HP 6255a schematic

ARMY
NAVY EE010-BJ-MMA-010/E154 DCDUAL
TM 11-6130-416-14
AIR FORCE
TECHNICAL MANUAL
T.O. 35C1-2-847-1
OPERATOR’S, ORGANIZATIONAL,
DIRECT SUPPORT AND GENERAL SUPPORT
FOR
POWER SUPPLY, DUAL DC
(H-P MODEL 6255A)
(NSN 6130-00-065-6811)
DEPARTMENTS OF THE ARMY, NAVY, AND AIR FORCE
31 JANUARY 1983
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
SAFETY STEPS TO FOLLOW IF SOMEONE IS THE VICTIM OF ELECTRICAL SHOCK
DO NOT TRY TO PULL OR GRAB THE lNDl-
VIDUAL
IF POSSIBLE, TURN OFF THE ELECTRICAL
POWER
IF YOU CANNOT TURN OFF THE ELECTRICAL POWER, PULL, PUSH, OR LIFT THE PERSON TO SAFETY USING A WOODEN POLE OR A ROPE OR SOME OTHER INSULATING MATERIAL
SEND FOR HELP AS SOON AS POSSIBLE
AFTER THE INJURED PERSON IS FREE OF CON­TACT WITH THE SOURCE OF ELECTRICAL
SHOCK, MOVE THE PERSON A SHORT
DISTANCE AWAY AND IMMEDIATELY START
ARTIFICIAL RESUSCITATION
TM 11-6130-416-14/EE010-BJ-JMA-010/E154 DCDUAL/T.O. 35C1-2-847-1
INSERT LATEST CHANGED PAGES. DESTROY SUPERSEDED PAGES.
LIST OF EFFECTIVE PAGES
Dates of issue for original and changed pages are:
Original . . 0 . .
TOTAL NUMBER OF PAGES IN THIS PUBLICATION IS
Page
No.
Title. . . . . . . . . .
A. . . . . . . . . . . .
i
- vii. . . . . . . . .
viii Blank. . . . . . . .
1-1 - 1-4. . . . . . . .
2-1 - 2-2. . . . . . . .
3-1 - 3-8
4-1 - 4-6..............
5-1 - 5-23 . . . . . . . .
5-24 - Blank . . . . . . . .
A-1 . . . . . . . . . . .
A-2 Blank. . . . . . . .
B-1
- B-4 . . . . . . . .
C-1
- C-2. . . . . . . .
D-1 . . . . . . . . . . .
D-2 Blank. . . . . . . .
E-1 . . . . . . . . . . .
E-2 Blank.... . . . .
Index-1
Report of Errors. . . . .
FO-l
- Index-10. . . .
- FO-2 . . . . . . .
# Change
No. No.
0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
Page
83 CONSISTING OF THE FOLLOWING:
# Change
No.
Page
No.
# Change
No.
# Zero in this column indicates an original page.
A
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35Cl-2-847-1

WARNING

DANGEROUS VOLTAGE
Is Used in the Operation of this Equipment
DEATH ON CONTACT
may result if personnel fail to observe safety precautions
Never work on electronic equipment unless there is another person
nearby who is familiar with the operation and hazards of the equipment and who is competent in administering first aid. is aided by operators, he must warn them about dangerous areas.
When the technician
Whenever possible, the power supply to the equipment must be shut off
before beginning work on the equipment. Take particular care to ground every capacitor likely to hold a dangerous potential. When
working inside the equipment, after the power has been turned off,
always ground every part before touching it.
Be careful not to contact high-voltage connections when installing or operating this equipment.
Whenever the nature of the operation permits, keep one hand away from
the equipment to reduce the hazard of current flowing through vital organs of the body.
Do not be misled by the term “low voltage.” Potentials as low as 50
volts may cause death under adverse conditions.
B
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.0.35Cl-2-847-1
Do not touch heat sinks or power transistors mounted on
heat sinks as they may be very hot after the instrument
has been on and operating.
CAUTION
Do not directly short out any of the large capacitors as
it places too much stress on them. Discharge capacitors
through a load resistor.
C/(D blank)
This manual contains copyright material reproduced by permission of the Hewlett-Packard Company.
TM 11-6130-416-14
EE010-BJ-MMA-010/E154 DCDUAL
T.O.35C1-2-847-1
TECHNICAL MANUAL NO. 11-6130-416-14 TECHNICAL MANUAL EEO10-BJ-MMA-010/E154 DCDUAL TECHNICAL ORDER NO. 35CI-2-847-I
OPERATOR’S, ORGANIZATIONAL, DIRECT SUPPORT, AND GENERAL SUPPORT
REPORTING ERRORS AND RECOMMENDING IMPROVEMENTS
DEPARTMENTS OF THE ARMY,
THE NAVY,
AND THE AIR FORCE
Washington, DC, 31 January 1983
MAINTENANCE MANUAL
FOR
POWER SUPPLY, DUAL DC
(H-P Model 6255A)
(NSN 6130-00-065-6811)
You can help improve this manual.
If you find any mistakes or if you know of a way to improve the procedures, please let us know. Publications and Blank of
Communications-Electronics Command and Fort Monmouth, DRSEL-ME-MP, Fort Monmouth,
Mail your letter, DA Form 2028 (Recommended Changes to
this
manual
Forms),
direct to:
or DA Form 2028-2 located in back
Commander, US
Army
ATTN:
NJ 07703.
For Air Force, submit AFTO Form 22 (Technical Order System Publication Improvement Report and Reply) in accordance with paragraph 6-5, Section VI, T.O. 00-5-1. Forward direct to prime ALC/MST.
For Navy, mail comments to the Commander, Naval Electronics Systems Command, ATTN:
ELEX 8122, Washington, DC 20360.
In either case, a reply will be furnished direct to you.
This manual is an authentication of the manufacturer’s commercial literature which,
through usage, has been found to cover the data required to operate and maintain this equipment. specifications and AR
Since the manual was not prepared in accordance with military
310-3,
the format has not been structured to consider levels
of maintenance.
i
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O35C1-2-847-1

