HP (Hewlett-Packard) 6205B User Manual

TM 11-6625-2965-14&P
TECHNICAL MANUAL
OPERATOR’S ORGANIZATIONAL
DIRECT SUPPORT AND GENERAL SUPPORT
MAINTENANCE MANUAL
[INCLUDING REPAIR PARTS
AND SPECIAL TOOLS LISTS]
POWER SUPPLY PP-7548/U
[NSN 6625-00-437-4861]
HEADQUARTERS, DEPARTMENT OF THE ARMY
25 FEBRUARY 1980

WARNING

HIGH VOLTAGE is used during the performance of maintenance as instructed in this manual. DEATH ON CONTACT may result if personnel fail to observe safety precautions.
DO NOT ATTEMPT to make internal connections or perform adjustments unless another person, capable of performing first aid, is present.
For electric shock protection, use only extension cord and power receptacles with a safety-ground connector, or otherwise connect the chassis to a safety ground.
CERTIFICATION
The Hewlett-Packard Company certifies that this instrument was thoroughly tested and inspected and found to meet its published specifications when it shipped from the factory. The Hewlett-Packard Company further certifies that its calibration measurements are traceable to the U.S. National Bureau of Standards to the extent allowed by the Bureau’s calibration facility.
Was
WARRANTY AND ASSISTANCE
All Hewlett-Packard products are warranted against defects in materials and workmanship. This warranty applies for one year from the date of delivery, or, in the case of certain major components listed in the operating manual, for the specified period. We will repair or replace products which prove to be defective during the warranty period. No other warranty is expressed or implied. We are not liable for consequential damages.
TM 11-6625-2965-14&P
This manual contains copyright material reproduced by permission of Hewlett-Packard Company
TECHNICAL MANUAL
HEADQUARTERS
DEPARTMENT OF THE ARMY
W
No. 11-6625-2965-14&P
OPERATOR’S, ORGANIZATIONAL, DIRECT SUPPORT AND
GENERAL SUPPORT MAINTENANCE MANUAL
(INCLUDING REPAIR PARTS AND SPECIAL TOOLS LISTS)
ASHINGTON, DC, 25 February 1980
POWER SUPPLY PP-7548/U (HEWLETT-PACKARD MODEL)
(NSN 6625-00-437-4861)
REPORTING OF ERRORS
Y
OU can improve this manual by recommending improvements using DA Form 2028-2
located in the back of the manual. Simply tear out the self-addressed form, fill it out as shown on the sample, fold it where shown, and drop it in the mail.
If there are no blank DA Forms 2028-2 in the back of your manual, use the standard DA Form 2028 (Recommended Changes to Publications and Blank Forms) and forward to the Commander, US Army Communications and Electronics Materiel Readiness Command, ATTN: DRSEL-ME-MQ, Fort Monmouth, NJ 07703.
In either case a reply will be furnished direct to you.
This manual is an authentication of the manufacturer’s commercial literature which, through usage, has been found to cover the data required to operate and maintain this equipment. Since the manual was not prepared
in accordance with military specifications, the format has not been structured to consider levels of
maintenance.
TABLE OF CONTENTS
TM 11-6625-2965-14&P
Section Page No.
O INSTRUCTIONS . . . . . . . . . . . . . . . . 0-1
0-l Scope
0-1
0-2 Indexes of Publications 0-1 0-3 Maintenance Forms,
Records and Reports
0-1
0-4 Reporting Equipment
Section
3-38
Special Operating Con-
siderations
Pulse Loading
3-39 3-41
Output Capacitance
3-43
Reverse Voltage Loading
3-45
Reverse Current Loading
Improvement Recommen-
dations (EIR)
0-5 Administrative Storage 0-1
0-6 Destruction of Army
Electronics Materiel 0-1
I
GENERAL INFORMATION . . . . . . . . . . . 1-1
1-1 Description 1-6 Specifications 1-8 Options 1-10 Accessories 1-12 Instrument and Service Man-
ual Identification
1-15 Ordering Additional Manuals 1-2
II INSTALLATION
2-1
Initia1 Inspection Mechanical Check
2-3
Electrical Check
2-5
Installation Data
2-7
Location
2-9
Outline Diagram
2-11
Rack Mounting
2-13 2-17
Input Power Requirements
2-19
Connections for 230 Volt
Operation
Power Cable
2-21 2-24
Repackaging for Shipment
I I I OPERATING INSTRUCTIONS . . . . . . . . 3-1
3-1
Turn-on Checkout Procedure
3-3
Operating Modes
3-5
Norma1 Operating Mode
3-7
Constant Voltage
3-9
Changing Current Limit
3-11
Connecting Load
3-14
Operation Beyond Norma 1
Rated Output
3-16
Optional Operating Modes
3-17
Remote Programming, Con-
stant Voltage
3-25
Remote Sensing
3-30
Series Operation
3-35
Auto-Tracking Operation
. . . . . . . . . . . . . . . . . . .
0-1
1-1 1-1 1-1 1-2
1-2
2-1 2-1 2-1 2-1 2-1 2-1 2-1 2-1 2-3
2-3 2-3 2-3
3-1 3-1
3-1 3-1 3-2 3-2
3-2 3-2
3-2 3-3 3-4 3-5
IV PRINCIPLES OF OPERATION . . . . . . . . 4-1
4-1
Overall Description 4-8 Detailed Circuit Analysis 4-9 Feedback Loop 4-13 Series Regulator 4-15 Constant Voltage Comparator 4-2 4-19 Error Amplifier and Driver 4-22 Current Limit Circuit 4-26 Reference Circuit
4-29 Meter Circuit
V MAINTENANCE
5-1
Introduction
5-3
General Measurement
Techniques
5-8
Test Equipment Required
Performance Test
5-10 5-12
Constant Voltage Tests
5-38
Output Impedance
Troubleshooting
5-48 5-53
Overa11 Troubleshooting
Procedure
5-58
Repair and Replacement
5-60
Adjustment and Calibration
Meter Zero
5-62 5-64
Ammeter Tracking
5-66
Constant Voltage Programming
Current
5-69
Reference Circuit Adjustments
5-71
Constant Voltage Transient
Recovery Time
5-73
Current Limit Adjustment
VI REPLACEABLE PARTS . . . . . . . . . . .
