR 208 VOLT OPERATION
(Model 6260B and 6269B: Option 027)
2-20 To convert Model 6260B or 6269B to operation from a 208Vac source, taps on the power and bias transformers must be changed as follows:
a. Perform Steps (a) through (c) of Paragraph
2-18.
b. Unsolder wire connected to to "230V” terminal
2-2
Power Transformer Primary
TM 11-6625-2958-14&P
Figure 2-4.
Connections for 208Vac Operation
(Model 6260B and 6269B)
of power transformer T1 (see Figure 7-4) and solder it instead to "208V" terminal of transformer (see Figure 2-4 B).
2-21 CONNECTIONS FOR 115 VOLT OPERATION
(Model -6259B, 6261B, and 6268B: Option 026)
2-22 To convert Model 6259B, 6261B, or 6268B to operation from a 115Vac source, a new circuit breaker must be installed and taps must be changed on the bias transformer, power transformer, and RFI choke as follows:
a. Obtain and install new LINE circuit breaker (A5CB1). Connections to new circuit breaker are same as old connections. Refer to Option 026 in Table 6-4 (Replaceable Parts) for current rating and HP Part Number.
b. Remove and partially disassemble RFI assembly as described in Steps (a) through (d) of Paragraph 5-67.
c. Unsolder jumper between terminals 2 and 3 of RFI choke mounting board and solder jumpers between terminals 1 and 3, 2 and 4 (see Figure 2-5 B). Replace cover on RFI assembly.
d. Unsolder wires from circuit breaker
A5CB1 and fan B2 connected to "230V" terminal of
bias transformer A3T2 (see Figure 7-2). Solder
wire from circuit breaker to "115V" terminal of transformer, and solder wire from fan to "0V" ter­minal of transformer (see Figure 2-2 C). Note that
Power Transformer T 1 Primary
Figure 2-5. RFI Choke (A2L1A/A2L1B)
Connections for 115Vac Operation
(Model 6259B, 6260B, 6261B, and 6268B)
fan B2 is not used in Model 6259B.
e. Re-install RFI assembly by reversing pro-
cedure of Step (b).
f. Unsolder jumper connecting terminals 2
and 3 of power transformer T1 (see Figure 7-4) and
solder jumpers between terminals 1 and 3, 2 and 5 (see Figure 2-3 C).
2-23 CONNECTIONS FOR 115 VOLT OPERATION
(Model 6260B: Option 016)
2-24 To convert Model 6260B to operation from a
115Vac source, a new power transformer and circuit breaker must be installed and taps must be changed on the RFI choke and bias transformer as follows:
a. Obtain and install new power transformer
(T1) and new circuit breaker (A5CB1). Refer to
Option 016 in Table 6-4 (Replaceable Parts) for
power ratings and HP Part Numbers. New transfor­mer has two primary terminals. Transfer wire from old transformer "0V" terminal to new transformer "0V" terminal, and wire from old transformer "230V"
terminal to new transformer "115V" terminal. New
circuit breaker connections are same as old.
2-3
TM 11-6625-2958-14&P
b. Perform Steps (b) through (e) of Paragraph
2-22.
2-25 CONNECTIONS FOR 50Hz OPERATION
2-26 For operation from a 50Hz ac input, R82 must be replaced with a 240 as specified under Option 005 in Table 6-4 (Re­placeable Parts). readjust the voltage drop across the series regula­tor (“Preregulator Tracking” , Paragraph 5-103) and to check the ripple imbalance as described in Steps
(a) through (e) of Paragraph 5-101. 2-27 POWER CABLE
2-28 A power cable is not supplied with the in­strument. It is recommended that the user-supplied power cable have three conductors (third conductor
In addition, it is necessary to
Ω, ±5%, ½ watt resistor
grounded) and be of sufficient wire size to handle the input current drawn by the supply (see Paragraph 2-16). Note that when the supply is operated from a 115Vac source, the input current is approximately double that shown in Paragraph 2-16.
2-29 REPACKAGING FOR SHIPMENT
2-30 To insure safe shipment of the instrument, it is recommended that the package designed for the instrument be used. The original packaging materi­al is reusable. If it is not available, contact your local Hewlett-Packard field office to obtain the materials. This office will also furnish the address of the nearest service center to which the instru­ment can be shipped. Be sure to attach a tag to the instrument specifying the owner, model number, full serial number, and service required, or a brief description of the trouble.
2-4
SECTION Ill
OPERATING INSTRUCTIONS
TM 11-6625-2958-14&P
Figure 3-1. Front Panel Controls and Indicators,’ Modal 6259B, 6260B, 6261B, 6268B or 6269B
3-1 TURN-ON CHECKOUT PROCEDURE
3-2 The following checkout procedure describes
the use of the front panal controls and indicators
(Figure 3-1) and ensures that the supply is opera-
tional.
a. Set LINE circuit breaker to ON, and
observe that pilot light lights.
b. Adjust VOLTAGE controls until desired
voltage is indicated on voltmeter .
c. To ensure that overvoltage crowbar cir­cuit is operational, rotate OVERVOLTAGE ADJUST control (screwdriver adjust) counterclockwise
until unit crowbars. light and output voltage will fall to zero volts.
d. To deactivate crowbar, return OVERVOLT-
AGE ADJUST control to its maximum clockwise po-
sition and turn off supply. Turn supply back on
and voltage should again be value obtained in step
(b).
e. To check out constant current circuit,
turn off supply. Short circuit rear output terminals
and turn on supply.
f. Adjust CURRENT controls until desired
output current is indicated on ammeter .
g. Remove short circuit and read following paragraphs before connecting actual load to supply.
Overvoltage lamp will
3-3 OPERATING MODES
3-4 The power supply is designed so that its mode of operation can be selected by making strapping connections between particular terminals on the ter­minal strip at the rear of the power supply. The ter­minal designations are stenciled in white on the power supply below their respective terminals. The following paragraphs describe the procedures for utilizing the various operational capabilities of the power supply. A more theoretical description con­cerning the operational features of this supply is contained in Application Note 90, Power Supply
Handbook (available at no charge from your local Hewlett-Packard sales office). Sales office ad­dresses appear at the rear of the manual.
3-5 NORMAL OPERATING MODE
3-6 The power supply is normally shipped with its rear terminal strapping connections arranged for constant voltage/constant current, local sensing, local programming, single unit mode of operation. This strapping pattern is illustrated In Figure 3-2. The operator selects either a constant voltage or a constant current output using the front panel con­trols (local programming; no strapping changes are necessary).
3-1
TM 11-6625-2958-14&P
Figure 3-2. Normal Strapping Pattern
Clockwise rotation of the control produces higher trip voltages. The factory sets the control fully clockwise. The crowbar may be disabled complete­ly if desired. (Refer to Paragraph 5-11 1.)
3-13 False crowbar tripping must be considered when adjusting the trip point. If the trip voltage is set too close to the operating output voltage of the supply, a transient in the output will falsely trip the crowbar. It is recommended that the crowbar be set higher than the output voltage by 5% of the out­put voltage plus 2 volts. However, If occasional crowbar tripping on unloading can be tolerated, the crowbar trip point can be set much closer to the
operating out put voltage of the supply. 3-7 CONSTANT VOLTAGE 3-8 To select a constant voltage output, proceed
as follows:
a. Turn on power supply and adjust VOLTAGE controls for desired output voltage with output ter­minals open.
b. Short circuit output terminals and adjust CURRENT controls for maximum output current al­lowable (current limit), as determined by load con­ditions. If a load change causes the current limit to be exceeded, the power supply will automatical­ly cross over to constant current output at the pre­set current limit and the output voltage will drop proportionately. In setting the current Iimit, al­lowance must be made for high peak currents which can cause unwanted crossover. (Refer to Paragraph
3-60. ) 3-9 CONSTANT CURRENT 3-10 To select a constant current output, proceed
as follows:
a. Short circuit output terminals and adjust
CURRENT controls for desired output current.
b. Open output terminals and adjust VOLT-
AGE controls for maximum output voltage allowable
(voltage limit ), as determined by load conditions. If a load change causes the voltage limit to be ex­ceeded, the power supply will automatically cross
over to constant voltage output at the preset volt-
age limit and the output current will drop propor-
tionately. In setting the voltage limit, allowance
must be made for high peak voltages which can cause unwanted crossover. (Refer to Paragraph 3-60.)
3-14 CONNECTING LOAD 3-15 Each load should be connected to the power
supply output terminals using separate pairs of connecting wires. This will minimize mutual cou­pling effects between loads and will retain full ad­vantage of the low output impedance of the power supply. Each pair of connecting wires should be as short as possible and twisted or shielded to reduce
noise pickup. (If a shielded pair is used, connect one end of the shield to ground at the power supply and leave the other end unconnected.)
3-16 If load considerations require that the output
power distribution terminals be remotely located from the power supply, then the power suppIy out­put terminals should be connected to the remote distribution terminals via a pair of twisted or
shielded wires and each load should be separately
connected to the remote distribution terminals. For this case, remote sensing should be used. (Refer to Paragraph 3-4 1.)
3-17 Positive or negative voltages can be obtained from this supply by grounding either one of. the out-
put terminals or one end of the load. Always use two leads to connect the load to the supply, regard­less of where the setup is grounded. This will elim­inate any possibility of output current return paths through the power source ground which would dam­age the line cord plug. This supply can also be operated up to 300Vdc above ground, if neither out­put terminal is grounded.
3-18 NO LOAD OPERATION
3-11 OVERVOLTAGE TRIP POINT ADJUSTMENT 3-12 The crowbar trip voltage can be adjusted by
using the screwdriver control on the front panel. The trip voltage range is as follows:
6259B, 6260B
2 to 12Vdc
When the crowbar trips, the output is shorted and
the amber indicator on the front panel lights.
6261B 6268B, 6269B
2 to 23Vdc
4 to 45Vdc
3-19 When the supply is operated without a load, down-programming speed is considerably slower
than in normal loaded operation. This slower pro­gramming speed is evident when using any method of down-programming - either turning the VOLTAGE controls fully counterclockwise, activating the
crowbar, or throwing the LINE circuit breaker to
OFF. Under any of these conditions, the supply output will rapidly fall to approximately two volts,
3-2
then proceed at a slower rate towards zero. The
actual time required for the output to fall from two volts to zero will vary from several seconds to several minutes, depending upon which down-pro-
gramming method is used.
3-20 OPERATION BEYOND RATED OUTPUT 3-21 The shaded area on the front panel meter face
indicates the approximate amount of output voltage or current that may be available in excess of the normal rated output. Although the supply can be operated in this shaded region without being dam-
aged, it cannot be guaranteed to meet all of its
performance specifications.
3-22 OPTIONAL OPERATING MODES
3-23 REMOTE PROGRAMMING, CONSTANT
VOLTAGE
3-24 The constant voltage output of the power supply can be programmed (controlled) from a re­mote location if required. Either a resistance or
voltage source can be used as the programming device. The wires connecting the programming terminals of the supply to the remote programming
device should be twisted or shielded to reduce
noise pickup. The VOLTAGE controls on the front
panel are automatically disabled in the following
procedures.
3-26 The output voltage of the supply should be
TM 11-6625-2958-14&P
-15mV ±5mV when zero ohms is connected across
the programming terminals. If a zero ohm voltage
closer to zero than this is required, it may be achieved by inserting and adjusting R110 as dis­cussed in Paragraph 5-83, or, if the instrument is equipped with Option 020, by adjusting potentiome-
ter R113 as discussed in Paragraph 5-85.
3-27 To maintain the stability and temperature co­efficient of the power supply, use programming re­sistors that have stable, low noise, and low temp­erature coefficient (less than 30ppm per degree Centigrade) characteristics. A switch can be used in conjunction with various resistance values in order to obtain discrete output voltages. The switch should have make-before-break contacts to avoid momentarily opening the programming terminals dur­ing the switching interval.
3-25 Resistance Programming
(Figure 3-3). In this mode, the output voltage will vary at a rate deter­mined by the voltage programming coefficient of 200 ohms/volt. The programming coefficient is de-
termined by the programming current. This current
is factory adjusted to within 1% of 5mA. If greater programming accuracy is required, it may be achieved by either adjusting R3 as discussed in Paragraph 5-88, or, if the instrument is equipped
with Option 020, by adjusting potentiometer R112
as discussed in Paragraph 5-89.
Figure 3-4.
Remet e Voltage Programming,
Unity Gain (Constant Voltage)
3-28 Voltage Programming,
Unity Gain (Figure 3-4). Employ the strapping pattern shown in Figure 3-4 for voltage programming with unity gain. In this mode, the output voltage will vary in a 1 to 1 ratio with the programming voltage (reference voltage) and the load on the programming voltage source will not exceed 20 microampere. Impedance matching resistor (R
) is required to maintain the temperature
x
coefficient and stability specifications of the sup-
ply .
3-29 Voltage Programming, Non-Unity Gain (Figure 3-5). The strapping pattern shown in Figure 3-5 can be utilized for programming the power supply using an external voltage source with a variable
voltage gain. The output voltage in this configura-
tion is found by multiplying the external voltage
source by (Rp/RR).
Figure 3-3.
Remet e Resistance Programming
(Constant Voltage)
3-30 External resistors Rp and R
R should have sta-
ble, low noise, and low temperature coefficient
3-3
TM 11-6625-2958-14&P
Figure 3-5. Remote Voltage Programming,
Non-Unity Gain (Constant Voltage)
(less than 30ppm Per degree Centigrade) character-
istics in order to maintain the Supply's temperature and stability specifications. Reference resistor R
should not exceed 10K. Note that it is possible to use the front panel voltage control already in the supply (A5R121) as the voltage gain
control (Rp) by simply removing the external Rp and strapping ter­minals Al and A2 together.
3-31 The output voltage of the supply may be ad­justed to exactly zero when the external program­ming voltage is zero by either inserting and adjust­ing R111 as discussed in Paragraph 5-84, or, if the
instrument is equipped with Option 020, by adjust­ing potentiometer R112 as discussed in Paragraph
5-86.
Figure 3-6. Remote Resistance Programming
(Constant Current)
with Option 021, by adjusting potentiometer R116 as discussed in Paragraph 5-98. The output current of the supply when zero ohms is placed across the programming terminals may be set to exactly zero
R
by either inserting and adjusting R117 as discussed
in Paragraph 5-92, or, if the instrument is equipped with Option 021, by adjusting potentiometer R119 as discussed in Paragraph 5-94.
3-35 Use stable, low noise, low temperature co­efficient (less than 30ppm/°C) programming resis­tors to maintain the power supply temperature coef­ficient and stability s pacifications. A switch may be used to set discrete values of output current. A make-before-break type of switch should be used since the output current will exceed the maximum rating of the power supply if the switch contacts open during the switching interval.
3-32 REMOTE PROGRAMMING, CONSTANT
CURRENT
3-33 Either a resistance or a voltage source can be used to control the constant current output of the supply. The CURRENT controls on the front
panel are automatically disabled in the following
procedures. 3-34 Resistance Programming (Figure 3-6). In this
mode, the output current varies at a rate determined by the programming coefficient as follows:
Model 6259B 6260B 6261B 6268B 6269B
Programming Coefficient
4 ohms/ampere 2 ohms/ampere 4 ohms/ampere
6 ohms/ampere
4 ohms/ampere The programming coefficient is determined by the constant current programming current which is ad­justed to within 10% of 2.5mA at the factory. If greater programming accuracy is required, it may be achieved by either adjusting R30 as discussed in Paragraph 5-97, or, if the instrument is equipped
CAUTION
If the programming terminals (A4 and A 6) should open at any time during the remote resistance programming mode, the output current will rise to a value that may damage the power supply and/or the load. If, in the particular
programming configuration in use, there is a chance that the terminals might become open, it is suggested that a 200 ohm resistor be connected across the programming terminals. Like the programming resistor, this resistor should be a low noise, low temperature coefficient type. Not e that when this resistor is used, the resistance value actually programming the supply is the parallel combination of the remote programming resistance and the resistor across the program­ming terminals.
3-4
TM 11-6625-2958-14&P programmed using an external voltage source with variable gain by utilizing the strapping pattern
shown in Figure 3-8. In this mode, the output cur­rent is found by multiplying the external voltage source (Es) by [Rp/(RR x Kp)], where Kp is the constant current voltage programming coefficient as
given in Paragraph 3-37. The value of reference resistor R
R and programming voltage source E
s
should be such that the value of ES/RR is equal to or greater than 2.5mA.
Figure 3-7.
Remote Voltage Programming,
Unity Gain (Constant Current]
3-36 Voltage Programming
, Unity Gain (Figure 3-7).
In this mode, the output current will vary linearly
with changes in the programming voltage. The pro-
gramming voltage should not exceed 0.6 volts.
Voltage in excess of 0.6 volts will result in exces-
sive power dissipation in the instrument and possi-
ble damage. 3-37 The output current varies at a rate determined
by the programming coefficient as follows:
Model 6259B 6260B 6261B 6268B 6269B
Programming Coefficient
10.0mV/ampere
5.0mV/ampere
10.0mV/ampere
16.7mV/ampere
10.0mV/ampere The current required from the voltage source will be less than 20µA. Impedance matching resistor R
is
x
required to maintain the temperature coefficient and
stability specifications of the supply. 3-38 Voltage Programming,
Non-Unity Gain (Figure
3-8). The power supply output current can be
3-39 External resistors Rp and R
R should have sta-
ble, low noise, and low temperature coefficient
(less than 30ppm per degree Centigrade) character­istics in order to maintain the stability and temper­ature specifications of the Power supply. Reference resistor R
R should not exceed 10K. Note that it is
possible to use the front panel current control al­ready in the supply (A5R123) as the gain
control (Rp) by simply removing the external Rp and strapping terminals AS and A6 together.
3-40 The output current of the supply may be ad­justed to exactly zero when the external program­ming voltage is zero by either inserting and adjust­ing R115 as discussed in Paragraph 5-93, or, if the instrument is equipped with Option 021, by adjust-
ing potentiometer R116 as discussed in Paragraph
5-95.
3-41 REMOTE SENSING (Figure 3-9)
3-42 Remote sensing is used to maintain good reg-
ulation at the load and reduce the degradation of regulation which would occur due to the voltage drop in the leads between the power supply and the load. Remote sensing is accomplished by utilizing the strapping pattern shown in Figure 3-9. The
Power supply should be turned off before changing strapping paterns. The leads from the sensing (±S) terminals to the load will carry much less current
than the load leads and it is not required that these
leads be as heavy as the load leads. However, they must be twisted or shielded to minimize noise
pickup.
Figure 3-8.
Remote Voltage Programming,
Non-Unity Gain (Constant Current)
3-5
Figure 3-9.
Remote Sensing
TM 11-6625-2958-14&P 3-43 For reasonable load lead lengths, remote
sensing greatly improves the performance of the
supply. However, if the load is located a consid­erable distance from the supply, added precautions must be observed to obtain satisfactory operation. Notice that the voltage drop in the load leads sub­tracts directly from the available output voltage and also reduces the amplitude of the feedback er­ror signals that are deveIoped within the unit. Be­cause of these factors it is recommended that the drop in each load lead not exceed 0.5 volt. If a larger drop must be tolerated, please consult an
HP Sales Engineer.
NOTE
Due to the voltage drop in the load leads, it may be necessary to read-
just the current limit in the remote
sensing mode.
3-44 Observance of the precautions in Paragraph
3-43 will result in a low dc output impedance at the load. However, another factor that must be
considered is the inductance of long load leads.
This causes a high ac Impedance and could affect the stability of the feedback loop seriously enough to cause oscillation. If this is the case, it is recommended that the following actions be taken:
a. Adjust equalization control R47 to remove
oscillation, or to achieve best possible transient response for given long load lead configuration.
Refer to Paragraph 5-27 for discussion of transient
response measurement.
b. If performing adjustment in step (a) above does not remove oscillation, disconnect output capacitor A3C3 and connect a capacitor having sim­ilar characteristics (approximately the same capa­citance, the same voltage rating or greater, and having good high frequency characteristics) direct­ly across load using short leads. Readjust equali­zation control R47 as in step (a) above after making this change. In order to gain access to capacitor
A3C3, it is necessary to remove the RFI assembly
as described in steps (a) through (c) of Paragraph
5-67. Lead from positive side of capacitor (shown
arrowed In Figure 7-2) can then be unsoldered from
A3 interconnection circuit board.
from the -S terminal to the negative side of the load. Note that there may be more than one lead connect­ed to the +S and -S terminals.
3-46 AUTO-PARALLEL OPERATION (Figure 3-10) 3-47 Two or more power supplies can be connected
in an Auto-Parallel arrangement to obtain an output
3-45 To employ remote sensing with any method of remote programming or with any method of combin­ing more than one supply discussed in the Preced-
ing or following paragraphs, use the following pro-
cedure:
a. Remove the two external leads connecting
the sensing terminals (±S) to the output bus bars
(±OUT).
b. Connect a lead from the +S terminal to the
positive side of the load, and connect another lead
Figure 3-10. Auto-Parallel Operation,
Two and Three Units
3-6
current greater than that available from one supply.
Auto-Parallel operation permits equal current shar-
ing under all load conditions, and allows complete control of the output current from one master power supply. The output current of each slave will be approximately equal to the master’s output current
regardless of the load conditions. Because the
output current controls of each slave are operative, they should be set to maximum to prevent the slave reverting to constant current operation; this would
OCCur if the master output current setting exceeded
the slave’s.
3-48 Additional slave supplies may be added in parallel with the master/slave combination as shown in the bottom half of Figure 3-10. All the
connections between the master and slave #1 are duplicated between slave #1 and the added slave
supply. In addition, the strapping pattern of the added slave should be the same as slave #1. Re­mote sensing and programming can be used, though the strapping arrangements shown in Figure 3-10
show local sensing and programming.
3-49 Overvoltage protection is controlled by the
crowbar circuit in the master supply which monitors the voltage acress the load and fires the SCR's in
both units if an overvoltage condition occurs. The
firing pulses are fed to the slave supply from trans-
former T90 (winding 5-6) of the master supply through the “ EXT. CROWBAR TRIGGER
"
terminals on
the rear panel of the master supply. Correct polari-
ty must be observed in connecting the crowbars to-
gether. The overvoltage trip point is adjusted on
the master supply, The OVERVOLTAGE ADJUST po­tentiometer on the slave supply should be set to maximum [clockwise) so that the master crowbar will control the slave.
TM 11-6625-2958-14&P
3-50 AUTO-SERIES OPERATION (Figure 3-11)
3-51 Two or more power supplies can be operated in Auto-Series to obtain a higher voltage than that available from a single supply. When this connec­tion is used, the output voltage of each slave sup­ply varies in accordance with that of the master
supply. At maximum output voltage, the voltage of
the slaves is determined by the setting of the front
panel VOLTAGE controls on the master. The master
supply must be the most positive supply of the
series. The output CURRENT controls of all series units are operative and the current limit is equal to the lowest control setting. If any of the output
CURRENT controls are set too low, automatic cross-
over to constant current operation will occur and the output voltage will drop. Remote sensing and
programming can be used, though the strapping ar­rangements shown in Figure 3-11 show local sensing
and programming.
3-52 In order to maintain the temperature coeffi-
Figure 3-11.
Auto-Series Operation,
Two and Three Units
cient and stability specifications of the power sup­ply, the external resistors (Rx) shown in Figure 3-11 should be stable, low noise, low temperature coefficient (less than 30ppm per degree Centigrade) resistors.
The value of each resistor is dependent
3-7
TM 11-6625-2958-14&P on the maximum voltage rating of the "master" sup-
ply. The value of R
is this voltage divided by the
X
voltage programming current of the slave supply
(1/Kp where K
P is the voltage programming coeffi-
cient). The voltage contribution of the slave is determined by its voltage control setting.
3-53 Overvoltage protection is provided in Auto­Series operation by connecting the crowbars in par­allel with correct polarity as in Auto-Parallel oper­ation (see Paragraph 3-49). The OVERVOLTAGE AD-
JUST potentiometer in each supply should be adjust-
ed so that it trips at a point slightly above the out­put voltage that the supply will contribute.