TABLE OF CONTENTS

Section
I
GENERAL INFORMATION . . . . . . . . . . . .1-1
1-A.1 1-A.3
1-A.4 1-A.6
1-A.8
Page No.
Scope
1-1
Index of Publications 1-1 Army Air Force Maintenance Forms,
1-1 1-1 1-1
Section
3-3 3-5 3-7 3-9 3-11 3-14
Operating Modes Normal Operating Mode Constant Voltage Constant Current Connecting Load Operation of Supply
Records and Reports
1-A.9
Reports of Maintenance
3-16
Optional Operational
and Unsatisfactory
1-A.11
1-A.13
1-A.15
Equipment
1-1
Report of Packaging
and Handling
Deficiencies
1-1
Discrepancy in Shipment
Report (DISREP)
(SF 361)
1-1
Reporting Equipment
3-17
3-24
3-30 3-35
3-39 3-42
Remote Programming,
Remote Programming
Parallel Operation Auto-Tracking
Improvement
1-1 1-1
1-1
1-2 1-2 1-2 1-3
1-3
1-3
3-45
3-46 3-48 3-51 3-53
3-55
IV PRINCIPLES OF OPERATION . . . . . . . ...4-1
4-1
4-5 4-8 4-9
1-A.18 l-A.20
1-A.22
1-A.24
1-1 1-6 1-8 1-10
1-13
Recommendations (EIR)
Air Force Navy Administrative
Storage
Destruction Of Army
Electronics Materiel
Description
Specifications
Options
Instrument Identifica-
tion
Ordering Additional
Manuals
4-14
II
INSTALLATION 2-1 2-3 2-5 2-7 2-9
Initial Inspection
Mechanical Check
Electrical Check Installation Data
Location
2-11 Rack Mounting 2-13 Input Power Requirements 2-1 2-15 Connections for 230 Volt
Operation 2-17 Power Cable 2-20 Repackaging for Shipment 2-2
. . . . . . . . . . . . . . . . . . .2-1
4-16 2-1 2-1
4-20
2-1 2-1
2-1
4-25 4-28
2-1
4-31
4-34
2-1 2-2
V MAINTENANCE . . . . . . . . . . . . . . . . . . . . .5-1
5-1
5-3
III OPERATING INSTRUCTIONS . . . . . . . . . . .3-1
3-1
Operating Controls and
Indicators
3-1
5-8
Page No.
3-1 3-1 3-1 3-2
3-2
Beyond Rated Output
Modes
Constant Voltage
Constant Current Remote Sensing Series Operation
3-2
3-2
3-2
3-3 3-4 3-4 3-5
Operation
3-6 Special Operating Consid­erations Pulse Loading
Output Capacitance Reverse Voltage Loading Reverse Current Loading
3-6
3-6
3-6
3-7
3-7 Overvoltage Protection
Crowbar
3-7
Overall Block Diagram
Discussion 4-1
Simplified Schematic
4-2
Detailed Circuit Analysis 4-3
Feedback Loop
Series Regulator
4-3
4-3 Constant Voltage Input
Circuit
4-3 Constant Current Input
Circuit 4-4
Voltage Clamp Circuit
4-4
Mixer and Error
Amplifiers Reference Circuit Meter Circuit
Introduction
4-4 4-5 4-5
5-1
General Measurement
Techniques
5-1
Test Equipment
Required
5-2
ii
TM 11-6130-416-14/EE010-BJ-NMA-010/E154 DCDUAL/T.O.35Cl-2-847-1
TABLE OF CONTENTS (CONTINUED)
Section
5-10 5-12
5-34
5-39
5-41
5-46
5-47A.1
5-47A.3 5-47A.5
5-47A.7
5-47A.9
5-47A.11
5-47A.13
5-47A.15
5-47A.17
5-47A.19
5-47A.21
5-47A.23
5-47A.25
5-47A.27
Page No.
Performance Test Constant Voltage
Tests
Constant Current
(CC) Tests
Troubleshooting Trouble Analysis Repair and Replace-
ment Fuse Replacement Cover Removal
Power Cable
Replacement
Switch S1
Replacement
Transformer T1
Replacement
Overvoltage
Protection Crowbar
P.C. Board Replace-
ment
Main Left P.C.
Board Replacement
(Viewed from Front
of Power Supply)
Main Right P.C.
Board Replacement
(Viewed from Front
of Power Supply)
Capacitator C14
Replacement
Capacitors C5, C6
Replacement
Power Transistor Q4,
Q6, Replacement
Power Transistor Q7,
Replacement
Transistor Q3
Replacement
Voltage/Current
Programming Control Replacement
5-2
5-2
5-8
5-9
5-9
5-14
5-15 5-15
5-17
5-17
5-17
5-18
5-18
5-18
5-19
5-19
5-19
5-20
5-20
5-20
Section
Page No.
5-47A.29 Silicon Rectifier
CR19 Replacement
5-47A.31
Meter Switch S2
Replacement
5-47A.33 Meter Replacement
5-20
5-21 5-21
5-47A.35 Shunt Resistor
(R81, R82, or R83)
Replacement
5-21
5-47A.37 Fuse Holder Assembly
Replacement
5-21
5-47A.39 Neon Lamp DS1
Replacement
5-21
5-47A.41 Crowbar Adjust
Potentiometer R5 Replacement
5-22
5-48 Adjustment and
Calibration
5-50 Meter Zero.
5-52 Voltmeter Tracking
5-54 Ammeter Tracking
5-22
5-22
5-22 5-22
5-56 Constant Voltage
Programming Current
5-22
5-59 Constant Current
Programming Current
5-23
5-62 Reference Circuit
Adjustments
5-23
5-64 Constant Voltage
Transient Response
5-23
VI REPLACEABLE PARTS . . . . . . . . . . . . . . .6-1
6-1 6-4
Introduction Ordering Information
6-1 6-1
APPENDIX A . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
APPENDIX B . . . . . . . . . . . . . . . . . . . . . . . . B-1
APPENDIX C . . . . . . . . . . . . . . . . . . . . . . . . C-1
APPENDIX D . . . . . . . . . . . . . . . . . . . . . . . D-1
APPENDIX E . . . . . . . . . . . . . . . . . . . . . . . E-1
INDEX
Index 1
iii
Figure
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
LIST OF ILLUSTRATIONS
Page No.
Figure
Page No.
1-1
2-1 3-1
3-2 3-3
3-4
3-5
3-6
3-7 3-8
3-9
3-10
3-11
3-12
3-13
4-1
4-2
DC Power Supply Primary Connections
Front Panel Control and
Indicators Normal Strapping Pattern Remote Resistance
Programming(Constant
Voltage)
Remote Voltage
Programming (Constant
Voltage) Remote Resistance
Programming (Constant Current)
Remote Voltage
Programming (Constant
Current) Remote Sensing Normal Series Connec­tions Auto-Series, Two and
Three Units
Normal Parallel ,
Connections
Auto-Parallel, Two and
Three Units
Auto-Tracking, Two and
Three Units
Model 6255A and 6289A
Overvoltage Protection
Crowbar Overall Block Diagram Simplified Schematic
v
2-1
3-1 3-1
3-2
3-3
3-3
3-3 3-4
3-4
3-5
3-5
3-5
3-6
3-8
4-1 4-2
4-3
4-4
5-1
5-2
5-3
5-4
5-5
5-6
5-7 5-8
5-9
5-10
5-11
5-12
5-13
5-14
FO-1 FO-2
Voltmeter Connections,
Simplified Schematic
Ammeter Connections,
Simplified Schematic
Front Panel Terminal
Connections
Output Current
Measurement Technique
Differential Voltmeter Substitute Test Setup Output Current, Test
Setup
Load Regulation, Constant
Voltage Test Setup
CV Ripple and Noise Test
Setup CV Noise Spike Test Setup 5-6 Transient Response Test Setup Transient Response,
Waveforms
CV Programming, Speed,
Test Setup Output Impedance,
Test Setup CC Ripple and Noise Test
Setup Servicing Printed Wiring
Boards
Model 6255A Modular
Cabinet
6255A Schematic
Parts Location/Intercon-
nection Diagram
4-5
4-5
5-1
5-1
5-2
5-2
5-4
5-4
5-6
5-6
5-7
5-7
5-8
5-13
5-16
Table
5-1 5-2
5-4
5-5
iv
1-1
5-3
LIST OF TABLES
Page No.
Specifications Test Equipment Required 5-3
Common Troubles
Reference, Bias, and
Filtered DC Troubleshooting
Low Output Voltage
Troubleshooting
High Output Voltage
Troubleshooting
1-4
5-9
5-11
5-11
5-12
Table
5-6
5-7
5-8
Selected Semiconductor
Characteristics
Checks and Adjustments
After Replacement of Semiconductor Devices
Calibration and
Adjustment Summary
Page No.
5-14
5-14
5-15
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.0.35C1-2-847-1
Figure 1-1.
Typical DPR Series DC Power Supply
v/(vi blank)
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.0.35C1-2-847-1

