IF YOU CANNOT TURN OFF THE ELECTRICAL
POWER, PULL, PUSH, OR LIFT THE PERSON TO
SAFETY USING A WOODEN POLE OR A ROPE OR
SOME OTHER INSULATING MATERIAL
SEND FOR HELP AS SOON AS POSSIBLE
AFTER THE INJURED PERSON IS FREE OF
CONTACT
WITH THE SOURCE OF ELECTRICAL
SHOCK, MOVE THE PERSON A SHORT DISTANCE
AWAY AND IMMEDIATELY START ARTIFICIAL
RESUSCITATION
This manual includes copyright material reproduced by permission of the HEWLETT-PACKARD Company.
TM 11-6625-2958-14&P
TECHNICAL MANUAL
No. 11-6625-2958-14&P
DEPARTMENT OF THE ARMY
Washington DC, 21 August 1980
HEADQUARTERS
OPERATOR’S, ORGANIZATIONAL, DIRECT SUPPORT AND
GENERAL SUPPORT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LISTS)
FOR
DC POWER SUPPLY PP-7545/U
(HEWLETT-PACKARD MODEL 6269B)
(NSN 6130-00-148-1796)
FOR SERIALS 1027A00101 AND ABOVE*
REPORTING OF ERRORS
You can improve this manual by recommending improvements using DA Form 2028-2 located
in the back of the manual. Simply tear out the self-addressed form, fill it out as shown on the sample, fold it where shown, and drop it in the mail.
If there are no blank DA Forms 2028-2 in the back of your manual, use the standard DA Form
2028 (Recommended Changes to Publications and Blank Forms) and forward to Commander, US
Army Communications and Electronics Materiel Readiness Command, ATTN: DRSEL-ME-MQ,
Fort Monmouth, NJ 07703.
In either case a reply will be forwarded direct to y
OU.
This manual is an authentication of the manufacturer's commercial literature which, through usage, has been found to cover the
data required to operate and maintain this equipment. Since the manual was not prepared0 in accordance with military specifications
and AR 310-3, the format has not been structured to consider Ievels of maintenance.
i
TABLE OF CONTENTS
Section
0
INSTRUCTIONS
0-1 Scope
0-2 Indexes of Publications
0-3 Forms and Records
0-4 Reporting Equipment Im-
provement Recommendations (EIR) 0-1
0-5 Administrative Storage
0-6 Destruction of Army
provides maintenance instructions.
Throughout this manual, PP-7545/U
is referred to as the Hewlett-Pack-
4430.3E
and DSAR 4140.55.
c. Discrepancy in Shipment Report (DISREP)
(SF 361). Fill out and forward Discrepancy in
Shipment Report (DISREP) (SF 361) as prescribed
in AR 55-38/NAVSUPlNST 4610.33B/AFR 75-
18\MCO P4610.19C and DLAR 4500.15.
ard (HP) Model 6269B DC Power
supply.
0-4. REPORTING EQUIPMENT
IMPROVEMENT
RECOMMENDATIONS (EIR).
0-2. INDEXES OF PUBLICATIONS.
a. DA Pam 310-4. Refer to the latest issue of
DA Pam 310-4 to determine whether there are new
editions, changes, additional publications per-
.
taining to the equipment.
b. DA Pam 310-7: Refer to DA Pam 310-7 to
determine whether there are modification work
orders (MWO’s) pertaining to the equipment.
0-3. FORMS AND RECORDS.
a. Reports of Maintenance and UnsatisfactoryEquipment. Maintenance forms, records, and
reports which are to be used by maintenance per-
EIR’s will be prepared using SF 368 (Quality Deficiency Report). Instructions for preparing EIR’s
are provided in TM 38-750, the Army Maintenance Management System. El R’s should be mailed
direct to Commander, US Army Communication
and Electronics Materiel Readiness Command,
ATTN: DRSEL-ME-MQ, Fort Monmouth, NJ
07703. A reply will be furnished direct to you.
0-5. ADMINISTRATIVE STORAGE.
Administrative storage of equipment issued to and
used by Army activities shall be in accordance with
TM 740-90-1 and paragraph 2-8.
sonnel at all maintenance levels are listed in and
SCribed by TM 38-750.
pre
b. Report of Packaging and Handling Deficienties. FiII out and forward DD Form 6 (PackagingImprovement Report) as prescribed in AR 735-11
-2/NAVUPINST4440.127E/AFR 400-54/MCO
0-6. DESTRUCTION OF ARMY
ELECTRONICS MATERIEL.
Destruction of Army electronics materiel to prevent enemy use shall be in accordance with TM
750-244-2.
SAFETY PRECAUTIONS.
A periodic review of safety precautions in TB 385-4 is
recommended.
When the equipment is operated with covers
removed while performing maintenance, DO NOT TOUCH exposed connections or compments. MAKE CERTAIN you are
not grounded when making connections or adjusting components inside the power supply.
WARNING
HIGH VOLTAGE is used during the “performance
of maintenance as instructed in this manual.
DEATH ON CONTACT may result if personnel
fail to observe safety precautions.
0-1
SECTION I
GENERAL INFORMATION
TM11-6625-2958-14&P
Figure 1-1.
1-1 DESCRIPTION
1-2 This power supply, Figure 1-1, is completely
transistorized and suitable for either bench or relay
rack operation. It is a well-regulated, constant
voltage/constant current supply that will furnish
full rated output voltage at the maximum rated output current or can be continuously adjusted throughout the output range. The front panel CURRENT controls can be used to establish the output current
limit (overload or short circuit) when the supply is
used as a constant voltage source and the VOLTAGE
controls can be used to establish the voltage limit
(ceiling) when the supply is used as a constant current source. The supply will automatically cross
over from constant voltage to constant current oper-
ation and vice versa if the output current or voltage
exceeds these preset limits.
1-3 The power supply contains an added feature
for protection of delicate loads. A limit can be set
on the output voltage. If this limit is exceeded the
output will automatically be shorted.
DC Power Supply, Model 6259B, 6260B, 6261B, 6268B, or 6269B
1-4 The power supply has rear output terminals.
Either the positive or negative output terminal may
be grounded or the power supply can be operated
floating at up to a maximum of 300 volts above
ground.
1-5 Output voltage and current are continuously
monitored on two front panel meters.
1-6 TerminaIs located at the rear of the unit allow
access to various control points within the unit to
expand the operating capabilities of the power supply. A brief description of these capabilities is
given below:
a. Remote Programming. The power supply
output voltage or current may be programmed (con-
trolled) from a remote location by means of an external voltage source or resistarice.
b. Remote-Sensing. The degradation in regulation which occurs at the load due to voltage drop
in the load leads can be reduced by using the power supply in the remote sensing mode of operation.
c. Auto-Series Operation. Power supplies
1-1
TM 11-6625-2958-14&P
may be used in series when a higher output voltage
is required in the constant voltage mode of opera-
t ion or when greater voltage compliance is required
in the constant current mode of operation. AutoSeries operation permits one-knob control of the
total output voltage from a “master” supply.
d. Auto-Parallel Operation. The power sup-
ply may be operated in parallel with a similar unit
when greater output current capability is required.
Auto-Parallel operation permits one-knob control of
the total output current from a “master” supply.
e. Auto-Tracking.The power supply may be
used as a “master” supply controlling one or more
“slave” supplies furnishing various voltages for a
system.
1-7 SPECIFICATIONS
1-8 Detailed specifications for the power supply
are given in Table 1-1 on Page 1-3.
1-9 OPTIONS
1-10 Options are customer-requested factory modifications of a standard instrument.
options are available for the instrument covered by
this manual. Where necessary, detailed coverage
of the options is included throughout the manual.
Option No.
005
007
008
009
010
013
50Hz Regulator Realignment: Stand-
ard instruments are designed for 57 to
63 Hz operation. Option 005 (factory
realignment) is necessary when the
instrument is to be operated from a
50Hz ac source. The option consists
of changing a resistor in the preregu -
lator circuit and adjusting the preregulator tracking.
Ten-Turn Output Voltage Control:
A single control that replaces the
coarse voltage control and allows
greater resolution in setting the out-
put voltage.
Ten-Turn Output Current Control:
A single control that replaces the
coarse current control and allows
greater resolution in setting the output current.
Ten-Turn Output Voltage and Current
Controls: Options 007 and 008 on the
same instrument.
