Honeywell Y9520Z, DT92E, ST9520C Installation Instructions Manual

1
95-3 Wireless room thermostats, wired valves, wireless
TPI boiler control
95-1 Wireless room thermostats, wired valves, wired TPI
boiler control
95-2 Wireless room thermostats, wired valves, OpenTherm 2
wire boiler control
Y9520Z Sundial RF² Pack 5
INSTALLATION INSTRUCTIONS
50047644-006 A
Application
This pack provides a wireless control solution for adding 2 wireless room thermostats to heating systems, in order to split the heating system into 2 separate zones and ensure compliance with the latest Building Regulations.
Pack Contents & Product Descriptions
1 x ST9520C1005 Wireless enabled 7 day programmer with 2
output control relays for switching boilers, pumps and zone valves in heating systems. It requires permanent mains 230Vac power.
2 x DTS92E1020 Wireless digital room thermostat with energy
saving ECO function. It operates on 2 x AA alkaline batteries, giving a battery life of at least 2 years under typical operating conditions.
2 x table stand for DT92E (optional)
Other Honeywell products, not supplied in this pack, may be required for a complete installation, depending on the application. For example BDR91T1004 relay box. See Schematic System Layouts (below) or refer to www.honeywelluk.com for full details.
Schematic System Layouts
System Operation
DT92E and ST9520C use 2-way communication on an 868MHz radio frequency (RF) band to control the heating system.
ST9520C operates as the control hub of the system and the DT92E thermostats are free to be positioned in suitable locations in the 2 separate heating zones.
This functionality is ideal for upgrading existing systems without a room thermostat to ensure compliance with Building Regulations. It is also ideal for refurbished systems, where running mains cable from the programmer to the thermostats and back to the boiler is difficult or impractical.
There are various options for how to connect to the boiler. The simplest is a direct 230Vac connection. If the boiler supports OpenTherm communications technology, it is possible to control it using a 2-wire connection from the ST9520C OpenTherm terminals. If the boiler is located remotely, it is possible to send the switching signal from the ST9520C to a remote located BDR91T relay box.
2-way wireless
communication
Honeywell
Sundial RF² is a registered trademark of Honeywell Inc.
OpenTherm® communication
V4043H
ZONE 1
ZONE 2
V4043H
Radiator(s)
Radiator(s)
DT92E
DT92E
ST9520C
Junction
Box
Junction
Box
Junction
Box
Hot Water
V4043H
ZONE 1
ZONE 2
V4043H
Radiator(s)
Radiator(s)
DT92E
DT92E
ST9520C
Boiler
Hot Water
BDR91T
V4043H
ZONE 1
ZONE 2
V4043H
Radiator(s)
Radiator(s)
DT92E
DT92E
ST9520C
Boiler
Hot Water
OpenTherm®
2-wire connection
This document is to be left with the user
2
The RF link between the Room Thermostats (DT92E) and the Zone Programmer (ST9520C) in Honeywell system packs is pre-configured at the factory and therefore all units should be installed at the same site.
• Ifproducts fromindividual systempacks areseparated, ormixed
with other pre-configured system packs during installation, or a faulty unit is being replaced, the desired units must be specially configured to allow them to communicate with each other. This process is called Binding. Please refer to section 6 Binding / Re- binding Procedure.
• DT92E or ST9520Cwillnotcommunicate with other RF products
that use different frequencies or communications protocols.
• TheDT92E roomthermostatrequires nopower sourceotherthan
the batteries provided.
• The ST9520C Programmer requires a permanent 230V~ supply.
• The ST9520C Programmer should be installed and powered up
before commencing installation on the DT92E room thermostats.
• IfcontrollingtheboilerviaanOpenThermconnection,theST9520C
must be configured to provide this form of output (see Section 4 System Configuration)
• Ifthe boilerisbeingswitchedusingaremote relaybox(BDR91T)
the relay box is not supplied in this pack and will require to be bound to ST9520C (see Section 6 Binding / Re-binding Procedure)
Within a typical house two RF products should communicate reliably within a 30m range. It is important to take into consideration that walls and ceilings will reduce the RF signal. The strength of the RF signal reaching the Programmer depends on the number of walls and ceilings separating it from the room thermostat, as well as the building construction - the diagram below illustrates an example of typical signal strength reduction. Walls and ceilings reinforced with steel or plasterboard walls lined with metal foil reduce the RF signal significantly more.