3-54 When the center tap of an Auto-Series combi­nation is grounded, coordinated positive and nega-
tive voltages result. This technique is commonly referred to as “robber-banding” and an external reference source may be employed if desired. Any
change of the internal or external reference source
(e.9. drift, ripple) will cause an equal percentage change in the outputs of both the master and slave supplies. This feature can be of considerable use in analog computer and other applications, where
the load requires a positive and a negative power
supply and is less susceptible to an output voltage change occurring simultaneously in both supplies
than to a change in either supply alone.
3-55 AUTO-TRACKING OPERATION (Figure 3-12) 3-56 The Auto-Tracking configuration is used when
several different voltages referred to a common bus must vary in proportion to the setting of a particular instrument (the control or master). A fraction of the master’s output voltage is fed to the comparison amplifier of the slave supply, thus controlling the slave's output. The master must have the largest output voltage of any power supply in the group. It must be the most positive supply in the example shown on Figure 3-12.
3-57 The output voltage of the slave (Es) is a per­centage of the master's output voltage (EM), and is determined by the voltage divider consisting of R
X
and the voltage control of the slave supply, Rp,
where E
S = EM [Rp/(R
+Rp)]. Remote sensing and
x
programming can be used (each supply senses at its
own load), though the strapping patterns given in
Figure 3-12 show only local sensing and program-
ming. In order to maintain the temperature coeffi­cient and stability specifications of the power sup­ply, the external resistors should be stable, low
noise, low temperature coefficient (less than 30ppm per degree Centigrade) resistors.
3-58 The overvoltage protection circuit in each unit is operable end independently monitors the
voltage across its own load. Notice that if the master supply crowbars, the output voltage of
Figure 3-12. Auto-Tracking, Tw
O and Three Units
each slave will also decrease. However, the re­verse is not true. If one of the slave units crow­bars, the other supplies in *the ensemble will not be affected.
3-59 SPECIAL OPERATING CONSIDERATIONS
3-60 “PULSE LOADING
3-61 The power supply
will automatically cross
3-8
over from constant voltage to constant current op­eration, or the reverse, in response to an increase
(over the preset limit) in the output current or volt­age, respectively. Although the preset limit may be set higher than the average output current or
voltage, high peak currents or voltages (as occur in pulse loading) may exceed the preset limit and cause crossover to occur. If this crossover limit­ing is not desired, set the preset limit for the peak
requirement and not the average.
3-62 OUTPUT CAPACITANCE 3-63 An internal capacitor (A3C3) connected across
the output terminals of the power supply, helps to
supply high-current pulses of short duration during constant voltage operation. Any capacitance added
externally will improve the
PUlSe current capability,
but will decrease the safety provided by the con-
stant current circuit. A high-current pulse may
damage load components before the average output
current is large enough to cause the constant cur-
rent circuit to operate.
3-64 The effects of the output capacitor during constant current operation are as follows:
a. The output impedance of the power supply
decreases with increasing frequency.
b. The recovery time of the output voltage is
longer for load resistance changes.
TM 11-6625-2958-14&P
c. A large surge current causing a high pow-
er dissipation in the load occurs when the load re-
sistance is reduced rapidly.
3-65 REVERSE VOLTAGE LOADING
3-66 A diode (A4CR106) is connected across the
output terminals. Under normal operation condi­tions, the diode is reverse biased (anode connect­ed to the negative terminal). If a reverse voltage
is applied to the output terminals (
POSitive voltage
applied to the negative terminal), the diode will conduct, shunting current across the output termi-
nals and limiting the voltage across the output
terminals to the forward voltage drop of the diode.
This diode protects the series transistors and the
output electrolytic capacitors.
3-67 REVERSE CURRENT LOADING 3-68 Active loads connected to the power supply
may actually deliver a reverse current to the power
supply during a portion of its operating cycle. An external source cannot be allowed to pump current into the supply without loss of regulation and pos­sible damage to the output capacitor. To avoid
these effects, it is necessary to preload the supply with a dummy load resistor so that the power supply delivers current through the entire operation cycle
of the load device.
3-9

SECTION IV

PRINCIPLES OF OPERATION
TM 11-6625-2958-14&P
Figure 4-1. Overall Block Diagram
4-1 OVERALL BLOCK DIAGRAM DISCUSSION
4-2 The major circuits of the power supply are
shown on the overall block diagram of Figure 4-1. The ac input voltage is first applied to the prereg­ulator triac which operates in conjunction with the preregulator control circuit to form a feedback loop.
This feedback loop minimizes the power dissipated
by the series regulator by keeping the voltage drop across the regulator at a low and constant level.
4-3 To accomplish this, the preregulator control circuit issues a phase adjusted firing pulse to the
triac once during each half cycle of the input ac.
The control circuit continuously samples the output voltage, the input line voltage (from A3T2), and the voltage across the series regulator and, on the
basis of these inputs, determines at what time each firing pulse is generated.
4-4 The phase adjusted output of the triac is ap-
plied to the power transformer where it is stepped­down and coupled to a full-wave rectifier and filter. The preregulated dc current is applied next to the
series reguIator which varies its conduction to pro­vide a regulated voltage or current at the output terminals.
4-5 The series regulator is part of another feed­back loop consisting of the error and driver ampli­fiers and the constant voltage/constant current
compactors. The series regulator feedback loop provides rapid, low magnitude regulation of the out­put while the preregulator feedback loop handles
large, relatively slow, regulation demands.
4-1
TM 11-6625-2958-14&P
4-6 The feedback signals controlling the conduc­tion of the series regulator originate within the
constant voltage or constant current comparator. During constant voltage operation the constant voltage comparator continuously compares the out­put voltage of the supply with the drop across the VOLTAGE controls.
If these voltages are not equal, the comparator produces an amplified error signal which is further amplified by the error amplifier and
then fed back to the series regulator in the correct
phase and amplitude to counteract the difference. In this manner, the constant voltage comparator helps to maintain a constant output voltage and also generates the error signals necessary to set
the output voltage at the level established by the VOLTA GE controls.
4-7 During constant current operation, the con­stant current comparator detects any difference be-
tween the voltage drop developed by the load cur­rent flowing through the current sampling resistor and the voltage acress the CURRENT controls. If the two inputs to the comparator are momentarily unequal, an error signal is generated which (after amplification) alters the conduction of the series regulator by the amount necessary to reduce the error voltage at the comparator input to zero.
Hence, the IR drop across the current sampling re­sistor, and therefore the output current, is main-
tained at a constant value. 4-8 Since the constant voltage comparator tends
to achieve zero output impedance and alters the output current whenever the load resistance changes, while the constant current comparator causes the output impedance to be infinite and changes the output voltage in response to any load
resistance change, it is obvious that the two com-
parison amplifiers cannot operate simultaneously. For any-given value of load resistance, the power supply must act either as a constant voltage source or as a constant current source - it cannot be both.
4-9 Figure 4-2 shows the output characteristic of a constant voltage/constant current power supply.
With no load attached (RL =
OUT = Es, the front panel voltage control setting.
E
∞), IOUT = O, and
When a load resistance is applied to the output terminals of the power supply, the output current
increases, while the output voltage remains con­stant; point D thus represents a typical constant voltage operating point. Further decreases in load
resistance are accompanied by further increases in
OUT with no change in the output voltage until the
I output current reaches Is, a value equal to the front panel current control setting. At this point the sup­ply automatically changes its mode of operation and becomes a constant current source; still further decreases in the value of load resistance are ac­companied by a drop in the supply output voltage with no accompanying change in the output current
Figure 4-2. Operating Locus of a CV/CC
Power Supply
value. With a short circuit across the output load
terminals, I 4-10 The ‘
be defined as R
OUT = ES and EOUT = O.
:
Crossover” value of load resistance can
C = Es/Is. Adjustment of the front
panel voltage and current controls permits this “crossover” resistance R value from 0 to
∞. If RL is greater than RC, the
C to be set to any desired
supply is in constant voltage operation, while if R is less than RC, the supply is in constant current operation.
4-11 The short circuit protection circuit (see Fig­ure 4-1) protects the series regulator in the event of a shorted output when the controls are set to a high output voltage and current. The protection cir-
cuit monitors the voltage drop across the series regulator. If the drop rises above a preset level, the protection circuit limits the current through the
series regulator until the preregulator can reduce the voltage across the series regulator. Once this
voltage returns to normal, the short circuit protec­tion circuit is turned off and has no effect on norm­al operation of the supply.
4-12 The overvoltage protect ion crowbar monitors the output of the supply, and if it exceeds a preset
(adjustable) threshold, fires an SCR which short circuits the supply.
The circuit also sends a turn-
down signal to the preregulator control circuit. 4-13 The overvoltage limit circuit protects the main
rectifier diodes and filter capacitors from damage
that might occur if the series regulator transistors were shorted or the voltage programming pot were
opened. The circuit monitors the output voltage of
L
4-2
the supply and, if it exceeds approximately 120% of maximum rated output, sends a turn-down signal to the preregulator control circuit. Hence, the out-
put voltage of the supply is limited to a “safe” val­ue despite any possible failure in the series regu-
lator feedback loop.
4-14 The turn-on control circuit is a long time
constant network which allows the supply to achieve a gradual turn-on characteristic. The slow turn-on feature protects the preregulator triac and the series regulator from damage which might occur when ac power is first applied to the unit. At turn­on, the control circuit sends inhibiting voltages to the preregulator control circuit and the s cries regu-
lator (via the error and driver amplifiers). A short time after the unit is in operation, the inhibiting
voltages are removed and the circuit no longer ex-
ercises any control over the operation of the supply.
4-15 The reference supply provides stable refer-
ence voltages used by the constant voltage and
current comparators. Less critical operating volt­ages are obtained from the bias supply.
4-16 DETAILED CIRCUIT ANALYSIS (See
Figure 7-11)
TM 11-6625-2958-14&P
Figure 4-3. Triac Phase Control Over
AC Input Amplitude
4-17 PREREGULATOR CONTROL CIRCUIT
4-18 The preregulator minimizes changes in the
power dissipated by the series regulating transis ­tors due to output voltage or. input line voltage var-
iations. Preregulation is accomplished by means of a phase control circuit utilizing triac A2CR1 as the switching element.
4-19 In order to understand the operation of the
preregulator, it is important to understand the op-
eration of the triac. The triac is a hi-directional device, that is, it can conduct current in either direction. Hence, the device fires whenever it receives a gating pulse regardless of the polarity
of the input a c that is applied to it. The triac is
fired once during each half-cycle (8.3 3 millisec­onds) of the input ac (see Figure 4-3). Notice that when the triac is fired at an early point during the
half-cycle, the ac level applied to the power trans­former is relatively high. When the triac is fired later during the half-cycle, the ac level is rela­tively low.
4-20 Normally the ac input signal must be at a certain minimum potential before the triac will con­duct. However, A2R1 and A2C1 provide a holding
current that allows the triac to conduct at any time during the ac input cycle. RFI choke A2L1A/A2L1B
(in series with the triac) slows down the turn-on of
the triac in order to minimize spikes at the output
of the supply. Components A2CR1, A2R1, A2L1A/ A2L1B, and A2C1 are all mounted inside a shielded
box (assembly A2) to minimize radiated and reflect­ed RFI. Further RFI suppression is provided by by-
pass capacitors C110 and C111.
4-21 The preregulator control circuit samples the input line voltage, the output voltage, and the voltage across the series regulator transistors. It
generates firing pulses, at the time required, to
fire the triac. This action maintains the ac input
voltage across the primary winding of T I at the de­sired level.
4-22 The inputs to the control circuit are algebra-
ically summed across capacitor C70. All inputs contribute to the time required to charge C70. The
input line voltage is rectified by CR81, CR82, CR83, and CR84, attenuated by voltage divider R86 and R83, and applied to the summing point at the col -
lector of Q71 (TP81) via capacitor C70. Capacitor
C73 is used for smoothing purposes.
4-23 Transistor Q71, connected in a common base
configuration, provides a charging current for the
summing capacitor varying in accordance with the
input signals applied to its emitter. Resistor R78,
connected between the negative output line and the
emitter of Q71, furnishes a signal which is propor-
tional to the output voltage. Resistors R75 and R76
sample the voltage across, and the current through,
the series regulator. Capacitor C72 and resistor
R82 stabilize the entire preregulator feedback loop.
Resistors R70 and R80 are the source of a constant
offset current which sustains a net negative charg-
4-3
TM 11-6625-2958-14&P
ing current to the summing point, ensuring that the triac will fire at low output “voltages.
4-24 The summation of the input signals results in the generation of a voltage waveform at TP80
similar to that shown in waveform (A) of Figure 4-4. When the linear ramp portion of the waveform reaches a certain negative threshold voltage, di­odes CR74 and CR75 become forward biased. The negative voltage is then coupled to the base of transistor Q72. Transistors Q72 and Q73 form a
squaring circuit resembling a Schmitt trigger con­figuration. Q72 is conducting prior to firing time due to the positive bias connected to its base through R84, Transistor Q73 is cut off at this time because its base is driven negative by the collect­or of Q72.
4-25 When the negative threshold voltage is reached, transistor Q72 is turned off and Q73 is turned on. The conduction of Q73 allows capacitor
C71 to discharge rapidly through pulse transformer T70 resulting in the generation of a firing pulse
across the secondary winding of T70. As shown in
waveform (C) of Figure 4-4, the firing pulse is quite narrow because Q73 saturates rapidly, causing the magnetic field surrounding T70 to collapse. Di­ode CR76 damps out positive overshoot.
4-26 Reset of the control circuit occurs once every
8.33 milliseconds when the rectified ac voltage at
the junction of CR77, CR78, and CR79 (TP82) in-
creases to a level at which diode CR78 becomes
forward biased. Summing capacitor C70 is then al-
lowed to discharge through CR78. Diodes CR74 and CR75 become reverse biased at reset and transistor Q72 reverts to its “on” state. Consequently, Q73 is turned off and capacitor C71 charges up through R79 at a comparatively slow rate until the collector voltage of Q73 reaches approximately +11 volts.
The above action causes the small positive spike
that appears across the windings of pulse transform­er at T70 at reset time.
4-27 SERIES REGULATOR AND DRIVER
4-28 The series regulator consists of transistors A4Q103 through A4Q108 connected in parallel. The transistors serve as the series or “pass” element which provides precise and rapid control of the out­put. Resistors A4R150 through A4R155 allow high output currents to be equally shared by the series regulator transistors. The conduction of the series transistors is controlled by signals obtained from driver A4Q102, which is connected in a Darlington
configuration with the parallel-connected series regulator transistors. Thermal switch A4TS101 opens
if the heat sink assembly temperature exceeds ap-
proximately 230°F, thus turning off the series regu-
lator transistors. This feature protects critical
components of the supply from excessive tempera­tures which could occur if cooling fan A4B1 failed.
Diode CR50 provides a discharge path for the out-
put capacitors when the supply is rapidly down-
programmed; R57 limits the discharge current flow-
ing through the diode and through error amplifier A4Q101. Diode A4CR105, connected across the reg-
ulator circuit, protects the series elements from
reverse voltages that could develop across them
during parallel operation if one supply is turned on
before the other.
Figure 4-4. Preregulator Control Circuit Waveforms
4-29 SHORT CIRCUIT PROTECTION
4-30 This circuit acts to initially protect the series
regulator against a simultaneous full-voltage, full-
current conditions such as might occur if the output
were shorted when the controls were set to deliver
a high output voltage and current. Under this con-
dition, Q20 goes into heavy conduction due to the
increased voltage across the series regulator, putting R26 in parallel with the current controls and
thus limiting the current to less than 10% of the
supply’s rating. short circuit is imposed, the preregulator shuts off.
4-4
Within 10 milliseconds after the
The input capacitor then begins to discharge through the series regulator, and the voltage across the regulator decreases until Q20 turns off. The dis-
charge time (typically ½ to 4 seconds) depends on the voltage and current ratings of the supply, the main filter capacitor, and the control settings. Once this recovery time has elapsed, the output
current will return to the level set by the current
controls, and the preregulator will return the volt-
age across the series regulator to the normal 3.5V
level, thus limiting the power dissipated by the
s cries regulator.
4-31 CONSTANT VOLTAGE COMPARATOR
4-32 This circuit consists of the programming re-
sistors (A5R121 and A5R122) and a differential am-
plifier stage (Z1 and associated components). An
integrated circuit is used for the differential ampli­fier to minimize differential voltages due to mis­matched transistors and thermal differentials.
4-33 The constant voltage comparator continuously
compares the voltage drop across the VOLTAGE con­trols with the output voltage and, if a difference
exists, produces an error voltage whose amplitude
is proportional to this difference. The error signal ultimately alters the conduction of the series regu-
lator which, in turn, alters the output current so that the output voltage becomes equal to the voltage drop across the VOLTAGE controls. Hence, through
feedback action, the difference between the two in-
puts to Z1 is held at zero volts.
during rapid down-programming; diodes CR5 and
TM 11-6625-2958-14&P
CR6 prevent excessive voltage excursions from over-driving the differential amplifier. Capacitor C2 prevents the gain of the feedback loop from changing during manipulation of the VOLTAGE con­trols. Resistor R2 limits the discharge current
through C2. Resistors Z2F, Z2M, and Z2N bias the differential amplifier; diode CR4 provides tempera­ture compensation.
4-36 During constant voltage operation, the pro-
gramming current flowing through the programming resistors (VOLTAGE controls) is held constant be-
cause the value of shunt resistor R3 is factory
selected to allow all of the +6.2 volt reference to
be dropped across R3, R4, and RS. Linear constant
voltage programming is thus assured with a constant
current flowing through A5R121 and A5R122. If the
supply is equipped with Option 020, resistor R111
and potentiometer R 112 allow the programming cur­rent to be adjusted by varying the bias applied to the summing point.
4-37 Main output capacitor A3C3 stabilizes the
series regulator feedback loop and helps supply
high-current pulses of short duration during con-
stant voltage pulse loading operation. An additional
output capacitor (C 19), connected directly across the output bus bars, helps maintain a low ac output
impedance by compensating for the inductive react-
ance of the main output capacitor at high frequencies.
C19 also prevents any spikes in the output from
reaching the load.
4-34 One input of the differential amplifier (pin
10) is connected to the output voltage sensing ter-
minal of the supply (+S) through impedance equaliz-
ing resistor R23. Resistors R1 and optional resistor
R110 are used to zero bias the input. If the supply
is equipped with Option 020, resistor R114 and po­tentiometer R 113 provide a variable input bias that allows the output voltage to be adjusted to exactly zero volts when the supply is programmed for zero output. The other input of the differential amplifier
(pin 1) is connected to a summing point (terminal
A2) at the junction of the programming resistors and
the current pullout resistors R3, R4, end R5. In-
stantaneous changes in the output voltage or
changes in the voltage at the summing point due to manipulation of the VOLTAGE controls produce a dif­ference voltage between the two inputs of the dif­ferential amplifier. This difference voltage is am­plified and appears at the output of the differential amplifier (pin 12) as an error voltage which ulti­mately varies the conduction of the series regulator.
4-3 S Resistor R6, in series with the summing-point
input to the differential amplifier, limits the cur­rent through the programming resistors during rapid
voltage turn-down. Diode CR7 prevents excessive
current drain from the +6.2 volt reference supply
4-38 CONSTANT CURRENT COMPARATOR
4-39 This circuit is similar in appearance and op­eration to the constant voltage comparator circuit. It consists of the coarse and fine current controls
(A5R123 and A5R124) and a differential amplifier stage (Z 1 and associated components). As in the constant voltage comparator, an integrated circuit
is used for the differential amplifier to minimize differential voltages due to mismatched transistors and thermal differentials.
4-40 The constant current comparator circuit con-
tinuously compares the voltage drop across the
CURRENT controls with the voltage drop across the current sampling resistor, A4R123. If a difference exists, the differential amplifier produces an error
signal which is proportional to this difference. The remaining components in the feedback loop
(mixer amplifier, error amplifiers, and the series regulator) function to maintain the voltage drop across the current sampling resistors, and hence
the output current, at a constant value.
4-41 One input of the differential amplifier (pin 7) is connected to the output bus through impedance equalizing resistor R20 and is zero-biased by R21
4-5
TM 11-6625-2958-14&P
and optional resistor R 117. The other input of the differential amplifier (pin 4) is connected to a sum­ming point (terminal A6) at the junction of the pro­gramming resistors and the current pullout resistors R30 and R31. Changes in the output current due to load changes or changes in the voltage at the sum­ming point due to manipulation of the CURRENT controls produce a difference voltage between the
two inputs of the differential amplifier. This differ-
ence voltage is amplified and appears at the output of the differential amplifier (pin 6) as an error volt­age which ultimately varies the conduction of the s cries regulator.
4-46 MIXER AND ERROR AMPLIFIERS
4-47 The mixer and error amplifiers amplify the error signal from the constant voltage or constant
current input circuit to a level sufficient to drive the series regulating transistors. Mixer amplifier Q41 receives the error voltage input from either the
constant voltage or constant current comparator via the OR-gate diode (CR1 or CR20) that is conducting
at the time. Diode CR1 is forward biased and CR20 reverse biased during constant voltage operation. The reverse is true during constant current opera­tion.
4-42 Resistor R30 serves as a trimming adjustment for the programming current flowing through A5R123 and A5R124. If the supply is equipped with Option
021, resistor R115 and potentiometer R116 provide a means of adjusting the programming current. As in the constant voltage comparator circuit, a vari-
able input bias (from resistor R118 and potentiome­ter R119) is provided to allow the output current to be adjusted to exactly zero when the supply is pro-
grammed for zero output. Diode CR21 limits exces-
sive voltage excursions at the summing-point input to the differential amplifier.
4-43 VOLTAGE CLAMP CIRCUIT
4-44 The voltage clamp circuit keeps the constant voltage programming current relatively constant when the power supply is operating in the constant current mode. This is accomplished by clamping
terminal A2, the voltage summing point, to a fixed
bias voltage. During constant current operation the constant voltage programming resistors are a shunt load acress the out put terminals of the power sup­ply. When the output voltage changes, the current
through these resistors also tends to change. Since this programming current flows through the current
sampling resistor, it is erroneously interpreted as
a load change by the current comparator circuit. The clamp circuit eliminates this undesirable effect by maintaining this programming current at a con-
stant level.
4-45 The voltage divider, Z2A, Z2B, and VR1, back biases CR2 and Q1 during constant voltage opera­t ion. When the power supply goes into constant
current operation, CR2 becomes forward biased by the voltage at pin 12 of Z 1. This results in conduc­tion of Q1 and the clamping of the summing point at a potential only slightly more negative than the
normal constant voltage potential. Clamping this
voltage at approximately the same potential that
exists in constant voltage operation results in a
constant voltage acress, and consequently a con-
stant current through, the current pullout resistors R3, R4, and R5.
4-48 Transistor Q40 provides a constant current to the collector of Q41 and also generates a negative going turn-off signal for the series regulator when
the unit is first turned off. Feedback network C41, R47, and R53 shapes the high frequency rolloff in the loop gain response in order to stabilize the
series regulator feedback loop. 4-49 Error amplifiers Q42 and A4Q101 serve as the
predriver elements for the series regulator. In addi­tion, transistor A4Q101 allows faster down-program­ming by providing a discharge path for output ca-
pacitors A3C3 and C19, and by supplying a bleed
current for the series regulator (thus keeping it in
its linear, active region) when the supply is set for
zero output current. Diode CR44, in the base cir-
cuit of transistor A4Q101, prevents the base from
going more negative than -3 volts. This action li-
mits the current through R57 to a relatively low
level, thus protecting A4Q101 from damage in the
event a voltage higher than the programmed output
voltage is placed across the output terminals (such
as might occur in Auto-Parallel or battery charging
applications).