SECTION I

GENERAL INFORMATION
1-A.1
1-A.2
6255A Dual DC Power Supply with Option
11 Overvoltage Protection Crowbar Cir­cuit (power supply serial numbers 2012A-4996 and up). Responsibilities for all levels of maintenance are spec­ified by the Maintenance Allocation Chart (MAC) contained in
1-A.3
1-A.4
1-A.5
PAM 310-1 to determine whether there
are new editions, changes or additional publications pertaining to the equip-
ment.
1-A.6
1-A.7
cal Index and Requirements Table
(NIRT).
1-A.8
REPORTS
1-A.9
UNSATISFACTORY EQUIPMENT
1-A.10
and procedures used for equipment main-
tenance will be those prescribed by
38-750,
System (Army).
will use AFM 66-1 for maintenance re-
porting and T.O. 00-35D54 for unsatis-
factory equipment reporting. Navy per­sonnel will report maintenance per­formed utilizing the Maintenance Data
Collection Subsystem (MDCS) IAW
OPNAVINST 4790.2, Vol 3, and unsatis-
factory material/conditions (UR submissions) IAW OPNAVINST 4790.2, Vol 2,
chapter 17.
SCOPE
This manual describes the Model
Appendix B.
INDEX OF PUBLICATIONS
ARMY
Refer to the latest issue of DA
AIR
FORCE
Use T.O. 0.1-31 Series Numeri-
MAINTENANCE FORMS, RECORDS AND
REPORTS
Department of the Army forms
The Army Maintenance Management
OF
MAINTENANCE AND
Air
Force personnel
TM
1-A.12
(Report of Discrepancy (ROD) as pre-
scribed in AR 735-11-2/DLAR 4140.55/
NAVMATINST 4355.73/AFR 400-54/MCO
4430.3E.
1-A.13
(DISREP) (SF
1-A.14
ancy in Shipment Report (DISREP) (SF
361) as prescribed in AR 55-38/
NAVSUPINST 4610.33B/AFR 75-18/MCO
P4610.19C/DLAR 4500.15.1-4.
1-A.15
IMPROVEMENT RECOMMENDATIONS) (EIR)
1-A.16
1-A.17
needs improvement, let us know. us an EIR. only one who can tell us what is not
liked about your equipment. Let us know why you do not like the design.
Tell us why a procedure is hard to per-
form.
Deficiency Report).
der, US Army Communications-Electronics Command and Fort Monmouth, ATTN:
DRSEL-ME-MP, Fort Monmouth, We will send you a
1-A.18
1-A.19
encouraged to submit EIRs in accordance
with AFM 900-4.
1-A.20
1-A.21
to submit EIRs through their local Beneficial Suggestion Program.
1-A.22
Fill out and forward SD 364
DISCREPANCY IN SHIPMENT REPORT
361)
Fill out and forward Discrep-
REPORTING EQUIPMENT
ARMY
If the Power Supply, Dual DC
Send
You, the user, are the
Put it on an SF 368 (Quality
Mail it to Comman-
NJ
07003.
reply
AIR FORCE
Air Force personnel are
NAVY
Navy personnel are encouraged
ADMINISTRATIVE STORAGE
1-A.11
HANDLING
REPORT OF PACKAGING AND DEFICIENCIES
1-1
1-A.23
Refer to
TM 11-5805-683-12
or
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
TM 11-5805-681-12,
Administrative storage of equip-
age. ment issued to and used by Army activi-
ties will have preventive maintenance
performed in accordance with the Pre-
ventive Maintenance Checks and Services
(PMCS) procedure listed before storing.
When removing the equipment from admin­istrative storage,the PMCS should be performed to assure operational readi-
ness.
equipment for shipment or limited stor-
age are also covered.
90-1 if
charts.
1-A.24
ELETRONICS
1-A.25
ics materiel to prevent enemy use shall
be in accordance with
Disassembly and repacking of
there are no published PM
DESTRUCTION OF ARMY
MATERIEL
Destruction of Army electron-
Administrative Stor-
Refer to
TM 750-244-2.
TM 749-
1-3
Each supply has both Either the positive or negative output terminal may be grounded or the power supply can be operated floating
at up to a
1-4
and operating controls. tiple range type and can measure output voltage or current. The voltage or current by the applicable METER switch
1-5 TWO
the rear of the unit allow ease in adapting to the many operational capabilities of the power supply. A below:
from a remote location by means of an external
voltage source or resistance.
Each section has its own front panel meter
sets of programming terminals located at
brief description
a.
Remote The power supply maybe programmed
b. Remote Sensing
front
maximum
Programming
and rear
of
300 volts off
The meters are of the mul-
ranges
on
of these capabilities
terminals.
are selected
the front panel.
ground.
is
given
1-1
DESCRIPTION
1-2
completely transistorized and suitable
for either rack or bench operation. It is a dual supply consisting of two inde­pendently controlled sections; both identical to each other.
will be referred to as the left and right side power supplies as viewed from front of unit. regulated,Constant Voltage/Constant Current source that will furnish full rated output rated output current or can be continu­ously adjusted throughout either output
range. can be used to establish the output cur-
rent limit when the supply is used as a constant voltage source and the VOLTAGE con­trol(s) voltage limit is used as a constant current source. Each section will automatically cross­over from constant voltage to constant
current operation and vice versa if the output current or voltage exceeds these preset limits.
This power supply,
Each section is a well-
voltage at
The front panel CURRENT controls
(overload or
can be
used to establish the
(ceiling) when
Figure 1-1,
These sections
the maximum
short circuit)
the supply
is
The degradation in regulation which would occur in
the
supply in the remote sensing mode of operation.
c.
when a higher output voltage is required in the voltage mode of operation or compliance
of operation. Auto-Series operation permits one knob control of the total output voltage
“master"
parallel rent capability permits one knob control from
“master” supply, having control “slave” supplies that furnish various voltages for
a system.
1-6 1-7
supply.
d. Parallel and Auto-Parallel Operation
a
e.
SPECIFICATIONS
Detailed specifications
at the
load leads can be reduced by using the power
Series and Auto-Series Operation
Power supplies maybe used in series
is
required in
The power supply may be operated
with a
is
required. Auto-Parallel
“master” supply. Auto-Tracking The power supply maybe used
load because of the voltage drop
when
the
similar unit when greater output cur-
of
the total output current
for
greater voltage
constant current mode
from a
in
operation
as
over
one (or more)
the power supply
a
1-2
TM 11-6130-416-14/EE010-BJ-MM-010/E154 DCDUAL/T.O.35C1-2-847-1
are given in
1-8
1-9
ard instrument that are requested by the customer. The following options are available for the instru-
ment covered by this manual. Where necessary,
detailed coverage of the options is included through-