Chassis Slides: Enables convenient
access to power supply interior for
maintenance purposes.
Three Digit Graduated Decadial
Voltage Control: A single control that
replaces the coarse voltage control
and allows accurate resetting of the
output voltage.
Description
The following
Option No.
014
020
021
022
027
1-11 lNSTRUMENT/MANUAL IDENTIFICATION
1-12 Hewlett-Packard power supplies are identified
by a two-part serial number. The first part is the
serial number prefix, a number-letter combination
that denotes the date of a significant design change
and the country of manufacture. The first two digits
indicate the year (10= 1970, 11= 1971, etc.), the
second two digits indicate the week, and the letter
“A” designates the U.S.A. as the country of manu-
facture. The second part is the power supply serial
number;
to each power supply, starting with 00101.
1-13 If the serial number on your instrument does
not agree with those on the title page of the manual,
Change Sheets supplied with the manual or Manual
Backdating Changes in Appendix A define the differences between your instrument and the instrument described by this manual.
a different sequential number is assigned
Three Digit Graduated Decadial Current Control:
replaces the coarse current control
and allows accurate resetting of the
output current.
Rewire for 115Vac Input (6260B only):
Consists of replacing the input power
transformer and circuit breaker, and
reconnecting the bias transformer, RFI
choke, and fans for 115Vac operation.
Voltage Programming Adjustment:
Two rear panel mounted, screwdriveradjustable controls that allow accu-
rately setting the zero volt output and
the constant voltage programming coefficient.
Current Programming Adjustment:
Two rear panel mounted, screwdriveradjustable controls that allow accurately setting the zero current output
and the constant current programming
coefficient.
Voltage and Current Programming
Adjustments: Options 020 and 021 on
the same instrument.
Rewire for 115Vac Input (6259B,
6261B, and 6268B only): Consists of
replacing the line circuit breaker, and
reconnecting the input power transformer, bias transformer, RF I choke, and
fans for 115Vac operation.
Rewire for 208Vac Input: Consists
of reconnecting the input power transformer and bias transformer for 208V
ac operation.
Description
A single control that
1-2
1-14 ORDERING ADDITIONAL MANUALS
1-15 One manual is shipped with each power sup-
ply. Additional manuals may be purchased from
Table 1-1. Specifications
TM 11-6625-2958-14&P
your local Hewlett-Packard field office (see list at
rear of this manual for addresses). Specify the
model number, serial number prefix, and HP part
number shown on the title page.
INPUT:
230Vac *10%, single phase, 57-63 Hz, 18A,
2500W @ 230V.
OUTPUT :
0-40 volts @ 0-50 amperes.
LOAD REGULATION:
Constant Voltage - Less than 0.01% plus 200µV
for a load current change equal to the current
rating of the supply.
Constant Current - Less than 0.02% plus 2mA
for a load voltage change equal to the voltage
rating of the supply.
LINE REGULATION :
Constant Voltage - Less than 0.01% plus 200µV
for a change in line voltage from 207 to 253 volts
at any output voltage and current within rating.
Constant Current - Less than 0.02% plus 2mA
for a change in line voltage from 207 to 253 volts
at any output voltage and current within rating.
RIPPLE AND NOISE:
Constant Voltage - Less than 1mV rms, 5mV
P-P (dc to 20MHz).
Constant Current - Less than 25mA rms.
TEMPERATURE RATINGS:
Operating: O to 55°C. Storage: -40 to +75°C.
TEMPERATURE COEFFICIENT:
Constant Voltage - Less than O .01% plus 200µV
change in output per degree Centigrade change in
ambient following 30 minutes warm-up.
Constant Current - Less than 0.01% plus 4mA
change in output per degree Centigrade change in
ambient following 30 minutes warm-up.
STABILITY :
Constant Voltage - Less than O .03% plus 2mV
total drift for 8 hours following 30 minutes warmup under constant ambient conditions.
Constant Current- Less than 0.03% plus 10mA
total drift for 8 hours following 30 minutes warmup under constant ambient conditions.
TRANSIENT RECOVERY TIME:
Less than 50µsec is required for output voltage
recovery (in constant voltage operation) to within
10mV of the nominal output voltage following a
S ampere change in output current.
METERS:
A front panel voltmeter (0-50V) and ammeter
(0-60A) is provided.
scale. )
OUTPUT CONTROLS:
Single-turn coarse and fine voltage and current
controls are included on the front panel.
OUTPUT TERMINALS:
Output bus bars are located on the rear of the
chassis. Both bus bars are isolated from the
chassis and either the positive or negative bus
bar may be connected to the chassis through a
separate, adjacent ground terminal.
REMOTE VOLTAGE PROGRAMMING:
All programming terminals are on a rear
barrier strip.
Constant Voltage -
Constant Current REMOTE RESISTANCE PROGRAMMING:
All programming terminals are on a rear
barrier strip.
Constant Voltage -200 ohms/volt (Accuracy:
1%).
Constant Current -4 ohms/ampere (Accuracy
10%).
OVERVOLTAGE PROTECTION CROWBAR:
The minimum crowbar trip setting above the
desired operating output voltage” to prevent false
crowbar tripping is 5% of output voltage setting
plus 2 volts. Range is 4 to 45Vdc.
2-2 Before shipment, this instrument was inspected and found to be free of mechanical and electrical defects. As soon as the instrument is unpacked,
inspect for any damage that may have occurred in
transit. Save all packing materials until the inspection is completed. If damage is found, file a
claim with the carrier immediately. HewlettPackard Sales and Service office should be notified.
TM11-6625-2958-14&P
2-3
2-4 This check should confirm that there are no
broken knobs or connectors, that the cabinet and
panel surfaces are free of dents and scratches,
and that the meters are not scratched or cracked.
2-6 The instrument should be checked against
its electrical specifications. Section V includes
a n “in-cabinet” performance check to verify proper
instrument operation.
operation. It is necessary only to connect the inoperation.
2-10 This instrument is fan cooled. Sufficient
cooling air can reach the sides of the instrument
when it is in operation. It should be used in an
area where the ambient temperature does not ex-
2-12 Figure 2-1 illustrates the outline shape and
dimensions of Models 6259B, 6260B, 6261B, 6268B,
and 6269B.
easily rack mounted in a conventional 19 inch rack
MECHANICAL CHECK
2-5 ELECTRICAL CHECK
2-7 INSTALLATION DATA
2-8 The instrument is shipped ready for bench
strument to a source of power and it is ready for
.
2-9
LOCATION
space should be allotted so that a free flow of
ceed 55°C.
2-11 OUTLINE DIAGRAM
2-13 RACK MOUNTING
2-14 This instrument is full rack size and can be
panel using standard mounting screws,
Figure 2-1.
2-15 INPUT POWER REQUIREMENTS
2-16 Model 6259B, 6260B, 6261B, or 6268B power
supply may be operated continuously from either a
nominal 230 volt, 208 volt, or 115 volt 57-63Hz
power source.
a 230 volt or 208 volt, 57-63Hz power source only.
The instrument as shipped from the factory is wired
for 230 volt operation. The input power when operated from a 230 volt power source at full load is:
Model
6259B
6260B
6261B
6268B
6269B
2-17 CONNECTIONS FOR 208 VOLT OPERATION
(Model 6259B, 6261B, or 6268B: Option 027)
2-18 To convert Model 6259B, 6261B, or 6268B to
operation from a 208Vac source, taps on the power
and bias transformers must be changed as follows:
a. Remove RFI assembly as described in
Steps (a) through (c) of Paragraph 5-67. Access is
now provided to bias transformer A3T2. (See Figure
7-2.)
Model 6269B may be operated from
Input Current
Outline Diagram
6A
12A
11A
11A
18A
Input Power
850W
1600W
1500W
1600W
2500W
2-1
TM 11-6625-2958-14&P
transformer (see Figure 2-2 B). Leave wire from fan
B2 (not used in 62599) soldered to “230V” terminal.
c. Re-install RFI assembly by reversing pro-
cedure of Step (a).
d. Unsolder wire connected to terminal 5 of
power transformer T1 (see Figure 7-4) and solder it
instead to terminal 4 of transformer (see Figure
b. Unsolder wire from circuit breaker A5CB1
connected to "230V" terminal of bias transformer
A3T2 and solder it instead to "208V" terminal of
Figure 2-3.
