Honeywell WT8840 User Manual

WT8840 TRADE WATER HEATER CONTROLS
WARNING
CAUTION
WARNING
WARNING
Perform Gas Leak Test
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
Water Damage Hazard. Can damage electrical components in the WT8840.
Do not spray soap and water solution on the WT8840 housing. Do not use an excessive amount of soap and water to perform the gas leak test.
Gas Leak Test
1. Paint pipe connections upstream of the water
heater control with a rich soap and water solution. Bubbles indicate a gas leak.
2. If a leak is detected, tighten the pipe connection.
3.
Stand clear of the burner while lighting to prevent injury caused from hidden leaks that could cause flashback in the appliance burner compartment.
4. With the burner in operation, paint the pipe
joints (including adapters) and the control inlet and outlet with a rich soap and water solution.
5. If another leak is detected, tighten the adapter
screw, joints, and pipe connections.
6. Replace the part(s) if a leak cannot be stopped.
Check the gas input and burner flow rate
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
Follow these warnings exactly:
1. Do not exceed input rating stamped on appliance nameplate or manufacturer recommended burner orifice pressure for size of orifice(s) used. Follow instructions of appliance manufacturer.
2. IF CHECKING GAS INPUT BY CLOCKING GAS METER: Make certain there is no gas flow through the meter other than to the appliance being checked. Other appliances must remain off with the pilots extinguished (or that consumption must be deducted from the meter reading). Convert flow rate to Btuh as described in form number 70-2602, Gas Controls Handbook, and compare to Btuh input rating on appliance nameplate.
3. IF CHECKING GAS INPUT WITH MANOMETER: Make sure the manual gas shutoff switch is in the OFF position before removing outlet pressure tap plug to connect the manometer (pressure gauge). Also, move the manual gas shutoff switch to the OFF position when removing the gauge and replacing the plug. Also shut off gas supply before disconnecting manometer and replacing plug. Repeat Gas Leak Test at plug with main burner operating.
Procedure to check the gas input and burner flow rate
1.
Check the full rate manifold pressure listed on the appliance nameplate. Water heater control full rate outlet pressure should match this rating.
2. With burner operating, check the water heater
control flow rate using the meter clocking method or check pressure using a manometer connected to the outlet pressure tap on the water heater control. See Fig. 5.
MAINTENANCE
Fire or Explosion Hazard. Can cause severe injury, death or property damage.
Do not attempt to take apart or clean the gas valve inside the WT8840 control. Improper cleaning or reassembly can cause gas leakage.
The maintenance program should include regular checkout of the control as outlined in the Startup and Checkout section, and the control system as described in the appliance manufacturer literature.
Maintenance frequency must be determined individually for each application. Some considerations are:
1. Cycling frequency. Appliances that may cycle
10,000 times annually should be checked monthly.
2. Intermittent use. Appliances that are used
seasonally should be checked before shutdown and again before the next use.
3. Consequence of unexpected shutdown. Where
the cost of an unexpected shutdown would be high, the system should be checked more often.
4. Dusty, wet or corrosive environment. Since these
environments can cause the control to deteriorate more rapidly, the system should be checked more often.
The system should be replaced if:
• It does not perform properly on checkout or troubleshooting.
• The control is likely to have operated for more than 150,000 cycles.
• The control is wet or looks as if it has been wet.
TROUBLESHOOTING
Troubleshooting With Status Indicator Assistance
1. Pilot burner must be lit. If not, push and hold
Pilot knob and light pilot with piezo. Error code will be displayed when thermopile heats up. Error code can be recognized by counting the number of flashes of the status indicator after a three second pause. One single flash (with set point knob in PILOT position) indicates that the control is in normal operation.
2. Observe status indicator on control; check and
repair the system as noted in Table 3 on page 6. Flash codes are displayed with a three-second delay between cycles. A continuous solid light indicates system shutdown when knob is turned from a temperature setting to OFF position. When the solid light is present, the pilot and
5 34-00013EF—03
WT8840 TRADE WATER HEATER CONTROLS
main valve will not hold. When the status indicator goes out, the user can restart the system. (Approximate shutdown time is one minute.)
3. After status indicator analysis and appliance
repair is complete, turn device knob to OFF, wait until the indicator goes out, then perform lighting procedure.
4. Status indicator light should be in normal mode
(1 flash) with the knob in the PILOT position. Turn the device knob past the water temperature in the tank should turn on the main burner. The Status indicator light will strobe every three seconds when there is a call for heat.
5. In the event of multiple failure codes, the next
failure code follows the previous failure code by approximately three seconds with higher flash count first.
Table 3. Troubleshooting with status light visual indication.
LED
Error
**
Normal operation. No action required.
Action required.
Code
1 flash every 3 seconds
Strobe every 3 seconds
2 flashes Low thermopile
4 flashes Temperature cut-out
5 flashes Water temperature
6 flashes Tank leakage
Number of LED Flashes*Detected Failure Recommended Action
Not an error; indicates the electronics is holding the Pilot Valve open and the Main Valve closed.
Not an error; indicates call for heat during normal operation, Main valve open.
voltage; main valve not turned ON.
limit reached.
sensor failure.
detected by accessory module.
You can now turn the knob to a desired setpoint temperature. LED will continue to flash 1 time every 3 seconds while in Idle mode (no call for heat).
None.
Check thermopile and its connections. Check pilot flame.
Check the valves and the water temperature sensor. Reduce the water temperature setpoint. Thoroughly check out main valve operation and water temperature control before walking away.
Check water temperature sensor and its connection for open circuits, shorts, or differences in resistance between the two sensor elements.
Control recovers after receiving message from accessory module.
7 flashes Electronics Failure Replace control module. 8 flashes This is just a warning;
Solid ON Not an error—
*
LED Error Codes are flashed once per second, with a three-second pause between repeating the error code.
**
Maximum two different errors can be displayed simultaneously if more than one error has been detected.
The control does not see power decaying with the knob in the OFF position.
indicates that the control is in OFF mode.
Check valves.
None; wait until LED turns off if you want to restart the system.
34-00013EF—03 6
Loading...
+ 4 hidden pages