out the manual. Option No.
Table 1-1.
NOTE Since both sections of this supply are identical, only one section will be discussed throughout the remain-
ing portions of this manual. All descriptions, illustrations, and adjustments apply equally to both sections of the supply.
OPTIONS
Options are factory modifications
Description
07
Voltage 10-Turn Pot: A single con­trol that replaces both coarse and fine voltage controls and improves output
settability. 6258A power supplies.
Standard item on Model
tests,
of a
stand-
Trip Voltage Margin: The minimum crowbar trip setting above the desired operating output voltage to false crowbar tripping is 4% of the output voltage setting +2V.
Refer to of operation and schematic diagram.
13
14 Three Digit Graduated Decadial Cur-
28
Paragraph 3-55
Figure 3-13
Three Digit Graduated Decadial Volt-
age Control: Control that replaces
coarse and fine voltage controls per­mitting accurate resettability.
rent Control: Control that replaces coarse and fine current controls per­mitting accurate resettability.
Rewire for 230V AC Input: Supply as normally shipped is wired for 115VAC input. Option 28 consists of recon­necting the input transformer for 230V AC operation.
prevent
for details
for the
08
09
10
11
Current 10-Turn Pot: A single con­trol that replaces both coarse and fine current controls and improves out put
settability.
Voltage and Current 10-Turn Pot: Consists of Options 07 and 08 on the
same instrument.
Chassis Slides: Enables convenient access to power supply interior for maintenance purposes.
Internal Overvoltage Protection “Crowbars”: This option includes two crowbar circuits, one for each power supply within the 6253A or or 6255A. Each crowbar protects
delicate loads by monitoring the out­put voltage and firing an SCR that shorts the output when the preset trip voltage is exceeded. The circuit boards are factory installed within the supply. The “Crowbar Adjust”
controls are mounted on the front
panel to permit convenient adjust-
ment.
Trip Voltage Range:
6253A
2.5 to 23V 2.5 to 44V
6255A
1-10
1-11
by a three-part serial number tag. The first part is the power supply model number. The second part is the serial number prefix, which consists of a num­ber-letter combination that denotes the date of a
significant design change. The number designates
the year, and the letter A through L designates the
month, January through December, respective y. The
third part is the power supply serial number.
1-12 If
ply does not agree with the prefix on the title page
of this manual, change sheets are included to up-
date the manual.
information is given in an appendix at the rear of
the manual.
power supply.
INSTRUMENT IDENTIFICATION Hewlett-Packard power supplies are identified
the serial number prefix on your power sup-
Where applicable, backdating
1-13
be obtained from regular publication distribution channels.
ORDERING ADDITIONAL MANUALS
1-14
One manual is shipped with each
Additional manuals may
1-3
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.0035C1-2-847-1
Table 1-1. Specifications
INPUT:
105-125/210-250
50-400
OUTPUT:
Two independent outputs each of which can
be set at 0-40 volts @ 0-1.5 amps.
LOAD REGULATION:
Constant Voltage
2mv for a full load to no load change in output
current.
Constant Current
250µa for a zero to maximum change in output
voltage.
LINE REGULATION:
Constant Voltage 2mv for any line voltage change within the input rating.
Constant Current -­250µa for any line voltage change within the in­put rating.
RIPPLE AND NOISE:
Constant Voltage
Constant Current --
cps.
VAC, single phase,
-- Less than 0.01% plus
-- Less than 0.01% plus
-- Less than 0.01% plus
Less than 0.01% plus
-- Less than 200µv rms. Less than 500µa rms.
OVERLOAD PROTECTION:
A continuously acting constant current circuit protects the power supply for all overloads in­cluding a direct short placed across the termi­nals in constant voltage operation. The constant voltage circuit limits the output voltage in the constant current mode of operation.
METERS:
Each front panel meter can be used as either a 0-50V or 0-5 volt voltmeter or as a 0-1.8A or 0-0.18 amp ammeter.
OUTPUT CONTROLS:
Coarse and fine voltage controls and coarse and fine current controls set desired output volt­age or current.
OUTPUT TERMINALS:
Six output posts (three per section) are provided on the front panel and output terminal strips are located on the rear of the chassis. All power supply output terminals are isolated from the chassis and either the positive or negative terminals may be connected to the chassis through a separate ground terminal located on the output terminal strip.
TEMPERATURE RANGES:
Operating:
TEMPERATURE COEFFICIENT:
Constant Voltage
500µv per degree Centigrade.
Constant Current
0.8ma per degree Centigrade.
STABILITY:
Constant Voltage
2.5mv total drift for 8 hours after an initial warm­up time of 30 minutes at constant ambient, con­stant line voltage, and constant load.
Constant Current -­4ma total drift for 8 hours after an initial warm-up time of 30 minutes at constant ambient, constant line voltage, and constant load.
OUTPUT
Approximated by a
resistance in series with a
microhenry inductance.
TRANSIENT RECOVERY TIME:
Less than 50µsec 15 mv following a full load current change in the
output.
0 to
50°C.
Storage: -20 to +85°C.
-- Less than 0.02% plus
-- Less than 0.02% plus
-- Less than 0.10% plus
Less than 0.10% plus
IMPEDANCE
for output recovery to within
10
(TYPICAL):
milliohm
1
ERROR SENSING:
Error sensing is normally accomplished at the front terminals if the load is attached to the front or at the rear terminals if the load is attached to the rear terminals. on the rear terminal strip for remote sensing.
REMOTE PROGRAMMING:
Remote programming of the supply output at ap-
proximately 200 ohms per volt is made available at the rear terminals. In con-
stant current mode of operation, the current can be remotely programmed at approximately 500 ohms per ampere.
COOLING:
Convection cooling is employed. The supply
has no moving parts.
SIZE:
3- 1/2" H x 14- 1/2"
mounted in a standard 19” relay rack.
WEIGHT:
28 lbs. net, 35 lbs. shipping.
FINISH:
Light gray front panel with dark gray case.
POWER CORD:
A three-wire, five-foot power cord is provided
with each unit.
Also, provision is included
in
constant voltage
D x
19” W. Easily rack
1-4
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1