Connections for 208Vac and 115Vac Operation
. (Model 6259B, 6261B, and 6268B)
2-19 CONNECTIONS FOR 208 VOLT OPERATION
(Model 6260B and 6269B: Option 027)
2-20 To convert Model 6260B or 6269B to operation
from a 208Vac source, taps on the power and bias
transformers must be changed as follows:
a. Perform Steps (a) through (c) of Paragraph
2-18.
b. Unsolder wire connected to to "230V” terminal
2-2
Power Transformer Primary
TM 11-6625-2958-14&P
Figure 2-4.
Connections for 208Vac Operation
(Model 6260B and 6269B)
of power transformer T1 (see Figure 7-4) and solder
it instead to "208V" terminal of transformer (see
Figure 2-4 B).
2-21 CONNECTIONS FOR 115 VOLT OPERATION
(Model -6259B, 6261B, and 6268B: Option 026)
2-22 To convert Model 6259B, 6261B, or 6268B to
operation from a 115Vac source, a new circuit
breaker must be installed and taps must be changed
on the bias transformer, power transformer, and RFI
choke as follows:
a. Obtain and install new LINE circuit
breaker (A5CB1). Connections to new circuit
breaker are same as old connections. Refer to
Option 026 in Table 6-4 (Replaceable Parts) for
current rating and HP Part Number.
b. Remove and partially disassemble RFI
assembly as described in Steps (a) through (d) of
Paragraph 5-67.
c. Unsolder jumper between terminals 2 and
3 of RFI choke mounting board and solder jumpers
between terminals 1 and 3, 2 and 4 (see Figure
2-5 B). Replace cover on RFI assembly.
d. Unsolder wires from circuit breaker
A5CB1 and fan B2 connected to "230V" terminal of
bias transformer A3T2 (see Figure 7-2). Solder
wire from circuit breaker to "115V" terminal of
transformer, and solder wire from fan to "0V" terminal of transformer (see Figure 2-2 C). Note that
Power Transformer T 1 Primary
Figure 2-5. RFI Choke (A2L1A/A2L1B)
Connections for 115Vac Operation
(Model 6259B, 6260B, 6261B, and 6268B)
fan B2 is not used in Model 6259B.
e. Re-install RFI assembly by reversing pro-
cedure of Step (b).
f. Unsolder jumper connecting terminals 2
and 3 of power transformer T1 (see Figure 7-4) and
solder jumpers between terminals 1 and 3, 2 and 5
(see Figure 2-3 C).
2-23 CONNECTIONS FOR 115 VOLT OPERATION
(Model 6260B: Option 016)
2-24 To convert Model 6260B to operation from a
115Vac source, a new power transformer and circuit
breaker must be installed and taps must be changed
on the RFI choke and bias transformer as follows:
a. Obtain and install new power transformer
(T1) and new circuit breaker (A5CB1). Refer to
Option 016 in Table 6-4 (Replaceable Parts) for
power ratings and HP Part Numbers. New transformer has two primary terminals. Transfer wire from
old transformer "0V" terminal to new transformer
"0V" terminal, and wire from old transformer "230V"
terminal to new transformer "115V" terminal. New
circuit breaker connections are same as old.
2-3
TM 11-6625-2958-14&P
b. Perform Steps (b) through (e) of Paragraph
2-22.
2-25 CONNECTIONS FOR 50Hz OPERATION
2-26 For operation from a 50Hz ac input, R82
must be replaced with a 240
as specified under Option 005 in Table 6-4 (Replaceable Parts).
readjust the voltage drop across the series regulator (“Preregulator Tracking” , Paragraph 5-103) and
to check the ripple imbalance as described in Steps
(a) through (e) of Paragraph 5-101.
2-27 POWER CABLE
2-28 A power cable is not supplied with the instrument.It is recommended that the user-supplied
power cable have three conductors (third conductor
In addition, it is necessary to
Ω, ±5%, ½ watt resistor
grounded) and be of sufficient wire size to handle
the input current drawn by the supply (see Paragraph
2-16). Note that when the supply is operated from
a 115Vac source, the input current is approximately
double that shown in Paragraph 2-16.
2-29 REPACKAGING FOR SHIPMENT
2-30 To insure safe shipment of the instrument, it
is recommended that the package designed for the
instrument be used. The original packaging material is reusable. If it is not available, contact your
local Hewlett-Packard field office to obtain the
materials. This office will also furnish the address
of the nearest service center to which the instrument can be shipped. Be sure to attach a tag to the
instrument specifying the owner, model number,
full serial number, and service required, or a brief
description of the trouble.
2-4
SECTION Ill
OPERATING INSTRUCTIONS
TM 11-6625-2958-14&P
Figure 3-1.Front Panel Controls and Indicators,’ Modal 6259B, 6260B, 6261B, 6268B or 6269B
3-1 TURN-ON CHECKOUT PROCEDURE
3-2 The following checkout procedure describes
the use of the front panal controls and indicators
(Figure 3-1) and ensures that the supply is opera-
tional.
a. Set LINE circuit breaker ① to ON, and
observe that pilot light ② lights.
b. Adjust VOLTAGE controls ③ until desired
voltage is indicated on voltmeter ④ .
c. To ensure that overvoltage crowbar circuit is operational, rotate OVERVOLTAGE ADJUST
control ⑤ (screwdriver adjust) counterclockwise
until unit crowbars.
light and output voltage will fall to zero volts.
d. To deactivate crowbar, return OVERVOLT-
AGE ADJUST control to its maximum clockwise po-
sition and turn off supply. Turn supply back on
and voltage should again be value obtained in step
(b).
e. To check out constant current circuit,
turn off supply. Short circuit rear output terminals
and turn on supply.
f. Adjust CURRENT controls ⑦ until desired
output current is indicated on ammeter ⑧ .
g. Remove short circuit and read following
paragraphs before connecting actual load to supply.
Overvoltage lamp ⑥ will
3-3 OPERATING MODES
3-4 The power supply is designed so that its mode
of operation can be selected by making strapping
connections between particular terminals on the terminal strip at the rear of the power supply. The terminal designations are stenciled in white on the
power supply below their respective terminals. The
following paragraphs describe the procedures for
utilizing the various operational capabilities of the
power supply. A more theoretical description concerning the operational features of this supply is
contained in Application Note 90, Power Supply
Handbook (available at no charge from your local
Hewlett-Packard sales office). Sales office addresses appear at the rear of the manual.
3-5 NORMAL OPERATING MODE
3-6 The power supply is normally shipped with
its rear terminal strapping connections arranged for
constant voltage/constant current, local sensing,
local programming, single unit mode of operation.
This strapping pattern is illustrated In Figure 3-2.
The operator selects either a constant voltage or a
constant current output using the front panel controls (local programming; no strapping changes are
necessary).
3-1
TM 11-6625-2958-14&P
Figure 3-2.Normal Strapping Pattern
Clockwise rotation of the control produces higher
trip voltages. The factory sets the control fully
clockwise. The crowbar may be disabled completely if desired. (Refer to Paragraph 5-11 1.)
3-13 False crowbar tripping must be considered
when adjusting the trip point. If the trip voltage is
set too close to the operating output voltage of the
supply, a transient in the output will falsely trip
the crowbar. It is recommended that the crowbar be
set higher than the output voltage by 5% of the output voltage plus 2 volts. However, If occasional
crowbar tripping on unloading can be tolerated, the
crowbar trip point can be set much closer to the
operating out put voltage of the supply.
3-7 CONSTANT VOLTAGE
3-8 To select a constant voltage output, proceed
as follows:
a. Turn on power supply and adjust VOLTAGE
controls for desired output voltage with output terminals open.
b. Short circuit output terminals and adjust
CURRENT controls for maximum output current allowable (current limit), as determined by load conditions. If a load change causes the current limit
to be exceeded, the power supply will automatically cross over to constant current output at the preset current limit and the output voltage will drop
proportionately. In setting the current Iimit, allowance must be made for high peak currents which
can cause unwanted crossover. (Refer to Paragraph
3-60. )
3-9 CONSTANT CURRENT
3-10 To select a constant current output, proceed
as follows:
a. Short circuit output terminals and adjust
CURRENT controls for desired output current.
b. Open output terminals and adjust VOLT-
AGE controls for maximum output voltage allowable
(voltage limit ), as determined by load conditions.