6-1 Introduction 6-1 6-4 Ordering Information
APPENDIX A
B C
D
VII CIRCUIT
Page No.
. . . . . . . . . . . . . . . . . . .
References
Components of End
Item
Maintenance
Allocation
Manual
Changes
DIAGRAMS
backdating
........... 7-1
3-6 3-6 3-6 3-6 3-6
4-1 4-2
4-2
4-2
4-2
4-3 4-3
4-3
5-1 5-1
5-1 5-2 5-3 5-3 5-7 5-9
5-9 5-12 5-13 5-13 5-13
5-13
5-15
5-15 5-15
. . . . 6-1
6-1
A-1 B-1
C-1
ii
TM 11-6625-2965-14&P
LIST OF ILLUSTRATIONS
Figure
2-1 2-2 2-3 2-4 3-1 3-2 3-3 3-4 3-5 3-6 3-7 3-8 3-9
3-10
4-1
Page No. Outline Diagram 2-1 Rack Mounting, Two Units 2-2 Rack Mounting, One Unit 2-2 Primary Connections 2-3 Front Panel Controls and Indicators 3-1 Normal Strapping Pattern Current Limit Alteration Remote Resistance Programming 3-3 Remote Voltage Programming Remote Sensing 3-3 Norma I Series Connections 3-4
Auto-Series, Two and Three Units 3-4 Auto-Parallel, Two and Three
Units
Auto-Tracking, Two and Three
Units 3-5
Overa11 Block Diagram 4-1
3-1 3-2
3-3
3-5
LIST OF TABLES
Figure
4-2
5-1 5-2
5-3 5-4
5-5 5-6 5-7 5-8
5-9
5-10 5-11
Page No.
Multiple Range Meter Circuit,
Simplified Schematic Front Panel Terminal Connections 5-1 Output Current Measurement
Technique Differential Voltmeter Substitute,
Test Setup Output Current, Test Setup 5-4 Load Regulation, Test Setup
CV Ripple and Noise, Test Setup 5-5 CV Noise Spike, Test Setup Transient Recovery Time,
Test Setup
Transient Recovery Time,
Waveforms Output Impedance, Test Setup Servicing Printed Wiring Boards
4-4
5-1 5-2
5-4 5-6
5-7
5-7 5-8 5-14
Table
1-1 Specifications 5-1 Test Equipment Required 5-2 Reference Circuit Troubleshooting 5-3 Overall Trouble shooting 5-9 5-4 High Output Voltage Troubleshooting 5-5 Low Output Voltage Troubleshooting 5-6 Selected Semiconductor Characteristics 5-7 Checks and Adjustments After Replacement of Semiconductor Devices 5-12
6-1 Reference Designators 6-2 Description Abbreviations 6-3 Code List of Manufacturers 6-4 Replaceable Parts
Page No.
1-3 5-2 5-9
5-11 5-11 5-12
6-1
6-1
6-2
6-5
iii
SECTION O
INSTRUCTIONS
TM 11-6625-2965-14&P
0-1.
Model 6205) having serial prefix number 7L2301 and up. For serial prefixes below 7L2301 refer to Appendix E.
inclusion of change page.
0-2.
whether there are new editions , changes, or additional publications pertain-
ing to the equipment.
modification work orders (MWO
0-3.
the Army forms and procedures used for equipment maintenance will be those
described by TM 38-750, The Army Maintenance Management System,
DD Form 6 (Packaging Improvement Report) as prescribed in AR 700-58/ NAVSUPINST 4030.29/AFR 71-12/MCO P4030.29A, and DLAR 4145.8.
SCOPE
This manual applies directly to Power Supply PP-7548/U (Hewlett-Packard
For serials above 7L4450 check for
INDEXES OF PUBLICATIONS
DA Pam 310-4.
a.
b.
DA Pam 310-7.
MAINTENANCE FORMS, RECORDS AND REPORTS
a.
Reports of Maintenance and Unsatisfactory Equipment.
b.
Report of Packaging and Handling Deficiencies.
Refer to the latest issue of DA Pam 310-4 to determine
Refer to DA Pam 310-7 to determine whether there are
S
) pertaining to the equipment.
Department of
Fill out and forward
c.
Discrepancy in Shipment Report (DISREP) (SF 361). Fill out and
forward Discrepancy in Shipment Report (DISREP) (SF 361) as prescribed in
AR 55-38/NAVSUPINST 4610.33B/AFR 75-18/MCO P461O.19C and DLAR 4500.15.
0-4.
Send us an EIR. don’t like about your equipment. Tell us why a procedure is hard to perform. Deficiency Report). Electronics Materiel Readiness Command and Fort Monmouth, ATTN: DRSEL-ME-
MQ, Fort Monmouth, New Jersey 07703. We'll send yOu a reply.
0-5.
shall be in accordance with paragraph 2-5.
0-6.
accordance with TM 750-244-2.
REPORTING EQUIPMENT IMPROVEMENT RECOMMENDATIONS(EIR)
If your Power Supply PP-7548/U (HP-6205) needs improvement, let us know.
You, the user,
Mail it to Commander, US Army Communications and
ADMINISTRATIVE STORAGE
Administrative storage of equipment issued to and used by Army activities
DESTRUCTION OF ARMY ELECTRONICS MATERIEL
Destruction of Army electronics materiel to prevent enemy use shall be in
are the only one who can tell us what you
Let us know why you don’t like the design.
