Honeywell Zio TR70, Zio TR70-H User Manual

Zio™ LCD Wall Modules
TR70 AND TR70-H with Sylk™ bus
• Programmable for: Home screen options, tenant
• Eight pre-programmed configurations (e.g. VAV with
• Ability to access and adjust most parameters in the
• Ability to balance the VAV system from the wall
• Home screen can display one to three of any of the
• Network bus jack.
• Simple 2-wire terminal connection to the
The TR70 and TR70-H are 2-wire, non-polarity sensitive, Sylk bus communicating wall modules for use with Spyder™ (PUL6438S, PVL6436AS, and PVL6438NS models only) and ComfortPoint™ (CP-UL6438S, CP-VL6436AS, and CP-VL6438NS models only) programmable controllers.
All models have a space-temperature sensor, network bus jack, and an LCD panel with three softkeys and two Up/Down adjustment keys. The TR70-H model includes an onboard humidity sensor.
NOTE: Refer to the Zio™ LCD Wall Modules TR70 and
TR70-H with Sylk™ bus – Operating Guide (form 63-2667) for information about customizing the wall module configuration, such as modifying the default Home screens or creating your own application.

FEATURES

The TR70 and TR70-H wall modules include:
• Ability to control user access to controller parameters.
• Customized parameter access, by using the Tridium Niagara Workbench tool.
• Retention of user configuration, including setpoints

SPECIFICATIONS

Construction: Two-piece construction, cover and internally
Mounting Options: The LCD wall modules can be mounted
Dimensions (H/W/D): See Fig. 2 on page 2.
Environmental Ratings:
Temperature Setpoint Range: Default range is 55°F to 85°F
Temperature Sensor Accuracy: ±0.36°F at 77°F (±0.2°C at
SPECIFICATION DATA
access, contractor access, access to controller parameters, setpoint, override, fan, and other parameters.
balancing) in the wall module configuration tool.
programmable controller (except Scheduling).
module.
following parameters: Temperature Setpoint, Room Temperature, Room Humidity, Outdoor Humidity, Outdoor Temperature, and Time, or one of virtually any parameter in the controller.
programmable controller and an optional 2-wire terminal connection for the network. All connections are polarity insensitive.
after a power outage.
wired subbase. Field wiring, 18 to 24 AWG (0.82 to 0.20 sq. mm), connects to a terminal block in the subbase.
on a standard two by four inch junction box or on a 60 mm diameter junction box. The modules may be mounted up to 200 ft. (61 m) from the programmable controller. Twisted pair wiring is recommended for distances longer than 100 ft. (30.5 m).
Operating Temperature: 30°F to 110°F (-1°C to 43°C) Shipping Temperature: -40°F to 150°F (-40°C to 65.5°C) Relative Humidity: 5% to 95% non-condensing
(10°C to 35°C); configurable for other ranges.
25°C)
63-1322-01
ZIO™ LCD WALL MODULES
Humidity Sensor Accuracy (TR70-H only): ±5% RH from
20% to 80% RH
Power: 18 Vdc power is supplied to the wall module from the
2-wire S-BUS connection to the programmable controller.
Accessories: 50007298-001 (pack of 12) medium, cover
plate; 6-7/8 x 5 in. (175 x 127 mm).
Approvals:
CE; UL94-HB plastic enclosure; FCC Part 15,
Class B

Terminal Wiring Location

Fig. 1 illustrates the location of the terminal block and other features on the TR70 and TR70-H wall modules.
NET-2
(optional)
S-BUS
4321
S-BUS
HONEYWELL
PATENT PENDING
GOLDEN VALLEY,MN
ASSEMBLED IN MEXICO
SLOTS FOR SUBBASE LOCKING TABS (X4)
WALL MODULE BUS ADDRESS DIAL (DEFAULT SETTING = 1)
S-BUS PROGRAMMABLE CONTROLLER CONNECTION
1
NETWORK BUS CONNECTION
M27349
NET-1
(optional)
TR70-H
YY WK
50028668-XXX
2
1
3
0
4
9
5
6
8
7
1 2 3 4
EACH OF T HE TWO WIRE CO NNECTI ONS FOR THE S- BUS AND NETW ORK
1
BUS TERM INALS ARE PO LARITY IN SENSITIVE.
Fig. 1. LCD wall module components (rear view of TR70).
NOTES:
1. 18 Vdc power for the LCD wall modules is sup­plied from the programmable controller.
2. Each of the 2-wire connections for the network bus and S-BUS are polarity insensitive.

Module Dimensions

3 5/16 (84)
4 5/8 (117)
15/16
(24)
M27347
Fig. 2. Wall module dimensions in inches (mm).

Communications

The wall modules use a sensor bus (S-BUS) for communications with the programmable controller.
For network communication, the building’s LON network wires connect to the two terminals (NET-1 and NET-2). See Fig. 1. A network bus port is accessible at the bottom of the wall module by removing the jack plug.
The network bus and S-BUS terminals (see Fig. 1) are insensitive to polarity, minimizing installation errors due to mis-wiring. The recommended wire size for the network bus and S-BUS is Level IV, 22 AWG (0.33 sq. mm) plenum or non­plenum rated, unshielded, twisted pair, solid conductor wire.

LCD Display

The LCD display may be customized for tenant and contractor users. The following are a few samples of the various Home screens that are configurable for the LCD Wall Modules. Not all possible Home screens are illustrated here. There are many other configurable Home screens.
63-1322—01 2
NOTES:
1. Home screens can display one to three of any of the following parameters: Temperature Setpoint, Room Temperature, Room Humidity, Outdoor Humidity, Outdoor Temperature, and Time, or one of virtually any parameter in the controller.
2. Refer to the Zio™ LCD Wall Modules TR70 and TR70-H with Sylk™ bus – Operating Guide (form 63-2667) for information about customizing the wall module configuration, such as modifying the default Home screens or creating your own appli­cation.