RF Signal Propagation
Installation Notes Installation Sequence: Step by Step
Typical example of Building Fabric Signal losses
= Signal Strength
Wall Wall Wall
Ceiling
Max. Signal Length 30 metres
Section Page
1 INSTALLING THE ST9520C PROGRAMMER
1.1 Mounting ST9520C .................................................................. 3
1.2 ST9520C Mounting options ..................................................... 3
1.3 Wiring ST9520C ....................................................................... 3
1.4 ST9520C Final Assembly ......................................................... 3
1.5 ST9520C Internal Wiring .......................................................... 4
1.6 Wiring Diagrams ...................................................................... 4
1.7 Replacing Other Time Controls ............................................... 5
1.8 Powering Up ST9520C ............................................................ 5
2 INSTALLING THE DT92E ROOM THERMOSTAT
2.1 Locating DT92E ....................................................................... 6
2.2 Powering Up DT92E ................................................................ 6
2.3 DT92E Signal Strength Test ..................................................... 6
2.4 Mounting DT92E ...................................................................... 7
2.5 Separating DT92E from its Mounting Plate .............................. 7
3 INSTALLING THE BDR91T WIRELESS RELAY BOX
3.1 Locating the BDR91T............................................................... 8
3.2 BDR91T Mounting Options ...................................................... 8
3.3 Wiring BDR91T ........................................................................ 8
3.4 BDR91T Final Assembly .......................................................... 8
4 SYSTEM CONFIGURATION: ST9520C
4.1 ST9520C Installer Modes......................................................... 9
4.2 Boiler Service Reminder / Shut-down Feature ......................... 9
4.3 Installer Setup ........................................................................ 10
4.4 Installer Setup Flowchart ....................................................... 11
4.5 OpenTherm Setup and Information Display .......................... 11
4.6 Set Service ............................................................................. 12
4.7 Change PIN ........................................................................... 14
4.8 What the User Will See When a Service is Due ..................... 14
4.9 Resetting the Service Timer Function .................................... 14
5 SYSTEM CONFIGURATION: DT92E
5.1 DT92E Installer Mode ............................................................ 15
6 BINDING / RE-BINDING PROCEDURE
6.1 Binding................................................................................... 16
6.2 ST9520C Guided Binding Menu ............................................ 16
6.3 Replacing Devices or Changing the Application .................. 16
6.4 Binding Menu Display............................................................ 17
6.5 How to Bind DT92E to ST9520C ............................................ 17
6.6 How to Bind BDR91T to ST9520C ......................................... 18
6.7 How to Test BDR91T Signal Strength .................................... 19
7 COMMISSIONING THE SYSTEM
7.1 System Test Checklist ............................................................ 20
7.1 Completion Checklist ............................................................. 20
3
For best performance, install in an open space. Leave at least 30cm distance from any metal objects including pipes and the boiler housing.
After locating the DT92E room thermostats, use the Signal Strength Test shown on Page 7 to determine if there is a reception problem. If problems persist, it is recommended that this metal wallbox is replaced by an equivalent plastic wallbox.
The Programmer should be mounted at a level where the display can be seen clearly, (compliance with Building Regulations part M requires a height of 1.2m from the floor) and the ambient temperature is within the range of 0 to 40°C. The ST9520C is for use in normal domestic environments.
To remove the unit from the wall-plate, slacken the two securing screws at the bottom of ST9520C and hinge the unit up to separate the two halves.
1
INSTALLING THE ST9520C PROGRAMMER
1.1 Mounting ST9520C
CAUTION
Isolate power supply and make safe before wiring the unit to prevent electric shock and equipment damage. Installation should be carried out by a qualified electrician or competent heating engineer.
Recommended clearance distances:
Above wallplate: 110mm Below wallplate: 100mm Left/right of wallplate: 10mm
a. Surface mounting concealed wiring b. Flush switchbox
Fixing holes are spaced to suit
BS4662 requirements
c. Surface mounting with
surface wiring in mini trunking
Clip the unit onto the hinges on the top of the wallplate and hinge down into position. Tighten the two securing screws using a screwdriver.
Switch on the power – the unit will now be operating according to the built-in programme.
Note: the ST9520C is supplied with a factory set clock for faster installation.