If a load change causes the voltage limit to be exceeded, the power supply will automatically cross
over to constant voltage output at the preset volt-
age limit and the output current will drop propor-
tionately. In setting the voltage limit, allowance
must be made for high peak voltages which can
cause unwanted crossover. (Refer to Paragraph 3-60.)
3-14 CONNECTING LOAD
3-15 Each load should be connected to the power
supply output terminals using separate pairs of
connecting wires. This will minimize mutual coupling effects between loads and will retain full advantage of the low output impedance of the power
supply. Each pair of connecting wires should be as
short as possible and twisted or shielded to reduce
noise pickup. (If a shielded pair is used, connect
one end of the shield to ground at the power supply
and leave the other end unconnected.)
3-16 If load considerations require that the output
power distribution terminals be remotely located
from the power supply, then the power suppIy output terminals should be connected to the remote
distribution terminals via a pair of twisted or
shielded wires and each load should be separately
connected to the remote distribution terminals. For
this case, remote sensing should be used. (Refer
to Paragraph 3-4 1.)
3-17 Positive or negative voltages can be obtained
from this supply by grounding either one of. the out-
put terminals or one end of the load. Always use
two leads to connect the load to the supply, regardless of where the setup is grounded. This will eliminate any possibility of output current return paths
through the power source ground which would damage the line cord plug. This supply can also be
operated up to 300Vdc above ground, if neither output terminal is grounded.
3-18 NO LOAD OPERATION
3-11 OVERVOLTAGE TRIP POINT ADJUSTMENT
3-12 The crowbar trip voltage can be adjusted by
using the screwdriver control on the front panel.
The trip voltage range is as follows:
6259B, 6260B
2 to 12Vdc
When the crowbar trips, the output is shorted and
the amber indicator on the front panel lights.
6261B6268B, 6269B
2 to 23Vdc
4 to 45Vdc
3-19 When the supply is operated without a load,
down-programming speed is considerably slower
than in normal loaded operation. This slower programming speed is evident when using any method
of down-programming - either turning the VOLTAGE
controls fully counterclockwise, activating the
crowbar, or throwing the LINE circuit breaker to
OFF. Under any of these conditions, the supply
output will rapidly fall to approximately two volts,
3-2
then proceed at a slower rate towards zero. The
actual time required for the output to fall from two
volts to zero will vary from several seconds to
several minutes, depending upon which down-pro-
gramming method is used.
3-20 OPERATION BEYOND RATED OUTPUT
3-21 The shaded area on the front panel meter face
indicates the approximate amount of output voltage
or current that may be available in excess of the
normal rated output. Although the supply can be
operated in this shaded region without being dam-
aged, it cannot be guaranteed to meet all of its
performance specifications.
3-22 OPTIONAL OPERATING MODES
3-23 REMOTE PROGRAMMING, CONSTANT
VOLTAGE
3-24 The constant voltage output of the power
supply can be programmed (controlled) from a remote location if required. Either a resistance or
voltage source can be used as the programming
device. The wires connecting the programming
terminals of the supply to the remote programming
device should be twisted or shielded to reduce
noise pickup. The VOLTAGE controls on the front
panel are automatically disabled in the following
procedures.
3-26 The output voltage of the supply should be
TM 11-6625-2958-14&P
-15mV ±5mV when zero ohms is connected across
the programming terminals. If a zero ohm voltage
closer to zero than this is required, it may be
achieved by inserting and adjusting R110 as discussed in Paragraph 5-83, or, if the instrument is
equipped with Option 020, by adjusting potentiome-
ter R113 as discussed in Paragraph 5-85.
3-27 To maintain the stability and temperature coefficient of the power supply, use programming resistors that have stable, low noise, and low temperature coefficient (less than 30ppm per degree
Centigrade) characteristics. A switch can be used
in conjunction with various resistance values in
order to obtain discrete output voltages. The switch
should have make-before-break contacts to avoid
momentarily opening the programming terminals during the switching interval.
3-25 Resistance Programming
(Figure 3-3). In this
mode, the output voltage will vary at a rate determined by the voltage programming coefficient of
200 ohms/volt. The programming coefficient is de-
termined by the programming current. This current
is factory adjusted to within 1% of 5mA. If greater
programming accuracy is required, it may be
achieved by either adjusting R3 as discussed in
Paragraph 5-88, or, if the instrument is equipped
with Option 020, by adjusting potentiometer R112
as discussed in Paragraph 5-89.
Figure 3-4.
Remet e Voltage Programming,
Unity Gain (Constant Voltage)
3-28 Voltage Programming,
Unity Gain (Figure 3-4).
Employ the strapping pattern shown in Figure 3-4
for voltage programming with unity gain. In this
mode, the output voltage will vary in a 1 to 1 ratio
with the programming voltage (reference voltage)
and the load on the programming voltage source will
not exceed 20 microampere. Impedance matching
resistor (R
) is required to maintain the temperature
x
coefficient and stability specifications of the sup-
ply .
3-29 Voltage Programming, Non-Unity Gain (Figure
3-5). The strapping pattern shown in Figure 3-5
can be utilized for programming the power supply
using an external voltage source with a variable
voltage gain. The output voltage in this configura-
tion is found by multiplying the external voltage
source by (Rp/RR).
Figure 3-3.
Remet e Resistance Programming
(Constant Voltage)
3-30 External resistors Rp and R
R should have sta-
ble, low noise, and low temperature coefficient
3-3
TM 11-6625-2958-14&P
Figure 3-5.Remote Voltage Programming,
Non-Unity Gain (Constant Voltage)
(less than 30ppm Per degree Centigrade) character-
istics in order to maintain the Supply's temperature
and stability specifications. Reference resistor R
should not exceed 10K. Note that it is possible to
use the front panel voltage control already in the
supply (A5R121) as the voltage gain
control (Rp) by
simply removing the external Rp and strapping terminals Al and A2 together.
3-31 The output voltage of the supply may be adjusted to exactly zero when the external programming voltage is zero by either inserting and adjusting R111 as discussed in Paragraph 5-84, or, if the
instrument is equipped with Option 020, by adjusting potentiometer R112 as discussed in Paragraph
5-86.
Figure 3-6.Remote Resistance Programming
(Constant Current)
with Option 021, by adjusting potentiometer R116
as discussed in Paragraph 5-98. The output current
of the supply when zero ohms is placed across the
programming terminals may be set to exactly zero
R
by either inserting and adjusting R117 as discussed
in Paragraph 5-92, or, if the instrument is equipped
with Option 021, by adjusting potentiometer R119
as discussed in Paragraph 5-94.
3-35 Use stable, low noise, low temperature coefficient (less than 30ppm/°C) programming resistors to maintain the power supply temperature coefficient and stability s pacifications. A switch may
be used to set discrete values of output current. A
make-before-break type of switch should be used
since the output current will exceed the maximum
rating of the power supply if the switch contacts
open during the switching interval.
3-32 REMOTE PROGRAMMING, CONSTANT
CURRENT
3-33 Either a resistance or a voltage source can
be used to control the constant current output of
the supply. The CURRENT controls on the front
panel are automatically disabled in the following
procedures.
3-34 Resistance Programming (Figure 3-6). In this
mode, the output current varies at a rate determined
by the programming coefficient as follows:
Model
6259B
6260B
6261B
6268B
6269B
Programming Coefficient
4 ohms/ampere
2 ohms/ampere
4 ohms/ampere
6 ohms/ampere
4 ohms/ampere
The programming coefficient is determined by the
constant current programming current which is adjusted to within 10% of 2.5mA at the factory. If
greater programming accuracy is required, it may
be achieved by either adjusting R30 as discussed
in Paragraph 5-97, or, if the instrument is equipped
CAUTION
If the programming terminals (A4 and
A 6) should open at any time during the
remote resistance programming mode,
the output current will rise to a value
that may damage the power supply
and/or the load. If, in the particular
programming configuration in use,
there is a chance that the terminals
might become open, it is suggested
that a 200 ohm resistor be connected
across the programming terminals.
Like the programming resistor, this
resistor should be a low noise, low
temperature coefficient type. Not e
that when this resistor is used, the
resistance value actually programming
the supply is the parallel combination
of the remote programming resistance
and the resistor across the programming terminals.