4-50 OVERVOLTAGE PROTECTION CROWBAR
4-51 The overvoltage protection circuit protects
delicate loads from high voltage conditions such
as might result from the failure of the series regu-
lator transistor. It accomplishes this by shorting the output of the supply. Under normal operation
(no overvoltage), Q92 is conducting since CR91 is
reverse biased and Q91 is off. Thus no trigger
signal is received by SCR A4CR110 and it acts as an open circuit, having no effect on normal output voltage.
4-52 A5R125 (OVERVOLTAGE ADJUST) adjusts the bias of Q92 with relation to -S. It establishes the point at which CR91 becomes forward biased and
Q92 is turned off. Zener diode VR90 provides a
stable reference voltage with which the -S potential is compared; R95 sets the upper crowbar trip limit.
When Q92 turns off, Q91 begins to conduct, send-
ing a positive going trigger pulse to A4CR110, causing it to create a near short circuit across the
4-6
output. When A4CR110 is fired, overvoltage lamp A5DS2 is tuned on, completing a path for a + 11V unregulated holding current through A5DS2. This
current holds A4CR110 on even after the output voltage has fallen. A4 CR110 will remain in conduc-
tion until the supply is turned off. R92 supplies the
holding current if lamp A5DS2 should open. R106 protects A4CR108 and A4CR110 from the large surge
current that occurs when A4CR110 is first fired. CR93 damps out positive overshoot in the trigger pulse.
4-53 The firing of SCR A4CR110 biases Q90 into conduction, placing approximately +11 volts on the cathode of CR74 in the preregulator control circuit and thus reverse biasing CR74 and CR75. This action, by preventing transistor Q 72 from turning off, prevents the generation of any trigger pulses and turns off the preregulator. This prevents the
series regulator from experiencing a full-voltage, full-current condition.
4-54 The crowbar circuit creates an extra current path during normal operation of the supply, thus
changing the current that flows through the sam­pling resistor. Diode CR92 keeps this extra current at a fixed level for which compensation can then be
made in the constant current comparator circuit.
4-55 A slaving arrangement of crowbar circuits in more than one unit is made possible by an extra
secondary winding (terminals 5 and 6) on transfor-
mer T90. Terminals on the rear barrier strip (±EXT.
CROWBAR TRIGGER) allow easy connection to this winding. Connecting these windings in parallel when operating in a multiple-supply configuration
will result in all the crowbars being activated if
one of the crowbars is tripped. To reset the crow­bars in this arrangement, all of the units must be turned off and then on. Correct polarity must be observed when connecting the windings in parallel.
Figures 3-10 and 3-11 (Auto-Parallel and Auto-
Series ) demonstrate these connections.
4-56 TURN-ON CONTROL CIRCUIT
4-57 This circuit is a long time-constant network which protects the triac and the series regulator
from possible damage during turn-on. When the
supply is first tuned on, C35 provides a positive
voltage to the anodes of CR35 and CR36. The volt­age from CR35 is connected to the cathode of diode CR74 in the preregulator control circuit to ensure that it is initially reverse biased. After C35 be-
comes sufficiently charged, diode CR35 becomes reverse biased and the preregulator control circuit is permitted to fire the triac.
TM 11-6625-2958-14&P plied to the series regulator. This negative voltage keeps the regulator cut off untill C35 charges up. Diode CR37 provides a discharge path for C35 when
the supply is turned off.
4-59 REFERENCE REGULATOR
4-60 The reference circuit is a feedback power
supply similar to the main supply. It provides stable reference voltages used throughout the unit.
AH the reference voltages are derived from dc ob­tained from full wave rectifier CR61-CR62 and filter capacitor C61. The total output of the reference circuit is 18.6V. Zener diodes VR60 and VR61 es­tablish moderately well regulated potentials of +6.2V and -6.2V respectively from the common point +S, while the regulator circuit establishes a very well regulated potential of +12.4 volts from +S. Resistor R63 limits the current through the Zener diodes to establish an optimum bias level.
4-61 The regulating circuit consists of s cries reg­ulating transistor Q60, driver Q61, and differential amplifier Q62 and Q63. The voltage across Zener diode VR60 (+6.2 volts with respect to +S) and the
voltage at the junction of divider Z2L-R69B and Z2J
are compared, and any difference is amplified by Q 62 and Q63. The error voltage thus appearing at the collector of Q62 is amplified by driver stage Q61 and applied to series regulator Q60 in the cor­rect phase and amplitude to maintain the +12.4 volt output at a constant level.
4-62 Diode CR60, connected from voltage divider R66 and R67 to the base of Q61, serves as a turn­on circuit for series regulator transistor Q60. When the supply is first turned on, CR60 biases driver Q61 on, thus turning on the series regulator. When the reference supply reaches normal output, the base voltage of Q61 is sufficient to reverse bias CR60, thus effectively removing it from the circuit. Capacitor C60, connected across the output of the reference supply, removes spikes and stabilizes the reference reguIator loop.
4-63 Unregulated 11Vdc is supplied from a sepa­rate winding on transformer A3T2 by diodes CR53 and CR54 and filter capacitor C44. Additional light­ly regulated reference voltages of -4V and -2.4V are provided by diodes CR45-CR46 and CR47-CR48-CR49 respectively. Diode CR43 prevents reverse current flow from damaging the main supply series reguIator transistors. Diode CR7, shown in the schematic near the current pullout resistors (R3, R4, and RS), protects the Zener diodes in the reference circuit by providing a path for surge currents which occur during rapid down programming.
4-58 Diode CR36 performs a similar function for
the series regulator. CR36 initially couples a pos-
itive voltage to Q41 where it is inverted and ap-
4-64 METER CIRCUIT 4-65 The meter circuit provides continuous indica-
4-7
TM 11-6625-2958-14&P tions of output voltage and current on the dc volt­meter and ammeter. Both meter movements can withstand an overload of many times the maximum rated output without damage.
4-66 The ammeter together with its series resistors
(R101, R105) is connected across current sampling resistor A4R123. As mentioned previously, the voltage drop across the current sampling resistor varies in proportion to the output current.
Potenti-
ometer R101 is adjusted for full scale deflection
(calibration) of the ammeter.
4-67 The voltmeter, in series with R103 and R104 and shunted by R102 and R106, is connected direct­ly across the output terminals of the supply. Poten-
tiometer R106 permits calibration of the voltmeter.
4-68 ADDITIONAL PROTECTION FEATURES 4-69 The supply contains several “special pur-
pose” components which protect the supply in the
event of unusual circumstances. One of these
components is diode A4CR106. Connected across the output terminals of the supply, it prevents in­ternal damage from reverse voltages that might be applied across the supply. This could occur, fo
r
example, during Auto-Series operation if one sup­ply was turned on before the other.
4-70 Resistors R108 and R109 limit the output of the supply if the connections between both output buses and the sensing terminals (+S and -S) are in­advertently removed.
4-71 Diode A4CR105, previously mentioned in the series regulator description, protects the regula-
ting transistor from the effects of reverse voltages.
4-8

SECTION V

MAINTENANCE
TM 11-6625-2958-14&P
5-1 INTRODUCTION
5-2 Upon receipt of the power supply, the per­formance check (Paragraph 5-5) should be made. This check is suitable for incoming inspection. If a fault is detected in the power supply while mak­ing the performance check or during normal opera-
tion, proceed to the troubleshooting procedures
(Paragraph 5-51). After troubleshooting and repair
(Paragraph 5-71), perform any necessary adjust-
ments and calibrations (Pare graph 5-73). Before section.
Table 5-1. Test Equipment Required
TYPE
Differential
Voltmeter
Oscilloscope Sensitivity and bandwidth;
Sensitivity: 1mV full scale (min.) Input impedance: 10M
I
100µV/cm and 400KHz for all
measurements except noise spike;
5mV sensitivity and 20 MHz band­width for noise spike measure­ment.
REQUIRED
CHARACTERISTICS
(rein.)
returning the power supply to normal operation, re­peat the performance check to ensure that the fault has been properly corrected and that no other faults
exist. Before performing any maintenance checks, turn on the power supply and allow a half-hour warm-up.
5-3 TEST EQUIPMENT REQUIRED
5-4 Table 5-1 lists the test equipment required to
perform the various procedures described in this
Measure dc voltages; calibration procedures.
Measure ripple; display
transient recovery wave-
form; measure noise spikes.
USE
RECOMMENDED
MODEL
3420A/B (See
Note on Page 5-2)
140A with 1423A
time base and
1400A vertical plug-in; 1402A plug-in for spike measurement.
Variable
Voltage
Transformer
AC Voltmeter
DC Voltmeter
Repetitive
Load Stitch Rise time: 2µsec.
Resistive
Loads
Current
Sampling
Resistors
Range: 207-253Vac. Recommend­ed minimum output current: 12A, 6259B; 22A, 6261B and 6268B; 24A, 6260B: 36A, 6269B.
Sensitivity: 1mV full scale de­flection (min). Accuracy: 2%. ripple.
Sensitivity: 1mV full scale de- Measure dc voltages. flection (rein). Accuracy: 1%.
I
Switching rate: 60-400Hz
I
Values: see Figures 5-2 and 5-5.
I
Values: see Figure 5-8. Measure output current;
I
Vary ac input for line
regulation measurement.
Measure ac voltages and
I
Measure transient re- See Figure 5-5. covery time.
I
Power supply load
resistors.
A4R123;: A4R123A-
calibrate ammeter.
I
A4R123B,
6260B only; see Replaceable Parts
Table.
----
403B
412A
----
5-1
TM 11-6625-2958-14&P
Table 5-1.
Test Equipment Required (Continued)
TYPE
REQUIRED
CHARACTERISTICS
USE
Terminating Value: 50 ohms, ½ watt, ±5%, Noise spike measure-
Resistors
Blocking
Capacitors
non-inductive. (Four required.) Value: 0.01µF, 100Vdc. (Two Noise spike measure-
required.) ment.
NOTE
A satisfactory substitute for a differen­tial voltmeter is a reference voltage
source and null detector arranged as shown in Figure 5-1. The reference voltage source is adjusted so that the voltage difference between the supply
being measured and the reference volt-
age will have the required resolution
for the measurement being made. The
ment.
1
5-5 PERFORMANCE TEST
5-6 The following test can be used as an incoming inspection check and appropriate portions of the test can be repeated either to check the operation of the instrument after repairs or for periodic main­tenance tests.
The tests are performed using a 230V ac, 60 Hz, single phase input power source. If the correct result is not obtained for a particular check, do not adjust any internal controls; proceed to troubleshooting (Paragraph 5-5 1).
voltage difference will be a function of
the null detector that is used. Exam-
5-7 CONSTANT VOLTAGE TESTS
ples of satisfactory null detectors are:
419A null detector, a dc coupled oscilloscope utilizing differential in­put, or a 50mV meter movement with a
100 division scale. For the latter, a
2mV change in voltage will result in a
meter deflection of four divisions.
5-8 If maximum accuracy is to be obtained in the following measurements, the measuring devices must be connected as close to the output terminals as possible. This is particularly important when measuring the transient response, regulation, or ripple of the power supply. A measurement made across the load includes the impedance of the leads to the load and such lead lengths can easily have an impedance several orders of magnitude greater than the supply impedance, thus invalidating the measurement.
RECOMMENDED
MODEL
----
----
Figure 5-1. Differential Voltmeter Substitute
Test Setup
Care must be exercised to avoid ground
loops and circulating currents when using an electronic null detector in which one input terminal is grounded.
5-9 To avoid mutual coupling effects, each moni­toring device must be’ connected to the output ter­minals by a separate pair of leads. Twisted pairs or shielded two-wire cables should be used to avoid
pickup on the measuring leads. The load resistor
should be connected across the output terminals as close to the supply as possible. When measuring the constant voltage performance specifications, the current controls should be set well above (at least
10%) the maximum output current which the supply will draw, since the onset of constant current action will cause a drop in output voltage, increased ripple, and other performance changes not properly ascribed to the constant voltage operation of the
supply . 5-10 Voltage Output and Voltmeter Accuracy. To
check the output voltage, proceed as follows:
a. Connect load resistor (R
L) indicated in
Figure 5-2 across output terminals of supply.
b. Connect differential voltmeter acress
+OUT and -OUT terminals of supply, observing
5-2
Figure 5-2. Constant Voltage Load Regulation
Test Setup
correct polarity.
c. Turn CURRENT controls fully clockwise.
d. Turn on supply and adjust VOLTAGE con­trols until front panel meter indicates exactly max­imum rated output voltage.
e. Differential voltmeter should indicate the following:
6259B, 6260B
6261B
6268B, 6269B
5-11
Load Regulation. Definition: The change static value of dc output voltage re­sulting from a change in load resist­ance from open circuit to a value
which yields maximum rated output current (or vice versa).
To check the constant voltage load regula-
5-12
proceed as follows:
tion,
‘a. Connect test setup shown in Figure 5-2.
b. Turn CURRENT controls fully clockwise. c. Turn on supply and adjust VOLTAGE con-
trols until front panel meter indicates exactly max-
imum rated output current.
d. Read and record voltage indicated on dif-
ferential voltmeter.
e. Disconnect load resistor.
f. Reading on differential voltmeter should not vary from reading recorded in Step (d) by more than the following:
6259B, 6260B 1.2mV
6261B
6268B, 6269B
10 ±0.2Vdc 20 ±0.4Vdc 40 ±0.8Vdc
EOUT in the
2.2mV
4.2mV
TM 11-6625-2958-14&P
Line Regulation.
5-13
Definition: The change
static value of dc output voltage re-
sulting from a change in ac input volt­age over the specified range from low line (usually 207 volts) to high line
(usually 253 volts), or from high line to low line.
To check the line regulation, proceed as
5-14
follows :
a. Connect test setup shown in Figure 5-2. b. Connect variable auto transformer between
input power source and power supply power input.
c. Adjust variable auto transformer for 207
volts a c input.
d. Turn CURRENT controls fully clockwise. e. Turn on supply and adjust VOLTAGE con-
trols until front panel meter indicates exactly maxi-
mum rated output voltage.
f. Read and record voltage indicated on dif-
ferential voltmeter.
g. Adjust variable auto transformer for 253V
ac input.
h. Reading on differential voltmeter should
not vary from reading recorded in Step (f) by more than the following:
6259B,6260B
6261B
6268B, 6269B 4.2mV
Ripple and Noise.
5-15
Definition: The residual ac voltage
superimposed on the dc output of a regulated power supply. Ripple and
noise may be specified and measured
in terms of its RIMS or (preferably)
peak-to-peak value.
Ripple and noise measurement can be made at any input ac line voltage combined with any dc output voltage and load current within the supply's rating.
5-16 The amount of ripple and noise that is pres­ent in the power supply output is measured either in terms of the RMS or (preferably) peak-to-peak value. The peak-to-peak measurement is particu­larly important for applications where noise spikes
could be detrimental to a sensitive load, such as logic circuitry. The RMS measurement is not an ideal representation of the noise, since fairly high output noise spikes of short duration can be pres­ent in the ripple without appreciably increasing the RMS value,
5-17 Ripple Measurements. Figure 5-3A shows an incorrect method of measuring p-p ripple. Note that a continuous ground loop exists from the third wire of the input power cord of the supply to the third wire of the input power cord of the oscillo-
scope via the grounded power supply case, the
EOUT in the
1.2mV
2.2mV
5-3
TM 11-6625-2958-14&P
wire between the negative output terminal of the power supply and the vertical input of the scope, and the grounded scope case. Any ground current circulating in this loop as a result of the difference in potential EG between the two ground points causes an IR drop which is in series with the scope input. This IR drop, normally having a 60Hz line frequency fundamental, plus any pickup on the un-
shielded leads interconnecting the power supply and scope, appears on the face of the CRT. The magnitude of this resulting noise signal can easily be much greater than the true ripple developed be­tween the plus and minus output terminals of the
power supply, and can completely invalidate the measurement.
5-18 The same ground current and pickup problems
can exist if an RMS voltmeter is substituted in
place of the oscilloscope in Figure 5-3. However, the oscilloscope display, unlike the true RMS
meter reading, tells the observer immediately whether the fundamental period of the signal dis-
played is 8.3 milliseconds (1/120 Hz) or 16.7 milli-
seconds (1/60 Hz). Since the fundamental ripple
frequency present on the output of an
120Hz (due to full-wave rectification), an oscillo­scope display showing a 120Hz fundamental com-
ponent is indicative of a “clean” measurement set­up, while the presence of a 60Hz fundamental usually means that an improved setup will result in
a more accurate (and lower) value of measured rip-
ple.
supply is
5-19 Although the method shown in Figure 5-3A is not recommended for ripple measurements, it may
prove satisfactory in some instances provided cer­tain precautionary measures are taken. One meth-
od of minimizing the effects of ground current (IG) flow is to ensure that both the supply and the test
instrument are plugged into the same ac power buss.
5-20 To minimize pick up, a twisted pair or (pref­erably) a shielded two-wire cable should be used to connect the output terminals of the power supply to the vertical input terminals of the scope. When using a twisted pair, care must be taken that one of the two wires is connected both to the grounded terminal of the power supply and the grounded input terminal of the oscilloscope. When using shielded two-wire cable, it is essential for the shield to be connected to ground at one end only to prevent any
ground current flowing through this shield from in­ducing a signal in the shielded leads.
5-21 To verify that the oscilloscope is not dis­playing ripple that is induced in the leads or pick­ed up from the grounds, the (+) scope lead should
be shorted to the (-) scope lead at the power sup-
ply terminals.
leads are shorted should be subtracted from the
The ripple value obtained when the
Figure 5-3.
actual ripple measurement. 5-22 If the foregoing measures are used, the
single-ended scope of Figure 5-3A may be adequate to eliminate non-real components of ripple so that a satisfactory measurement can be obtained. How­ever, in stubborn cases or in measurement situa­tions where it is essential that both the power sup­ply case and the oscilloscope case be connected to ground (e. g. if both are rack-mounted), it may be necessary to use a differential scope with floating input as shown in Figure 5-3B. If desired, two single-conductor shielded cables may be sub­stituted in place of the shielded two-wire cable with equal success.
Ripple Test Setup
5-4
Because of its common mode rejection, a differen-
tial oscilloscope displays only the difference in
signal between its two vertical input terminals,
thus ignoring the effects of any common mode sig-
nal produced by the difference in the ac potential
between the power supply case and scope case.
Before using a differential input scope in this man-
ner, however, it is imperative that the common mode rejection capability of the scope be verified by shorting together its two input leads at the pow-
er supply and observing the trace on the CRT. If this trace is a straight line, then the scope is pro-
perly ignoring any common mode signal present. If this trace is not a straight line, then the scope is
not rejecting the ground signal and must be realign-
ed in accordance with the manufacturer’s instruc­tions until proper common mode rejection is attain-
ed.
5-23 To check the ripple output, proceed as fol-
lows :
a. Connect oscilloscope or RMS voltmeter
as shown in Figures 5-3A or 5-3B.
b. Turn CURRENT controls fully clockwise. c. Adjust VOLTAGE controls until front panel
meter indicates maximum rated output voltage.
d. The observed ripple should be less than
the following:
6259B, 6260B, 6261B
6268B, 6269B
500µVrms and 5mV p-p
1mVrms and 5mV p-p
5-24 Noise Spike Measurement. When a high fre-
quency spike measurement is being made, an in-
strument of sufficient bandwidth must be used; an oscilloscope with a bandwidth of 20 MHz or more is adequate. Measuring noise with an instrument that has insufficient bandwidth may conceal high fre­quency spikes detrimental to the load.
5-25 The test setup illustrated in Figure 5-3A
is generally not acceptable for measuring spikes;
a differential oscilloscope is necessary. Further-
more, the measurement concept of Figure 5-3B
must be modified if accurate spike measurement
is to be achieved
1. As shown in Figure 5-4, tw
O coax cables
must be substituted for the shielded two-wire cable.
2. Impedance matching resistors must be in-
cluded to eliminate standing waves and cable ring­ing, and capacitors must be inserted to block the dc current path.
3. The length of the test leads outside the coax is critical and must be kept as short as pos­sible; the blocking capacitor and the impedance
matching resistor should be connected directly from the inner conductor of the cable to the power supply terminals.
4. Notice that the shields of the power sup­ply end of the two coax cables are not connected to
the power supply ground, since such a connection would give rise to a ground current path through the
TM 11-6625-2958-14&P
Figure 5-4. Noise Spike Measurement Test Setup
coax shield, resulting in an erroneous measurement.
5. Since the impedance matching resistors
constitute a 2-to-1 attenuator, the noise spikes
observed on the oscilloscope should be less than
2.5mV p-p instead of 5mV p-p. 5-26 The circuit of Figure 5-4 can also be used for
the normal measurement of low frequency ripple:
simply remove the four terminating resistors and
the blocking capacitors and substitute a higher gain
vertical plug-in in place of the wide-band plug-in required for spike measurements. Notice that with these changes, Figure 5-4 becomes a two-cable version of Figure 5-3B.
5-27 Transient Recovery Time.
Definition: The time "X" for the output voltage recovery to within "Y" millivolts
of the nominal output voltage following a
"Z" amp step change in load current,
where: "Y" is specified as 10mV, the
nominal output Voltage is defined as the dc level ‘halfway between the static out-
put voltage before and after the imposed
load change, and "Z" is the specified
load current change of S amps or the full
load current rating of the supply, which-
ever is less.
5-28 Transient recovery time may be measured at any input line voltage combined with any output
voltage and load current within rating,
5-29 Reasonable care must be taken in switching the load resistance on and off. A ha rid-operated
s-s
TM 11-6625-2958-14&P
switch in series with the load is not adequate,
since the resulting one-shot displays are difficult to observe on most oscilloscopes, and the arc energy occurring during switching action completely masks the display with a noise burst. Transistor load switching devices are expensive if reasonably
rapid load current changes are to be achieved.
5-30 A mercury-wetted relay, as connected in the load switching circuit of Figure 5-5 should be used for loading and unloading the supply. When this load switch is connected to a 60Hz ac input, the mercury-wetted relay will open and close 60 times per second. Adjustment of the 25K control permits adjustment of the duty cycle of the load current switching and reduction in jitter of the oscilloscope display.
5-31 The load resistances shown in Figure 5-5 are the minimum resistances that must be used in order
to preserve the mercury-wetted relay contacts.
Switching of larger load currents can be accom­plished with mercury pool relays; with this tech-
nique fast rise times can still be obtained, but the large inertia of mercury pool relays limits the max­imum repetition rate of load switching and makes the clear display of the transient recovery charac­teristic on oscilloscope more difficult.
5-32 To check the transient recovery time, pro-
ceed as follows:
a. Connect test setup shown in Figure 5-5. b. Turn CURRENT controls fully clockwise.
c. Turn on supply and adjust VOLTAGE con­trols until front panel ammeter indicates 5 amps output current.
d. Close line switch on repetitive load
switch setup.
e. Set oscilloscope for internal sync and
lock on either positive or negative load transient
spike.
f. Set vertical input of oscilloscope for ac
coupling so that small dc level changes in power supply output voltage will not cause display to
shift.
g. Adjust the vertical centering on the scope
so that the tail ends of the no load and full load waveforms are symmetrically displayed about the horizontal center line of the oscilloscope. This
center line now represents the nominal output volt­age defined in the specification.
h. Adjust the horizontal positioning control
so that the trace starts at a point coincident with a major graticule division. This point is then repre-
sentative of time zero.
i. Increase the sweep rate so that a single
transient spike can be examined in detail.
j. Adjust the. sync controls separately for
the positive and negative going transients so that
not only the recovery waveshape but also as much
as possible of the rise time of the transient is dis-
played.
k. Starting from the major graticule division
representative of time zero, count to the right 50µ-
sec and vertically 10mV. Recovery should be with-
in these tolerances as illustrated in Figure 5-6.
Figure 5-5. Transient Recovery Time Test Setup
Figure 5-6. Transient Recovery Time Waveforms
5-6
5-33 Temperature Coefficient.
Definition: The change in output volt­age per degree Centigrade change in the ambient temperature under condi­tions of constant input ac line voltage, output voltage setting, and load re-
sistance.