Put it on an SF 368 (Quality
0-1
TM 11-6625-2965-14&P
1-1 DESCRIPTION
1-2
This power supply, Figure 1-1, is completely transistorized and suitable for either bench or re­lay rack operations, The dual supply consists of two independently controlled dual range sections; both identical to the other. Each section can fur-
nish either a 0-40 Volt output at 300mA or a 0-20 Volt output at 600mA. Each section has its own front panel meter and operating controls, The oper-
ating modes (40V or 20V) are selected by means of the front panel RANGE switches, The VOLTAGE con­trols permit each output voltage to be continuously
adjusted throughout either output range.
may be programmed from a remote location by means of an external voltage source or resistance.
b. Remote Sensing. The degradation in regulation which would occur at the load because of the voltage drop which takes place in the load leads can be reduced by using the power supply in
the remote sensing mode of operation.
c. Series and Auto-Series Operation, Power supplies may be used in series when a higher out­put voltage is required in the voltage mode of op­eration or when greater voltage compliance is re­quired in the constant current mode of operation,
Auto-Series operation permits one knob control of the total output voltage from a “master” supply.
d. Parallel and Auto-Parallel Operation, The power supply may be operated in parallel with a
similar unit when greater output current capability is required. knob control of the total output current from a “master” supply.
e. Auto-Tracking.
used as a “master” supply, having control over one
(or more) “slave”
ages for a system.
1-6 SPECIFICATIONS
Auto-Parallel operation permits one
The power supply may be
supplies that furnish various volt-
Figure 1-1. DC Power Supply, Model 6205B
1-3 Both sections of the supply are of the regu­lated, Constant Voltage/Current Limiting, type. Each section is fully protected from overloads by the fixed current limit which is set by means of an
internal adjustment.
1-4 Both front and rear terminals are available
for each section. Either the positive or negative terminals may be grounded or the supply can be
operated at up to a maximum of 300 Volts off ground.
Each meter can be used to measure either output
voltage or output current in one of two ranges. The
voltage or current ranges are selected by the ap-
plicable METER switch on the front panel.
1-5 Two sets of programming terminals, located at the rear of the unit, allow ease in adapting to the many operational capabilities of the supply. A brief description of these capabilities is given below:
a, Remote Programming,
The power supply
1-7 Detailed specifications for the power supply
are given in Table 1-1.
1-8 OPTIONS
1-9 Options are factory modifications of a stand­ard instrument that are requested by the customer. The following options are available for the instru-
ment covered by this manual, Where necessary, de-
tailed coverage of the options is included through-
out the manual.
Option No.
07
11
Voltage 10-Turn Pot: A single control that replaces both coarse and fine voltage controls and improves output
nettability.
Overvoltage_Protection_“Crowbar”: A completely separate circuit for pro­tecting delicate loads against power
supply failure or operator error. This independent device monitors the out­put voltage and within 10µsec imposes a virtual short-circuit (crowbar) across
the power supply output if the preset
Description
11
TM 11-6625-2965-14P
trip voltage is exceeded. When Op­tion 11 is requested by the customer the device is connected at the factory.
Trip Voltage Range: 2.5 to 44 Volts, screwdriver adjustable.
Detailed coverage of Option 11 is in­cluded in Appendix A at the rear of manuals that support power supplies containing Option 11.
13
28
1-10 ACCESSORIES
1-11 The accessories listed in the following chart may be ordered with the power supply or separately from your local Hewlett-Packard field sales office
(refer to list at rear of manual for addresses).
Three Digit Graduated Decadial
Voltage Control: Control that replaces
coarse and fine voltage controls per­mitting accurate resettability.
230Vac Input: shipped is wired for l15Vac input. Option 28 consists of reconnecting the input transformer for 230Vac oper­ation.
Supply as normally
14523A
1-12 INSTRUMENT AND SERVICE MANUAL
IDENTIFICATION
1-13 Hewlett-Packard power supplies are identi­fied by a three-part serial number tag. The first part is the power supply model number. The sec­ond part is the serial number prefix, which con­sists of a number-letter combination that denotes the date of a significant design change. The num­ber designates the year, and the letter A through
L designates the month, January through December respectively, with “I” omitted. The third part is the power supply serial number.
1-14 If the serial number prefix on your power supply does not agree with the prefix on the title page of this manual, change sheets are included to update the manual. Where applicable, back­dating information is given in an appendix at the
rear of the manual.
ORDERING ADDITIONAL MANUALS
1-15
Rack Kit for mounting two 3½” high
supplies. (Refer to Section II for de-
tails.)
C05
14513A
Description
8” Black Handle that can be attach-
ed to side of supply.
Rack Kit for mounting one 3½” high supply. (Refer to Section II for de­tails.)
1-16
One manual is shipped with each power sup­ply, Additional manuals may be purchased from your local Hewlett-Packard field office (see list at rear of this manual for addresses). Specify the model number, serial number prefix, and Part number provided on the title page.
1-2
Table 1-1.
Specifications
TM 11-6625-2965-14&P
INPUT:
l15Vac ±10%, single phase, 48-440 Hz.
OUTPUT:
Two independent outputs, each of which can be set at either 0-40 Volts @ 0.3 Amp or 0-20 Volts @ 0.6 Amp.
LOAD REGULATION:
Less than 0,01% plus 4mV for a full load to no
load change in output current.
LINE REGULATION:
Less than 0.01% plus 4mV for any line voltage
change within the input rating.
RIPPLE AND NOISE:
Less than 200µVrms 1mV p-p,
TEMPERATURE RANGES:
operating: 0 to 50°C. Storage: -40 to + 750C.
TEMPERATURE COEFFICIENT:
Less than 0.02% plus lmV per degree Centi-
grade. STABILITY.
Less than 0.10% plus 5mV total drift for 8 hours after an initial warm-up time of 30 min­utes at constant ambient, constant line voltage, and constant load.
INTERNAL IMPEDANCE AS A CONSTANT VOLT-
AGE SOURCE:
Less than 0.02 ohms from dc to lkHz. Less than 0.5 ohms from lkHz to 1OOkHz. Less than 3.0 ohms from 1OOkHz to lMHz.
TRANSIENT RECOVERY TIME:
Less than 50µsec for output recovery to with-
in 10mV following a full load current change in the output.
OVERLOAD PROTECTION:
A fixed current limiting circuit protects the power supply for all overloads including a direct short placed across the terminals in con-
stant voltage operation.
METERS:
Each front panel meter can be used as either a
0-50 or 0-5 Volt voltmeter or as a 0-0.75 or
0.075 Amp ammeter.
OUTPUT CONTROLS:
RANGE switches select desired operating mode
for each section and coarse and fine VOLTAGE
controls set desired output voltages.