3-4
TM 11-6625-2958-14&P
programmed using an external voltage source with
variable gain by utilizing the strapping pattern
shown in Figure 3-8. In this mode, the output current is found by multiplying the external voltage
source (Es) by [Rp/(RR x Kp)], where Kp is the
constant current voltage programming coefficient as
given in Paragraph 3-37. The value of reference
resistor R
R and programming voltage source E
s
should be such that the value of ES/RR is equal to
or greater than 2.5mA.
Figure 3-7.
Remote Voltage Programming,
Unity Gain (Constant Current]
3-36 Voltage Programming
, Unity Gain (Figure 3-7).
In this mode, the output current will vary linearly
with changes in the programming voltage. The pro-
gramming voltage should not exceed 0.6 volts.
Voltage in excess of 0.6 volts will result in exces-
sive power dissipation in the instrument and possi-
ble damage.
3-37 The output current varies at a rate determined
by the programming coefficient as follows:
Model
6259B
6260B
6261B
6268B
6269B
Programming Coefficient
10.0mV/ampere
5.0mV/ampere
10.0mV/ampere
16.7mV/ampere
10.0mV/ampere
The current required from the voltage source will be
less than 20µA. Impedance matching resistor R
is
x
required to maintain the temperature coefficient and
stability specifications of the supply.
3-38 Voltage Programming,
Non-Unity Gain (Figure
3-8). The power supply output current can be
3-39 External resistors Rp and R
R should have sta-
ble, low noise, and low temperature coefficient
(less than 30ppm per degree Centigrade) characteristics in order to maintain the stability and temperature specifications of the Power supply. Reference
resistor R
R should not exceed 10K. Note that it is
possible to use the front panel current control already in the supply (A5R123) as the gain
control (Rp)
by simply removing the external Rp and strapping
terminals AS and A6 together.
3-40 The output current of the supply may be adjusted to exactly zero when the external programming voltage is zero by either inserting and adjusting R115 as discussed in Paragraph 5-93, or, if the
instrument is equipped with Option 021, by adjust-
ing potentiometer R116 as discussed in Paragraph
5-95.
3-41 REMOTE SENSING (Figure 3-9)
3-42 Remote sensing is used to maintain good reg-
ulation at the load and reduce the degradation of
regulation which would occur due to the voltage
drop in the leads between the power supply and the
load. Remote sensing is accomplished by utilizing
the strapping pattern shown in Figure 3-9. The
Power supply should be turned off before changing
strapping paterns. The leads from the sensing (±S)
terminals to the load will carry much less current
than the load leads and it is not required that these
leads be as heavy as the load leads. However,
they must be twisted or shielded to minimize noise
pickup.
Figure 3-8.
Remote Voltage Programming,
Non-Unity Gain (Constant Current)
3-5
Figure 3-9.
Remote Sensing
TM 11-6625-2958-14&P
3-43 For reasonable load lead lengths, remote
sensing greatly improves the performance of the
supply. However, if the load is located a considerable distance from the supply, added precautions
must be observed to obtain satisfactory operation.
Notice that the voltage drop in the load leads subtracts directly from the available output voltage
and also reduces the amplitude of the feedback error signals that are deveIoped within the unit. Because of these factors it is recommended that the
drop in each load lead not exceed 0.5 volt. If a
larger drop must be tolerated, please consult an
HP Sales Engineer.
NOTE
Due to the voltage drop in the load
leads, it may be necessary to read-
just the current limit in the remote
sensing mode.
3-44 Observance of the precautions in Paragraph
3-43 will result in a low dc output impedance at
the load. However, another factor that must be
considered is the inductance of long load leads.
This causes a high ac Impedance and could affect
the stability of the feedback loop seriously enough
to cause oscillation. If this is the case, it is
recommended that the following actions be taken:
a. Adjust equalization control R47 to remove
oscillation, or to achieve best possible transient
response for given long load lead configuration.
Refer to Paragraph 5-27 for discussion of transient
response measurement.
b. If performing adjustment in step (a) above
does not remove oscillation, disconnect output
capacitor A3C3 and connect a capacitor having similar characteristics (approximately the same capacitance, the same voltage rating or greater, and
having good high frequency characteristics) directly across load using short leads. Readjust equalization control R47 as in step (a) above after making
this change. In order to gain access to capacitor
A3C3, it is necessary to remove the RFI assembly
as described in steps (a) through (c) of Paragraph
5-67. Lead from positive side of capacitor (shown
arrowed In Figure 7-2) can then be unsoldered from
A3 interconnection circuit board.
from the -S terminal to the negative side of the load.
Note that there may be more than one lead connected to the +S and -S terminals.
3-46 AUTO-PARALLEL OPERATION (Figure 3-10)
3-47 Two or more power supplies can be connected
in an Auto-Parallel arrangement to obtain an output
3-45 To employ remote sensing with any method of
remote programming or with any method of combining more than one supply discussed in the Preced-
ing or following paragraphs, use the following pro-
cedure:
a. Remove the two external leads connecting
the sensing terminals (±S) to the output bus bars
(±OUT).
b. Connect a lead from the +S terminal to the
positive side of the load, and connect another lead
Figure 3-10. Auto-Parallel Operation,
Two and Three Units
3-6
current greater than that available from one supply.
Auto-Parallel operation permits equal current shar-
ing under all load conditions, and allows complete
control of the output current from one master power
supply. The output current of each slave will be
approximately equal to the master’s output current
regardless of the load conditions. Because the
output current controls of each slave are operative,
they should be set to maximum to prevent the slave
reverting to constant current operation; this would
OCCur if the master output current setting exceeded
the slave’s.
3-48 Additional slave supplies may be added in
parallel with the master/slave combination as
shown in the bottom half of Figure 3-10. All the
connections between the master and slave #1 are
duplicated between slave #1 and the added slave
supply. In addition, the strapping pattern of the
added slave should be the same as slave #1. Remote sensing and programming can be used, though
the strapping arrangements shown in Figure 3-10
show local sensing and programming.
3-49 Overvoltage protection is controlled by the
crowbar circuit in the master supply which monitors
the voltage acress the load and fires the SCR's in
both units if an overvoltage condition occurs. The
firing pulses are fed to the slave supply from trans-
former T90 (winding 5-6) of the master supply
through the “ EXT. CROWBAR TRIGGER
"
terminals on
the rear panel of the master supply. Correct polari-
ty must be observed in connecting the crowbars to-
gether. The overvoltage trip point is adjusted on
the master supply, The OVERVOLTAGE ADJUST potentiometer on the slave supply should be set to
maximum [clockwise) so that the master crowbar
will control the slave.
TM 11-6625-2958-14&P
3-50 AUTO-SERIES OPERATION (Figure 3-11)
3-51 Two or more power supplies can be operated
in Auto-Series to obtain a higher voltage than that
available from a single supply. When this connection is used, the output voltage of each slave supply varies in accordance with that of the master
supply. At maximum output voltage, the voltage of
the slaves is determined by the setting of the front
panel VOLTAGE controls on the master. The master
supply must be the most positive supply of the
series. The output CURRENT controls of all series
units are operative and the current limit is equal to
the lowest control setting. If any of the output
CURRENT controls are set too low, automatic cross-
over to constant current operation will occur and
the output voltage will drop. Remote sensing and
programming can be used, though the strapping arrangements shown in Figure 3-11 show local sensing
and programming.
3-52 In order to maintain the temperature coeffi-
Figure 3-11.
Auto-Series Operation,
Two and Three Units
cient and stability specifications of the power supply, the external resistors (Rx) shown in Figure
3-11 should be stable, low noise, low temperature
coefficient (less than 30ppm per degree Centigrade)
resistors.
The value of each resistor is dependent
3-7
TM 11-6625-2958-14&P
on the maximum voltage rating of the "master" sup-
ply. The value of R
is this voltage divided by the
X
voltage programming current of the slave supply
(1/Kp where K
P is the voltage programming coeffi-
cient). The voltage contribution of the slave is
determined by its voltage control setting.
3-53 Overvoltage protection is provided in AutoSeries operation by connecting the crowbars in parallel with correct polarity as in Auto-Parallel operation (see Paragraph 3-49). The OVERVOLTAGE AD-
JUST potentiometer in each supply should be adjust-
ed so that it trips at a point slightly above the output voltage that the supply will contribute.