5-34 The temperature coefficient of a power supply is measured by placing the power supply in an oven and varying it over any temperature span within its
rating. (Most HP power supplies are rated for oper-
ation from 0°C to 55°C.) The power supply must be allowed to thermally stabilize for a sufficient period
of time at each measurement temperature.
5-35 The temperature coefficient given in the spec­ifications is the maximum temperature-dependent output voltage change which will result over any one degree Centigrade interval. The differential volt­meter or digital voltmeter used to measure the out­put voltage change of the supply should be placed outside the oven and should have a long term sta­bility adequate to insure that its drift will not affect the overall measurement accuracy.
5-36 To check the temperature coefficient, pro-
ceed as follows:
a. Connect load resistance and differential
voltmeter as illustrated in Figure 5-2.
b. Turn CURRENT controls fully clockwise.
c. Adjust front panel VOLTAGE controls until front panel voltmeter indicates maximum rated out­put voltage.
d. Place power supply in temperature-con-
trolled oven (differential voltmeter remains outside
oven). Set temperature to 30°C and allow 30 minutes warm-up.
e. Record differential voltmeter reading.
f. Raise temperature to 40°C and allow 30 minutes warm-up.
g. Observe differential voltmeter reading.
Difference in voltage reading between Step (e) and
(g) should be less than the following:
62599,62600
6261B
6268B, 6269B
Qutput Stability.
5-37
Definition: The change in output voltage
for the first eight hours following a 30-
minute warm-up period. During the in-
terval of measurement all parameters,
such as load resistance, ambient temp-
erature, and input line voltage are held
constant.
5-38 This measurement is made by monitoring the output of the power supply on a differential voltme­ter or digital voltmeter over the stated measurement
interval; a strip chart recorder can be used to
12mV 22mV 42mV
TM 11-6625-2958-14&P
provide a permanent record. A thermometer should be placed near the supply to verify that the ambi-
ent temperature remains constant during the period
of measurement. The supply should be put in a lo-
cation immune from stray air currents (open doors
or windows, air conditioning vents); if possible, the supply should be placed in an oven which is held at a constant temperature. Care must be taken that the measuring instrument has a stability over the eight hour interval which is at least an order of magnitude better than the stability specification of the power supply being measured. Typically, a supply may drift Iess over the eight hour measure-
ment interval than during the half-hour warm-up. 5-39 To check the output stability, proceed as
follows :
a. Connect load resistance and differential
voltmeter as illustrated in Figure 5-2.
b. Turn CURRENT controls fully clockwise. c. Adjust front panel VOLTAGE controls until
differential voltmeter indicates maximum rated out-
put voltage.
d. Allow 30 minutes warm-up, then record
differential voltmeter reading.
e, After 8 hours, differential voltmeter should
change from reading recorded in Step (d) by less
then the following:
6259B, 62600 6261B, 6268B 8.0mV
6269B 5-40 CONSTANT CURRENT TESTS 5-41 The instruments, methods, and precautions
for the proper measurement of constant current pow-
er supply characteristics are for the most part iden-
tical to those already described for the measurement of constant voltage power supplies. There are, however, two main differences: first, the power supply performance will be checked between short
circuit and full load rather than open
load. Second, a current monitoring resistor is in-
serted between the output of the power supply and
the load.
5-42 For all output current measurements the cur-
rent sampling resistor must be treated as a four terminal device. In the manner of a meter shunt,
the load current is fed to the extremes of the wire leading to the resistor while the sampling terminals are located as close as possible to the resistance portion itself (see Figure 5-7). Generally, any cur­rent sampling resistor should be of the low noise,
low temperature coefficient (Iess then 30ppm/°C) type and should be used at no more than 5% of its rated power so that its temperature rise will be
minimized, If difficulty is experienced in obtaining
a low resistance, high current resistor suitable for
current sampling, a duplicate of the sampling resis­tor used in this unit (A4R123 or A4R123A-A4R123B)
5.0mV
14.0mV
circuit and full
5-7
TM 11-6625-2958-14&P
Figure 5-7. Current Sampling Resistor Connections
NOTE
When using the HP current sampling resistor recommended for this instru-
ment, an external fan must be employed to cool the resistor. This precaution will maintain the sampling resistance
at a constant value.
may be obtained from the factory.
5-43 Rated Output and Meter Accuracy.
a. Connect test setup shown in Figure 5-8.
b. Turn VOLTAGE controls fully clockwise.
c. Turn on supply and adjust CURRENT con-
trols until front panel ammeter indicates maximum
rated output current.
d. Differential voltmeter should read 0.5 ±
0.01Vdc. 5-44
Load Regulation.
Definition: The change
static value of the dc output current
resulting from a change in load re-
sistance from short circuit to a value
which yields maximum rated output
voltage.
5-45
To check the constant current load regulation,
proceed as follows:
a. Connect test setup shown in Figure 5-8.
b. Turn VOLTAGE controls fully clockwise.
c. Adjust CURRENT controls until front panel
meter reads exactly maximum rated out voltage.
d. Read and record voltage indicated on dif-
ferential voltmeter.
e, Short circuit load resistor (RL). f. Reading on differential voltmeter should
not vary from reading recorded in Step (d) by more
than the following:
6259B 6260B 6261B 6268B 6269B
IOUT in the
110µv 110µv 110µv 134µv 120µV
Figure 5-8.
5-46 Line Regulation.
Definition: The change
static value of dc output current re­sulting from a change in ac input volt­age over the specified range from low line (usually 207 volts) to high line
(usually 253 volts), or from high line to low line.
5-47 To check the line regulation, proceed as fol-
lows:
a. Utilize test setup shown in Figure 5-8. b. Connect variable auto transformer between
input power source and power supply power input.
c. Adjust auto transformer for 207Vac input. d. Turn VOLTAGE controls fully clockwise. e. Adjust CURRENT controls until front panel
ammeter reads exactly maximum rated output current.
f. Read and record voltage indicated on dif-
ferential voltmeter.
g. Adjust variable auto transformer for 253V
ac input.
h. Reading on differential voltmeter should
not vary from reading recorded in Step (f) by more
than the following:
Ripple and Noise.
5-48
Definition: The residual ac current which is superimposed on the dc output current
Constant Current Load Regulation
Test Setup
IOUT in the
6259B, 6269B
6260B, 6261B
6268B
120µV 110µV 134µV
5-8
TM 11-6625-2958-14&P
also apply to the measurement of constant current
ripple and noise. important precautions to be observed when measur­ing the ripple and noise of a constant current sup­ply. The presence of a 120Hz waveform on the os­cilloscope is normally indicative of a correct mea­surement method. A waveshape having 60Hz as its fundamental component is typically associated with an incorrect measurement setup.
5-50 Ripple and Noise Measurement. To check the ripple and noise, proceed as follows:
a. Connect oscilloscope or RMS voltmeter
as shown in Figures 5-9A or 5-9B.
b. Turn VOLTAGE controls fully clockwise.
c.
Adjust CURRENT controls until front pan­e 1 ammeter reads exactly maximum rated output cur­rent.
d. The observed ripple and noise should be
less than:
Figure 5-9 illustrates the most
6259B 6260B 6261B 6268B 6269B
250µVrms 250µVrms 250µVrms 334µVrms 250µVrms
Figure 5-9. Constant Current Ripple and Noise
Test Setup
of a regulated power supply. AC ripple and noise current is usually specified and measured in terms of its RMS value.
Most of the instructions pertaining to the
s -49 ground loop and pickup problem-s associated with constant voltage ripple and noise measurement
5-51 TROUBLESHOOTING
5-52 Before attempting to troubleshoot this instru­ment, ensure that the fault is with the instrument and not with an associated circuit. The perform-
ance test (Paragraph 5-5) enables this to be deter­mined without having to remove the instrument from the cabinet.
5-53 A good understanding of the principles of op­eration is a helpful aid in troubleshooting, and it
is recommended that the reader review Section IV of the manual before attempting to troubleshoot the
unit in detail. Once the principles of operation are understood, refer to the overall troubleshooting
procedures in Paragraph S-S 6 to locate the symptom
and probable cause.
5-54 The schematic diagram at the rear of the manual (Figure 7-11) contains normal voltage read-
ings taken at various points within the circuits. These voltages are positioned adjacent to the ap­plicable test points (identified by encircled num­bers). The component location diagrams (Figures 7-1 through 7-8, and Figure 7-10) at the rear of the manual should be consulted to determine the loca­tion of components and test points.
5-55 If a defective component is located, replace it and re-conduct the performance test. When a component is replaced, refer to the repair and re­placements (Paragraph 5-71) and adjustment and calibration (Paragraph 5-73) sections of this man­ual
5-9
TM 11-6625-2958-14&P
5-56 OVERALL TROUBLESHOOTING PROCEDURE 5-57 To locate the cause of trouble, follow Steps
1, 2, and 3 in sequence:
(1) Check for obvious troubles such as trip­ped circuit breaker, defective power cord, incor­rectly strapped rear terminals, input power failure or defective meter.
tom covers and inspect for open connections, charred components, etc. , paying particular atten-
tion to both sides of the main circuit board. to Paragraph 5-64 for the main circuit board remov-
Next, remove the top and bot-
(Refer
Table 5-2. Reference and Bias Voltages
(Refer to Schematic and Figure 7-10 for test point locations)
al procedure. ) If the trouble source cannot be de­tected by visual inspection, re-install the main circuit board and proceed to Step (2).
(2) In almost all cases, the trouble can be caused by incorrect dc bias or reference voltages; thus, it is a good practice to check the voltages in Table 5-2 before proceeding with Step (3). Re­fer to Figure 7-10 for the location of the test points listed in Table 5-2.
(3) Disconnect load and examine Table 5-3 to determine your symptom and its probable cause.
STEP
1
2 3 4 5
6
(Overvoltage lamp may be on or off)
METER
COMMON
+S
+S +S +S +S
+S
SYMPTOM
Low or no output voltage
METER
POSITIVE
TP63
TP64 TP65 TP66 TP67
TP68
NORMAL
VDC RIPPLE (P-P)
+12.4 ± 7%
+6.2 ±5%
-6.2 ±5% +11 ±15%
-4.0 ±12.5%
-2.4±12.5%
Table 5-3.
a. b. Crowbar not reset or defective. Refer to Table 5-4.
NORMAL
2.0mV
0.5mV
2.0mV
2.0V
0.8V
0.4V
Overall Trouble shooting
Front panel meter defective.
CR61, CR62, Q60, Q61, Q62,
Q63 VR60, VR61, Q62, Q63 VR60, VR61, Q62, Q63
C44, CR53, CR54
C44, CR53, CR54, CR45, CR46,
CR47, CR48, CR49
CR54, CR45, CR46, CR47,
CR48, CR49
PROBABLE CAUSE
PROBABLE CAUSE
.
High output voltage
High ripple
c.
Series regulator or preregulator feedback loop defective.
Refer to Table 5-4. Front panel meter defective.
a. b. Open circuit between sensing terminals (*S) and output ter-
minals (*OUT).
c. Series regulator or preregulator loop defective. If crowbar
does not trip, it also is faulty. Refer to Table 5-4.
a.
Ground loops in operating setup. Refer to Paragraph 5-15.
b. Incorrect reference and\or bias voltages. Refer to Table
5-2.
c. Supply crossing over to constant current operation under
loaded conditions.
5-10
Refer to Table 5-4.
Check current limit setting or constant
Table 5-3.
TM 11-6625-2958-14&P
Overall Troubleshooting (Continued)
SYMPTOM High ripple (continued) Poor line regulation
Poor load regulation
(Constant voltage)
Poor load regulation
(Constant current)
Oscillates (Constant current\constant voltage)
PROBABLE CAUSE
current comparator circuit (Z1 and associated components).
a.
Improper measurement technique. Refer to Paragraph 5-13.
b. Incorrect reference and/or bias voltages. Refer to Table
5-2. Improper measurement technique. Refer to Paragraph 5-11.
a. b. Incorrect reference and/or bias voltages. Refer to Table
5-2.
c. Supply current limiting.
tor circuit (Z1 and associated components). Improper measurement technique. Refer to Paragraph 5-44.
a.
b. Incorrect reference and/or bias voltages. Refer to Table
5-2.
c.
Supply voltage limiting. Check constant voltage compa­rator circuit (Z1 and associated components) and voltage clamp circuit, Q1.
d. Leaky C19, A3C3. a. Adjustment of R47.
b. Faulty C40, C41, C19, A3C3, R50.
Check constant current compara-
Refer to Paragraph 5-99.
c. Open sensing Iead (+S).
Instability a. Incorrect reference and/or bias voltages; CR92 defective.
(Constant current/constant voltage)
Cannot reach maximum output
5-58 Table 5-3 contains symptoms and probable causes of many possible troubles. If either high or low output voltage is a symptom, Table 5-4
contains the steps necessary to isolate the trouble
to one of the feedback loops and instructions dir-
ecting the tester to the proper table for further iso-
lation. back loops, it is necessary to refer to Table 5-4 before proceeding to Tables 5-5, 5-6, or 5-7.
5-59 Tables 5-5, 5-6, and 5-7 contain trouble­shooting methods for the series regulator and pre­regulator feedback loops once the fault has been
Because of the interaction between feed-
Refer to Table 5-2.
b. Noisy voltage or current controls (A5R121, A5R122, or
A5R123, A5R124); noisy VR60 or VR61.
Integrated circuit Z1 defective.
c.
d. CR4, CR5, CR6, or CR21 leaky.
e.
R2, R3, R4, R5, R6, R22, R30, R31, C2 noisy or drifting.
a. Q20 shorted.
(A4Q103 through A4Q108) open,
One or more of series regulator transistors
isolated to either one.
tain instructions for driving each stage of the
series regulator feedback loop into conduction or cut-off. the fault can be isolated to a circuit or to a com­ponent.
5-60 Table 5-7 contains troubleshooting proce­dures for the preregulator feedback loop. The troubleshooting method is based upon comparing the waveforms shown in Figure 7-9 with those ac­tually found at the various test points in the pre­regulator control circuit. As indicated in Table
By following the steps in these tables,
Tables 5-5 and 5-6 con-
5-11
TM 11-6625-2958-14&P
5-7, the circuit is checked by starting with the
output waveform and tracing backwards. 5-61 Performing the tests given in Table 5-5, 5-6,
and 5-7 will usually require partial disassembly of
the supply in order to gain access to components
(such as the series regulator transistors) that are not mounted on the main circuit board. If this is the case, refer as necessary to Paragraphs 5-65 through 5-70 for disassembly procedures.
STEP
ACTION
NOTE: After each step, crowbar should be reset by turning supply off and then on.
1
Inspect LINE circuit breaker.
2 Inspect overvoltage lamp on
front pane 1.
Table 5-4.
b. Not tripped;
c. Not tripped;
Feedback Loop Isolation
RESPONSE
a. Tripped.
PROBABLE CAUSE
a. Check rectifier, filter, and
triac for short. Faulty pre­regulator. Procceed to Step
3.
b. Series regulator loop in
High voltage output.
high voltage condition. Proceed to Step 2.
c. Proceed to Step 2.
Low voltage output.
a.
On.
a.
Check setting of overvolt­age adjust (A5R125). Check A4CR110 for short. Series regulator loop in high voltage condition.
Proceed to Step 3.
b. Off;
b. Check setting of overvolt-
High voltage output. age adjust (A5R125).
Check A4CR110 for open, Q91 for open, Q92 for
short.
Series regulator
loop in high voltage con-
dition. Proceed to Step 3.
3 Isolate fault to either series
regulator or preregulator by
using the following steps: to about 9 volts. through A4Q108) for open.
(1) Open the gate lead to triac A2CR1 by disconnect­ing either end of resistor R88 (TP87 or TP88).
(2) Place a small dc pow­er supply across the input capacitors (C 101 through C104). A 0-10V, 2A sup
-
ply is sufficient.
(3) Set external supply to
ten volts.
(4) Vary front panel volt-
age controls.
c.
off;
Low voltage output.
a.
Output voltage normal.
Variable from O volts
b. Output voltage high.
Varying controls has
little or no effect.
c. Output voltage low,
Varying controls has
little or no effect.
5-12
c.
Check overvoltage adjust
(A5R125). Check A4CR110 for short. Check Q20 for for short.
Proceed to Step
3.
a. Check each series regula-
tor transistor (A4Q103 Then check preregulator
by disconnecting source and proceeding to Table 5-7.
b. High voltage condition in
series regulator.
Proceed to Table 5-5. Leave ex­ternal source connected.
c. Low voltage condition in
series regulator loop. Proceed to Table 5-6. Leave external source connected.
TM 11-6625-2958-14&P
Table 5-5. Series Regulator Troubleshooting, High Voltage Condition
STEP
These tests should be made with
1
2
3
4
Check turn-off of series regulator transistors A4Q103 through A4Q108 by shorting base (TP101) to emitter
(TP103).
Check turn-off of driver A4Q102 by shorting base
(TP100) to emitter (TP101).
Check conduction of error amplifierA4Q101 by connect-
ing base (TP45) to cathode of CR45 (TP67) through a
100 Ω resistor.
Check conduction of error amplifier Q42 by connecting base (TP44) to cathode of
CR45 (TP67) through a 1K resistor.
ACTION
RESPONSE
external source connected as described
a. Output voltage remains high.
b. Output voltage decreases.
a. Output voltage remains high.
b. Output voltage decreases.
a. Output voltage remains high. b. Output voltage decreases.
a. Output voltage remains high, b. Output voltage decreases.
PROBABLE CAUSE
in Table 5-4, Step 3.
a. One or more of A4QI03
through A4Q108 shorted or A4CR105 shorted. Check A4R150-A4R155.
b. Remove short. Proceed
to Step 2.
a. A4Q102 shorted. b. Remove short. Proceed
to Step 3.
a. A4Q101 open. b. Remove resistor. Pro-
ceed to Step 4.
a. Q42 open. b. Remove resistor. Pro-
ceed to Step S.
s Check turn-off of mixer am-
plifier Q41 by connecting base (TP40) to +11 volt sup-
ply (TP66) through a 1K resistor.
6 Check turn-off of constant
voltage comparator Z 1 by
shunting R 1 with a 10K
sistor, or by installing a
resistor in R1 position
10K if resistor is not installed in the supply.
Table 5-6. Series ReguIator Troubleshooting, Low Voltage Condition
STEP
These tests should be made with external source connected as described in Table 5-4, Step 3.
1
Check conduction of series
regulator transistors A4Q103
through A4Q108 by connect-
ing base (TP101) to +11 volt
supply (TP66) through a 100
ohm resistor.
ACTION
re-
a. Output voltage remains high. b. Output voltage decreases.
a. Qutput voltage remains high.
b. Output voltage decreases.
RESPONSE
a. Output voltage remains low.
b. Output voltage rises.
a. Q41 shorted. b. Remove resistor. Pro-
ceed to Step 6.
a. Z1 defective, R110
shorted.
b. R23 open, open strap
between A 1 and A2, A5R121 or A5R122 open.
PROBABLE CAUSE
a.
A4Q103 throughA4Q108
open and/or A4R150 through A4R155 open, A4CR106 shorted.
Remove resistor. Pro-
b.
ceed to Step 2.
1
I
5-13
TM 11-6625-2958-14&P
Table 5-6.
Series Regulator Troubleshooting, Low Voltage Condition (Continued)
STEP
2
3
4
5 Isolate fault to either con- a, Output voltage rises.
6 Check conduction of mixer a. Output voltage remains low.
Check conduction of driver A4Q102 by shorting A4Q101 switch A4TS101 open. emitter (TP100) to base
(TP45).
Check turn-off of error am­plifier A4Q10 1 by connecting
base (TP45) to Q42 base
(TP44).
Check turn-off of error am-
plifier Q42 by connecting base (TP44) to +11V supply (TP66) through a 1K Ω resistor.
stant voltage comparator or
constant current comparator by opening the cathode of
CR20.
amplifier Q41 by connecting base (TP40) to +S terminal.
ACTION
RESPONSE
a. Output voltage remains low. a. A4Q102 open, thermal
b. Output voltage rises. b. Remove short. Proceed
a, Output voltage remains low. b. Output voltage rises. b. Remove short. Proceed
a. Output voltage remains low, a. Q42 shorted. b. Output voltage rises. b. Remove resistor. Pro-
b. Output voltage remains low. b. Reconnect lead and
b. Output voltage rises.
PROBABLE CAUSE
to Step 3.
a. A4Q101 or CR44 shorted.
to Step 4.
teed to Step 5.
a. Z1 defective, open
strap between A6 and
A7, or shorted A5R123
or A5R124.
proceed to Step 6.
a. Q41 or CR40 open, Q40
shorted.
b. Remove short. Proceed
to Step 7.
.
7
STEP
1 Connect oscilloscope be-
Check conduction of con-
stant voltage comparator Z 1 by shunting R110 with a 10K ohm resistor, or by installing
resistor in R110 po-
a 10K
sition if resistor is not in-
stalled in the supply.
Table 5-7.
ACTION
A differential oscilloscope must be used for these tests in order to avoid a potentially dangerous shock hazard.
recommended, because it may result in the oscilloscope chassis being at 230Vac line potential.
tween TP89 (+) and TP86 (-).
Preregulator Troubleshooting (Refer to Waveforms in Figure 7-9)
a. Output voltage remains low. a. Z1 defective, R1
shorted.
b. Output voltage rises.
RESPONSE
Floating a single-ended oscilloscope for these tests is not
a. Normal waveform.
b. Little or no voltage.
b. A5R121 and A5R122
shorted, open strap’ between AZ and A3, R5 open, C2 shorted, CR7
shorted.
PROBABLE CAUSE
a. Defective A2CR1, R88,
CR88, A2L1A/A2L1B,
T1, A2C1, A2R1.
b. Proceed to Step 2.
5-14
Table 5-7. Preregulator Troubleshooting (Continued)
TM 11-6625-2958-14&P
STEP
2
3
Connect oscilloscope be­tween TP85 (+) and TP103
(-).
1
Connect oscilloscope be­tween TP80 (+) and TP103
ACTION
RESPONSE
a. Normal waveform.
b. Little or no voltage.
I
Amplitude incorrect.
a.
(-).
b. Period incorrect.
Connect oscilloscope be- a. Amplitude, dc reference or
4
tween TP82 (+) and TP103 period incorrect.
(-).
5 Connect oscilloscope be- a. Amplitude, dc reference or
tween TP81 (+) and TP103 period incorrect.
(-) .
5-62 DISASSEMBLY PROCEDURES 5-63 The following seven paragraphs describe
procedures for removing and disassembling the five subassemblies in this supply (A1 main circuit board, A2 RFI assembly, A3 interconnection circuit board, A4 heat sink, and A5 front panel). These procedures are referenced throughout the manual wherever necessary. For example, in the instruc­tions for converting the supply to 115Vac opera­tion, reference is made to the RFI assembly remov­al procedure in order to allow access to the bias transformer (A3T2) primary connections.
5-64 Main C
ircult Board (Al) Removal. To remove
the main printed circuit board, proceed as follows:
a. Unplug unit and remove top cover of
supply.
b. Remove six hold-down screws visible on component side of main circuit board (arrowed “A” through “F” in Figure 7-1 O).
c. Unplug board from receptacle mounted on interconnection circuit board by gently pulling on finger hole in opposite end of circuit board. Only finger hole should be used to remove board; do not pull on beard-mounted components to aid re­moval. Care must be taken that rear barrier strip clears opening in rear panel.