OUTPUT TERMINALS:
Six “five-way” output posts (three for each
section of supply) are provided on the front
panel and two output terminal strips (one per
section) are located on the rear of the chassis. A1l power supply output terminals are isolated from the chassis and either the positive or neg­ative terminals may be connected to the chassis through separate ground terminals located on the output termina1 strips.
ERROR SENSING:
Error sensing is normally accomplished at the front terminals if the load is attached to the front or at the rear terminals if the load is at-
tached to the rear terminals. Also, provisions are included on the rear termina1 strips for re­mote sensing.
REMOTE RESISTANCE PROGRAMMING:
200 ohms per Volt.
REMOTE VOLTAGE PROGRAM MING:
1 Volt per Volt.
COOLING:
Convection cooling is employed. The supply
has no moving parts. SIZE:
3~½" H x 12-5/8" D x 8½" W. Two of the units
can be mounted side by side in a standard 19” relay rack.
WEIGHT:
10 lbs, net, 13 lbs. shipping.
FINISH:
Light gray front panel with dark gray case.
POWER CORD:
A three-wire, five-foot power cord is provided
with each unit.
1-3
TM 11-6625-2965-14&P

SECTION II

INSTALLATION
2-1 INITIAL INSPECTION
2-2 Before shipment, this instrument was in-
spected and found to be free of mechanical and electrical defects. As soon as the instrument is unpacked, occurred in transit. Save all packing materials until the inspection is completed. If damage is found, a claim should be filed with the carrier. Hewlett-Packard Sales and Service office should be notified.
2-3 MECHANICAL CHECK
2-4 This check should confirm that there are no broken knobs or connectors, that the cabinet and panel surfaces are free of dents and scratches, and that the meter is not scratched or cracked.
2-5
inspect for any damage that may have
ELECTRICAL CHECK
2-6 The instrument should be checked against its electrical specifications. Section V includes an “ in-cabinet” performance check to verify proper instrument operation,
2-7 INSTALLATION DATA
2-8 The instrument is shipped ready for bench operation. It is necessary only to connect the in­strument to a source of power and it is ready for
operation.
2-9 LOCATION
2-10 This instrument is air cooled. Sufficient
space should be allotted so that a free flow of cooling air can reach the sides and rear of the in-
strument when it is in operation. It should be used in an area where the ambient temperature does not exceed 50°C.
2-11 OUTLINE DIAGRAM
2-12 Figure 2-1 is an outline diagram showing the dimensions of the instrument.
2-13 RACK MOUNTING
2-14 This instrument may be rack mounted in a
standard 19 inch rack panel either alongside a
similar unit or by itself. Figures 2-2 and 2-3 show
Figure 2-1. Outline Diagram
how both types of installations are accomplished.
2-15 To mount two units side-by-side, proceed
as follows:
a. Remove the four screws from the front
panels of both units.
b. Slide rack mounting ears between the
front panel and case of each unit.
c. Slide combining strip between the front
panels and cases of the two units.
d. After fastening rear portions of units to­gether using the bolt, nut, and spacer, replace panel screws.
2-16 To mount a single unit in the rack panel, proceed as follows:
a. Bolt rack mounting ears, combining
straps, and angle brackets to each side of center
2-1
TM 11-6625-2965-14&P
Figure 2-2. Rack Mounting, Two Units
Figure 2-3.
Rack Mounting, One Unit
TM 11-6625-2965-14&P
spacing panels. Angle brackets are placed behind
combining straps as shown in Figure 2-3.
b. Remove four screws from front panel of
unit.
Slide combining strips between front
c.
panel and case of unit.
d. Bolt angle brackets to front sides of case
and replace front panel screws.
2-17 INPUT POWER REQUIREMENTS
2-18 This power supply may be operated from either a nominal 115 Volt or 230 Volt 48-440 Hertz power source. The unit, as shipped from the fac­tory, is wired for 115 Volt operation. The input power required when operated from a 115 Volt 60 Hertz power source at full load is 31 Watts and
0.35 Amperes.
2-19 CONNECTIONS FOR 230 VOLT OPERATION
2-20 Normally, the two primary windings of the
input transformer are connected in parallel for op­eration from 115 Volt source. To convert the power
supply to operation from a 230 Volt source, the
power transformer windings are connected in series
as follows:
a.
Unplug the line cord and remove the unit
from case.
b. Break the copper between 54 and 55 and also between 50 and 51 on the printed circuit board. The se are shown in Figure 2-4, and are labeled on copper side of printed circuit board.
Add strap between 50 and 55.
c.
d. Replace existing fuse with 1 Ampere,
230 Volt fuse.
normally.
Return unit to case and operate
2-21 POWER CABLE
2-22 To protect operating personnel, the National Electrical Manufacturers Association (NEMA) rec­ommends that the instrument panel and cabinet be grounded. This instrument is equipped with a three conductor power cable. The third conductor is the ground conductor and when the cable is plugged into an appropriate receptacle, the instru­ment is grounded. The offset pin on the power cable three-prong connector is the ground connec­tion.
2-23 To preserve the protection feature when op­erating the instrument from a two-contact outlet, use a three-prong to two-prong adapter and con­nect the green lead on the adapter to ground.
2-24 REPACKAGING FOR SHIPMENT
2-25 To insure safe shipment of the instrument, it is recommended that the package designed for the
Figure 2-4.
instrument be used. The original packaging mate­rial is reusable. If it is not available, contact your local Hewlett-Packard field office to obtain
the materials. This office will also furnish the address of the nearest service office to which the instrument can be shipped. Be sure to attach a tag to the instrument which specifies the owner, model number, full serial number, and service re-
quired, or a brief description of the trouble,
2-3
Primary Connections
SECTION Ill
OPERATING INSTRUCTIONS
TM 11-6625-2965-14&P
3-1 TURN-ON CHECKOUT PROCEDURE
Figure 3-1.
3-2 The front panel controls and indicators are shown in Figure 3-1.
is described below:
A. Push ON/OFF button
that button lights,
B. Set range switch
mode and meter switch to desired voltage range.
C. Adjust coarse and fine voltage controls
Front Panel Controls and Indicators
The normal turn-on sequence,
and observe
to desired operating
until desired output voltage is indicated on
meter.