SECTION II

INSTALLATION
2-1
INITIAL INSPECTION
2-2
Before shipment, this instrument was inspec­ted and found to be free of mechanical and electri­cal defects. As soon as the instrument is un-
packed, inspect for any damage that may have oc-
curred in transit. Save all packing materials until
the inspection is completed.
2-3
MECHANICAL CHECK
2-4
This check should confirm that there are no
broken knobs or connectors, that the cabinet and
panel surfaces are free of dents and scratches,
and that the meter is not scratched or cracked.
either power tory, is wired for 115 volt operation. The input power required when operated from a 115 volt 60
cycle power source at full load is 235 watts and
2.6 amperes.
2-15
a nominal 115 volt or 230 volt 50-400 cycle source. The unit, as shipped from the fac-
CONNECTIONS FOR 230 VOLT OPERATION
(Figure 2-1)
2-5
ELECTRICAL CHECK
2-6
The instrument should be
electrical
“in-cabinet” performance check to verify proper instrument operation.
2-7 2-8
operation. It is necessary only to connect the
instrument to a source of power and it is ready for
operation.
2-9 2-10
space should be allotted so that a free flow of cooling air can reach the sides and rear of the instrument when it is in operation. It should be used in an area where the ambient temperature does not exceed 50°C.
2-11 2-12
easily rack mounted in a conventional 19 inch rack panel using standard mounting screws.
2-13 2-14
specifications.
INSTALLATION DATA
The instrument is shipped ready for bench
LOCATION
This instrument is air cooled. Sufficient
RACK MOUNTING
This instrument is full rack size and can be
INPUT POWER REQUIREMENTS
This power supply may be operated from
checked
Section V includes an
against its
Figure 2-1.
2-16
put transformer are connected in parallel for opera­tion from 115 volt source. To convert the power
power transformer windings are connected in series as follows:
Normally, the two primary windings of the in-
supply to operation from a 230 volt source, the
Primary Connections
2-1
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
a.
Unplug the line cord and remove the
unit covers.
b.
Break the copper between 54 and 55 and also between 50 and 51 on the printed circuit board. These are shown in
Figure 2-1,
and are
labeled on copper side of printed circuit board.
c.
Add strap between 50 and 55.
d.
Replace existing fuse with 2 ampere, 230 volt fuse. Return unit to case and operate
cable three-prong connector is the ground connec­tion.
2-19 To
operating the instrument from a two-contact outlet,
use a three-prong to two-prong adapter and con­nect the green lead on the adapter to ground.
2-20
REPACKAGING FOR SHIPMENT
normally.
2-21 To
2-17
POWER CABLE
it is recommended that the package designed for the instrument be used. The original packaging
2-18 To
protect
operating
personnel,the
National
material is reusable.
Electrical Manufacturers Association(NEMA)rec­ommends that the instrument panel and cabinet be grounded.
This instrument is equipped with a
three conductor power cable. The third conductor
is the ground conductor and when the cable is plugged into an appropriate receptacle, the in­strument is grounded. The offset pin on the power
preserve the protection feature when
insure safe shipment of the instrument,
2-2
TM ll-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
OPERATING INSTRUCTIONS
3-1
OPERATING CONTROLS
3-2
The front panel controls and indicators, to­gether with the normal turn-on sequence, are shown in
Figure 3-1.
AND
INDICATORS

SECTION III

graphs describe the procedures for uti-
lizing the various operational capabil­ities of the power supply. oretical description concerning the op­erational features of this supply is contained in Application Note 90, DC
Power Supply Handbook.
3-5
NORMAL
3-6
The power supply rear terminal strapping connections arranged for Constant local programming, single unit mode of operation.
This strapping pattern The operator selects either constant current output using the front panel con­trols (local programming, no strapping changes are necessary).
OPERATING MODE
is
normally shipped with
Voltage/Constant
is
illustrated
a
constant voltage or
A more the-
its
Current,
local sensing,
in Figure 3-2.
a
Figure 3-1.
3-3
3-4
that its mode of operation can be se-
lected by making strapping connections
between particular terminals on the terminal strip at the rear of the power
supply. The terminal designations are stenciled in white on the power supply above their respective terminals.
Although the strapping patterns illus-
trated in this section show the posi­tive terminal grounded, the operator
can ground either terminal or operate the power supply up to 300vdc off ground(floating).
OPERATING MODES
The power supply is designed so
Dangerous voltages exist in this equipment. when working with the power supplies and their circuits.
Front Panel Controls and Indicators
Be careful
The following
para-
Figure 3-2.
3-7
for
3-8
as follows: controls for desired output voltage (output terminals
open).
RENT controls for maximum output current allowable
(current
If a load change causes the current limit to be ex­ceeded, the power supply will automatically cross­over to constant current output at the preset current limit and the output voltage will drop proportionate­ly.
made for high peak current which can cause un-
wanted cross-over.
CONSTANT VOLTAGE (See
controls and indicators.)
To select a constant voltage output, proceed a. Turn-on power supply and adjust VOLTAGE
b. Short output terminals and adjust CUR-
limit),
as
In setting the current limit, allowance must be
Normal Strapping Pattern