3-54 When the center tap of an Auto-Series combination is grounded, coordinated positive and nega-
tive voltages result. This technique is commonly
referred to as “robber-banding” and an external
reference source may be employed if desired. Any
change of the internal or external reference source
(e.9. drift, ripple) will cause an equal percentage
change in the outputs of both the master and slave
supplies. This feature can be of considerable use
in analog computer and other applications, where
the load requires a positive and a negative power
supply and is less susceptible to an output voltage
change occurring simultaneously in both supplies
than to a change in either supply alone.
3-55 AUTO-TRACKING OPERATION (Figure 3-12)
3-56 The Auto-Tracking configuration is used when
several different voltages referred to a common bus
must vary in proportion to the setting of a particular
instrument (the control or master). A fraction of the
master’s output voltage is fed to the comparison
amplifier of the slave supply, thus controlling the
slave's output. The master must have the largest
output voltage of any power supply in the group. It
must be the most positive supply in the example
shown on Figure 3-12.
3-57 The output voltage of the slave (Es) is a percentage of the master's output voltage (EM), and is
determined by the voltage divider consisting of R
X
and the voltage control of the slave supply, Rp,
where E
S = EM [Rp/(R
+Rp)]. Remote sensing and
x
programming can be used (each supply senses at its
own load), though the strapping patterns given in
Figure 3-12 show only local sensing and program-
ming. In order to maintain the temperature coefficient and stability specifications of the power supply, the external resistors should be stable, low
noise, low temperature coefficient (less than 30ppm
per degree Centigrade) resistors.
3-58 The overvoltage protection circuit in each
unit is operable end independently monitors the
voltage across its own load. Notice that if the
master supply crowbars, the output voltage of
Figure 3-12. Auto-Tracking, Tw
O and Three Units
each slave will also decrease. However, the reverse is not true. If one of the slave units crowbars, the other supplies in *the ensemble will not
be affected.
3-59 SPECIAL OPERATING CONSIDERATIONS
3-60 “PULSE LOADING
3-61 The power supply
will automatically cross
3-8
over from constant voltage to constant current operation, or the reverse, in response to an increase
(over the preset limit) in the output current or voltage, respectively. Although the preset limit may
be set higher than the average output current or
voltage, high peak currents or voltages (as occur
in pulse loading) may exceed the preset limit and
cause crossover to occur. If this crossover limiting is not desired, set the preset limit for the peak
requirement and not the average.
3-62 OUTPUT CAPACITANCE
3-63 An internal capacitor (A3C3) connected across
the output terminals of the power supply, helps to
supply high-current pulses of short duration during
constant voltage operation. Any capacitance added
externally will improve the
PUlSe current capability,
but will decrease the safety provided by the con-
stant current circuit. A high-current pulse may
damage load components before the average output
current is large enough to cause the constant cur-
rent circuit to operate.
3-64 The effects of the output capacitor during
constant current operation are as follows:
a. The output impedance of the power supply
decreases with increasing frequency.
b. The recovery time of the output voltage is
longer for load resistance changes.
TM 11-6625-2958-14&P
c. A large surge current causing a high pow-
er dissipation in the load occurs when the load re-
sistance is reduced rapidly.
3-65 REVERSE VOLTAGE LOADING
3-66 A diode (A4CR106) is connected across the
output terminals.Under normal operation conditions, the diode is reverse biased (anode connected to the negative terminal). If a reverse voltage
is applied to the output terminals (
POSitive voltage
applied to the negative terminal), the diode will
conduct, shunting current across the output termi-
nals and limiting the voltage across the output
terminals to the forward voltage drop of the diode.
This diode protects the series transistors and the
output electrolytic capacitors.
3-67 REVERSE CURRENT LOADING
3-68 Active loads connected to the power supply
may actually deliver a reverse current to the power
supply during a portion of its operating cycle. An
external source cannot be allowed to pump current
into the supply without loss of regulation and possible damage to the output capacitor. To avoid
these effects, it is necessary to preload the supply
with a dummy load resistor so that the power supply
delivers current through the entire operation cycle
of the load device.
3-9
SECTION IV
PRINCIPLES OF OPERATION
TM 11-6625-2958-14&P
Figure 4-1. Overall Block Diagram
4-1 OVERALL BLOCK DIAGRAM DISCUSSION
4-2 The major circuits of the power supply are
shown on the overall block diagram of Figure 4-1.
The ac input voltage is first applied to the preregulator triac which operates in conjunction with the
preregulator control circuit to form a feedback loop.
This feedback loop minimizes the power dissipated
by the series regulator by keeping the voltage drop
across the regulator at a low and constant level.
4-3 To accomplish this, the preregulator control
circuit issues a phase adjusted firing pulse to the
triac once during each half cycle of the input ac.
The control circuit continuously samples the output
voltage, the input line voltage (from A3T2), and the
voltage across the series regulator and, on the
basis of these inputs, determines at what time each
firing pulse is generated.
4-4 The phase adjusted output of the triac is ap-
plied to the power transformer where it is steppeddown and coupled to a full-wave rectifier and filter.
The preregulated dc current is applied next to the
series reguIator which varies its conduction to provide a regulated voltage or current at the output
terminals.
4-5 The series regulator is part of another feedback loop consisting of the error and driver amplifiers and the constant voltage/constant current
compactors. The series regulator feedback loop
provides rapid, low magnitude regulation of the output while the preregulator feedback loop handles
large, relatively slow, regulation demands.
4-1
TM 11-6625-2958-14&P
4-6 The feedback signals controlling the conduction of the series regulator originate within the
constant voltage or constant current comparator.
During constant voltage operation the constant
voltage comparator continuously compares the output voltage of the supply with the drop across the
VOLTAGE controls.
If these voltages are not equal,
the comparator produces an amplified error signal
which is further amplified by the error amplifier and
then fed back to the series regulator in the correct
phase and amplitude to counteract the difference.
In this manner, the constant voltage comparator
helps to maintain a constant output voltage and
also generates the error signals necessary to set
the output voltage at the level established by the
VOLTA GE controls.
4-7 During constant current operation, the constant current comparator detects any difference be-
tween the voltage drop developed by the load current flowing through the current sampling resistor
and the voltage acress the CURRENT controls. If
the two inputs to the comparator are momentarily
unequal, an error signal is generated which (after
amplification) alters the conduction of the series
regulator by the amount necessary to reduce the
error voltage at the comparator input to zero.
Hence, the IR drop across the current sampling resistor, and therefore the output current, is main-
tained at a constant value.
4-8 Since the constant voltage comparator tends
to achieve zero output impedance and alters the
output current whenever the load resistance
changes, while the constant current comparator
causes the output impedance to be infinite and
changes the output voltage in response to any load
resistance change, it is obvious that the two com-
parison amplifiers cannot operate simultaneously.
For any-given value of load resistance, the power
supply must act either as a constant voltage source
or as a constant current source - it cannot be both.
4-9 Figure 4-2 shows the output characteristic of
a constant voltage/constant current power supply.
With no load attached (RL =
OUT = Es, the front panel voltage control setting.
E
∞), IOUT = O, and
When a load resistance is applied to the output
terminals of the power supply, the output current
increases, while the output voltage remains constant; point D thus represents a typical constant
voltage operating point. Further decreases in load
resistance are accompanied by further increases in
OUT with no change in the output voltage until the
I
output current reaches Is, a value equal to the front
panel current control setting. At this point the supply automatically changes its mode of operation and
becomes a constant current source; still further
decreases in the value of load resistance are accompanied by a drop in the supply output voltage
with no accompanying change in the output current
Figure 4-2.Operating Locus of a CV/CC
Power Supply
value. With a short circuit across the output load
terminals, I
4-10 The ‘
be defined as R
OUT = ES and EOUT = O.
:
Crossover” value of load resistance can
C = Es/Is. Adjustment of the front
panel voltage and current controls permits this
“crossover” resistance R
value from 0 to
∞. If RL is greater than RC, the
C to be set to any desired
supply is in constant voltage operation, while if R
is less than RC, the supply is in constant current
operation.
4-11 The short circuit protection circuit (see Figure 4-1) protects the series regulator in the event
of a shorted output when the controls are set to a
high output voltage and current. The protection cir-
cuit monitors the voltage drop across the series
regulator. If the drop rises above a preset level,
the protection circuit limits the current through the
series regulator until the preregulator can reduce
the voltage across the series regulator. Once this
voltage returns to normal, the short circuit protection circuit is turned off and has no effect on normal operation of the supply.
