Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
This document and the information in it are the property of Trane and may not be used
or reproduced in whole or in part, without the written permission of Trane. Tranereserves
the right to revise this publication at any time and to make changes to its content without
obligation to notify any person of such revision or change.
Trademarks
Trane and its logo are trademarks of Trane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.
Warnings, Cautions, and Notices
Warnings, cautions, and notices are provided in appropriate places throughout this
document:
WARNING: Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to alert against
unsafe practices.
NOTICE: Indicates a situation that may result in equipment or property-damage-
only accidents.
This section provides a description of the sensors, as well as part numbers and dimensions.
Product Description
The Trane®programmable zone sensor (p/n X1379088401) can be used with UCP, Reliatel, and
IntelliPak control units. It has the following features:
•A liquid crystal display (LCD) with symbols for zone temperature, temperature setpoints,
system operating modes, day of the week, time of day, and occupancy settings
•Configurable to operate with constant-volume (CV) units, heat pump (HP) units, and variableair-volume (VAV) units
•System modes:
– CV: Heat, Cool, Auto, Off
– HP: Emergency Heat, Heat, Cool, Auto, Off
– VAV: Auto, Off
•A cooling setpoint range (occupied) of 45ºF to 98ºF (7.2ºC to 36.7ºC)
•A heating setpoint range (occupied) of 43ºF to 96ºF (6.1ºC to 35.6ºC)
•Two fan modes (CV and HP only): On, Auto
•A table of configurable functional options (see Tab l e 3 , p . 1 4 and Ta bl e 4 , p . 16 )
•Scheduling function: 7 days per week and up to 4 periods per day, occupied/unoccupied mode
•Temporary override function
•During occupied periods, an auxiliary relay rated for 1.25 A @ 30 Vac with one set of single-pole
double-throw contacts is activated.
4BAS-SVX17B-EN
Dimensions
2.9 in (73.5 cm)
1.08 in (27.5 mm)
4.68 in (118.9 mm)
1.34 in (34.14 mm)
0.58 in (14.76 mm)
0.31 in (8 mm)
0.12 in (3 mm)
TYP R.07 in
(R1.80 mm)
3.39 in (86 mm)
0.24 in (6.00 mm)
2.62 in (66.5 mm)
General Information
The following illustration provides specific dimension details. The dimensions are the same for all
models.
BAS-SVX17B-EN5
Pre-Installation
This section provides the following pre-installation information:
•Location considerations
•Height requirements
•Mounting surfaces
•Recommended wire lengths
Location Considerations
Placement of the sensor is critical to proper operation. When selecting a location, avoid the
following:
•Areas of direct sunlight
•Areas in the direct airstream of air diffusers
•Exterior walls and other walls that have a temperature differential between the two sides
•Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys,
or other heat-generating equipment
•Drafty areas
•Dead spots behind doors, projection screens, or corners
•Walls that are subject to high vibration
•Areas with high humidity
•High traffic areas (to reduce accidental damage or tampering)
Height Requirements
It is recommended that you mount the back plate a maximum distance of 54 inches above the floor.
If a parallel approach by a person in a wheelchair is required, reduce the maximum height to 48
inches.
Note: Consult section 4.27.3 of the 2002 ADA (Americans with Disability Act) guideline, and local
building codes, for further details regarding wheelchair requirements.
Mounting Surfaces
Using the hardware provided, mount the back plate to a flat surface such as sheetrock or plaster,
or an electrical junction box. The sensor must be mounted plumb for accurate temperature control
and to ensure proper air movement through the sensor.
•If mounting onto sheetrock or plaster, use the plastic threaded anchors (pre-drilling holes is not
usually necessary) and the two M3.5 x 20 mm mounting screws.
•For mounting onto an electrical junction box, use the two 6-32 x 3/4 in. screws.
•If you are replacing a horizontally mounted sensor and need to cover an opening in the wall,
use the adapter kit (p/n BAYMTPL103A).
6BAS-SVX17B-EN
Wire Length
Pre-Installation
Maximum recommended wire lengths for the sensor are given in Ta b l e 1:
Table 1.Recommended wire lengths
Wire size
AWGmm
220.330–460–150
200.5047–73151–240
180.7574–117241–385
161.30118–185386–610
142.00186–296611–970
Note: The total resistance of these low voltage wires must not exceed 2.5 Ω/conductor. Any resistance greater than 2.5 Ω
may cause the control to malfunction due to an excessive voltage drop.
2
Maximum recommended wire length from unit
controller to sensor
MetersFeet
BAS-SVX17B-EN7
Security screw
Installation
This section provides step-by-step installation instructions. Read through the pre-installation
information before proceeding with the installation.