Set meter switch to highest current range
D.
and short
meter.
terminals be used for both sections of supply.
circuit output terminals.
E.
Observe short circuit output current on Remove short and connect load to output
F.
(front or rear),
For Model 6205B, this procedure should
G.
erational capabilities of the supply. A more theo­retical description concerning these operational features is contained in Application Note 90 and in various Tech Letters. Copies of these can be obtained from your local Hewlett-Packard field office,
3-5 NORMAL OPERATING MODE
3-6 The power supply is normally shipped with its rear terminal strapping connections arranged for Constant Voltage/Current Limiting, local sens­ing, local programming, single unit mode of oper­ation. This strapping pattern is illustrated in Fig­ure 3-2. The operator selects a constant voltage output using the front panel controls (local pro­gramming, no strapping changes are necessary).
Figure 3-2.
Norma 1 Strapping Pattern
3-3 OPERATING MODES
3-4 The power supply is designed so that its mode of operation can be selected by making strapping connections between particular terminals on the terminal strip at the rear of the power sup­ply.
The terminal designations are stenciled in white on the power supply above their respective terminals. Although the strapping patterns illus­trated in this section show the positive terminal grounded, the operator can ground either termina1 or operate the power supply up to 300Vdc off ground (floating). The following paragraphs de­scribe the procedures for utilizing the various op-
3-7 CONSTANT VOLTAGE
3-8 To select a constant voltage output turn on the supply and, with no load connected, adjust the VOLTAGE controls for the desired output volt-
age. To check the current limit, connect an ex-
ternal ammeter across the output of the turn the VOLTAGE controls fully clockwise, and observe the reading. adjusted to approximately 100mA above the current rating of the supply. is not compatible with the anticipated load re­quirements, the limit can be changed as outlined in the following paragraphs.
3-1
The current limit is factory
If the existing current limit
supply,
TM 11-6625-2965-14&P
3-9 CHANGING CURRENT LIMIT
3-10 The current limit can be varied by adjusting resistor R81, located on the printed wiring board. This adjustment procedure is described in Para­graph 5-74. In Models 6204B and 6206B, the cur­rent limit may be reduced to a value lower than that attainable by adjusting R81, by adding an ex­ternal resistor as shown in Figure 3-3. The ap­proximate value of the external resistance (Rx) can be determined by using the following equation
=1.75
R
X
I
E
where: I = the output current
E
R = the internal current sampling resist-
I
ance for the particular operating mode to be used.
1.75 . the approximate voltage drop across the internal sampling resistance at the current limit crossover point.
NOTE
The power supply’s performance will be somewhat degraded if it is operated too close to (within 10OmA) the current limit crossover point.
3-13 If load considerations require that the output
power distribution terminals be remotely located from the power supply, then the power supply out­put terminals should be connected to the remote distribution terminals via a pair of twisted or
shielded wires and each load separately connected
to the remote distribution termina1s. For this case, remote sensing should be used (Paragraph 3-25).
3-14 OPERATION BEYOND NORMAL RATED OUTPUT
3-15 Although the supply can deliver greater than the rated output on both the lower and higher volt­age ranges without being damaged, it can not be
guaranteed to meet all of its performance specifi­cations.
Generally when operating the supply in this manner, the output is unstable when connect­ed to a load.
When greater than the lower rated
voltage is required, the higher voltage range
should be used.
This range will deliver half as much output current and all specifications will apply as listed in Table 1-1. However, if the line voltage is maintained above its nomina1 value, the
supply will probably operate within specifications
above its rated output.
3-16 OPTIONAL OPERATING MODES
3-17 REMOTE PROGRAMMING, CONSTANT VOLTAGE
A1 A2 A6 A7 A8 A9 -S – GND + +S A10
Rx
Figure 3-3.
Current Limit Alteration
R
L
3-11 CONNECTING LOAD
3-12 Each load should be connected to the power supply output terminals using separate pairs of
connecting wires.
This will minimize mutual cou-
pling effects between loads and will retain full advantage of the low output impedance of the power
supply.
Each pair of connecting wires should be
as short as possible and twisted or shielded to re­duce noise pickup. (If shield is used, connect one end to power supply ground terminal and leave the other end unconnected. )
3-18 The constant voltage output of the power supply can be programmed (controlled) from a re­mote location if required. Either a resistance or voltage source can be used for the programming device.
The wires connecting the programming terminals of the supply to the remote programming device should be twisted or shielded to reduce noise pickup. The VOLTAGE controls on the front panel are disabled according to the following pro-
cedures.
3-19 Resistance Programming (Figure 3-4). In this mode, the output voltage will vary at a rate determined by the programming coefficient (200
ohms per Volt for Model 6204B and 6205B or 300 ohms per Volt for Model 6206 B). The output volt­age will increase by 1 Volt for each 200 ohms (or
300 ohms) added in series with the programming terminals. The programming accuracy is 1% of the programmed voltage. If greater programming ac-
curacy is required, it may be achieved by chang-
ing resistor R13 as outlined in Section V.
3-20 The output voltage of the power supply should be zero Volts ± 20 millivolts when zero ohms is connected across the programming termi­nals. If a zero ohm voltage closer than this is re­quired, it may be achieved by changing resistor R6 or R8 as described in Section V.
3-2
A7 A6 A8 A10+S + GND - –S
Figure 3-4.
PROGRAMMING
RESISTOR
Remote Resistance Programming
R
L
3-21 To maintain the stability and temperature coefficient of the power supply, u se programming resistors that have stable, low noise, and low temperature (less than 30ppm per degree Centi­grade) characteristics. A switch can be used in conjunction with various resistance values in order to obtain discrete output voltages.
The
switch should have make-before-break contacts to avoid momentarily opening the programming terminals during the switching interval.
TM 11-6625-2965-14&P
programming voltage source should be approxi­mately 1000 ohms if the temperature and stability specifications of the power supply are to be main­tained. The programming accuracy is 1% of the programmed voltage.
3-24 Methods of voltage programming with gain are discussed in Application Note 90, Power Supply Handbook; available at no charge from your local
Sales Office.