4-12 The overvoltage protect ion crowbar monitors
the output of the supply, and if it exceeds a preset
(adjustable) threshold, fires an SCR which short
circuits the supply.
The circuit also sends a turn-
down signal to the preregulator control circuit.
4-13 The overvoltage limit circuit protects the main
rectifier diodes and filter capacitors from damage
that might occur if the series regulator transistors
were shorted or the voltage programming pot were
opened. The circuit monitors the output voltage of
L
4-2
the supply and, if it exceeds approximately 120%
of maximum rated output, sends a turn-down signal
to the preregulator control circuit. Hence, the out-
put voltage of the supply is limited to a “safe” value despite any possible failure in the series regu-
lator feedback loop.
4-14 The turn-on control circuit is a long time
constant network which allows the supply to
achieve a gradual turn-on characteristic. The slow
turn-on feature protects the preregulator triac and
the series regulator from damage which might occur
when ac power is first applied to the unit. At turnon, the control circuit sends inhibiting voltages to
the preregulator control circuit and the s cries regu-
lator (via the error and driver amplifiers). A short
time after the unit is in operation, the inhibiting
voltages are removed and the circuit no longer ex-
ercises any control over the operation of the supply.
4-15 The reference supply provides stable refer-
ence voltages used by the constant voltage and
current comparators. Less critical operating voltages are obtained from the bias supply.
4-16 DETAILED CIRCUIT ANALYSIS (See
Figure 7-11)
TM 11-6625-2958-14&P
Figure 4-3.Triac Phase Control Over
AC Input Amplitude
4-17 PREREGULATOR CONTROL CIRCUIT
4-18 The preregulator minimizes changes in the
power dissipated by the series regulating transis tors due to output voltage or. input line voltage var-
iations. Preregulation is accomplished by means
of a phase control circuit utilizing triac A2CR1 as
the switching element.
4-19 In order to understand the operation of the
preregulator, it is important to understand the op-
eration of the triac. The triac is a hi-directional
device, that is, it can conduct current in either
direction. Hence, the device fires whenever it
receives a gating pulse regardless of the polarity
of the input a c that is applied to it. The triac is
fired once during each half-cycle (8.3 3 milliseconds) of the input ac (see Figure 4-3). Notice that
when the triac is fired at an early point during the
half-cycle, the ac level applied to the power transformer is relatively high. When the triac is fired
later during the half-cycle, the ac level is relatively low.
4-20 Normally the ac input signal must be at a
certain minimum potential before the triac will conduct. However, A2R1 and A2C1 provide a holding
current that allows the triac to conduct at any time
during the ac input cycle. RFI choke A2L1A/A2L1B
(in series with the triac) slows down the turn-on of
the triac in order to minimize spikes at the output
of the supply. Components A2CR1, A2R1, A2L1A/
A2L1B, and A2C1 are all mounted inside a shielded
box (assembly A2) to minimize radiated and reflected RFI. Further RFI suppression is provided by by-
pass capacitors C110 and C111.
4-21 The preregulator control circuit samples the
input line voltage, the output voltage, and the
voltage across the series regulator transistors. It
generates firing pulses, at the time required, to
fire the triac. This action maintains the ac input
voltage across the primary winding of T I at the desired level.
4-22 The inputs to the control circuit are algebra-
ically summed across capacitor C70. All inputs
contribute to the time required to charge C70. The
input line voltage is rectified by CR81, CR82, CR83,
and CR84, attenuated by voltage divider R86 and
R83, and applied to the summing point at the col -
lector of Q71 (TP81) via capacitor C70. Capacitor
C73 is used for smoothing purposes.
4-23 Transistor Q71, connected in a common base
configuration, provides a charging current for the
summing capacitor varying in accordance with the
input signals applied to its emitter. Resistor R78,
connected between the negative output line and the
emitter of Q71, furnishes a signal which is propor-
tional to the output voltage. Resistors R75 and R76
sample the voltage across, and the current through,
the series regulator. Capacitor C72 and resistor
R82 stabilize the entire preregulator feedback loop.
Resistors R70 and R80 are the source of a constant
offset current which sustains a net negative charg-
4-3
TM 11-6625-2958-14&P
ing current to the summing point, ensuring that the
triac will fire at low output “voltages.
4-24 The summation of the input signals results
in the generation of a voltage waveform at TP80
similar to that shown in waveform (A) of Figure 4-4.
When the linear ramp portion of the waveform
reaches a certain negative threshold voltage, diodes CR74 and CR75 become forward biased. The
negative voltage is then coupled to the base of
transistor Q72. Transistors Q72 and Q73 form a
squaring circuit resembling a Schmitt trigger configuration. Q72 is conducting prior to firing time
due to the positive bias connected to its base
through R84, Transistor Q73 is cut off at this time
because its base is driven negative by the collector of Q72.
4-25 When the negative threshold voltage is
reached, transistor Q72 is turned off and Q73 is
turned on. The conduction of Q73 allows capacitor
C71 to discharge rapidly through pulse transformer
T70 resulting in the generation of a firing pulse
across the secondary winding of T70. As shown in
waveform (C) of Figure 4-4, the firing pulse is
quite narrow because Q73 saturates rapidly, causing
the magnetic field surrounding T70 to collapse. Diode CR76 damps out positive overshoot.
4-26 Reset of the control circuit occurs once every
8.33 milliseconds when the rectified ac voltage at
the junction of CR77, CR78, and CR79 (TP82) in-
creases to a level at which diode CR78 becomes
forward biased. Summing capacitor C70 is then al-
lowed to discharge through CR78. Diodes CR74 and
CR75 become reverse biased at reset and transistor
Q72 reverts to its “on” state. Consequently, Q73
is turned off and capacitor C71 charges up through
R79 at a comparatively slow rate until the collector
voltage of Q73 reaches approximately +11 volts.
The above action causes the small positive spike
that appears across the windings of pulse transformer at T70 at reset time.
4-27 SERIES REGULATOR AND DRIVER
4-28 The series regulator consists of transistors
A4Q103 through A4Q108 connected in parallel. The
transistors serve as the series or “pass” element
which provides precise and rapid control of the output. Resistors A4R150 through A4R155 allow high
output currents to be equally shared by the series
regulator transistors. The conduction of the series
transistors is controlled by signals obtained from
driver A4Q102, which is connected in a Darlington
configuration with the parallel-connected series
regulator transistors. Thermal switch A4TS101 opens
if the heat sink assembly temperature exceeds ap-
proximately 230°F, thus turning off the series regu-
lator transistors. This feature protects critical
components of the supply from excessive temperatures which could occur if cooling fan A4B1 failed.
Diode CR50 provides a discharge path for the out-
put capacitors when the supply is rapidly down-
programmed; R57 limits the discharge current flow-
ing through the diode and through error amplifier
A4Q101. Diode A4CR105, connected across the reg-
ulator circuit, protects the series elements from
reverse voltages that could develop across them
during parallel operation if one supply is turned on
before the other.
Figure 4-4. Preregulator Control Circuit Waveforms
4-29 SHORT CIRCUIT PROTECTION
4-30 This circuit acts to initially protect the series
regulator against a simultaneous full-voltage, full-
current conditions such as might occur if the output
were shorted when the controls were set to deliver
a high output voltage and current. Under this con-
dition, Q20 goes into heavy conduction due to the
increased voltage across the series regulator,
putting R26 in parallel with the current controls and
thus limiting the current to less than 10% of the
supply’s rating.
short circuit is imposed, the preregulator shuts off.
4-4
Within 10 milliseconds after the
The input capacitor then begins to discharge through
the series regulator, and the voltage across the
regulator decreases until Q20 turns off. The dis-
charge time (typically ½ to 4 seconds) depends on
the voltage and current ratings of the supply, the
main filter capacitor, and the control settings.
Once this recovery time has elapsed, the output
current will return to the level set by the current
controls, and the preregulator will return the volt-
age across the series regulator to the normal 3.5V
level, thus limiting the power dissipated by the
s cries regulator.
4-31 CONSTANT VOLTAGE COMPARATOR
4-32 This circuit consists of the programming re-
sistors (A5R121 and A5R122) and a differential am-
plifier stage (Z1 and associated components). An
integrated circuit is used for the differential amplifier to minimize differential voltages due to mismatched transistors and thermal differentials.