Note: Before installing the sensor, ensure that:
•A wire access hole is available at the sensor location
•The wires are accessible through the hole
•The wires are attached to the appropriate unit controller
•There is continuity between the sensor location and the unit controller
•The wires are accurately labeled or identified by color
Mounting the Back Plate
WARNI NG
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the sensor will permanently damage it.
Note: Refer to the illustration below when installing the sensor.
1. Shut off power to the unit controller.
2. Remove the cover by firmly pressing the thumb tab at the bottom of the cover and pulling the
cover away from the back plate.
Note: If present, remove the security screw before removing the cover.
3. Determine the number of wires required by referring to Tab le 2 , p . 1 0 .
4. Feed the wires through the opening in the back plate.
5. Hold the back plate against the mounting surface and mark the screw locations.
6. Secure the back plate to the mounting surface using the included hardware.
8BAS-SVX17B-EN
Wiring the Sensor
WARNI NG
Hazardous voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE
Equipment damage!
Applying excessive voltage to the sensor will permanently damage it.
To wire the sensor to the unit controller (see guidelines for wire sizes and lengths in Table 1, p. 7.):
1. Ensure that the wires are connected to the appropriate
2. Connect the wires to the terminal block (included in the hardware package with the sensor). See
Ta b le 2, p. 10 to determine where to terminate wires in the terminal block.
Note: The numbers on the terminal block correspond to the numbers on the terminals of the
3. Attach the terminal block to the pins on the circuit board inside the sensor cover (Figure 1).
Installation
terminals at the unit controller.
unit controllers most frequently used with the sensor.
Figure 1. Attaching the terminal block to the pins on the circuit board
4. Push the excess wire into the wall cavity and plug it with nonflammable insulation to prevent
drafts from affecting the sensor.
Important: Do not coil excess wire inside the back plate.
BAS-SVX17B-EN9
10BAS-SVX17B-EN
Table 2. Programmable zone sensor wiring diagram
3–25 ton
packaged rooftops
split
system
units
27.5–50 ton
packaged rooftops
*CD/*CH/*SC/
3–20
*HC
UCP
control
Sensor
(5)
(2)
(2)
S2Optional remote sensor
S1Optional remote sensor
14 -------14
12 -------1212121212121212121TB8-12
11 -------11111111116711111TB8-11
8-------8888889881TB8-8
7-------7777778771TB8-7
A3
A1
REMOTE SENSOR INPUT
REMOTE SENSOR INPUT
24 VAC INPUT
COMMUNICATIONS
COMMON
SERVICE STATUS (UCM INPUT)10 -------1010101010101110101TB8-10
SYSTEM STATUS (ON/OFF INPUT)9-------99999910991TB8-9
COOL STATUS
(UCM INPUT)
HEAT S TATU S
(UCM INPUT)
AUX RELAY (CLOSED—
UNOCCUPIED)
AUX RELAY (CLOSED—
OCCUPIED)
(1)LTB and LTB1 refer to low-voltage terminal boards with numbers 1–20 and two test terminals.
(2)Connect an optional remote sensor (p/n BAYSENS017) to terminals S1 and S2. Connect the shield wire (drain wire) from the shielded cable to terminal 11.
(3)Connect the 24 Vac power supply from the unit controller to terminals 11 and 14. (IntelliPak power supply voltage is 12–15 Vac.)
(4)Use terminal 15 on older 3–25 ton Voyager units with low-voltage terminal boards numbered 1–18 with two test terminals.
(5)Data communication between the unit controller and the sensor is accomplished by a serial link connected at terminal 12.
(3)
(3)
LTB
(1)
(4)
ReliaTel
Control
The auxiliary relay on the sensor is form C, rated for 1.25 A at 30 Vac. It is energized during occupied periods.AUX RELAY (COMMON)A2
TTA/TWA
ReliaTel
Control
J6
1414141414114141TB11-4
J6
YC*/TC*/TE*
UCP
control
LTB1
ReliaTel
Control J6IntelliPak
(1)
ton
packaged
rooftops
S*HF/
W*HB
1TB4
90–162
ton
packaged
rooftops
S*HJ
IntelliPak
1TB4
20–130
TC
330–600
model
number
10th digit
= A+ L
LTB1
UCP
control
LTB1
YC* TE*
(1)
YC* TE*
TC
330–600
model
number
10th digit
= M+
RTRM J6
ReliaTel
Control
J6IntelliPak
Commercial
self-
contained
(CSC)
S**F, S**G
Installation
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.