3-25 REMOTE SENSING (See Figure 3-6)
3-26 Remote sensing is used to maintain good regulation at the load and reduce the degradation of regulation which would occur due to the voltage drop in the leads between the power supply and the load. Remote sensing is accomplished by uti-
lizing the strapping pattern shown in Figure 3-6. The power supply should be turned off before changing strapping patterns. The leads from the
+S terminals to the load will carry less than 10
milliamperes of current, and it is not required that
these leads be as heavy as the load leads. How­ever, they must be twisted or shielded to minimize
noise pick-up.
CAUTION
3-22 Voltage Programming (Figure 3-5). Employ the strapping pattern shown on Figure 3-5 for voltage programming.
In this mode, the output
voltage will vary in a 1 to 1 ratio with the pro-
gramming voltage (reference voltage) and the load
on the programming voltage source will not exceed 25 microampere.
A7 A6 A8 A10 +S + GND - -S
REFERENCE
VOLTAGE
Figure 3-5. Remote Voltage Programming
3-23 The impedance (Rx) looking into the external
Observe polarity when connecting the sensing leads to the load.
A7 A6 A8 A10+S + AND– –S
R
L
Figure 3-6. Remote Sensing
3-27 For reasonable load lead lengths, remote sensing greatly improves the performance of the supply. However, if the load is located a consid-
erable distance from the supply, added precautions
must be observed to obtain satisfactory operation. Notice that the voltage drop in the load leads sub-
3-3
TM 11-6625-2965-14&P
tracts directly from the available output voltage and also reduces the amplitude of the feedback er­ror signals that are developed within the unit. Be­cause of these factors it is recommended that the drop in each load lead not exceed 1 Volt. If a
larger drop must be tolerated, please consuIt a
sales
engineer.
NOTE
Due to the voltage drop in the load
leads, it may be necessary to readjust the current limit in the remote sensing mode.
3-28
Another factor that must be considered is
the inductance of long load leads which could af­fect the stability of the feedback loop and cause oscillation. In these cases, it is recommended that the output capacitor (C20) be physically re­moved from the power supply and placed across the output terminals.
3-29 Although the strapping patterns shown in
Figures 3-4 and 3-5 employ local sensing, notice that it is possible to operate a power supply si­multaneously in the remote sensing and the remote programming modes.
ages of the individual supplies. Each of the indi­vidual supplies must be adjusted in order to obtain the total output voltage. The power supply con­tains a protective diode connected internally across the output which protects the supply if one power supply is turned off while its series part­ner(s) is on.
3-32 Auto-Series Connections (Figure 3-8). The Auto-Series configuration is used when it is de­sirable to have the output voltage of each of the
series connected supplies vary in accordance with the setting of a control unit. The control unit is called the master; the controlled units are called slaves. At maximum output voltage, the voltage of the slaves is determined by the setting of the front panel VOLTAGE control on the master. The master supply must be the most positive supply of the series.
The current limit settings of all series
3-30 SERIES OPERATION 3-31 Normal Series Connections (Figure 3-7).
Two or more power supplies can be operated in
series to obtain a higher voltage than that avail­able from a single supply. When this configuration is used, the output voltage is the sum of the volt-
A7 A6 A8 A10-S + GND – –S
A7 A6 A8 A10 - S + GND – –S
Figure 3-7. Normal Series Connections
Figure 3-8, Auto-Series, Two and Three Units
3-4
units are effective and the current limit for the entire configuration is equal to the lowest current
limit setting. If any of the settings are too low, automatic crossover to current limiting operation
will occur and the output voltage will drop. Re-
mote sensing and programming can be used; how­ever, the strapping arrangements shown in the ap­plicable figures show local sensing and program­ming.
3-33 In order to maintain the temperature coeffi-
cient and stability specifications of the power
supply, the external resistors (Rx) shown in Figure 3-8 should be stable, low noise, low temperature
coefficient (less than 30ppm per degree Centigrade)
resistors. The value of each resistor is dependant
on the maximum voltage rating of the master sup-
ply,
The value of Rx is this voltage divided by the
voltage programming current of the slave supply
(l/Kp where Kp is the voltage programming coeffi-
cient). The voltage contribution of the slave is
determined by its voltage control setting.
TM 11-6625-2965-14&P
3-34 Auto-Parallel. The strapping patterns for Auto-Parallel operation of two and three plies are shown in Figure 3-9. Auto-Parallel op­eration permits equal current sharing under all load conditions, and allows complete control of the out­put current from one master power supply. The out­put current of each slave will be approximately equal to the master’s regardless of the load condi­tions. Because the output current controls of each
slave are operative, they should be set to maximum to avoid having the slave revert to constant current operation; this would occur if the master output current setting exceeded the slave’s. In Model
6205B, it is necessary to make internal connections
in order to operate the supply in this mode. The
internal connections, specified in Figure 3-9, made to the sampling terminals of the current sam-
pling terminals of the current sampling resistor,
R54 (see Figure 5-2).
power sup-
are
3-5
TM 11-6625-2965-14&P
3-35 AUTO-TRACKING OPERATION (See Figure 3-10)
3-36 The Auto-Tracking configuration is used when it is necessary that several different voltages referred to a common bus, vary in proportion to the setting of a particular instrument (the control or master).
A fraction of the master’s output voltage is fed to the comparison amplifier of the slave sup­ply, thus controlling the slave’s output. The mas­ter must have the largest output voltage of any
power supply in the group (must be the most posi-
tive supply in the example shown on Figure 3-10).
3-37 The output voltage of the slave is a percent­age of the master’s output voltage, and is deter­mined by the voltage divider consisting of R Rx and R
supply, R
Y) and the voltage control of the slave
, where:
p
E
M RP
E = Rx+Rp
S
Turn-on and turn-off of the power supplies is con­trolled by the master.
Remote sensing and pro­gramming can be used; although the strapping pat­terns for these modes show only local sensing and programming.
In order to maintain the temperature
coefficient and stability specifications of the pow-
er supply, the external resistors should be stable, low noise, low temperature (less than 30ppm per
O
C) resistors.