4-33 The constant voltage comparator continuously
compares the voltage drop across the VOLTAGE controls with the output voltage and, if a difference
exists, produces an error voltage whose amplitude
is proportional to this difference. The error signal
ultimately alters the conduction of the series regu-
lator which, in turn, alters the output current so
that the output voltage becomes equal to the voltage
drop across the VOLTAGE controls. Hence, through
feedback action, the difference between the two in-
puts to Z1 is held at zero volts.
during rapid down-programming; diodes CR5 and
TM 11-6625-2958-14&P
CR6 prevent excessive voltage excursions from
over-driving the differential amplifier. Capacitor
C2 prevents the gain of the feedback loop from
changing during manipulation of the VOLTAGE controls. Resistor R2 limits the discharge current
through C2. Resistors Z2F, Z2M, and Z2N bias the
differential amplifier; diode CR4 provides temperature compensation.
4-36 During constant voltage operation, the pro-
gramming current flowing through the programming
resistors (VOLTAGE controls) is held constant be-
cause the value of shunt resistor R3 is factory
selected to allow all of the +6.2 volt reference to
be dropped across R3, R4, and RS. Linear constant
voltage programming is thus assured with a constant
current flowing through A5R121 and A5R122. If the
supply is equipped with Option 020, resistor R111
and potentiometer R 112 allow the programming current to be adjusted by varying the bias applied to
the summing point.
4-37 Main output capacitor A3C3 stabilizes the
series regulator feedback loop and helps supply
high-current pulses of short duration during con-
stant voltage pulse loading operation. An additional
output capacitor (C 19), connected directly across
the output bus bars, helps maintain a low ac output
impedance by compensating for the inductive react-
ance of the main output capacitor at high frequencies.
C19 also prevents any spikes in the output from
reaching the load.
4-34 One input of the differential amplifier (pin
10) is connected to the output voltage sensing ter-
minal of the supply (+S) through impedance equaliz-
ing resistor R23. Resistors R1 and optional resistor
R110 are used to zero bias the input. If the supply
is equipped with Option 020, resistor R114 and potentiometer R 113 provide a variable input bias that
allows the output voltage to be adjusted to exactly
zero volts when the supply is programmed for zero
output. The other input of the differential amplifier
(pin 1) is connected to a summing point (terminal
A2) at the junction of the programming resistors and
the current pullout resistors R3, R4, end R5. In-
stantaneous changes in the output voltage or
changes in the voltage at the summing point due to
manipulation of the VOLTAGE controls produce a difference voltage between the two inputs of the differential amplifier. This difference voltage is amplified and appears at the output of the differential
amplifier (pin 12) as an error voltage which ultimately varies the conduction of the series regulator.
4-3 S Resistor R6, in series with the summing-point
input to the differential amplifier, limits the current through the programming resistors during rapid
voltage turn-down. Diode CR7 prevents excessive
current drain from the +6.2 volt reference supply
4-38 CONSTANT CURRENT COMPARATOR
4-39 This circuit is similar in appearance and operation to the constant voltage comparator circuit.
It consists of the coarse and fine current controls
(A5R123 and A5R124) and a differential amplifier
stage (Z 1 and associated components). As in the
constant voltage comparator, an integrated circuit
is used for the differential amplifier to minimize
differential voltages due to mismatched transistors
and thermal differentials.
4-40 The constant current comparator circuit con-
tinuously compares the voltage drop across the
CURRENT controls with the voltage drop across the
current sampling resistor, A4R123. If a difference
exists, the differential amplifier produces an error
signal which is proportional to this difference.
The remaining components in the feedback loop
(mixer amplifier, error amplifiers, and the series
regulator) function to maintain the voltage drop
across the current sampling resistors, and hence
the output current, at a constant value.
4-41 One input of the differential amplifier (pin 7)
is connected to the output bus through impedance
equalizing resistor R20 and is zero-biased by R21
4-5
TM 11-6625-2958-14&P
and optional resistor R 117. The other input of the
differential amplifier (pin 4) is connected to a summing point (terminal A6) at the junction of the programming resistors and the current pullout resistors
R30 and R31. Changes in the output current due to
load changes or changes in the voltage at the summing point due to manipulation of the CURRENT
controls produce a difference voltage between the
two inputs of the differential amplifier. This differ-
ence voltage is amplified and appears at the output
of the differential amplifier (pin 6) as an error voltage which ultimately varies the conduction of the
s cries regulator.
4-46 MIXER AND ERROR AMPLIFIERS
4-47 The mixer and error amplifiers amplify the
error signal from the constant voltage or constant
current input circuit to a level sufficient to drive
the series regulating transistors. Mixer amplifier
Q41 receives the error voltage input from either the
constant voltage or constant current comparator via
the OR-gate diode (CR1 or CR20) that is conducting
at the time. Diode CR1 is forward biased and CR20
reverse biased during constant voltage operation.
The reverse is true during constant current operation.
4-42 Resistor R30 serves as a trimming adjustment
for the programming current flowing through A5R123
and A5R124. If the supply is equipped with Option
021, resistor R115 and potentiometer R116 provide
a means of adjusting the programming current. As
in the constant voltage comparator circuit, a vari-
able input bias (from resistor R118 and potentiometer R119) is provided to allow the output current to
be adjusted to exactly zero when the supply is pro-
grammed for zero output. Diode CR21 limits exces-
sive voltage excursions at the summing-point input
to the differential amplifier.
4-43 VOLTAGE CLAMP CIRCUIT
4-44 The voltage clamp circuit keeps the constant
voltage programming current relatively constant
when the power supply is operating in the constant
current mode. This is accomplished by clamping
terminal A2, the voltage summing point, to a fixed
bias voltage. During constant current operation the
constant voltage programming resistors are a shunt
load acress the out put terminals of the power supply. When the output voltage changes, the current
through these resistors also tends to change. Since
this programming current flows through the current
sampling resistor, it is erroneously interpreted as
a load change by the current comparator circuit.
The clamp circuit eliminates this undesirable effect
by maintaining this programming current at a con-
stant level.
4-45 The voltage divider, Z2A, Z2B, and VR1, back
biases CR2 and Q1 during constant voltage operat ion. When the power supply goes into constant
current operation, CR2 becomes forward biased by
the voltage at pin 12 of Z 1. This results in conduction of Q1 and the clamping of the summing point at
a potential only slightly more negative than the
normal constant voltage potential. Clamping this
voltage at approximately the same potential that
exists in constant voltage operation results in a
constant voltage acress, and consequently a con-
stant current through, the current pullout resistors
R3, R4, and R5.
4-48 Transistor Q40 provides a constant current to
the collector of Q41 and also generates a negative
going turn-off signal for the series regulator when
the unit is first turned off. Feedback network C41,
R47, and R53 shapes the high frequency rolloff in
the loop gain response in order to stabilize the
series regulator feedback loop.
4-49 Error amplifiers Q42 and A4Q101 serve as the
predriver elements for the series regulator. In addition, transistor A4Q101 allows faster down-programming by providing a discharge path for output ca-
pacitors A3C3 and C19, and by supplying a bleed
current for the series regulator (thus keeping it in
its linear, active region) when the supply is set for
zero output current. Diode CR44, in the base cir-
cuit of transistor A4Q101, prevents the base from
going more negative than -3 volts. This action li-
mits the current through R57 to a relatively low
level, thus protecting A4Q101 from damage in the
event a voltage higher than the programmed output
voltage is placed across the output terminals (such
as might occur in Auto-Parallel or battery charging
applications).
4-50 OVERVOLTAGE PROTECTION CROWBAR
4-51 The overvoltage protection circuit protects
delicate loads from high voltage conditions such
as might result from the failure of the series regu-
lator transistor. It accomplishes this by shorting
the output of the supply. Under normal operation
(no overvoltage), Q92 is conducting since CR91 is
reverse biased and Q91 is off. Thus no trigger
signal is received by SCR A4CR110 and it acts as
an open circuit, having no effect on normal output
voltage.
4-52 A5R125 (OVERVOLTAGE ADJUST) adjusts the
bias of Q92 with relation to -S. It establishes the
point at which CR91 becomes forward biased and
Q92 is turned off. Zener diode VR90 provides a
stable reference voltage with which the -S potential
is compared; R95 sets the upper crowbar trip limit.
When Q92 turns off, Q91 begins to conduct, send-
ing a positive going trigger pulse to A4CR110,
causing it to create a near short circuit across the
4-6
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.