Figure 3-1

determined by
(Refer to
Paragraph 3-46.)
load conditions.
3-1
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.351-2-847-1
3-9
for controls and indicators.)
3-10
as follows: RENT controls for desired output current. controls for maximum output voltage allowable (volt-
age limit), as determined by load conditions. If a load change causes the voltage limit to be exceeded,
the power supply will automatically constant voltage output at the preset voltage limit and the output current will drop proportionately.
setting the voltage limit, allowance must be made for high peak voltages which can cause unwanted crossover.
3-11
for output terminals.)
3-12
supply output terminals using separate pairs of con­necting wires. This will minimize mutual coupling effects between loads and will retain full advantage of the low output impedance of the power supply.
Each pair of connecting wires should be as short as
possible and twisted or shielded to reduce noise pickup. (If shield is used, connect one end to power supply ground terminal and leave the other
end unconnected.)
CONSTANT CURRENT (See
To select a
a. Short output terminals and adjust CUR-
b. Open output terminals and adjust VOLTAGE
(Refer to
CONNECTING LOAD (See
Each load should be connected to the power
constant
Paragraph 3-46.)
Figure 3-1
current output, proceed
y
crossover to
Figure 3-1
In
source can be used for the programming device. The wires connecting the programming terminals of the supply to the remote programming device should be twisted or shielded to reduce noise pick-up. The VOLTAGE controls on the front panel are dis­abled according to the following procedures.
3-19
Resistance Programming mode, the output voltage will vary at a rate deter­mined by the programming coefficient (200 ohms per Volt for Models 6253A, 6255A, 6281A, 6284A, and
6289A or 300 ohms per Volt for Models 6294A and 6299A). The output voltage will increase 1 Volt for each 200 ohms (or 300 ohms) added in series with the programming terminals. The programming coeffi­cient is determined by the programming current. This current is factory adjusted
Models 6253A, 6255A, 6281A, 6284A, and 6289A or
2% of 3.3mA for Models 6294A and 6299A. If greater programming accuracy by changing resistor-R 13.
is
(Figure 3-3). In
to
within 2% of 5mA for
required, it maybe achieved
this
3-13 If
power distribution
from the power supply, then the power supply out-
put terminals should be connected to the remote distribution shielded wires and each load separately connected to the remote distribution
remote sensing should be used
3-14
3-15
indicates the amount of output voltage or current that is available in excess of the normal rated out­put. Although the supply can be operated in this
shaded region without being damaged, it cannot be guaranteed to meet all of its performance specif­ications. tained above 115 Vac, the supply will probably op­erate
3-16
3-17
3-18
ply can be programmed (controlled) location if required. Either a resistance or voltage
load considerations
terminals be remotely located
terminals via a pair of twisted or
OPERATION OF SUPPLY BEYOND RATED OUTPUT
The shaded area on
However, if the line voltage is main-
within its specifications.
OPTIONAL OPERATING REMOTE PROGRAMMING, CONSTANT VOLTAGE The constant voltage output of the power sup-
require that the output
terminals. For this case,
(Paragraph 3-20).
the
front panel meter face
MODES
from
a
remote
Figure 3-3.
3-20
The output voltage of the power supply should be zero Volts ±2O millivolts when zero ohms is con­netted acress the programming terminals. If a zero ohm voltage closer than this is required, it may be achieved by changing resistor R6 or R8 as described in
Paragraph 5-59.
3-21 To
efficient of the power supply, use programming resistors that have stable, low noise, and low temperature (less than 30 ppm per degree Centi­grade)characteristics. conjunction to obtain discrete output voltages. The switch should have make-before-break momentarily opening the programming terminals during the switching interval.
3-22
Voltage Programming
the strapping pattern shown on
Remote Resistance Programming
(Constant Voltage)
maintain the stability and temperature co-
A switch can be used in
with various resistance
(Figure 3-4). Employ
values in
contacts to avoid
Figure 3-4
for
order
3-2
‘m 11-6130-416-14/EEOI O-BJ-M.MA-0113/E154 DCDUAL/T.0.35Cl -2-847-l
3-27 Use stable, low noise, low temperature coef­ficient (less than 3 to maintain the power supply temperature coefficient
and stability specifications. A switch may be used to set discrete values of output current. before-break type of switch should be used since the output current will exceed the maximum rating of the power supply if the switch contacts open during the switching interval.
Oppm/oC) programming resistors
A
make-
Figure 3-4.
Remote Voltage Programming
(Constant Voltage)
voltage programming. In this mode, the output
volt-
age will vary in a 1 to 1 ratio with the programming voltage (reference voltage) and the load on the pro­gramming voltage source will not exceed
25mA.
3-23 The impedance matching resistor (Rx) for the programming voltage source should be approximately 500 ohms to maintain the temperature and stability
SUPP1
specifications of the power
REMOl’E
3-24
CURRENl! (Ses
PROGRAMMING, CONSTANT
Figure 3-1 for controls and
y.
indicators. )
3-25 Either a resistance or a voltage source can be used to control the constant current output of the
supply. The CURRENT controls on the front panel
are disabled according to the following procedures.
3-26 Resistance Programming (Figure 3-5). In this
outpdt
mode, the by the programming coefficient — 200 ohms per Amp for Model 628
6253A, 6255A, 6284A,
Ampere for Models ming coefficient is determined by the Constant Cur-
rent programming current
6255A, 6284A,
for Model current is adjusted to within 10% at the factory. If greater programming accuracy is required, it maybe
a thieved by changing resistor R 19 as outlined in
Section V.
current varies at a rate determined
1A,
500 ohms per Ampere for Models
and
6289A,
and 1000 ohms per
6294A
and
6299A.
The program-
(2mA
for Models
and
6294A
6289A, 5mA
and
1.33mA
for Model’
for Model
6253A,
6281A lmA
6299A).
This
If the programming terminals
should open at any time during this mode, the output current will rise to a value that may damage the power sup­ply and/or the load. To avoid this possibility, connect a resistor across the programming terminals having the value listed below. Like the program­ming resistor, this resistor should be of the low noise, low temperature coef­ficient type.
Model
Resistance
Model
Resistance
3-28 Voltage Programming (Figure 3-6). In this
mode, the output current will vary linearly with changes in the programming voltage. The program­ming voltage should not exceed 1.2 Volts. Voltage in excess of 1.2 Volts will result in excessive power
dissipation in the instrument and possible damage.
Al A2 A3 A4 AS A6 A? A8 A9 -S – GNO + +S
6253
A,6284A 6255
1.
5Kn
6281A, 6294A
lKA
(Al and AS)
A,6289A,6299A
750n
AIO
AI A2A3A4A5A6A7A8A9
OlOlOIQ1~lQ1
u
-----
1
-----
PROGRAMMING
RESISTOR
Figure 3-5.
b
Remote Resistance Programming
(Constant Current)
VOLTAGE
-S-
GM++ SAIO
u
1%’lddq@..j&l
y
3-3
Figure 3-6.
3-29 The output current will be the programming voltage divided by 1 ohm. The current required
from the voltage source will be ampere. The impedance matching resistor (Rx)
should be approximately 500 ohms if the temperature coefficient and stability specifications of the power supply are to be maintained.
Remote Volta ge Programming
(Constant Current)
less
than 25
micro-
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
3-30 REMOTE SENSING (See Figure 3-7) 3-31 Remote sensing is used to maintain good regu-
lation at the load and reduce the degradation of reg­ulation which would occur due to the voltage drop
in the leads between the power supply and the load.
Remote sensing is accomplished by utilizing the strapping pattern shown in Figure 3-7. The pwer supply should be turned off before changing strap-
ping patterns. The leads from the +S terminals to
the load will carry less than 10mA of current, and
it is not required that these leads be as heavy as
the load leads. However, they must be twisted or
shielded to minimize noise pick-up.
Observe polarity when connecting the
sensing leads to the load.
that it is possible to operate a power supply simul­taneously in the remote sensing and Constant Volt­age/Constant Current remote programming modes.
3-35 SERIES OPERATION 3-36 Normal Series Connections (Figure 3-8). Two
or more power supplies can be operated in series to obtain a higher voltage than that available from a
single supply. When this connection is used, the output voltage is the sum of the voltages of the in­dividual supplies. Each of the individual supplies
must be adjusted in order to obtain the total output voltage. The power supply contains a protective
diode connected internally across the output which
protects the supply if one power supply is turned off while its series partner(s) is on.
Figure 3-7.
Remote Sensing