Front Panel (A5) Removal. To remove the
5-65
front panel, proceed as follows:
a. Unplug unit, turn supply upside down, and remove four screws holding handlers to front
panel.
b. Front panel may now be swung outward,
hinging on wires to LINE circuit breaker. Access
is provided to all panel-mounted components. 5-66 Main Filter Capacitor Bank Removal. To re-
move the main filter capacitors (Cl 01 through C104), proceed as follows:
a. Unplug unit, remove top and bottom cov-
ers of supply.
b. Remove one long screw and hold-down bracket on top of supply (arrowed “A” in Figure 7-3), and one long screw and hold-down bracket on bottom of supply (arrowed “A” in Figure 7-4).
c. Sufficient lead length is provided to al-
low capacitors to be lifted partially out of instru-
ment. 5-67 RFI Assembly
RFI assembly, proceed as follows:
a. Unplug unit, turn supply upside down, and remove bottom cover.
b. Remove four screws holding RFI heat sink to mounting brackets (arrowed “A” through “D” in Figure 7-5). sible through holes in chassis flanges.
C. Lift out RFI assembly and turn over.
d. Remove four screws holding cover to heat sink (screw holes are arrowed “A” through “ D“ in Figure 7-1). and A2L1A/A2L1B with its jumpers for 115/230 volt operation.
mounting bracket to heat sink. (Two of the screws
PROBABLE CAUSE
a.
Defective T70.
b. Defective Q72, Q73,
CR76, or C71. pro­ceed to Step 3.
a.
Defective Q71, C70, C72, CR74, CR75, R82, R75, or R78.
b. CR78 defective. Pro-
ceed to Step 4.
a.
Defective CR82, CR84, CR79, CR80, CR77, CR78. Check
R87.
a.
Defective CR81, CR83, R86, R83, C73.
,
(A2) Removal. To remove the
Two of the screws are acces -
This allows access to A2R1, A2C1,
Remove four screws holding A2L1A/A2LlB
.
5-15
TM 11-6625-2958-14&P are arrowed “E” and “F“ in Figure 7-1.) Lifting brackets away from heat sink allows access to
triac A2CR1. A magnetized screwdriver is useful in performing this step.
5-68 Heat Sink (A cess to the following components, it is necessary to remove the heat sink assembly. Transistors A4Q101 through A4Q108; diodes A4CR1OI through A4CR106, A4CR108, and A4CR110; resistors A4R106, A4R123, and A4R150 through A4R155; ca-
pacitors A4C1 through A4C5; cooling fan A4B1; and thermal switch A4TS101. components, see Figures 7-5, 7-6, 7-7, and 7-8. To remove the heat sink assembly, proceed as fol-
lows:
a.
Unplug unit, stand it on left side, and
remove top and bottom covers.
b. Remove main printed circuit board as
described in Paragraph 5-64.
Remove two screws holding upper edge
c.
of heat sink to upper chassis flange (arrowed “E”
and “F” in Figure 7-D).
d. Disengage two pins holding lower sec­tion of heat sink assembly to main circuit board support tray by sliding heat sink down about ½ inch and slightly away from chassis. Before fully removing heat sink assembly, observe lead dress so assembly may be returned easily to correct po-
s it ion.
e.
Maneuver heat sink assembly down­wards and away from chassis until it is resting on table (sufficient lead length is provided). Gentle
leverage with a thin screwdriver may be necessary to allow heat sink assembly to clear upper chassis flange.
mounted on heat sink except resistors A4R150 through A4R155, and A4R123,
5-69 Heat Sink (4) Disassembly. To gain access
to resistors A4R123 and A4R150 through A4R155
(shown in Figures 7-6 and 7-8) it is necessary to disassemble the heat sink assembly by utilizing the following procedure:
in Paragraph 5-68 above. sink assembly partially into chassis so fan (A4B1)
is protruding above chassis.
washers attaching fan mounting plate to heat sink.
Do not remove fan from mounting plate. When re­assembling heat sink, do not overtighten these
screws. Too much tension will damage the insu-
lating rods.
pling resister A4R123 to topmost two portions of heat sink.
Access is now provided to all components
a.
Remove heat sink assembly as described
b. Turn supply upside down and place heat
Remove four screws and four shoulder
c.
d. Remove two screws holding current sam-
4) Removal. In order to gain ac-
For the location of these
If necessary, the resistor may be
unsoldered at this point.
e.
Remove mounting nuts from A4CR106 on left side of heat sink, and from A4CR108 on right side of heat sink. and shoulder washers on transistor A4Q102 on right side of heat sink (see Figure 7-5).
f. Slide top section of heat sink forward and
off insulating rods.
Remove four screws holding emitter re-
9.
sistor circuit board to bottom half of heat sink. A
magnetized screwdriver is useful here. Access is now provided to series regulator emitter resistors
A4R150 through A4R155 (see Figure 7- 6).
h. If necessary to completely remove emit-
ter resistor circuit board, unsolder connections to
board, marking wires to enable correct replacement, and remove board.
5-70 Interconnection Circuit Board (A3) Removal. To replace capacitor A3C3 or transformer A3T2,
(shown in Figure 7- 2), it is necessary to remove the interconnection circuit board by utilizing the following procedure:
Remove main circuit board, RFI assembly,
a.
and heat sink assembly as described in Paragraphs
5-64, 5-67, and 5-68 respectively.
b. Remove six screws holding back panel to
chassis frame.
c. Stand supply on left side, and remove
two screws holding main circuit board support tray
to back panel.
d. Remove two screws holding main circuit
board support tray to internal chassis divider.
Working from top rear of supply, inter-
e, connection circuit board (still attached to main circuit board support tray) can be angled up enough to allow access.
f. If necessary to completely remove inter­connection circuit board, remove two screws hold­ing board to support tray, one screw holding ca­pacitor clamp (A3C3) to support tray, and two
screws holding bias transformer (A3T2) to support tray. Unsolder connections to board, marking wires to enable correct replacement, and remove board.
5-71 REPAIR AND REPLACEMENT
5-72 Section VI of this manual contains a list of
replaceable parts. If the part to be replaced does
not have a standard manufacturers’ part number, it
is a “special” part and must be obtained directly
from Hewlett-Packard. After replacing a semicon-
ductor device, refer to Table 5-8 for checks and
adjustments that may be necessary. All compo-
nents listed in Table 5-8 without A-designators are
on the main printed circuit board (Al).
Remove mounting nuts, bolts
Move panel away from frame.
5-16
TM 11-6625-2958-14&P
Table 5-8. Checks and Adjustments After Replacement of Semiconductor Devices
REFERENCE
Z1
Q1 Q20 Q40, Q41
Q42, A4Q101, A4Q102
Q60, Q61, Q62, Q63
Q70 Q71, Q72, Preregulator control cir- Output voltage, rippIe imbalance, and
Q73
FUNCTION OR CIRCUIT
Constant voltage and con-
stant current differential
amplifiers.
Voltage clamp circuit.
Short circuit protection. Output current, protection action.
Mixer amplifier. CV/CC load reguIation. CV transient
Driver and error amplifiers.
Reference regulator.
Overvoltage limit.
cuit.
Constant voltage (CV) line and load reg­uIation. Zero volt output.
Constant current (CC) line and load reg­ulation. Zero current output.
CC load regulation.
response. CV/CC load regulation.
+12.4V, +6.2V, and -6.2V reference volt­ages and reference circuit line operation.
Limiting action and level.
preregulator waveforms.
CHECK
ADJUST
R110, or R113 (OP­tion 020); R117, or R119
(Option
021)
---
---
R47
---
---
---
R70, R82
Q90, Q91, Q92
A4Q103 thru A4Q108
A42CR1 CR1, CR20 CR2, CR3 CR4, CR40,
CR41
CR5, CR6, CR21
CR7, CR60, CR61, CR62
CR35, CR36, CR37
CR43, CR45 thru CR49, CR53, CR54
Crowbar.
Series regulator.
Preregulator. CV/CC OR gate. Voltage clamp circuit. Temperature stabilizing
diodes. Limiting diodes.
Reference regulator.
Turn-on circuit.
Bias supply.
Crowbar action, trip voltage, voltage across series regulator when tripped.
CV/CC load regulation.
Output voltage. CV/CC crossover operation. CC load regulation. Temperature coefficient.
CV/CC load regulation.
+12.4V, +6.2V, and -6.2V reference voltages.
Preregulator control turn-on delay.
+11V, -4V, and -2.4V bias voltages.
A5R125
---
R7O
---
---
---
---
---
---
---
I
CR44, CR50
Driver and error amplifier.
Down-programming speed, CV/CC
load regulation.
5-17
---
TM 11-6625-2958-14&P
Table 5-8. Checks and Adjustments After Replacement of Semiconductor Devices (Continued)
REFERANCE
CR90 thru
CR93, A4CR108, A4CR110
A4CR101 thru A4CR104
A4CR105
and
A4CR106
VR1
VR40
FUNCTION OR CIRCUIT
I
Crowbar.
Main rectifier diodes.
Reverse voltage protection.
Voltage clamp circuit.
Mixer amplifier stabiliza­tion diode.
CHECK
Limiting action and level.
Output voltage, ripple imbalance, and preregulator waveforms.
Trip voltage, voltage across series regu-
lator when crowbar is tripped, supply stability.
Voltage across main filter capacitors.
Output voltage.
CC load regulation. CV transient response.
+6.2V and -6.2V reference voltages. Trip voltage.
ADJUST
---
R70, R82
R95,
A5R125
---
---
---
R47
---
R95,
A5R125
5-73 ADJUSTMENT AND CALIBRATION
5-74 Adjustment and calibration may be required after performance testing, troubleshooting, or re­pair and replacement.
Perform only those adjust­ments that affect the operation of the faulty cir­cuit and no others.
5-75 METER ZERO .5-76 The meter pointer must rest on the zero cal-
ibration mark on the meter scale when the instru­ment is at normal operating temperature, resting in its normal operating position, and turned off. To zero set the meter proceed as follows:
a.
Connect load resistor of value shown in
Figure 5-2.
b. Turn on instrument and allow it to come up to normal operating temperature (about 30 min­utes).
c. Turn instrument off.
Wait one minute for
power supply capacitors to discharge completely.
d. Insert sharp pointed object (pen point or awl) into small indentation near top of round black plastic disc located directly below meter face.
e.
Rotate plastic disc clockwise until me-
ter reads zero, then rotate counterclockwise
slightly in order to free adjustment screw from meter suspension. Pointer should not move during
latter part of adjustment. 5-77 VOLTMETER CALIBRATION 5-78 To calibrate the voltmeter, proceed as fol-
lows:
a.
Connect differential voltmeter across
supply, observing correct polarity.
b. Turn on supply and adjust VOLTAGE con­trols until differential voltmeter reads exactly the maximum rated output voltage.
c. Adjust R106 until front panel voltmeter also indicates exactly the maximum rated output voltage.
5-79 AMMETER CALIBRATION 5-80 To calibrate the ammeter, proceed as fol-
lows:
a.
Connect test setup shown in Figure 5-8. b. Turn VOLTAGE controls fully clockwise. c.
Turn on supply and adjust CURRENT con-
trols until differential voltmeter reads 0.5Vdc.
d. Adjust R101 until front panel ammeter in-
dicates exactly maximum rated output current.
5-18
5-81 CONSTANT VOLTAGE PROGRAMMING
CURRENT
5-82 Zero Output Voltage. To calibrate the zero
voltage programming accuracy, proceed as direct­ed in Paragraphs 5-83, 5-84, 5-85, or 5-86, whichever applies to your particular instrument.
5-83 Standard instrument with resistance or unity-
gain voltage programming.
a. Connect differential voltmeter between
+OUT and -OUT bus bars.
b. If unit is to be used in local program­ming mode, turn VOLTAGE controls fully counter­clockwise. If unit is to be used in remote pro­gramming mode, connect remote programming setup
(Figure 3-3 or 3-4) and adjust remote resistance or
voltage to zero (minimum).
c.
Connect decade resistance box between
pads of position marked for resistor R110 in “ZERO
ADJUST” section of main circuit board (points “A”
and “B” in Figure 5-10; also see Figure 7-10).
d. Rotate CURRENT controls fully clockwise and turn on supply.
e. Adjust decade resistance box until dif-
ferential voltmeter reads exactly zero volts.
f. Replace decade resistance box with fixed, metal film, 1%, 1/4 or 1/8 watt resistor of same value.
5-84 Standard instrument with non-unity gain voltage programming.
Perform Steps (a) and (b) in Paragraph
a.
5-83.
b. Solder jumper between “wiper” pad and “+12.4V” pad of position marked for potentiometer R112 in “ZERO ADJUST” section of main circuit board (points “C” and “ D“ in Figure 5-10; also see Figure 7-10).
c. Connect decade resistance box between
pads marked for resistor R111 in “ZERO ADJUST”
section of main circuit board (points “ E“ and “ F“ in Figure 5-10; also see Figure 7-10).
d. Perform Steps (d) through (f) in Paragraph
5-83.
TM 11-6625-2958-14&P
voltage programming.
a.
Perform Steps (a) and (b) in Paragraph
5-83.
b. Rotate CURRENT controls fully clockwise
and turn on supply.
c. If reading on differential 1 voltmeter is not exactly zero volts, adjust potentiometer R113 (la­beled "VOLTAGE ZERO" and accessible through hole in’ rear panel) until reading is exactly zero.
5-86 Option 020 with non-unity gain voltage pro­gramming.
Perform Steps (a) and (b) in Paragraph
a.
5-83.
b. Rotate CURRENT controls fully clockwise and turn on supply.
c. If reading on differential voltmeter is not exactly zero volts, adjust potentiometer R112 (la­beled “VOLTAGE PROG” and accessible through hole in rear panel) until reading is exactly zero.
5-87 CV Programming Accuracy. To caIibrate the constant voltage programming current, proceed as directed in Paragraphs 5-88 or 5-89, whichever applies to your particular instrument.
5-88 Standard instrument.
a. Connect 0.1%, 1/8 watt resistor of value shown below between terminals -S and A3 on rear barrier strip.
Model
62596 62606 62616 6268B
62696
b. Disconnect strap between terminals Al
and A2 on rear barrier strip.
c. Connect differential voltmeter between
+OUT and -OUT bus bars.
d. Connect decade resistance box in place
of R3 (mounted on standoffs on main circuit board;
see Figure 7-10).
e.
Rotate CURRENT controls fully clockwise
and turn on supply.
f. Adjust decade resistance box until dif-
ferential voltmeter indicates exactly maximum rated output voltage.
g. Replace decade resistance box with
fixed, composition, 5%, 1/2 watt resistor of same vaIue.
Value
2K
2K
4K 8K 8K
Figure 5-10. “ZERO ADJUST” Section of Main
circuit Board
5-85 Option 020 with resistance or unity-gain
5-89 Option 020.
a.
Perform Steps (a) through (c) in Paragraph
5-88.
b. Rotate CURRENT controls fully clockwise
and turn on supply.
c. Adjust potentiometer R112 (labeled
“VOLTAGE PROG” and accessible through hole in
rear panel) until differential voltmeter indicates
5-19
TM 11-6625-2958-14&P exactly maximum rated output voltage.
5-90 CONSTANT CURRENT PROGRAMMING
CURRENT
5-91 Zero Current OutPut. To calibrate the zero
current programming accuracy, proceed as direct-
ed in Paragraphs 5-92, 5-93, 5-94, or 5-95,
whichever applies to your particular instrument.
5-92 Standard instrument with resistance or unity-gain voltage programming.
Connect test setup shown in Figure 5-8.
a.
b. If unit is to be used in local program­ming mode, turn CURRENT controls fully counter­clockwise. gramming mode, connect remote programming setup
(Figure 3-6 or 3-7) and adjust remote resistance or
voltage to zero. (minimum).
c. Connect decade resistance box between
pads of position marked for resistor R117 in “ZERO
ADJUST” section of main circuit board (points “G”
and “H” in Figure 5-10; also see Figure 7-10).
d. Rotate VOLTAGE controls fully clockwise
and turn on supply.
e.
ferential voltmeter reads exactly zero volts.
f. Replace decade resistance box with
fixed, metal film, 1%, 1/4 or 1/8 watt resistor of
same value. 5-93 Standard instrument with non-unity gain
voltage programming.
a.
5-92.
b. Solder jumper between “wiper” pad and
“-6.2V” pad of position marked for potentiometer
R116 in “ZERO ADJUST” section of main circuit
board (points “I” and “J” in Figure 5-10; also see Figure 7-10).
c. pads marked for resistor R115 in “ZERO ADJUST” section of main circuit board (points “ K“ and “ L“ in Figure 5-1 O; also see Figure 7-10).
d. 5-92.
If unit is to be used in remote pro-
Adjust decade resistance box until dif-
Perform Steps (a) and (b) in Paragraph
Connect decade resistance box between
Perform Steps (d) through (f) in Paragraph
b. Rotate VOLTAGE controls fully clockwise
and turn on supply.
c. If reading on differential voltmeter is not
exactly zero volts, adjust potentiometer R116 (la-
beled “CURRENT PROG” and accessible through hole in rear panel) until reading is exactly zero.
5-96 CC Programming Accuracy. To calibrate the
constant current programming current, proceed as
directed in Paragraphs 5-97 or 5-98, whichever applies to your particular instrument.
5-97 Standard instrument.
a. Connect test setup shown in Figure 5-8. b, Disconnect strap between terminals A5
and A6 on rear barrier strip.
c.
Connect 0.1%, 1/8 watt resistor of value shown below between terminals A4 and A6 on rear barrier strip.
Mode 1
6259B 6260B 6261B 6268B 6269B
d. Connect decade resistance box in place
of R30 (mounted on standoffs on main circuit
board; see Figure 7-1 O).
e.
Rotate VOLTAGE controls fully clockwise
and turn on supply.
f. Adjust decade resistance box until dif-
ferential voltmeter indicates exactly 0.5Vdc.
Replace decade resistance box with fixed, composition, 5%, 1/2 watt resistor of same value.
and turn on supply.
panel) until differential voltmeter indicates exactly
9.
5-98 Option 021.
Perform Steps (a) through (c) in Paragraph
a.
5-97.
b. Rotate VOLTAGE controls fully clockwise c. Adjust potentiometer R116 (labeled “CUR-
RENT PROG” and accessible through hole in rear
0.5Vdc.
Value
200 200 200
180 200
Ω Ω Ω Ω Ω
5-94 Option 021 with resistance or unity-gain voltage programming.
Perform Steps (a) and (b) in Paragraph
a.
5-92.
b. Rotate VOLTAGE controls fully clockwise
and turn on supply.
If reading on differential voltmeter is
c.
not exactly zero volts, adjust potentiometer R119
(labeled “CURRENT ZERO” and accessible through
hole in rear panel) until reading is exactly zero. 5-95 Option 021 with non-unity gain voltage pro-
gramming.
Perform Steps (a) and (b) in Paragraph
a.
5-92.
5-99 TRANSIENT RECOVERY TIME 5-100 To adjust the transient response, proceed
as follows:
a.
Connect test setup shown in Figure 5-5.
b. Repeat Steps (a) through (k) as outlined
in Paragraph 5-32.
Adjust R47 until transient response is
c.
within specification as shown in Figure 5-6.
5-101 RIPPLE IMBALANCE (50 and 60Hz Operation)
5-102 This procedure ensures balanced operation
of the triac by ensuring that the conduction time
5-20
is equal in either direction (within 25%). To check for imbalance, proceed as follows:
a.
Connect appropriate Ioad resistance
across rear output terminals of supply as follows:
MODEL
6259B 6260B 62610 6268B 6269B
b. Connect variable auto transformer be­tween input power source and power supply power input; adjust auto transformer for 230Vac input to supply.
c. Connect oscilloscope (ac coupled) be-
tween TP102 and TP103 (across series regulator).
d. Turn CURRENT controls fully clockwise, turn on supply, and adjust VOLTAGE controls for maximum rated output voltage.
e. Adjust oscilloscope to observe 120Hz sawtooth waveform. sawtooth peaks should be within 25% of each other.
f. If amplitude difference is greater than
25%, turn off supply and replace R82 with decade
resistance.
Turn on supply and adjust decade resist-
ance to reduce imbalance to within 25%. ac and insure that imbalance does not exist any-
where within this range. equivalent resistor.
9. h. Vary input line voltage from 207 to 253V
Load Resistance
0.2 500W, ±5% O.1 Ω, 1000W, ±5%
0.4
Ω, 1000W, ±5%
1.33 Ω, 1200W, ±5%
0.8 Ω, 2000W, ±5%
Peak amplitudes of adjacent
Replace decade box with
NOTE
TM 11-6625-2958-14&P
Connect dc voltmeter acress series reg-
ulator (TP102 and TP103).
d. Turn CURRENT controls fully clockwise. e,
To check voltage drop across regulator at low output voltage, short circuit load resistor and adjust VOLTAGE controls for maximum rated output current on front pane 1 ammeter.
f. Adjust R70 until voltmeter reads 3.5±
0.3Vdc. g. To check the voltage drop at high output
voltage, remove short circuit from acress load re-
sistor and adjust VOLTAGE controls for maximum rated output current. again be 3.5 ± 0.3Vdc.
h. Vary input line voltage from 207 to 253V
ac. Voltmeter reading should vary between 3.2
(minimum) and 3.8 (maximum) volts. If reading ex-
ceeds this range, proceed with Step (i).
i.
Replace resistor R77 with decade resis-
tance box. Vary input line voltage between 207
and 253Vac while adjusting decade box until volt­meter reading variation is minimal and within range of 3.2 to 3.8Vdc. alent resistor.
5-105 50Hz OPERATION (Option 005)
5-106 If the supply is to be operated from a 50Hz ac input, the following modifications are required:
a. Replace resistor R82 with 240
1/2 watt resistor, and check ripple imbalance as described in Steps (a) through (e) of Paragraph
5-101.
b. Perform preregulator tracking adjustment
described in Paragraph 5-103.
Voltmeter reading should
Rep lace decade box with equiv-
Ω, ±5%,
If imbalance cannot be reduced to
within 25%, check capacitors C70 and
C72, and diodes CR79 through CR84. If these components test satisfactori-
ly, the problem may be due to distor-
tion present on the ac power line.
5-103 PREREGULATOR TRACKING (50 and 60Hz
Operation)
5-104 To adjust the voltage drop across the series
regulator, proceed as follows:
a. Connect appropriate load resistance
across rear output terminals of supply as follows:
Model
62S9B 6260B 6261B 6268B 6269B
b. Connect variable auto transformer be-
tween input power source and power supply power
input adjust auto transformer for 230Vac input to supply.
Load Resistance
0.2
0.1 Ω, 1000W, ±5%
0.4
1.33
0.8
500W, ±5%
Ω, 1000W, ±5%
Ω,
1200W, ±5%
2000W, ±5%
Ω,
5-107 CROWBAR TRIP VOLTAGE
5-108 To adjust A5R125 (OVERVOLTAGE ADJUST),
proceed as follows:
Turn screwdriver adjustment, A5R125,
.
fully clockwise.
b. Turn on supply. c. Set voltage output to desired trip voltage.
d. Turn A5R125 slowly counterclockwise until the crowbar is tripped (meter falls to zero volts).
e. Turn off supply and turn down output
voltage.
f. Turn on supply and set desired operating
output voltage.
NOTE
It is recommended that the crowbar be set to no less than 5% of the desired
output voltage plus two volts, in or-
der to avoid false tripping of the
crowbar. However, if occasional crowbar tripping on unloading can be
tolerated, the crowbar trip point can
5-21
TM 11-6625-2958-14&P
be set much closer to the operating output voltage of the supply.
5-109 MAXIMUM CROWBAR TRIP VOLTAGE 5-110 To adjust the maximum voltage at which the
crowbar trips, proceed as follows:
a. Rotate A5R125 (OVERVOLTAGE ADJUST)
and CURRENT controls fully clockwise.
b. Disconnect either end of R72 (TP70 or
TP71; see Figure 7-10).
c. Connect decade resistance box in place of R95 (mounted on standoffs on main circuit board).
d. Turn on supply and adjust VOLTAGE con­trols for output voltage shown below:
Model 6259B 12Vdc 6260B
Value
12Vdc
Model 6261B 23Vdc 6268B 6269B
Adjust decade resistance box until crow-
e.
bar trips (amber OVERVOLTAGE lamp lights up).
f.