Refer to Y9520Z User Guide for programming details.
Ensure the mounting surface is supporting and fully covers the wiring wall-plate.
ALL WIRING MUST BE IN ACCORDANCE WITH IEE REGULATIONS. THIS UNIT IS FOR FIXED WIRING ONLY.
A switch, having contact separation of at least 3mm in all poles must be incorporated in the fixed wiring as a means of disconnecting the supply.
The unit is a Class II (double insulated) device. A parking terminal is provided for external earth continuity.
The system must be appropriately fused. A fuse rated at no more than 3 Amps should be installed.
The unit has 4 knockouts for surface wiring. Care must be taken to ensure that the cable or mini-trunking completely fills the knockout hole without leaving any gaps.
If the OpenTherm 2 wire connection is used, maintain as large a separation as possible between these wires and any mains voltage wiring.
EMC compliance considerations
Keep AC mains supply/load cables separate from signal wiring.
Refer to Code of Practice standards EN61000-5-1 and -2 for guidance.
1.2 ST9520C Mounting Options
1.3 Wiring ST9520C
1.4 ST9520C Final Assembly
4
Notes
1. DT92E is completely wireless and so is not shown connected on these wiring diagrams.
2. The ST9520C is a Class II (double insulated) device. A parking terminal is provided for earth wiring continuity, if required.
3. The OpenTherm boiler connection (diagram 95-2) is a low voltage polarity-free connection and is not for 230V~ mains voltages.
4. The BDR91T Relay Box (diagrams 95-3) requires a permanent 230V~ supply.
1.6 Wiring Diagrams
1.5 ST9520C Internal Wiring
Clock
N L 1 2 3 4
3 AMPS MAX
Zone1
OFF
Zone2
OFF
Zone1
ON
Zone2
ON
N L
OFF ON OFF ON
230V~
50...60Hz
A B
OpenTherm low voltage
output to boiler.
NOT MAINS
95-1 Wireless room thermostat, wired valves, wired TPI boiler control
95-2 Wireless room thermostat, wired valves, OpenTherm 2 wire boiler control
V4043H
2 PORT ZONE VALVE
ZONE 2
BLUE
G/YELLOW
BROWN
ORANGE
GREY
V4043H
2 PORT ZONE VALVE
ZONE 1
BLUE
G/YELLOW
BROWN
ORANGE
GREY
3 AMPS
MAX
L N
230V~
50...60Hz
BOILER
PUMP
L N E
ST9520C
*NOTE 2
N
L 1 2 3 4AB
T1
L N E
1 2 3 4 5 6 7 8 9 10
V4043H
2 PORT ZONE VALVE
ZONE 2
BLUE
G/YELLOW
BROWN
ORANGE
GREY
V4043H
2 PORT ZONE VALVE
ZONE 1
BLUE
G/YELLOW
BROWN
ORANGE
GREY
3 AMPS
MAX
L N
230V~
50...60Hz
BOILER
PUMP
L N E
ST9520C
*NOTE 2
N
L 1 2 3 4AB
T1
T2
PL
L N E
1 2 3 4 5 6 7 8 9 10
Additional notes
a. Orange wires from zone valves are ‘parked’ for
convenience.
b. Pump live is taken from boiler. If boiler does not
provide this output, connect live input to pump from terminal 10
5
95-3 Wireless room thermostat, wired valves, wireless TPI boiler control
Check the unit powers up correctly and that the display does not remain blank.
ST9520C must be powered up before the DT92E thermostats are installed, so that the signal strength tests can be conducted.
The initial signal strength test will verify that both units have each others addresses in their memory, and can therefore communicate. The process of writing respective addresses into memory is called BINDING.
ST9520C is supplied with its own wiring back-plate. As this is for new or upgraded installations it is recommended this is used, and it MUST be used for OpenTherm applications (95-3).
ST9520C may mount on the back-plate of existing time controls, but it is likely major wiring changes will be required for compatibility with the plumbing and controls changes. Refer to the Honeywell Technical Help Desk for advice.
1.8 Powering Up ST9520C
1.7 Replacing Other Time Controls
1.6 Wiring Diagrams (cont.)
Additional notes
a. Orange wires from zone valves are ‘parked’ for
convenience.
b. Pump live is taken from boiler. If pump is located next
to zone valves, take the pump N and E from the 10-way junction box (terminals 2 & 3 respectively) and the pump switched Live from terminal 10.