3-38
SPECIAL OPERATING CONSIDERATIONS
X (or
not desired, set the preset limit for the peak re­quirement and not the average.
3-41 OUTPUT CAPACITANCE
3-42 An internal capacitor, acress the output ter­minals of the power supply, helps to supply high­current pulses of short duration during constant voltage operation.
Any capacitance added exter-
nally will improve the pulse current capability, but
will decrease the safety provided by the current
limiting circuit.
A high-current pulse may damage
load components before the average output current is large enough to cause the current limiting cir­cuit to operate.
3-43 REVERSE VOLTAGE LOADING
3-44 A diode is connected across the output ter­minals.
Under normal operating conditions, the diode is reverse biased (anode connected to neg­ative terminal).
If a reverse voltage is applied to the output terminals (positive voltage applied to negative terminal), the diode will conduct, shunt­ing current across the output terminals and limit­ing the voltage to the forward voltage drop of the diode.
This diode protects the series transistors
and the output electrolytic capacitors.
3-45 REVERSE CURRENT LOADING
3-39 PULSE LOADING
3-40 The power supply will automatically cross over from constant voltage to constant current op­eration in response to an increase (over the preset
limit) in the output current, Although the
preset
limit may be set higher than the average output
current high peak currents (as occur in pulse load­ing) may exceed the preset current limit and cause crossover to occur.
If this crossover limiting is
3-46 Active loads connected to the power supply may actually deliver a reverse current to the power supply during a portion of its operating cycle. An external source cannot be allowed to pump current into the supply without loss of regulation and pos­sible damage to the output capacitor.
To avoid these effects, it is necessary to preload the sup­ply with a dummy load resistor so that the power supply delivers current through the entire operat­ing cycle of the load device.
3-6

SECTION IV

PRINCIPLES OF OPERATION
REFERENCE REGULATOR
CIRCUIT
TM 1 I-6625-2965-14&P
t
AC
INPuT TRANSFORMER
POWER
NOTE
— DENOTES VOLTAGE
— DENOTES CURRENT
FEEOBACK PATH VOLTAGE
LIMIT PATH
I
~o
Pm
RANGE
SWITCH
(s2)
BIAS
SUPPLY
RECTIFIER
AND
FILTER
Figure 4-1.
IAS
B
v
VOLTAGES
SERIES
REGULATOR
A
DRIVER
AMPL
Overall Block Diagram
CURRENT LIMITING CIRCUIT
+
4
*
CURRENT
sAMPLING
RESISTORS
CONSTANT
INPUT
CIRCUIT
CIRCUIT
P/o
2
4
4
4
4
4
1,
Q
4-1 OVERALL DESCRIPTION
4-2
Figure 4-1 shows one section of the Model
6205B
dual power supply. The supply
consistsof
two dual range sections; each identical to the other. Each section consists ofa rectifier and fil-
ter, a series regulator, an error amplifier and driver,
a constant voltage input circuit, a
cument limiting
circuit, a reference regulator circuit, a bias supply, and a metering circuit.
Since both sections of the
supply are identical, only one section is described
below.
4-3 The ac line voltage is first applied to the
power transformer, The tap for the appropriate voltage range is selected by S2. The input is then rectified and filtered. This raw dc is then fed to the series regulator which alters its conduction to
obtain the proper regulated dc output voltage. 4-4 Any changes in output voltage are felt by
constant voltage comparator which compares a portion of the output with a fixed reference volts ge.
If a difference exists, the comparator circuit sends a n error signal to the series regulator via the error amplifier and driver stages. This error signal
changes the conduction of the series regulator so that a constant output voltage is maintained.
4-5 Changes
in output current are reflected in the
voltage drop across the current sampling resistor network. If this voltage drop exceeds a preset limit, the current limit transistor conducts, sending a turn-down signal to the series regulator via the driver. This signal changes the conduction of the
4-1
the
TM 11-6625-2965-14&P
series regulator so that the output current is limited to the proper value.
4-6 The reference circuit provides stable refer­ence voltages used in the constant voltage compar­ator and current limit circuits. The bias circuit provides the less critical bias voltages used in the
supply. 4-7 The meter circuit provides a continuous indi-
cation of output voltage or current in both ranges.
4-8 DETAILED CIRCUIT ANALYSIS
4-9 FEEDBACK LOOP 4-10 The feedback loop functions continuously to
keep the output voltage constant during normal op-
eration of the supply. For purposes of this discus­sion, assume that the output voltage instantane-
ously rises (goes positive) due to a variation in the
external load circuit. Note that the change may be in the form of a slow rise in the output voltage or a positive going ac signal. An ac signal is coupled
to summing point A6 through capacitor Cl and a dc
voltage is coupled to A6 through R 10.
4-11 The rise in output voltage causes the voltage at A6 and thus the base of Q1A to decrease (go neg­ative). Q1A now decreases its conduction and its
collector voltage rises. The positive going error
voltage is amplified and inverted by Q3 and fed to the base of the series transistor(s) via emitter fol-
lower Q4. The negative going input causes the
series transistor(s) to decrease its conduction so that it drops more of the line voltage, reducing the
output voltage to its original level.
4-12 If the external load resistance decreases to
a certain crossover point, the supply will operate
in the current limiting mode. In the current limit
mode, Q1O conducts sending a negative going,
turn-down signal to the series regulator via driver
Q4 .
4-13 SERIES REGULATOR
4-14 The series regulator consists of transistor stage Q7 (and Q6 on Model 6206 B). The regulator serves as a series control element by altering its conduction so that the output voltage is kept con­stant and the current limit is never exceeded, The conduction of the transistor(s) is controlled by the feedback voltage obtained from driver Q4. Diode
CR11, connected across the regulator circuit, pro­tects the series transistor(s) against reverse volt­ages that could develop across it during parallel or auto-parallel operation if one supply is turned on
before the other.
4-15 CONSTANT VOLTAGE COMPARATOR
4-16 The circuit consists of the coarse and fine programming resistors (Rl0A and R 10 B), and a dif­ferential amplifier stage (Ql and associated com-
ponents). Transistor Q1 consists of two transistors housed in a single package. The transistors have matched characteristics minimizing differential voltages due to mismatched stages. Moreover, drift due to thermal differentials is minimized, since both transistors operate at essentially the same temperature.