Replace decade resistance with appro­priate value resistor in R95 position and reconnect resistor R72. Maximum crowbar trip voltage is
now set at voltage given in Step (d).
5-111 CROWBAR DISABLEMENT
5-112 To disable the crowbar completely, discon­nect either end of R98 (TP97 or TP98). This resis-
tor is mounted on the main circuit board (see Fig-
ure 7-10).
Value
45Vdc
45Vdc
5-22

SECTION VI

REPLACEABLE PARTS
TM 11-6625-2958-14&P
6-1 INTRODUCTION
6-2 This section contains information for ordering
replacement parts. Table 6-4 lists parts in alpha­numeric order by reference designators and provides the following information:
a.
Reference Designators. Refer to Table 6-1.
b. Description.
Refer to Table 6-2 for ab-
breviations.
c. Total Quantity (TQ). Given only the first time the part number is listed except in instruments containing many sub-modular assemblies, in which case the TQ appears the first time the part number is listed in each assembly.
d. Manufacturer’s Part Number or Type.
Manufacturer’s Federal Supply Code Num-
e. ber. Refer to Table 6-3 for manufacturer’s name and address.
f. Hewlett-Packard Part Number.
g. Recommended Spare Parts Quantity (RS) for complete maintenance of one instrument during one year of isolated service.
h. Parts not identified by a reference desig-
nator are listed at the end of Table 6-4 under Me-
chanical and/or Miscellaneous.
The former consists
of parts belonging to and grouped by individual as-
semblies; the latter consists of all parts not im-
mediately associated with an assembly.
6-3 ORDERING INFORMATION
6-4 Table 6-5 is a part number-national
stock number cross reference index.
The
items on this cross reference index are source coded PAHZZ. Items that do not appear on this cross reference index are
source coded XD and shall be procured
using the FSCM and the NPN at the near-
est wholesale level.
Table 6-1. Reference Designators
A
= assembly = blower (fan)
B
= capacitor
C
= circuit breaker
CB
= diode
CR
DS
= device, signal- L
ing (lamp)
E
= miscellaneous
electronic part
F = fuse
= jack, jumper
J
K
= relay
= inductor
M = meter
Table 6-1.
P
= plug = transistor
Q R
= resistor
s = switch
T
= transformer
TB
= terminal block
TS
= therms 1 switch
Reference Designators (Continued)
v . vacuum tube,
VR x z
Table 6-2. Description Abbreviations
A
ac
= ampere = alternating
mf r mod.
current
= assembly
ass y.
bd
= board
bkt = bracket
°C
= degree
Centigrade
= card
cd coef
= coefficient
comp
= composition
CRT
= cathode-ray
mtg n
NC NO NP
W obd
OD
tube
= center-tapped
CT
dc
= direct current
DPDT = double pole,
double throw
DPST = double pole,
p
P.C. pot. = potentiometer P-P
ppm
single throw elect = electrolytic encap =
F
OF
encapsulated
= farad
= degree
pvr
rect = rectifier rms
Farenheit
= fixed
fxd
= germanium
Ge H
= Henry
Hz
= Hertz
IC
= integrated
circuit
= inside diameter
ID incnd = k m M
µ met.
incandescent = kilo =10 = mini = = mega = 10 = micro = 10 = metal
10-
3
3
6
-6
S1
SPDT = single pole, SPST = single pole,
SS
T
tan.
T1
V
var ww
w = Watt
neon bulb, photocell, etc.
= zener diode
= socket
= integrated cir-
cuit or network
= manufacturer = modular or
modified = mounting = nano =10-
9
= normally closed = normally open = nickel-plated = ohm = order by
description = outside
diameter
= pico =10-
12
= printed circuit = peak-to-peak
= parts per
million
= peak reverse
voltage
= root mean
square
= silicon
double throw
single throw = small signal = slow-blow = tantulum = titanium = volt = variabIe = wirewound
6-1
TM 11-6625-2958-14&P
Table 6-3.
Code List of Manufacturers
CODE
NO.
00629 00656 00853
01121 01255
01281 01295
01686 01930 02107 02114 02606 02660 02735
03508 03797
03877 03888 04009 04072
04213 04404 04713 05277 05347
05820 06001
06004 06486 06540 06555 06666 06751 06776
06812 07137
MANUFACTURER EBY Sales Co. , Inc.
Aerovox Corp.
Sangamo Electric Co.
S. Carolina Div.
Allen Bradley Co.
Litton Industries, Inc. TRW Semiconductors, Inc. Texas Instruments, Inc.
Semiconductor-Components Div.
RCL Electronics, Inc. Manchester, N. H.
Amerock Corp.
Sparta Mfg. Co. Ferroxcube Corp. Fenwal Laboratoriess
Amphenol Corp.
Radio Corp. of America, Solid State
and Receiving Tube Div. Somerville, N. J.
G. E. Semiconductor Products Dept.
Eldema Corp. Transitron Electronic Corp.
Pyrofilm Resistor Co. Inc.
Arrow, Hart and Hegeman Electric Co.
ADC Electronics, Inc. Harbor City, Calif,
Caddell & Bums Mfg. Co. Inc.
*Hewlett-Packard Co. Palo Alto Div, Motorola Semiconductor Prod. Inc.
Westinghouse Electric Corp.
Semiconductor Dept. Ultronix, Inc. Wake field Engr. Inc. Wakefield, Mass. General Elect, Co. Electronic
Capacitor & Battery Dept.
Bassik Div. Stewart-Warner Corp.
IRC Div. of TRW Inc.
Semiconductor Plant
Amatom Electronic Hardware Co. Inc.
Beede Electrical Instrument Co. General Devices Co. Inc. Semcor Div. Components, Inc. Robinson Nugent, Inc.
Torrington Mfg. Co. , West Div. Transistor Electronics Corp.
New Bedford, Mass.
Milwaukee, Wis.
Beverly Hills, Caltf.
Lawndale, Calif.
Saugerties, N. Y.
Morton Grove, Ill.
Compton, Calif.
Wakefield, Mass.
Cedar Knolls, N. J.
Hartford, Corm.
Palo Alto, Calif,
Phoenix, Arizona
Youngwood, Pa.
Grand Junction, Colo.
Bridgeport, Corm.
New Rochelle, N. Y.
Penacook, N. H.
Indianapolis, Ind.
Phoenix, Arizona
New Albany, Ind.
Van Nuys, Calif.
Minneapolis, Minn.
ADDRESS
Jamaica, N. Y.
Pickens, S. C.
Dallas, Texas
Rockford, 111.
Dover, Ohio
Broadview, Ill.
Syracuse, N. Y.
Mineola, N. Y.
Irmo, S. C.
Lynn, Mass.
CODE
NO. 07138 07263
07387 07397
07716 07910 07933
08484
08530 08717 08730 08806
08863 08919 09021
09182 09213 09214 09353
09922 11115
11236 11237
11502 11711 12136 12615
12617 12697 13103 14493
14655
14936 15801
16299
MANUFACTURER Westinghouse Electric Corp.
Electronic Tube Div.
Fairchild Camera and Instrument
Corp. Semiconductor Div.
Mountain View, Calif. Birtcher Corp-,The Sylvania Electric Prod. Inc.
Sylvania Electronic Systems
Western Div.
IRC Div. of TRW Inc. Burlington Plant
Continental Device Corp. Raytheon Co. Components Div.
Semiconductor Operation
Breeze Corporations, Inc. Reliance Mica Corp.
Sloan Company, The
Vemaline Products Co. Inc. Wyckoff, N. J. General Elect. Co. Minia-
ture Lamp Dept. Cleveland, Ohio Nylomatic Corp. RCH Supply Co.
Airco Speer Electronic Components
*Hewlett-Packard Co. New Jersey Div.
General Elect. Co. Semiconductor
Prod. Dept. Buffalo, N. Y.
General Elect. Co. Semiconductor
Prod. Dept. C & K Components Inc. Burndy Corp. Wagner Electric Corp.
Tung-Sol Div. CTS of Berne, Inc. Berne, Ind. Chicago Telephone of Cal. Inc.
IRC Div. of TRW Inc. Boone Plant General Instrument Corp
Rectifier Div.
Philadelphia Handle Co. Inc.
U. S. Terminals, Inc. Cincinnati, Ohio Hamlin Inc. Clarostat Mfg. Co. Inc. Thermally Co. Dallas, Texas *Hewlett-Packard Co. Loveland Div.
Comell-Dubilier Electronics Div.
Federal Pacific Electric Co.
General Instrument Corp. Semicon-
ductor Prod. Group Hicksville, N. Y. Fenwal Elect. Corning Glass Works, Electronic
Components Div.
Los Angeles, Calif.
Mountain View, Calif.
Burlington, Iowa
Hawthorne, Calif.
Mountain View, Calif.
Sun Valley, Calif.
Norrisville, Pa.
Rockaway, N. J.
Norwalk, Corm.
Bloomfield, N. J.
So. Pasadena, Calif.
Lake Mills, Wisconsin
Loveland, Colo.
Framingham, Mass.
ADDRESS
Elmira, N. Y.
Union, N. J.
Brooklyn, N. Y.
Vernon, Calif.
Bradford, Pa.
Auburn, N. Y.
Newton, Mass.
Boone, N.C.
Newark, N. J.
Camden, N. J.
Dover, N. H.
Newark, N. J.
Raleigh, N. C.
*Use Code 28480 assigned to Hewlett-Packard Co. , Palo Alto, California
6-2
Table 6-3. Code List of Manufacturers (Continued)
TM 11-6625-2958-14&P
CODE
NO. 16758 17545 17803
17870 18324
19315 19701 21520 22229 22753
23936 24446 24455
24655 24681
26982 27014
28480 28520 28875
31514
31827 33173 35434 37942
42190
43334
.
44655
46384 47904
49956 55026
56289 58474 58849
59730 61637 63743
MANUFACTURER Delco Radio Div. of General Motors Corp.
Atlantic Semiconductors, Inc.
Asbury Park, N. J.
Fairchild Camera and Instrument Corp
Semiconductor Div. Transducer Plant
Mountain View, Callf.
Daven Div. Thomas A. Edison Industries
McGraw-Edison Co. Slgnetics Corp. Bendix Corp. The Navigation and
Control Div.
Electra/Midland Corp. Fansteel Metallurgical Corp. Union Carbide Corp. Electronics Div. UID Electronics Corp.
Pamotor, Inc. General Electric Co. General Electric Co. Lamp Div. of Con-
sumer Prod. Group
Nela Park, Cleveland, Ohio General Radio Co. LTV Electrosystems Inc Memcor/Com-
ponents Operations Dynacool Mfg. Co. Inc. Saugerties, N.Y. National Semiconductor Corp.
Hewlett-Packard Co. Heyman Mfg. Co.
IMC Magnetics Corp.
New Hampshire Div. SAE Advance Packaging, Inc.
Budwig Mfg. Co.
G. E. Co. Tube Dept.
Lectrohm, Inc. P. R. Mallory & Co. Inc.
Muter Co. New Departure-Hyatt Bearings Div.
General Motors Corp.
Ohmite Manufacturing Co.
Penn Engr. and Mfg. COrp.
Polaroid Corp. Raytheon Co. Simpson Electric Co. Div. of American
Gage and Machine Co.
Sprague Electric Co. North Adams, Mass. Superior Electrlc Co. Syntron Div. of FMC Corp.
Thomas and Betts Co.
Union Carbide Corp. Ward Leonard Electric Co.
Sunnyvale, Callf.
Mineral Wells, Texas
No. Chicago, Ill.
Mountain View, Calif.
Hollywood, Fla.
Schenectady, N.Y.
West Concord, Mass.
Huntington, Ind.
Santa Clara, Callf.
Palo Alto, Calif. Kenilworth, N. J.
Rochester, N. H.
Santa Ana, Callf.
Owensboro, Ky.
Indianapolis, Ind.
Sanclusky, Ohio
Doylestown, Pa.
Cambridge, Mass.
Lexington, Mass.
Homer City, Pa.
Philadelphia, Pa.
New York, N. Y.
Mt. Vernon, N. Y.
ADDRESS
Kokomo, I.nd.
Orange, N. J.
Teterboro, N. J.
Pampa, Texas
Ramona, Calif.
Chicago, Ill.
Chicago, 111.
Skokie, 111.
Chicago, 111.
Bristol, Corm.
CODE
NO.
70563 70901 70903
71218
71279 71400
71450
71468 71590 71700 71707
71744 71785 71984
72136
72619
72699
72765
72962
72982
73096
73138
73168
73293 73445
73506
73559 73734
74193 74545 74868
74970 75042 75183
75376 75382 75915 76381
76385 76487
76493
MANUFACTURE R
Amperite Co. Inc.
Beemer Engrg. Co. Belden Corp. Bud Radio, Inc.
Cambridge Thermionic Corp.
Bussmann Mfg. Div. of McGraw &
Edison Co.
CTS Corp.
I. T. T. Cannon Electric Inc.
Globe-Union Inc.
Centralab Div. Milwaukee, Wis.
General Cable Corp. Cornish
Wire Co. Div. Coto Coil Co. Inc. Chicago Miniature Lamp Works
Cinch Mfg. Co. and Howard
B. Jones Div. Dow Coming Corp. Electro Motive Mfg. Co. Inc.
Dialight Corp. General Instrument Corp. Drake Mfg. Co. Elastic Stop Nut Div. of
Amerace Esna Corp. Erie Technological Products Inc. Erie, Pa. Hart Mfg. Co. Beckman Instruments Inc.
Helipot Div. Fenwal, Inc. Hughes Aircraft Co. Elecmon
Dynamics Div. Torrance, Calif.
Amperex Electronic Corp.
Bradley Semiconductor Corp.
Carling Electric, Inc.
Federal Screw Products, Inc.
Heinemann Electric Co.
Hubbell Harvey Inc.
Amphenol Corp. Amphenol RF Div.
E. F. Johnson Co. IRC Div. of TRW, Inc. l Howard B. Jones Div. of Cinch
Mfg. Corp.
Kurz and Kasch, Inc. Kilka Electric Corp. Llttlefuse, Inc. Minnesota Mining and Mfg. Co.
Minor Rubber Co. Inc. James Millen Mfg. Co. Inc.
J. W. Miller Co.
Union City, N. J.
Fort Washington, Pa.
Willoughby, Ohio
Cambridge, Mass.
Los Angeles, Callf.
Williams town, Mass.
Providence, R. 1.
Midland, Mich.
Willimantic, Corm.
Harwood Heights, Ill.
Hartford, Corm.
Fullerton, Calif.
Ashland, Mass.
Hicksville, N, Y.
New Haven, Corm.
Hartford, Corm.
Bridgeport, Corm.
Danbury, Corm.
Waseca, Minn.
Philadelphla, Pa.
New York, N. Y.
Mt. Vernon, N. Y.
Des Plaines, Ill.
St. Paul, Minn.
Bloomfield, N.J.
Maiden, Mass.
Compton, Callf.
ADDRESS
Chicago, III.
St. Louis, Mo.
EIkhart, Ind.
Chicago, Ill.
Chicago, III.
Brooklyn, N. Y.
Newark, N. J.
Union, N. J.
Chicago, Ill.
Trenton, N. J.
Dayton, Ohio
l Use Code 71785 assigned to Cinch Mfg. Co. , Chicago, III.
6-3
TM 11-6625-2958-14&P
Table 6-3.
Code List of Manufacturers (Continued)
CODE
NO.
76530
768.54 77068
77122 77147 77221
77252 77342 77630 77764
78189
78452
78488
78526
78553
78584
79136
79307
79727
79963
80031
80294
81042 81073
81483 81751
82099
82142
82219
82389
82647
82866 82877
82893
83058
83186
83298
83330
83385
83501
MANUFACTURER Cinch City of Industry, Calif.
Oak Mfg. Co. Div. of Oak
Electro/Netics Corp.
Bendix Corp. , Electrodynamics Div. Palnut Co.
Patton -Mac Guyer Co.
Phaostron Instrument and Electronic Co.
Philadelphia Steel and Wire Corp.
American Machine and Foundry Co.
Potter and Brumfield Div. Princeton, Ind.
TRW Electronic Components Div. Resistance Products Co.
Illinois Tool Works Inc. Shakeproof Div. Everlock Chicago, Inc.
Stackpole Carbon Co. Stanwyck Winding Div. San Fernando
Electric Mfg. Co. Inc. Newburgh, N.Y. Tinnerman Products, Inc. Cleveland, Ohio Stewart Stamping Corp. Waldes Kohinoor, Inc. Whitehead Metals Inc. New York, N. Y. Continental-Wirt Electronics Corp.
Zierick Mfg. Co. Mt. Kisco, N.Y. Mepco Div. of Sessions Clock Co.
Bourns, Inc. Howard Industries Div. of Msl Ind. Inc.
Grayhiil, Inc. La Grange, III. International Rectifier Corp.
Columbus Electronics Corp. Yonkers, N. Y.”
Goodyear Sundries & Mechanical Co. Inc.
Airco Speer EIectronic Components
Sylvania Electric Products Inc.
Electronic Tube Div. Receiving
Tube Operations Switchcraft, Inc. Metals and Controls Inc. Control
Products Group Research Products Corp. Rotron Inc. Vector Electronic Co. Cam Fastener Co. Victory Engineering Corp.
Bendix Corp. Electric Power Div. Herman H. Smith, Inc.
Central Screw Co. Gavitt Wire and Cable Div. of
Amerace Esna Corp.
Crystal Lake, III.
No. Hollywood, Calif.
Mountainside, N. J.
Providence, R. I.
South Pasadena, Calif.
Philadelphia, Pa.
Philadelphia, Pa.
Morristown, N. J.
Riverside, Calif.
El Segundo, Calif.
Attleboro, Mass.
Woodstock, N. Y.
Glendale, Calif.
Cambridge, Mass.
Springfield, N. J.
Eatontown, N, J.
BrookfieId, Mass.
ADDRESS
Camden, N. J.
Harrisburg, Pa.
Elgin, Ill.
Chicago, 111.
St. Marys, Pa.
Yonkers, N. Y.
L.I.C., N.Y.
Racine, Wise.
New York, N. Y.
Du Bois, Pa.
Emporium, Pa.
Chicago, Ill.
Madison, Wis.
Brooklyn, N. Y.
Chicago, Ill.
CODE
NO. 83508 83594 83835
83877 84171
84411 86684
86838 87034
87216 87585
87929 88140
88245 90634
90763 91345
91418 91506 91637 91662 91929
92825 93332
93410 94144
94154 94222
95263 95354 95712
35987 96791
97464 97702 98291
98410 38978
39934
MANUFACTURER
Grant Pulley and Hardware Co.
West Nyack, N. Y.
Burroughs Corp. Electronic
Components Div. U. S. Radium Corp. Yardeny Laboratoriess, Inc.
Arco Electronics, Inc.
TRW Capacitor Div. Ogallala, Neb.
RCA Corp. Electronic Components
Rummel Fibre Co. Marco & Oak Industries a Div. of Oak
Electro/netics Corp.
Philco Corp. Lansdale Div. Lansdale, Pa. Stockwell Rubber Co. Inc.
Tower-Olschan Corp. Cutler-Hammer Inc. Power Distribution
and Control Div. Lincoln Plant
Litton Precision Products Inc, USECO
Div. Litton Industries Van Nuys, Calif. Gulton Industries Inc. United-Car Inc. Chicago, III. Miller Dial and Nameplate Co.
Radio Materials Co.
Augat, Inc.
Dale Electronics, Inc. Columbus, Neb. Elco Corp. Honeywell Inc. Div. Micro Switch
Whitso, Inc. Schiller Pk. , III.
Sylvania Electric Prod. Inc. Semi-
conductor Prod. Div.
Essex Wire Corp. Stemco
Controls Div.
Raytheon Co. Components Div.
Ind. Components Oper.
Wagner Electric Corp.
Tung-Sol Div. Livingston, N. J. Southco Inc.
Leecraft Mfg. Co. Inc.
Method Mfg. Co. Rolling Meadows, III, Bendix Corp. Microwave
Devices Div. Franklin, Ind.
Weckesser Co. Inc. Chicago, Ill.
Amphenol Corp. Amphenol
Controls Div.
Industrial Retaining Ring Co. IMC Magnetics Corp. Eastern Div. Sealectro Corp.
ETC Inc.
‘International Electronic Research Corp.
Renbrandt, Inc.
Morristown, N.J.
Great Neck, N.Y
Anaheim; Calif.
Philadelphia, Pa.
Bridgeport, Corm.
El Monte, Calif.
Attleboro, Mass.
Willow Grove, Pa.
Mansfield, Ohio
Janesville, Wis.
Westbury, N. Y.
Mamaroneck, N. Y.
Cleveland, Ohio
ADDRESS
Plainfield, N.J.
New York, N.Y.
Harrison, N. J.
Newark, N, J.
Lincoln, III.
Metuchen, N,J.
Chicago, Ill.
Freeport, Ill.
Woburn, Mass.
Quincy, Mass.
Lester, Pa.
L.I.C., N.Y.
Irvington, N.J.
Burbank, Calif.
Boston, Mass.
6-4
Table 6-4.
Replaceable Parts
TM 11-6625-2958-14&P
REF.
DESIG.
Al MAIN PRINTED CIRCUIT BOARD
A1
C1 C2 C20 C35 C40, 41 C44 C60 C61 C70 C71 C72, 73 C90
CR1-7,20,
21,35-37 Diode, Si. 200mA 200prv CR40 CR41,43,44 Diode, Si 200mA 200prv CR42,51,52 CR45-50,
53,54 Diode, Si. CR60-62,
70-84,88,
90-93 Diode, Si. 200mA 200prv
Q1
Q20, 40
Q41, 42
Q60
Q61-Q63
Q70, 71
Q72, 73 Q90 Q91, 92
R1
R2
R3
R4
R5
R6
R20
R21
R22
R23
R24
R25
R26
R27
R28, 29
R30
R31
R35, 36
R37
R40
Printed Circuit Board, Main
fxd, mylar. 01µF 200V fxd, elect. 5µF 50Vdc
fxd, elect. 68µF 15Vdc fxd, elect. 20µF 50Vdc fxd, mylar .022µF 200Vdc fxd, elect. 1,400µF 30Vdc fxd, elect. 4.7µF 35Vdc fxd, elect. 325µF 35Vdc fxd, elect. 1µF 35Vdc fxd, mylar .1µF 200Vdc fxd, elect. 5µF 50Vdc fxd, mylar .1µF 200Vdc
Stabistor 1
NOT ASSIGNED
SS PNP Si.
SS NPN Si.
SS PNP Si.
SS PNP Si
SS NPN Si.
SS PNP Si.
SS NPN Si.
SS PNP Si. SS NPN Si.
fkd, met. film 1M Ω ±1% ¼ 1
fxd, comp 160 ±5% ½
fxd, comp (selected) +5% ½
fxd, ww 680 ±5%5W
fxd, ww 600Ω ±5%5W
fxd, ww 1K
fxd, met. film 330 ±1% 1/8W
fxd, met. film 200k ±1% 1/8W
fxd, met. film 196 ±1% 1/8W
fxd, met. film 1.21k ±1% 1/8W
fxd. met. film 7.5K ±1% 1/8W
fxd, met. film 5.49K
fxd, met. film 21.5K ±1% 1/8W 1
fkd, comp 3.9M ±5%½W
fxd, comp 3.3
fxd, comp (Selected) ±5%½W
fxd, ww 2.6K
fxd, compp 10k ±5%½W 2
fxd, comp 180k ±5%½W 1
fxd, comp 1.5K
DESCRIPTION
± 5% 3W
±1% 1/8W
±5%½W
±5% 3W
±5%½W
TQ
38
MFR. PART NO.