V4043H
2 PORT ZONE VALVE
ZONE 2
BLUE
G/YELLOW
BROWN
ORANGE
GREY
V4043H
2 PORT ZONE VALVE
ZONE 1
BLUE
G/YELLOW
BROWN
ORANGE
GREY
3 AMPS
MAX
5 AMPS
MAX
L N
L N
230V~
50...60Hz
230V~
50...60Hz
BOILER
PUMP
L N E
ST9520C
BDR91T
*NOTE 2
N
L 1 2 3 4
N
L L
A
B
T1
T2
PL
L
N
E
1 2 3 4 5 6 7 8 9 10
A-B:5(3)A A-C:5(3)A
A
B C
6
This pack contains 2 x DT92E room thermostats for location in each control zone. The DT92E for Zone 1 has a zone ID label number 1 under the battery cover. The other DT92E has zone ID label 2. These thermostats must be located in the correct zone to ensure the correct valve is operated in response to their commands.
For best performance, install each DT92E in an open space where it can sense the room temperature, and where the signal strength is high.
The Room Thermostats can be mounted on a wall or on the optional table stand. Do not mount on metal wall-boxes.
Leave at least 30cm distance from any metal objects and at least 1 metre from any other electrical equipment.
Select the preferred location and test the Signal Strength before installation.
2
INSTALLING THE DT92E ROOM THERMOSTATS
2.1 Locating DT92E
DT92E is supplied in the pack with the mounting plate separated from the rest of the unit for ease of installation. The next sequence of operations should be done before mounting DT92E onto its mounting plate.
First hold DT92E between 1 and 2 meters away from ST9520C. To power it up, unclip the battery cover and then remove the paper tab that isolates the batteries from their contacts. When the display powers up the battery cover should be clipped back on.
Immediately on power up, DT92E will try to communicate and synchronise with ST9520C. This process may take up to 4 minutes, and will be indicated by the word ‘Sync’ on the DT92E display.
When ‘Sync’ disappears from the display, DT92E is ready for a test of the RF signal strength between it and the ST9520C programmer.
Now go to section 2.3 to conduct the Signal Strength Test.
2.2 Powering Up DT92E
1
2
Honeywell 2-way RF communications allows signal strength testing to ensure DT92E can be positioned in the best possible location.
To enter Signal Strength Test:
a. Hold down the button for 2 seconds until the symbol is
displayed.
b. Hold down the
and
buttons together for 3 seconds until ‘Inst’
appears in the display.
c. Press the button (‘Cont’ is now displayed)
d. Hold the button for 3 seconds to enter Test mode.
e. Signal Strength Test is entered from Test mode by holding the
button for 3 seconds, until the display shows ‘SS’.
Step 1
Hold DT92E between 1 and 2 meters away from ST9520C and check the signal strength is high
(3 or more). This confirms the two units are in the condition they left the factory and are bound together, and you can move to Step 2.
If the signal strength is shown as 0, the units are possibly not bound together. Go to the
section 6 Binding / Rebinding, follow the procedure there, and then repeat the complete Signal Strength Test sequence.
Step 2
Whilst staying in Signal Strength Test mode, take the DT92E to the preferred location. Wait for
10 seconds and check the signal strength is 3 or more. If so, the DT92E is ready to mount.
If the signal strength is less than 3, re-position the room thermostat within the local area +/- 1 or
2m to see if the signal strength improves. If this fails, try to reduce the range/distance between the room thermostat and the ST9520C.
2.3 DT92E Signal Strength Test
3 s
2 s
3 s
Poor signal,
reposition Room
Thermostat.
Strong signal,
proceed to
mount the Room
Thermostat.
10 s
= 0, 1, 2= 3, 4, 5
3 s
ST9520C measures the strength of the DT92E signal every 5-10 seconds and will communicate this to DT92E as a number between 0 and 5. The value drops to 0 briefly as each new signal strength measurement is made.
A signal strength of 3 or more is recommended to ensure reliable communications.
Exit Signal Strength Test by holding the button for 5 seconds. The DT92E will timeout of this mode after 10 minutes.
Zone ID Number (1 or 2)
1.2m
Loading...
+ 14 hidden pages