3-32 Note that it is desirable to minimize the drop in the load leads and it is recommended that the
drop not exceed 1 Volt per lead if the power supply
is to meet its dc specifications. If a larger drop must be tolerated, please consult a Hewlett-Packard field representative.
NOTE
Due to the voltage drop in the load leads, it may be necessary to readjust the current limit in the remote sensing mode.
3-33 The procedure just described will result in a low dc output impedance at the load. If a low ac impedance is required, it is recommended that the following precautions be taken:
a. Disconnect output capacitor C20 by dis-
connecting the strap between A9 and -S.
b. Connect a capacitor having similar char-
acteristics (approximately same capacitance, same
voltage rating or greater, and having good high fre­quency characteristics) across the load using short leads.
3-34 Although the strapping patterns shown in Fig­ures 3-3 through 3-6 employ local sensing, note
Figure 3-8.
Normal Series Connections
3-37 Auto-Series Connections (Figure 3-9). The
Auto-Series configuration is used when it is desir-
able to have the output voltage of each of the series connected supplies vary in accordance with the
setting of a control unit. The control unit is called the master; the controlled units are called slaves. At maximum output voltage, the voltage of the
slaves is determined by the setting of the front
panel VOLTAGE control on the master. The master
supply must be the most positive supply of the
series. The output CURRENT controls of all series
units are operative and the current limit i
S equal to
the lowest control setting. If any output CURRENT
controls are set too low, automatic crossover to
constant current operation will occur and the out-
put voltage will drop. Remote sensing and pro-
gramming can be used; however, the strapping ar-
rangements shown in the applicable figures show
local sensing and programming.
3-38 In order to maintain the temperature coeffic­ient and stability specifications of the power supply, the external resistors (Rx) shown in Figure 3-9 should be stable, low noise, low temperature co­efficient (less than 30 ppm per degree Centigrade) resistors. The value of each resistor is dependant
3-4
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35Cl-2-847-1
on the maximum voltage rating of the “master” sup-
ply. The value of Rx is this voltage divided by the
voltage programming current of the slave supply
(1/Kp where K
P is the voltage programming coef-
ficient). The voltage contribution of the slave is determined by its voltage control setting.
controls of each power supply can be separately set. The output voltage controls of one power sup­ply should be set to the desired output voltage; the other power supply should be set for a slightly larger output volts ge.
The supply set to the lower
output voltage will act as a constant voltage
source; the supply set to the higher output will act
as a constant current source, dropping its output
Figure 3-10.
Normal Parallel Connections
Figure 3-9.
Auto-Series, Two and Three Units
3-39 PARALLEL OPERATION (See Figure 3-1 for controls and indicators.)
3-40 Normal Parallel Connections (Figure 3-10). Two or more power supplies can be connected in parallel to obtain a total output current greater than
that available from one power supply. The total
output current is the sum of the output currents of the individual power supplies. The output CURRENT
3-5
Figure 3-11.
Auto-Parallel, Two and Three Units
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
voltage until it equals that of the other supply. The constant voltage source will deliver only that frac-
tion of its total rated output current which is neces-
sary to fulfill the total current demand,
3-41
Auto-Parallel
shown in permits equal current sharing under all load con­ditions, and allows complete control of output cur-
rent from one master power supply. The output cur­rent of each slave will be approximately equal to the master’s regardless of the load conditions.
Because the output current controls of each slave
are operative, the y should be set to maximum to avoid having the slave revert to constant current
operation; this would occur if the master output
Auto-Parallel.
Figure 3-11.
current setting exceeded the slave’s.
The strapping patterns for
operation of two power supplies are
Auto-Parallel
operation
3-42
AUTO-TRACKING OPERATION (See
3-43
it is necessary that several different voltages re­ferred to a common bus, vary in proportion to the setting of a particular instrument (the control or
master). A fraction of the master’s output voltage is fed to the comparison amplifier of the slave sup­ply, thus controlling the slave’s output. The master must have the largest output voltage of any power supply in the group (must be the most positive sup­ply in the example shown on
3-44
age of the master's mined by the voltage divider consisting of Rx (or Rx
and Ry)
Rp.
of the power supplies is controlled by the master. Remote sensing and programming can be used; al­though the strapping patterns for these modes show only local sensing and programming. In order to maintain the temperature coefficient and stability
specifications
sistors should be stable, low noise, low temperature
(less than 30ppm per °C) resistors.
The Auto-Tracking configuration
Figure 3-12).
The output voltage of the slave is a percent-
output voltage, and is deter-
and
where:
the voltage control of the slave supply,
ES=EMRp/Rx+Rp.
Turn-on and turn-off
of
the power supply, the external re-
Figure 3-12)
is
used when
3-45 3-46 3-47
over from constant voltage to constant current oper­ation, or the reverse, in response to an increase
(over the preset limit) in the output current or volt-
age, respective y. Although the preset limit may be
set higher than the average output current or voltage, high peak currents or voltages (as occur in pulse loading) may exceed the preset limit and cause
crossever desired, set the preset limit for the peak require­ment and not the average.
3-48
3-49 An
output terminals of the power supply, helps to sup­ply high-current pulses of short duration during
constant voltage operation. Any capacitance added
externally will improve the pulse current capability, but will decrease the safety provided by the con-
stant current circuit. A high-current pulse may dam­age load components before the average output cur­rent is large enough to cause the constant current
circuit to operate.
SPECIAL OPERATING CONSIDERATIONS PULSE LOADING The power supply will automatically
to
occur.
OUTPUT CAPACITANCE
internal capacitor, connected acress the
If this crossover limiting is not
cross-
Figure 3-12.
Auto-Tracking,
Two and Three Units
3-50
constant current operation are as follows:
3-6
The effects of the output capacitor during
The output impedance of the power supply
a.
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
decreases with increasing frequency.
b. The recovery time of the output voltage is
longer for load resistance changes.
c.A
large surge current causing a high pow­er dissipation in the load occurs when the load re­sistance is reduced rapidly.
3-51 3-52
nals. Under norms 1 operating conditions, the diode is reverse biased (anode connected to negative ter­minal). If a reverse voltage is applied to the output terminals (positive voltage applied to negative ter­minal), the diode will conduct, shunting current across the output terminals and limiting the voltage to the forward voltage drop of the diode. This diode protects the series transistors and the output elec­trolytic capacitor.
3-53 3-54
may actually deliver a reverse current to the power supply during a portion of its operating cycle. An external source cannot be allowed to pump current into the supply without loss of regulation and pos-
sible damage to the output capacitor. To avoid
these effects, it is necessary to preload the sup-
ply with a dummy load resistor so that the power
supply delivers current through the entire operating
cycle of the load device.
REVERSE VOLTAGE LOADING
A diode is connected across the output termi-
REVERSE CURRENT LOADING
Active loads connected to the power supply
3-55
OVERVOLTAGE PROTECTION CROWBAR
(See
Figure 3-1
indicators and schematic diagram.)
3-56
Use the following steps to adjust
the crowbar circuit.
a. Turn CROWBAR ADJUST fully clockwise to set trip voltage to maximum.
b. control for desired crowbar trip
voltage. tripping, trip voltage should exceed
desired output voltage by the following amount:4% of 2V.
c.
ccw until crowbar trips, output goes to
OV or a small positive voltage.
d.
and output shorted until supply is
turned off.
supply off, then on.
e.
disabled, remove lead attached to CROWBAR ADJUST potentiometer R5.
for controls and
Figure 3-13
Set power supply VOLTAGE
To prevent false crowbar
the output voltage plus
Slowly turn CROWBAR ADJUST
Crowbar will remain activated
To reset crowbar, turn
If CROWBAR must be completely
for the
3-7
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
Figure 3-13.
Model 6255A and 6289A Overvoltage Protection Crowbar
3-8
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1