1 1
30D505G050BB2
3 2
150D686X0015R2 56285
30 D206G050C02
1
2
192P22392 56289 1 1
150D475X9035B2 56289 1 1
150D105X9035A2 56289
192P10492
2
30D505G050BB2 56289
192P10492 56289
- ­8
1N5059
6 9
1
Type CEB T-O 2
EB-1615 2
Type EB (obd)
243E6815 56289
1
243E6015 56289
1 1
242E1025 56289
1
Type CEA T-0 1
Type CEA T-0 1
Type CEA T-0 2
Type CEA T-0 3
Type CEA T-0
2
Type CEA T-0
Type CEA T-0 1
EB-3955 2
EB-0335
Type EB (obd) 1
242E2625 EB-1035 EB-1845
1
EB-1525
MFR.
CODE
28480 28480
56289 56289 28480 28480
56289
28480 28480 28480
03508
28480
28480 28480 28480 28480 28480 28480 28480 28480 1853-009-9
09182
07716 01121 01121
07716 07716 07716 07716
07716 077,16 07716
01121
01121
01121
56289
01121
01121
01121
HP
PART NO.
5060-6189 0160-0161
0180-0301 0180-1835 0180-0049 0160-0162 1 0180-1860 1 0180-0100 1 0180-0332 0180-0291 0160-0168
.0180-0301
0160-0168
1901-0033 1901-0460 1901-0033
1901-0327
1901-0033 1853-0099
1854-0071 1853-0099 1853-0041 1854-0071 1853-0099 1854-0071
1854-0071
0757-0344 0686-1615
­0811-2099 0811-1869 1 0813-0001 0698-5663 0757-0472 0698-3440 1 0757-0274 1 0757-0440 0698-3382 1 0698-3430 1 0686-3955 0686-0335
­0811-1808 0686-1035
0686-1845
0686-1525
RS
1 1 1 1
1 1 1
12
1
6
6 6
1
1 1 1 1
1 1 1
1
1 1
1 1 1 1
62690
6-5
TM11-6625-2958-14&P
REF.
DESIG.
R41 R42 R43 R44 R45 R46 R47 R48 R49 R50 R51 R52 R53 R54 R56 R57 R58 R60 R61 R62 R63 R64 R65 R66 R67 R68 R69 R69B
fxd, comp 510 Ω ±5% ½W fxd, met. film 560 ±1% ¼W fxd, ww 50 ±5% 5W fxd, met. oxide 22 ±5% 2W 1 fxd, comp 820 Ω ±5% ½W
fxd, comp 1K Ω ±5% ½W var. ww 5k ±10%, Equalizer Adj.
fxd, comp 5.1k ±5% ½W fxd, comp 47 Ω ±5% ½W fxd, comp 39
fxd, comp 1k Ω ±5% ½W
fxd, met. film 61.9k ±1% 1/8W fxd, comp 560 Ω ±5% ½W
fxd, ww 50 ±5% 5W fxd, comp 75
fxd, ww 3.9 2W
fxd, ww 400 ±5% 10W 1 fxd, met. film 600 ±1% 1/8W 1 Type CEA T-O fxd, met. film 7.5K ±1% 1/8W fxd, met. oxide 180 ±5% 2W 1 fxd, met. film 499 ±1% ¼W 1 Type CEB T-O fxd, met. film 2k ±1% ¼W 1 Type CEB T-O fxd, comp I00kW ±5% ½W 2 fxd, comp 200k ±5% ½W 3 fxd, comp 33k Ω ±5% ½W fxd, met. film 5.49k ±1% 1/8W Type CEA T-O fxd, met. film 7.5k ±1% 1/8W Type CEA T-O fxd, met. film 3.4k ±1% 1/8W
R70 var, ww 5k R71 R72 R73 R74 R75, 76 R77 R78 R79 R80 R81 R82 R83 R84 R85 R86 R87 R88
R90 fxd, met. oxide 820 ±5% 2W
R91
R92 R93 R94 R95 R96
R97 R98 R99
R101
R102
fxd, met. film 12k ±1% 1/8W 1
fxd, met. film 45k ±1% 1/8W 1 fxd, comp 12k Ω ±5% ½W
fxd, comp 82k Ω ±5% ½W fxd, met. film 4,75k ±1% 1/8W fxd, comp 430k Ω ±5% ½W fxd, met. film 249k ±1% 1/8W fxd, comp 3.9k ±5% ½W fxd, met. film 4.32k ±1% 1/8W fxd, comp 4.7 ±5% ½W fxd, comp 9.1k ±5% ½W
fxd, comp 27 Ω ±5% ½W
fxd, comp 100k Ω ±5% ½W fxd, comp 9.1k ±5% ½W fxd, met. oxide 270 ±5% 2W fxd, met. oxide 1.5k ±5% 2W fxd, comp 10 Ω ±5% ½W
fxd, comp 180 ±5% 1W fxd, ww 220 2W fxd, comp 3.9k ±5% ½W fxd, comp 510 fxd, met. film 1.5k ±1% 1/8W fxd, comp 200k Ω ±5% ½W fxd, comp 4.7 ±5% ½W fxd, comp 10 Ω ±5% ½W fxd, comp 200k ±5% ½W var. ww 250 ±10%, Ammeter Adj. fxd, met. film 909 ±1% 1/8W
DESCRIPTION
±5% ½W
±5% ½W
±10%, Ramp Adjust.
±5% ½W
TQ
MFR. PART NO.
EB-5115
2
1
Type CEB T-O
243E5005
2
Type C42S
1
EB-8215
2
EB-1025
2 Type 110-F4
EB-5125
1 1
EB-4705
1
EB-3905
EB-1025 1 Type CEA T-O 1
EB-5615
243 E5005
1
EB-7505
Type BWH
1
Type 10XM
Type CEA T-O
Type C42S
EB-1045
EB-2045 1
EB-3335
1
Type CEA T-O
Type 110-F4
Type CEA T-O
Type CEA T-O 1
EB-1235 1
EB-8235 2 Type CEA T-O 1
EB-4345 1 Type CEA T-O
EB-3925
2 1 Type CEA T-O 2
EB-47G5 2
EB-9125 1
EB-2705 EB-1045 EB-9125 Type C42S
1 1
Type C42S
2
EB-1OO5
1
Type C42S
1
GB-1815 Type BWH
1
EB-3925 EB-5115 Type CEA T-O
2
EB-2045 EB-47G5 EB-1005 EB-2045
2 Type 110-F4 1 Type CEA T-O
MFR.
CODE
01121 07716 56289 16299
01121 01121 11236 01121 01121 01121 01121 07716 01121 56289 01121 07716 63743 07716 07716 16299 07716 07716 01121 01121 01121 07716 07716 07716 11236 07716 07716 01121 01121 07716 01121 07716 01121 07716 01121 01121
01121 01121 01121 16299
16299 01121 16299 01121 07716 01121 01121 07716 01121 01121 01121 01121 11236 07716
HP
PART NO.
RS
0686-5115 1 0698-5146 1 0811-1854 1 0698-3609 1 0686-8215 1 0686-1025 1 2100-1824 1 0686-5125 0686-4705 1 0686-3905
0686-1025
0757-0460 1
0686-5615 1
0811-1854
0686-7505 1 0811-1673 1 0811-0942 1 0757-1100 0757-0440 0698-3626 1 0698-3207 1 0757-0739 1
0686-1045 1 0686-2045 0686-3335 1 0698-3382
0757-0440
0698-4440 1 2100-1824 0698-5088 1
0698-5091 1
0686-1235 0686-8235 1 0757-0437 1
0686-4345 1
0757-0270 1
0686-3925 1
0757-0436 1
0698-0001
0686-9125 1
0686-2705
0686-1045
0686-9125
0698-3629 1
0698-3338 1 0686-1005 1 0698-3637 1
0689-1815 1
0811-1763 1
0686-3925
0686-5115
0757-0427 1
0686-2045
0698-0001 0686-1005
0686-2045 2100-0439 1
0757-0422 1
1 1
1
1
1
1 1
6269B
6-6
TM 11-6625-2958-14&P
REF.
DESIG.
R103 R104 R105 R106 R108, 109
T70, 90
VR1, 40
VR60, 61
VR90
Z1 22
A2
C1
CR1
L1A/L1B
R1
A3
C3 J1 R120 T2
DESCRIPTION
fxd, met. film 1.5k ±1% 1/8W
fxd, met. film 19.1k ±1% 1/8W fxd, met. film 422 ±1% ¼W var. ww 250 ±10%, Voltmeter Adj.
fxd, comp 100 Ω ±5% ½W
Pulse Transformer
Diode, zener 4.22V ±5% 2
Diode, zener 6.2V ±5%
Diode, zener 6.19V ±5%
Dual Differential Amplifier Resistor Network 1
A2 RFI FILTER ASSEMBLY
RFI Filter Assembly 1 fxd, paper .22µF 600Vdc Triac, 40A 400prv Filter Choke 1.5mH fxd, met. oxide 270 ±5% 2W
A3 INTERCONNECTION BOARD
Interconnection Board Assembly fxd, elect. 5000µF 45Vdc P.C. Board Edge Connector fxd, comp 51k Bias Transformer
±5% ½W
TQ
MFR. PART NO.
Type CEA 7-0 1 Type CEA T-O 1 Type CEB T-O
Type 110-F4
2
EB-1015
2
2
1 1
CA3026
1
Type 160P 56289
2N5445
1 1 1
Type C42S
1
1 1 64-718-22 1
EB-5135
1
MFR.
CODE 07716
07716 07716 11236 01121
28480 28480 1902-.3070
28480 28480
02735
28480
28480
02735 28480 16299
28480 28480 76530 01121 28480
HP
PART NO.
0757-0427 0698-4484 1 0698-4590 1 2100-0439 0686-1015
5080-7122 1
1902-1221 1902-0049
1820-0240 1 1810-0042 1
06269-60007
0160-2461 1884-0080 5080-7146 1 0698-3629 1
5060-7906 0180-1919
1251-1887
0686-5135
9100-26O7
RS
1
2 2 1
1
1
1
1 1
A4
B1
C1-C4 C5
CR101, 102 CR103, 104 CR1O5 CR106 CR108 CR110
Q101 Q102 Q103-Q108
R106 R123
R150-R155
A4 HEAT SINK ASSEMBLY
Heat Sink Assembly Fan
fxd, ceramic .05µF 400V
fxd, elect. 15µF 50V Rect. Si. 40A 50prv
Rect. Si. 40A 50prv Rect. Si. 40A 50prv Rect. Si. 40A 50prv Rect. Si. 40A 50prv
SCR 35A 4ooprv
Power PNP Si. Power NPN Si. Power NPN Si.
fxd, ww .125 ±5% 5W fxd, cupron 0.01 20ppm, Cur-
rent Sampling
Emitter Resistor Assembly
fxd, wire helix O.1
Emitter Resistor Assembly
±5% - Part of
1
1
WS2107F
4 1
4
1N1183AR 02577 1N1183A 02577
3
1N1183AR 02577 1N1183A 1N1183AR 28480
1 1
1
6
1
1 1
6
28480 97702 28480
28480
02577 28480
28480 28480 28480
28480 28480
28480
28480
06269-60004
3160-0056 0150-0052 1
0180-1834 1 1901-0316
1901-0315 1901-0316 1901-0315 1901-0316 1884-0058
1853-0063 1854-022S 1854-0458
0811-1846 1
5080-7144 1
06260-60023 1
0811-2545
1
4
3
1 1
1 6
2
6269B
6-7
TM 11-6625-2958-14&P
REF.
DESIG.
TS101
A5
CB1 DS1
DS2
Ml M2
R121 R122 R123 R124
R125
DESCRIPTION
Thermal Switch, open 230°F, close
200°F
A5 FRONT PANEL ASSEMBLY
Front Panel Assembly Circuit Breaker, 25A @ 250Vac max. 1 Indicator Light, Neon, Red
Overvoltage Indicator, 6V, Amber
Voltmeter, 0-50V Ammeter, 0-60A 1
var. ww 10k ±5%, Voltage
Control, Coarse
var. ww 50 ±5%, Voltage
Control, Fine 2
var. ww 200 ±5%, Current
Control, Coarse
var.
ww 10
Control, Fine 1
var. ww 10k ±5%, Overvoltage
Adjustment
±5%, Current
TQ
MFR. PART NO.
1
1
AM33 Curve 5
1
599-124
1 MCL-A3-1730 1
2
1
MFR. HP
CODE
28480
28480 74193 72765
07137 28480
28480 1120-1181
28480 28480 28480 28480 28480
PART NO.
0440-0079 1
06269-60005
2110-0213 1 1450-0048 1
1450-0305 1 1120-1173 1
2100-1854 1 2100-1858 1 2100-1856 1 2100-1857 1 2100-1854
RS
1
CHASSIS - ELECTRICAL
B2
C19 C101-C104 fxd, elect. 50,000µF 50Vdc 4 C110, 111
T1
Fan
fxd, elect. 15µF 50Vdc fxd, ceramic .01µF 300Vdc
Power Transformer
CHASSIS ASSEMBLY- MECHANICAL Chassis Assembly (Welded) 1
Bracket, RFI Filter Mounting 2 Standoff, Insulated, RFI Filter
Mounting 4
Grommet, 5/8” (Internal
Chassis Divider) 1 Cover 2 Chassis, Internal, Ckt. Board Tray 1 Chassis, Internal, Capacitor Tray 1
Bus Bar, C101-C102 Bus Bar, C103-C104 Clamp, C101-C104 3 Bracket, Fan B2
Rear Panel (Blank, with labeling) 1
Cover, AC Input Barrier Block 1 Cover, Rear Control Barrier Strip Bus Bar, Output Barrier Block, AC Input Rubber Bumper Spacer, Insulated, AC Input
Barrier (2), Output Bus Bars (4)
Serial I.D. Plate 1
1
8500
1
150D156X0050R2
41C21A5
2
1
1661
2 2
2
1 2 1 603-3 4 2097-W
6
23936 56289
28480 56289
28480
28480 28480
28480 73734
28480 28480 28480
28480 28480 28480 28480
28480 28480 28480 28480 75382 87585
28480 28480
3160-0056 1 0180-1834 1
0180-2346 1 0160-2568 1
06269-80091 1
5060-6186 5000-6257
0380-0902 0400-0062
5000-6250 5000-6248
06269-00002
5000-6251 5000-6253 5000-6017
06269-00003 06260-60008
5000-6249
00712-20001
5000-6252
0360-1596 1
0403-0089 0380-0710 6
7120-1111
6269B
6-8
TM 11-6625-2958-14&P
REF.
DESIG.
DESCRIPTION
Shoulder Washer, Bus Bar Binding Post, 5 Way, N. P. Brass
(Ground)
Al - MECHANICAL
Barrier Strip, Rear Control
Jumper, Barrier Strip
A2 - MECHANICAL
Heat Sink, RFI Filter Ass’y. (CRl) 1 Cover, RFI Assembly
Terminal, Insulated, Cl 1
Wafer, Insulated, CR1 1
Shoulder Washer, CR1 Hole Plug, Heat Sink, 7/8” dia.
A3-MECHANICAL
Clamp, Capacitor, C3 1
A4 -MECHANICAL
Heat Sink, Q103-104-107-108,
Q105-106 Heat Sink, CR101-103, CR102-104 Heat Sink, CR106,108,Q102 Heat Sink, CR105, CR110,Q101 Bracket, Mounting, Fan-Heat Sink Bracket, Mtg. Heat Sink-Chassis Insulator Strip, Heat Sink Divider
Washers, Nylon, Heat Sink Spacing
Rod, Insulated Spacing, 8-3/4 Lg.,
Threaded 6-32 4 Rubber Bumper, Heat Sink Protection 1 Insulator, Mica, Q101-102 Shoulder Washer, Q101-102 Insulator, Transistor Pins, Q101-110
Insulator, Mica, CR109 Shoulder Washer, CR109 Shoulder Washer, Heat Sink Bracket
Mounting
TQ
12
16
MFR. PART NO.
4
137
1
1 4
422-13-11-013
1
1 1
2 2 1 1 1 1 2
8203-PH0632 734
2 4
1 1
4
MFR.
CODE 28480
83330
28480 71785
28480 28480 28480 28480 28480 28480
28480
28480 28480 28480 28480 28480 28480 28480 28480
‘ 06540
28480 08530 28480 28480 28480 28480
28480
HP
PART NO. 2190-0491 1510-0044
0360-1518 0360-1143
5020-5785 5020-5768 0360-1449 0340-0175 2190-0898 6960-0047
1400-0472
5020-5763 5020-5769 5020-5766 5020-5765 5000-6256 5000-6255 5020-5787 3050-0455
0380-0879 0403-0002 0340-0174 2190-0490 0340-0166 2190-0709 2190-0898
3050-0483
RS
4
1 2
1
1
1
1
1
1
3 1
1
2 4 8
1 1
4
AS -MECHANICAL
Front Panel (Blank)
Knob, Front Panel, Black Fastener, DS1, DS2 Bushing, Potentiometer R125 Nut, Hexagon, R125 Locknut, R121-R124 Bezel, Gray Plastic, 2¼" Mod. Spring, M1, M2 Handle, 7“ Machine Screw, Fillister Phillips
Head, 10-32x 1-3/4
6269B
6-9
1 4 2
C17373-012-248 1 1 4 2 8 2
4
28480 28480 89032 28480 28480 28480 28480 28480 28480
28480
5000-6254 0370-0137 0510-0123 1410-0052 2950-0034 0590-0013 4040-0296 1460-0256 5020-5762
2680-0173
1 1
1
2
TM 11-6625-2958-14&P
REF.
DESIG.
R82
I
Manual Carton, Packing Floater Pad, Packing
fxd, comp 240 Ω ±5% ½W Label, Identification
10-Turn Voltage Coarse Control
DESCRIPTION
MISCELLANEOUS
OPTION 005
50Hz Operation
OPTION 007
TQ
1
1
2
1 1
MFR. PART NO.
EB-2415
MRF. CODE
28480 06269-90002 28480
28480
01121
HP
PART NO.
9211-1181 9220-1402
0686-2415 7124-1719
RS
1
A5R121
A5R123
A5R121 A5R123
R3
A5R121
R30
A5R123
var. ww 10k ±5% 10-Turn
10-Turn Current Coarse Control
var. ww 200 ±5% 10-Turn
10-Turn Voltage & Current Controls
var. ww 10k ±5% 10-Turn var. ww 200
Slides, Chassis
Decadial Voltage Control
fxd, comp (Selected) ±5% ½W var. ww 10k
Decadial Control
Decadial Current Control
fxd, comp (Selected) ±5% ½W var. ww 200
Decadial Control
OPTION 008
OPTION 009
±5% 10-Turn
OPTION 010
Chassis Slides
OPTION 013
±5% 10-Turn
OPTION 014
±5% 10-Turn
1 I
1
1 1
1 CTS 120 E6
1
Type EB (obd) 1 1 RD-411
1
Type EB (obd)
1
1
RD-411
28480
28480
28480
28480
01121 28480 07716
01121 28480 07716
2100-1866
2100-1863
2100-1866 2100-1863
2100-1866 1140-0020
2100-1863 1140-0020
1
1
1
1
1
1 1
1 1
R111 R112,113 R114
R115 R116 R118 R119
Voltage Programming Adjust
fxd, met. film 221k var. ww 5k fxd, met. film 249k ±1% 1/8W
Label, Identification
Current Programming Adjust
fxd, met. film 23K
var. ww 5k fxd, met. film 200k ±1% 1/8W var. ww 5k Label, Identification
OPTION 020
±1% 1/8W
OPTION 021
±1% 1\8W
Ω Ω
6269B
6-10
1
Type CEA T-O 2 1
Type CEA T-O 1
1
Type CEA T-O 2
1
Type CEA T-O
1
07716 28480 07716
07716 28480 07716
28480
0757-0473 2100-0806 0757-0270 7124-1721
0698-3269 2100-0806 0757-0472 2100-0806 7124-1721
1 1 1
1 1 1
TM 11-6625-2958-14&P
REF DESCRIPTION TQ MFR HP RS
DESIGN MFR PART NO CODE PART NO
OPTION 022
VOLTAGE & CURRENT PROGRAMMING ADJUST
R111 FXD, MET. FILM 221KW ±1% 1/8W 1 TYPE CEA T-O 07716 0757-0473 1
R112,113 VAR. WW 5K
4 28480 2100-0806 1
R114 FXD, MET. FILM 249KW ±1% 1/8W 1 TYPE CEA T-O 07716 0757-0270 1
R115 FXD, MET. FILM 23KW ±1% 1/8W 1 TYPE CEA T-O 07716 0698-3269 1
R116 VAR. WW 5K
28480 2100-0806
R118 FXD, MET. FILM 200KW ±1% 1/8W 1 TYPE CEA T-O 07716 0757-0472 1
R119 VAR. WW 5KW 28480 2100-0806
LABEL, IDENTIFICATION 1 28480 7124-1721
OPTION 027
208VAC INPUT
LABEL, IDENTIFICATION 1 28480 7124-1717
6269B
6-11
TM11-6625-2958-14&P TABLE 6-5. PART NUMBER - NATIONAL STOCK NUMBER
CROSS REFERENCE INDEX
NATIONAL NATIONAL
PART STOCK PART STOCK
NUMBER FSCM NUMBER NUMBER FSCM NUMBER
0150-0052 28480 5910-00-797-4909 0757-0437 28480 5905-00-904-4404
0160-0161 28480 5910-00-911-9271 0757-0440 28480 5905-00-858-6795
0160-0162 28480 5910-00-850-2162 0757-0460 28480 5905-00-858-8959
0160-0168 28480 5910-00-917-0668 0757-0472 28480 5905-00-257-9210
0180-0049 28480 5910-00-781-9398 0757-0473 28480 5905-00-994-8480
0180-0100 28480 5910-00-752-4172 0757-0739 28480 5905-00-830-6078
0180-0291 28480 5910-00-931-7055 0757-1100 28480 5905-00-917-0586
0180-0332 28480 5910-00-943-6709 0813-0001 28480 5905-00-932-0413
0180-1860 28480 5910-00-931-7061 1N5059 03508 5961-00-088-8792
0686-1035 28480 5905-00-451-0540 1140-0020 28480 5355-00-584-0840
0686-1045 28480 5905-00-195-6761 1251-1887 28480 5935-00-147-7384
0686-1525 28480 5905-00-279-1757 137 83330 5940-00-321-4984
0686-3335 28480 5905-00-997-5436 1410-0052 28480 5895-00-061-2906
0686-4345 28480 5905-00-279-2518 1450-0048 28480 6210-00-761-8898
0686-5125 28480 5905-00-279-2019 150D105X9035A2 56289 5910-00-104-0144
0689-1815 28480 5905-00-403-9066 150D475X9035B2 56289 5910-00-177-4300
0698-0001 28480 5905-00-682-4247 1661 73734 5325-00-301-8656
0698-3338 28480 5905-00-431-6842 1810-0042 28480 5905-00-450-0107
0698-3430 28480 5905-00-420-7136 1853-0041 28480 5961-00-931-8259
0698-3440 28480 5905-00-828-0377 1853-0063 28480 5961-00-867-9319
0698-3629 28480 5905-00-405-3727 1853-0099 28480 5961-00-450-4689
0698-4440 28480 5905-00-431-6840 1854-0071 28480 5961-00-137-4608
0698-4484 28480 5905-00-140-5675 1854-0225 28480 5961-00-072-0094
0698-5088 28480 5905-00-469-2838 1901-0033 28480 5961-00-821-0710
0698-5146 28480 5905-00-431-6837 1901-0327 28480 5961-00-931-0213
0757-0270 28480 5905-00-491-4596 1901-0460 28480 5961-00-867-9206
0757-0274 28480 5905-00-858-9105 1902-0049 28480 5961-00-911-9277
0757-0344 28480 5905-00-269-2629 1902-3070 28480 5961-00-931-6989
0757-0422 28480 5905-00-728-9980 192P10492 56289 5910-00-728-8472
0757-0427 28480 5905-00-917-0578 192P22392 56289 5910-00-993-8308
0757-0436 28480 5905-00-858-6792 2100-0439 28480 5905-00-851-3924
6-12
PART NUMBER - NATIONAL STOCK NUMBER TM 11-6625-2958-14&P
CROSS REFERENCE INDEX
NATIONAL NATIONAL
PART STOCK PART STOCK
NUMBER FSCM NUMBER NUMBER FSCM NUMBER
2100-0806 28480 5905-00-929-0485
2100-1824 28480 5905-00-892-9626
2100-1857 28480 5905-00-575-8853
2100-1866 28480 5905-00-110-0282
242E1025 56289 5905-00-504-4892
243E5005 56289 5905-00-950-5551
2950-0034 28480 5310-00-903-8729
30D505G050BB2 56289 5910-00-081-6159
3160-0056 28480 4140-00-758-6113
422-13-11-013 71785 5935-00-917-9079
599-124 72765 6210-00-761-8898
734 08530 5970-00-840-5109
6-13
TM 11-6625-2958-14&P
SECTION Vll
CIRCUIT DIAGRAMS AND COMPONENT LOCATION DIAGRAMS
This section contains the circuit diagrams neces­sary for the operation and maintenance of this power supply. Included are:
a.