4-17 The constant voltage comparator continuous­ly compares a fixed reference voltage with a por­tion of the output voltage and, if a difference ex-
ists, produces an error voltage whose amplitude and phase is proportional to the difference. error output is fed back to the series regulator, through the (mixer) error and driver amplifiers. The error voltage changes the conduction of the series regulator which, in turn, alters the output voltage
so that the difference between the two input volt­ages applied to the differential amplifier is reduced to zero. voltage constant.
4-18 Stage Q1B of the differential amplifier is connected to a common (+S) potential through im­pedance equalizing resistor R5. Resistors R6 and R8 are used to zero bias the input stage, offset­ting minor base-to-emitter voltage differences in Q1. The base of Q1A is connected to a summing point at the junction of the programming resistors and the current pullout resistors, R12 and R13. Instantaneous changes in output voltage result in
an increase or decrease in the summing point po­tential. Q1A is made to conduct more or less, in accordance with summing point voltage change.
The resultant output error voltage is fed back to
the series regulator via the remaining components of the feedback loop. the base Q1A, limits the current through the pro-
gramming resistors during rapid voltage turn-down. Diodes CR1 and CR2 form a limiting network which
prevent excessive voltage excursions from over driving stage Q1A. programming resistors, increases the high frequen­cy gain of the input amplifier. Resistor R1 3, shunt-
ing pullout resistor R12, is factory selected so
that all of the + 6.2 Volt reference is dropped across
R12 and R13. Linear constant voltage programming is assured with a constant current flowing through R1O.
removed to avoid current surges and increase the programming speed.
4-19 ERROR AMPLIFIER AND DRIVER
4-20 The error and driver amplifiers amplify the error signal from the constant voltage comparator circuit to a leve1 sufficient to drive the series regulator transistor(s). current limiting input if Q10, the current limiting transistor, conducts.
The above action maintains the output
Resistor Rl, in series with
Capacitor Cl, shunting the
C20 stabilizes the feedback loop and may be
Driver Q4 also receives a
The
4-2
4-21 Stage Q3 contains a feedback equalizer net­work, C5 and R30, which provides for high fre­quency roll off in the loop gain in order to stabilize the feedback loop. Q17 establishes a stable emit­ter bias potential for error amplifier Q3. Emitter follower transistor(s) Q4 (and Q5) serves as the driver (and predriver) element for the series regula-
tor.
4-22 CURRENT LIMIT CIRCUIT
4-23 The current limit circuit limits the output current to a preset value determined by the setting of R81. Switch S2B selects the proper sampling resistance to maintain an equal voltage drop acress the current sampling network in both ranges.
TM 11-6625-2965-14&P
4-28 The reference circuit consists of series reg­ulating transistor Q9 and error amplifier Q8. Out­put voltage changes are detected by Q8 whose base is connected to the junction of a voltage divider
(R41, R42) connected directly across the supply.
Any error signals are amplified and inverted by Q8 and applied to the base of series transistor Q9. The series element then alters its conduction in the direction, and by the amount, necessary to main­tain the voltage across VR1 and VR2 constant. Re­sistor R46, the emitter resistor for Q8, is connected in a manner which minimizes changes in the refer-
ence voltage caused by variations in the input line.
Output capacitor C9 stabilizes the regulator loop.
4-29 METER CIRCUIT (Figure 4-2)
4-24 When S2 is set to the 20 Volt position, R54 and R55 are connected in parallel. When S2 is set to the 40 Volt position, the current sampling net­work consists solely of R54. Note that in the
twenty Volt range, twice as much current can be
delivered as in the forty Volt range. Since the twenty Volt range has a sampling resistance equal to half the value of that for the forty Volt range, an equal sampling resistor voltage drop is obtained in both ranges. This also applies to S2 in the 6206B.
4-25 R81 sets the bias of Q10, and thus, the threshold point at which Q10 conducts and current
limiting begins. If this threshold is exceeded, Q10 begins to conduct, forward biasing CR16 and send-
ing a turn-down signal to the series regulater via
the driver. If the current through the current sam­pling network decreases below the threshold point, Q10 turns off and no longer affects the operation of
the supply.
4-26 REFERENCE CIRCUIT
4-27 The reference circuit (see schematic) is a feedback power supply similar to the main supply. It provides stable reference voltages which are used throughout the unit. The reference voltages are a 11 derived from smoothed dc obtained from the full wave rectifier (CR22 and CR23) and filter cap­acitor C10. The +6.2 and -6.2 voltages, which are used in the constant voltage input circuit for com­parison purposes, are developed across temperature compensated Zener diodes VR1 and VR2. Resistor
R43 limits the current through the Zener diodes to establish an optimum bias level.
4-30 The meter circuit provides continuous indi­cations of output voltage or current on a single multiple range meter.
The meter can be used either
as a voltmeter or an ammeter depending upon the
position of the METER section of switch S2 on the front panel of the supply. This switch also selects one of two meter ranges on each scale. The meter circuit consists
of METER-RANGE switch S2, vari-
ous multiplying resistors and the meter movement. 4-31 When measuring voltage, the meter is placed
directly across the output of the supply between the +S and -S terminals. With the METER section of S2A in the higher voltage position (terminals A2
and A10) multiplying resistors R60, R61, R72, and
the parallel combination of R73 and R87, are in series with the meter. For low output voltages, the
METER switch S2A can be set to the first position
(terminals 1 and 9) which removes R61 from its series position allowing a larger percentage of the
output voltage to be felt acress the meter.
4-32 When measuring current; the meter circuit is
connected across the current sampling resistor network as shown on Figure 4-2 and indicates the output current that flows through the network. The RANGE section S2B connects the appropriate re-
sistance in series with the meter so that its maxi-
mum deflection range is full-scale in the high cur­rent (low voltage) operating mode and half-scale in the low current (high voltage) operating mode. This circuit obviates the need for a dual current scale
which would be necessary since the voltages drop-
ped across the current sampling network in both operating modes are equal for proportional currents.
4-3
Loading...
+ 47 hidden pages