SECTION IV

PRINCIPLES OF OPERATION
Figure 4-1.
4-1
OVERALL BLOCK DIAGRAM DISCUSSION
4-2
The power supply, as shown on the overall block diagram on transformer,
Figure 4-1,
a
rectifier and filter, a series regu-
consists of a power
lator, the mixer and error amplifiers, an “OR” gate, a constant voltage input circuit, a constant current input circuit, a reference regulator circuit, a bias supply, and a metering circuit.
4-3
The input line voltage passes through the power transformer to the rectifier and filter. The rectifier-filter DC
which is fed to the positive terminal via the
converts the AC input to raw
regulator and current sampling resister network. The regulator, part of the feedback loop,
is
made to alter its conduction to maintain a constant out­put voltage or current. The voltage developed
across the current sampling resistor network is the
input to the constant current input circuit. The
constant voltage input circuit obtains its input by
sampling the output voltage of the supply.
4-4
Any changes in output voltage/current
detected in the constant voltage/constant
are
current input circuit, amplified by the mixer and error am­plifiers, and applied to the series regulator in the
correct phase and amplitude to counteract the change in output voltage/output current. The refer­ence circuit provides stable reference voltages which are used by the constant voltage/current
in-
put circuits for comparison purposes. The bias
supply furnishes voltages which are used through-
out the instrument for biasing purposes. The meter
circuit provides an indication of output voltage or
current for both operating modes.
4-1
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
Figure 4-2.
4-5
SIMPLIFIED SCHEMATIC (See Figure
3-1 for controls and indicators.)
4-6 A simplified schematic of the power supply
is shown in Figure 4-2. It shows the operating controls; the ON-off switch, the voltage and cur­rent programming controls R10 and R16. Figure 4-2 also shows the internal sources of bias and reference voltages and their nominal magnitudes
with an input of 115 VAC.
4-7
Diode CR34, connected across the output
terminals of the power supply, is a protective de-
vice which prevents internal damage that might
occur if a reverse voltage were applied across the output terminals. connected across the output terminals when the normal strapping pattern shown on Figure 4-2 is employed.
Note that this capacitor can be removed if an increase in the programming speed is desired. Under these conditions, insure loop stability.
4-2
Output capacitor, C20, is also
capacitor C19 serves to
TM 11-6130-416-14/EE010-BJ-MMA-010/E154 DCDUAL/T.O.35C1-2-847-1
4-8 DETAILED CIRCUIT ANALYSIS [Refer
to overall schematic diagram (FO-1) at rear of manual.] 4-9
controls and indicators.)
4-10 The feedback loop functions continuously to keep the output voltage constant, during constant voltage operation, and the output current constant, during constant current operation. For purposes of this discussion, assume that the unit is in con-
stant voltage operation and that the programming resistors R10 A and B have been adjusted so that the supply is yielding the desired output voltage. Further assume that the output voltage instanta­neously rises (goes positive) due to a variation in the external load circuit.
4-11 Note that the change maybe in the form of a
slow rise in the output voltage or a positive going AC signal.
point A6 through capacitor C1 and a DC voltage is coupled to A6 through R10.
4-12 The rise in output voltage causes the voltage at A6 and thus the base of Q1A to decrease (go negative). Q1A now decreases its conduction and its collector voltage rises. The positive going er­ror voltage is amplified and inverted by Q3 and fed to the bases of series transistors Q6 and Q7 via
emitter followers Q5 and Q4. The negative going
input causes Q6 and Q7 to decrease their conduc­tion so that they drop more of the line voltage, and reduce the output voltage to its original level.
FEEDBACK LOOP (See Figure 3-1 for
An AC signal is coupled to summing
dissipated in series transistor Q6. The bias voltage
for Q7 is developed across zener diode VR5, The
The conduction of Q7 will decrease as the collector-
to-emitter voltage of Q6 approaches the voltage
developed across the biasing diodes, At low out­put voltages Q7 is completely cutoff and all of the load current flows through the shunt resistors. The
voltage that is dropped acress Q7 and the shunt
resistors reduces the voltage dropped across Q6, thus diminishing its power dissipation. The reli­ability of the regulator is further increased by
mounting the shunt resistors outside the rear of the cabinet so that the internal components are operated under lower temperature conditions.
Diode CR11, connected across Q6, protects it from
reverse voltages that could develop across it dur-
ing parallel or auto-parallel operation if one sup­ply is turned on before the other. Diodes CR18
and CR19 perform a similar function for Q7.
4-16 CONSTANT VOLTAGE INPUT CIRCUIT
(See Figure 3-1 for controls and in-
dicators.)
4-17 The circuit consists of programming resistor
R10A and B, and a differential amplifier stage (Q1
and associated components). Transistor Q1 con-
sists of two transistors housed in a single package.
The transistors have matched characteristics min-
imizing differential voltages due to mismatched
stages.
tials is minimized, since both transistors operate
at essentially the same temperature.
Moreover, drift due to thermal differen-
4-13 If the external load resistance is decreased to a certain crossover point, the output current in-
creases until transistor Q2A begins to conduct.
During this time, the output voltage has also de­creased to a level so that the base of Q1A is at a high positive potential. tion, its collector voltage decreases by the amount necessary to back bias OR gate diode CR3 and the
supply is now in the constant current mode of op­eration. current operation commences is determined by the
setting of CURRENT control R16. The operation of
the feedback loop during the constant current op­erating mode is similar to that occuring during constant voltage operation except that the input to the differential amplifier comparison circuit is ob­tained from the current sampling resistor network.
4-14 SERIES REGULATOR
4-15 The series regulator consists of transistor
stages Q6 and Q7 (see schematic at rear of manual). Transistor Q6 is the series element, or pass transis-
tor, which controls the output. Transistor Q7, to­gether with shunt resistors R81, R82, and R83, are connected in a manner which minimizes the power
The crossover point at which constant
With Q1A in full conduc-
4-18 The constant voltage input circuit continu­ously compares a fixed reference voltage with a portion of the output voltage and, if a difference exists, produces an error voltage whose amplitude and phase is proportional to the difference. error output is fed back to the series regulator, through an OR gate and the mixer/error amplifiers. The error voltage changes the conduction of the
series regulator which, in turn, alters the output voltage so that the difference between the two in­put voltages applied to the differential amplifier is reduced to zero. output voltage constant.
4-19 Stage Q1B of the differential amplifier is connected to a common (+S) potential through im­pedance equalizing resistor R5. Resistors R6 and R8 are used to zero bias the input stage, offsetting minor base-to-emitter voltage differences in Q1. The base of Q1A is connected to a summing point at
the junction of the programming resistor and the current pullout resistor, R12. Instantaneous changes in output voltage result in an increase or
decrease in the summing point potential. Q1A is then made to conduct more or less, in accordance with the summing point voltage change.
The above action maintains the
The
The re-
4-3
Loading...
+ 66 hidden pages