Component location diagrams (Figures 7-1 through 7-8, and 7-10), showing the physical loca­tion and reference designators of parts mounted on the printed circuit boards and chassis.
b. Preregulator control circuit waveforms
(Figure 7-9), showing the waveforms found at vari-
ous points in the preregulator control circuit.
c.
Schematic diagram (Figure 7-1 1), illustrat­ing the circuitry for the entire power supply. Volt­ages are given adjacent to test points, which are identified by encircled numbers on the schematic.
7-1
TM 11-6625-2958-14&P
Figure 7-1.
(Shown removed from supply with assembly cover off.)
A2 RFI Assembly Component Location Diagram
Figure 7-2. A3 Interconnection Circuit Board Assembly Component
Location Diagram (Shown with A2 RF I assembly removed.)
7-2
TM 11-6625-2958-14&P
Figure 7-3. Top Front Chassis Assembly Component Location Diagram
7-3
TM 11-6625-2958-14&P
Figure 7-4. Bottom Front Chassis Assembly Component Location Diagram
7-4
TM 11-6625-2958-14&P
Figure 7-5. Bottom Rear Chassis Assembly
Component Location Diagram
7-5
TM 11-6625-2958-14&P
Figure 7-6. Series Regulator Emitter Resistor
(Circuit board is part of A4 heat sink assembly.)
Assembly Component Location Diagram
Figure 7-7.
A4 Heat Sink Assembly Component Location Diagram
(Top view, assembly removed from supply.)
7-6
TM 11-6625-2958-14&P
Figure 7-8.
NOTES
1. ALL WAVEFORMS TAKEN AT MAXIMUM RATED OUTPUT VOLTAGE, 230 VAC INPUT, NO LOAD CONNECTED AND CURRENT CONTROLS FULLY CLOCKWISE.
2. SCOPE DC COUPLED AND REFERENCED TO TP103 (INBOARD SIDE OF CURRENT SAMPLING RESISTOR) UNLESS
OTHERWISE SHOWN.
3. FOR CLARITY, WAVEFORMS ARE NOT DRAWN TO SCALE.
A4 Heat Sink Assembly Component Location Diagram
(End view, assembly removed from supply.)
Figure 7-9. Preregulator Control Circuit Waveforms
7-7

Figure 7-10

This publication does not contain Figure 7-10. Figure 7-10 does not exist in paper or digital form.
NOT DIGITIZED
APPENDIX A REFERENCES
TM 11-6625-2958-14&P
DA Pam 310-4
DA Pam 310-7 TM 38-750 TM 740-90-1 TM ‘750-244-2
TB 43-180
TB 385-4
Index of Technical Manuals, Technical Bulletins,
Supply Manuals (Types 7, 8 and 9), Supply
Bulletins, and Lubrication Orders. Index of Modification Work Orders.
The Army Maintenance Management System (TAMMS). Administrative Storage of Equipment. Procedures for Destruction of Electronics Materiel
to Prevent Enemy Use (Electronics Command).
Calibration Requirements for the Maintenance of
Army Materiel. Safety Precautions for Maintenance of Electrical/
Electronic Equipment.
A-1

APPENDIX B

COMPONENTS OF END ITEM LIST
TM 11-6625-2958-14&P
Section L
B-1.
This appendix lists integral components of and basic issue items for the PP-7545/U to help
you inventory items required for safe and efficient
operation.
.
.
B-2. General
This Components of End Item List is divided into the following sections:
item. Not applicable. The-se items, when assem-
bled, comprise the PP-754.5/U and must accom­pany it whenever it is transferred or turned in.
The illustrations will help you identify these items.
These are the minimum essential items required to place the PP-7545/U in operation, to operate
it, and to perform emergency repairs. Although shipped separately packed they must accompany the PP-7545/U during operation and whenever it is transferred between accountable officers. The illustrations will assist you with hard-b-identify items. This manual is your authority to requisition replacement BII, base don TOE/MTOE authoriza­tion of the end item.
B-3. Explanation of Columns
lows :
ber of the illustration on which the item is shown.
Scope
a. Section II. Integral Components of the End
b. Section III. Basic Issue Items. Not applicable.
a. Illustration. This column is divided as fol-
(1) Figure number. Indicates the figure num-
INTRODUCTION
(2) Item number. The number used to iden-
tify item called out in the illustration.
b. National Stock Number. Indicates the Na­tional stock number assigned to the item and which will be used for requisitioning.
c. Description. Indicates the Federal item name and, if required, a minimum description to iden­tify the item. The part number indicates the pri­mary number used by the manufacturer, which controls the design and characteristics of the item by means of its. engineering drawings, specifica­tions, standards, and inspection requirements to identify an item or range of items. Following the part number, the Federal Supply Code for Manu-
facturers (FSCM) is shown in parentheses
d. Location The physical location of each item listed is given in this column. The lists are de­signed to inventory all items in one area of the major item before moving on to an adjacent area.
e. Usable on Code. Not applicable.
f. Quantity Required (Qty Reqd). This column lists the quantity of each item required for a
complete major item.
g. Quantity. This column is left blank for use during an inventory. Under the Rcvd column, list
the quantity you actually receive on your major
item. The Date columns are for your use when you
inventory the major item.
(Next printed page is B-2.)
B-1
SECTION II INTEGRAL COMPONENTS OF END ITEM TM 11-6625-2958-14&P
SECTION III BASIC ISSUE ITEMS
(1) (2) (3) (4) (5) (6) (7)
ILLUSTRATION NATIONAL DESCRIPTION LOCATION USABLE QTY QUANTITY
(A) (B) STOCK ON REQD
FIG ITEM NUMBER CODE RCVD DATE
NO NO PART NUMBER (FSCM)
1-1 N/A 6130-00-148-1796 PP-7545/U 28480 1
TM 11-6625-2958-14&P 1
B-2

APPENDIX D

MAINTENANCE ALLOCATION
Section L INTRODUCTION
TM 11-6625-2958-14&P
D-1. General
This appendix provides a summary of the main-
tenance operations for the PP-7545/U. It authorizes categories of maintenance for specific maintenance functions on repairable items and components and the tools and equipment required to perform each function. This appendix may
be used as an aid in planning maintenance opera­tions.
D-2. Maintenance Function
Maintenance functions will be limited to and de­fined as follows:
a. Inspect. To determine the serviceability of an item by comparing its physical, mechanical, and/ or electrical characteristics with established stand­ards through examination.
b. Test. To verify serviceability and to detect incipient failure by measuring the mechanical or
electrical characteristics of an item and compar­ing those characteristics with prescribed stand­ards.
c. Service. Operations required periodically to keep an item in proper operating conditions, i.e., to clean (decontaminate), to preserve, to drain,
to paint, or to replenish fuel, lubricants, hydraulic fluids, or compressed air supplies.
d. Adjust To maintain, within prescribed limits,
by bringing into proper or exact position, or by
setting the operating characteristics to the speci-
fied parameters.
e. Align To adjust specified variable elements of an item to bring about optimum or desired performance.
f. Calibrate. To determine and cause corrections to be made or to be adjusted on instruments or test measuring and diagnostic equipments used
in precision measurement. Consists of compari­sons of two instruments, one of which is a certified standard of known accuracy, to detect and adjust any discrepancy in the accuracy of the instrument being compared.
g. install. The act of emplacing, seating, or fix­ing into position an item, part, module (compo­nent or assembly) in a manner to allow the proper functioning of the equipment or system.
h. Replace. The act of substituting a serviceable like type part, subassembly, or module (component or assembly) for an unserviceable counterpart.
i. Repair. The application of maintenance serv­ices (inspect, test, service, adjust, align, calibrate, replace) or other maintenance actions (welding, grinding, riveting, straightening, facing, rema­chining, or resurfacing) to restore serviceability to an item by correcting, specific damage, fault, malfunction, or failure in a part, subassembly, module (component or assembly), end item, or system.
j. Overhaul. That maintenance effort (service/ action) necessary to restore an item to a complete­ly serviceable/operational condition as prescribed by maintenance standards (i.e., DMWR) in appro­priate technical publications. Overhaul is normally the highest degree of maintenance performed by the Army. Overhaul does not normally return an item to like new condition.
k. Rebuild. Consists of those services actions necessary for the restoration of unserviceable equipment to a like new condition in accordance with original manufacturing standards. Rebuild is the highest degree of materiel maintenance applied to Army equipment. The rebuild operation includes the act of returning to zero those age measurements (hours, miles, etc. ) considered in classifying Army equipments/components.
D-1
TM 11-6625-2958-14&P
D-3. Column Entries
u. Column 1, Group Number. Column 1 lists group numbers, the purpose of which is to identify components, assemblies, subassemblies, and mod­ules with the next higher assembly.
b. Column 2, Component/Assembly. Column 2 contains the noun names of components, assem­blies, subassemblies, and modules for which main­tenance is authorized.
c. Column 3, Maintenance Functions. Column 3 lists the functions to be performed on the item listed in column 2. When items are listed without maintenance functions, it is solely for purpose of having the group numbers in the MAC and RPSTL coincide.
d. Column 4, Maintenance Category. Column 4
specifies, by the listing of a “worktime” figure in the appropriate subcolumn (s), the lowest level of maintenance authorized to perform the function listed in column 3. This figure represents the ac­tive time required to perform that maintenance function at the indicated category of maintenance.
If the number or complexity of the tasks within
the listed maintenance function vary at different maintenance categories, appropriate “worktime” figures will be shown for each category. The num-
ber of task-hours specified by the “worktime” figure represents the average time required to restore an item (assembly, subassembly, compo-
nent, module, end item or system) to a serviceable condition under typical field operating conditions. This time includes preparation time, troubleshoot­ing time, and quality assurance/quality control time in addition to the time required to perform
the specific tasks identified for the maintenance functions authorized in the maintenance allocation chart. Subcolumns of column 4 are as follows:
C - Operator/Crew 0- Organizational F - Direct Support H - General Support D - Depot
e. Column 5, Tools and Equipment. Column 5
specifies by code, those common tool sets (not
individual tools) and special tools, test, and sup­port equipment required to perform the designated function.
f. Column 6, Remarks. Column 6 contains an
alphabetic code which leads to the remark in section IV, Remarks, which is pertinent to the item opposite the particular code.
D-4. Tool and Test Equipment Requirement
(sect Ill)
a. Tool or Test Equipment Reference Code. The numbers in this column coincide with the numbers used in the tools and equipment column of the MAC. The numbers indicate the applicable tool or test equipment for the maintenance functions.
b. Maintenance Category. The codes in this column indicate the maintenance category allo­cated the tool or test equipment.
c. Nomenclature. This column lists the noun
name and nomenclature of the tools and test
equipment required to perform the maintenance
functions.
d. National/NATO Stock Number. This column lists the National, NATO stock number of the specified tool or test equipment.
e. Tool Number. This column lists the manu­facturer’s part number of the tool followed by the Federal Supply Code for manufacturers (5-digit)
in parentheses.
D-5. Remarks (sect IV)
a. Reference Code. This code refers to the ap-
propriate item in section II, column 6.
b. Remarks. This column provides the required explanatory information necessary to clarify items appearing in section II.
D-2
SECTION II MAINTENANCE ALLOCATION C
HART
TM 11-6625-2958-14&P
D-3
TM11-6625-2958-14&P SECTION III TOOL AND TEST EQUIPMENT REQUIREMENTS
FOR
POWER SUPPLY PP-7545/U
TOOL OR TEST
EQUIPMENT MAINTENANCE NOMENCLATURE NATIONAL/NATO TOOL NUMBER
REF CODE CATEGORY STOCK NUMBER
1 O MULTIMETER AN/URM-105 6625-00-581-2036
2 O TOOL KIT, ELECTRONIC EQUIPMENT TK-101/G 5180-00-064-5178
3 H, D TOOL KIT, ELECTRONIC EQUIPMENT TK-105/G 5180-00-610-8177
4 H, D GENERATOR, SIGNAL SG-321/U 6625-00-880-5791
5 H, D MULTIMETER, AN/USM-223/U 6625-00-999-7465
6 H, D MULTIMETER, ELECTRONIC, ME-260/U 6625-00-913-9781
7 H, D OSCILLOSCOPE AN/USM-281 6625 00-106-9622
8 H, D RESISTANCE BRIDGE, ZM-4()/U 6625-00-500-9370
9 H, D TRANSFORMER, VARIABLE CN-16/U 5950-00-235-2086
10 H, D VOLTMETER DIGITAL, AN/GSM-64 6625-00-022-7894
11 H, D VOLTMETER DIGITAL, ME-202/U 6625-00-709-0288
D-4
REFERENCE
CODE
SECTION IV. POWER SUPPLY PP-7545/U
REMARKS
REMARKS
TM 11-6625-2958-14&P
A B
C
D
Exterior Operational Interior
All
D-5
Figure 7-11. Schematic Diagram, Model 6269B
MANUAL CHANGES
Model 6269B DC Power Supply
Manual HP Part No. 06269-90002
Make all corrections in the manual according to errata below, then check the following table for your power
supply serial number and enter any listed” change(s) in the manual.
In the Replaceable Parts list under AZ RFI Filter
SERIAL
Prefix
Number
ALL
1027A
0245, 0246, 0255
1027A
0236, 0239, 0241 - 0244, 0247, 0248, 0252 -0254, 0256-0305
1027A
1027A
1027A
1027A 1027A
1027A 1027A
1027A 1436A 1506A 1513A
1535A
0306 - 0355 0356 - 0380
0381 - 0429 0430 - 0455 0456 - 0540
0541
- 0870
0871
- 1080
1081
- 1260
1261
- 1470
1471
- 1510
1511
- 1630
1631
- up ERRATA:.
In the Replaceable Parts List, make the following
changes:
Knob, front panel, black: Change to HP Part No.
0370-0084.
Option 007: Add knob, HP Part No. 0370-0137,
quantity 1.
Option 008: Add knob, HP Part No. 0370-0137,
MAKE
CHANGES
Errata
1 1,2
1,2,3
1,2, 3,4 1 thru S
1 thru 6 1 thru 7
1 thru 8 1 thru 9 1 thru10 1 thru 11 1 thru 12 1 thru 13 1 thru 14
Assembly:
C2: Add, 0.047µF, 600V, HP Part No. 0160-0005. R2: Add, 220
Ω, ±5%, 2W, HP Part No. 0811-1763.
In the Replaceable Parts Iist, make the following
changes:
CR1: Delete Mfr. Part No. and change HP Part
No. to 1884-0209.
Under A2-Mechanical:
Wafer, Insulated, CR1: Delete. Shoulder Washer, CR1: Delete.
CHANGE 2:
In the Replaceable Parts List under A4 Heat Sink
Assembly and on the Schematic, make the follow-
ing changes:
A4R106 (in the Overvoltage Protection Crowbar):
Change to fxd,
WW, 0.2 Ω, 12W, HP Part No.
0811-3081.
A4Q102 (in the Series Regulator and Driver Cir-
cuit): change to HP Part No. 1854-0458.
CHANGE 3:
In the Replaceable Parts list, make the following changes:
A1C71: Change to 0.22µF, 80V, HP Part No.
0160-2453.
A1R5: Change to 680 Ω, 5W, HP Part No.
0811-2099.
A1R79: Change to 1.8k, ½W, HP Part No.
0686-1825.
quantity 1.
Option 009: Add knob, HP Part No. 0370-0137,
ERRATA :
quantity 2.
Under AS-Mechanical:
Bezel, Gray Plastic: Change to HP Part No.
4040-0293 (Black).
Under Chassis Assembly-Mechanical
Bus Bar, C103-C104: Change to HP Part No.
5000-6251.
In the Replaceable Parts List on Page 6-8, under Chassis-Electrical, change:
C110, C111 to 3000 Vdc. On the schematic, Figure 7-11, connect the +S output terminal to the A8 terminal on the inboard side of the + OUT BUS (these terminals are inter-
nally connected).
CHANGE 1:
Add new RC network (C2 and R2) on the RFI filter
board assembly A2.
On the schematic, C2 and R2 are connected directly across Triac CR1 (C2 is on the inboard side of CR1).
C2 and R2 prevent the misfiring (turning on too
soon) of triac CR1 by slowing the rate of voltage increase across L1A/B (in series with T1) when
the triac turns off.
CHANGE 4:
In the Replaceable Parts List and on the schematic make the following changes:
A2C1: Change Cl to O.1µF, 400Vdc, HP Part No.
0160-0013.
A1C41: Change C41 to 0.01µF, 200Vdc, HP Part
No. 0160-0161.
Manual Changes/Model 6269B Manual HP Part No, 06269-90002 Page -2-
CHANGE 5:
The standard colors for this instrument are now mint gray (for front and rear panels) and olive, gray
(for all top, bottom, side, and other external sur-
faces). color scheme of light gray and blue gray. Option A85 designates use of a light gray front panel with
olive gray used for all other external surfaces.
New part numbers are shown below:
In the replaceable parts table under AI Main P. C.
Board - Electrical and on the schematic (in the Overvoltage Protection Crowbar circuit), make the following changes:
C91: Add, 0.0047µF, 200V, HP Part No. 0160­R99: Change to 10k Ω, ±5%, ½W, HP Part No.
T70, T90: Change to HP Part No. 5080-7192.
Option X95 designates use of the former
DESCRIPTION
Front Panel, Complete
Front Panel, Lettered Rear Panel 5000-9475 Cover, Top and Bottom Chassis, Assembly
(weIded)
CHANGE 7:
0157.
0686-1035.
STANDARD
06269-60005
I
06269-60009
5000-9476
5060-7972
CHANGE 6:
In the Replaceable Parts list and on the schematic, make the following changes:
A1R24: Change to 127k
No. 0698-6659.
A1R25: Change to 90.9k
No. 0757-0464.
These changes insure that the Short Circuit Protec­tion circuit operates correctly.
HP PART NO.
OPTION A85
06269-60006
with the secondary winding of the new Pulse Generator Pulse Transformer T70 (HP Part No. 5080-7192) as shown below:
Ω, ±25%, 1/8W, HP Part
Ω, ±1%, 1/8W, HP Part
OPTION X95
5000-6247 5000-6250
5060-6186
The above changes have been made to improve the noise immunity of the overvoltage protection crow­bar and thereby eliminate spurious triggering of the crowbar. the collector of Q92 (which also connects to the base of Q91) and
disconnected fmm +12.4V and connected instead to
the junction of R94-R95 (the other end of R95 still connects to the base of Q92 through CR91).
In order to eliminate false triggering and ripple im-
balance in the Preregulator Control Circuit, the
following changes have been made:
Diode CR88 and resistor R88 are now in series
In the replaceable parts table under A2 RFI Filter
Assembly, change Triac CR1 HP Part No. to 1884-
0218.
Capacitor C91 is connected from between
The top of R99 has been
CHANGE 8:
Manual Changes/Model 6269B Manual HP Part No. 04269-90002 Page -3-
ERRATA :
In the parts list
Under A4 Mechanical, add Transistor Insu-
lator, HP Part No. 0340-0795, quantity 2.
Under AS Front Panel Assembly, change the
HP Part No. of circuit breaker CB1 to 3105-0034.
CHANGE 12:
The following changes enable the master crowbar
to trip the slave crowbar(s) when two or more units are connected in parallel. under Al Main Printed Circuit Board and on the schematic, change A1C90 to .47µF 25Vdc HP Part No. 0160-0174. Also, add resistor A1R120, 4.7K
¼W HP Part No. 0758-0005. Connect A1R20 in parallel with A1Z2C in the Overvoltage Protection Crowbar Circuit on schematic.
In the parts list
CHANGE 9:
In the parts list under A4 Heat Sink Assembly,
change the HP Part No. of CR101, 102, 105, and
108 to 1901-0318, and change CR103, 104, and 106 to 1901-0317.
CHANGE 10:
In the parts list under AS Front Panel Assembly,
change R122 to 100 ohms, variable, HP Part No.
2100-1987.
CHANGE 11:
In the parts list and on the schematic, make the following additions and changes:
Under AS: Add C112, fxd, .01µF 3KV HP Part
No. 0160-2568
Under A2: Add RV1, varistor, MOV HP Part No.
0837-0117
Change: C110 and C111 have been moved from
chassis to the front panel assembly. Connect the added and changed components as shown below.
The following change prevents series regulator failure under short circuit conditions. On sche­matic, in the Constant Voltage Comparator Cir­cuit disconnect anode of A1CR6 from A1Z1 pin 1 side of A1R6. Connect anode of A1CR6 to rear terminal A2 side of A1R6.
CHANGE 13:
In the parts list under A4 Heat Sink Assembly. change the part number of CR101 and CR102 to
1901-0729 and change CR103 and CR104 to 1901-
0730.
CHANGE 14:
The RFI Assembly is changed to HP Part No. 06269-
60010. This new RFI Assembly is completely inter­changeable in all previously built 6269B power supplies.
In the parts list under A2-Mechanical make the following changes:
Change the Cover, RFI Assembly to 5020-
2284. Change the Heat Sink, RFI Filter Ass ‘y to
5020-2282.
Manual Changes/Model 6269B Manual HP Part No. 06269-90002 Page -4-
In the parts list, delete the entire listing under A2 RFI Filter Assembly and replace with the fol­lowing.
REF.
DESIG.
A2
C1, C2 C3 C4
CR1
L1 R1, R2 R4 RV1
RFI Filter Assembly fxd, metalized paper, 0.1µF 250Vac
fxd, metalized paper, .047µF 250v fxd mica, 5000pF, 1kV Thyristor, Si. (Triac)
Filter choke, 20A fxd, metal oxide, 1.5k 2W fxd, metal oxide, 220 2W
Varistor, MOV
DESCRIPTON
A schematic of RFI Filter Assembly 06269-60010 is shown below. This schematic replaces the A2 Filter portion of the schematic shown in Change 11.
HP
PART NO.
06269-60010
0160-4065 0160-4323 0160-0899 1884-0248
5080-1782 0698-3338 0698-3628 0837-0117
9-26-75
By Order of the Secretary of the Army:
Official:
J. C. PENNINGTON
Major General, United States Army
The Adjutant General
Distribution:
Active Army:
TSG (1)
USAARENBD (1) USAINSCOM (2)
TRADOC (2) DARCOM (1) TECOM (2) OS Maj Cored (2)
USACC (2)
HISA (Ft Monmouth) (21)
Armies (1)
USASIGS (10)
Svc Colleges (1) Ft Richardson (CERCOM Oft) (1)
Ft Carson (5)
Ft Gillem (10) WSMR (1)
ARNG; None
USAR: None
For explanation of abbreviations used, see AR 310-50.
E. C. MEYER
General, United States Army
Chief of Staff
USAERDAA (1) USAERDAW (1) Army Dep (1) except
SAAD (20) TOAD (14)
SHAD (2) USA Dep (1) Sig Sec USA Dep (1) Units org under fol TOE:
(2 copies each unit)
29-207 29-610
(1 copy each unit)
29-134
29-136
THE METRIC SYSTEM AND EQUIVALENTS
PIN: 046413-000
Loading...