WSK-HEAT & WSK-HEAT-ROR
I56-4270-000
Wireless Intelligent
12 Clintonville Road, Northford, CT 06472-1610
Temperature Sensors
SPECIFICATIONS
Maximum Operating Voltage: 3.3 VDC Maximum Standby Current: 210µA LED Current: 10 mA Maximum Transmit RF Power: 17dBm Radio Frequency Range: 902-928 MHz Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing Installation Temperature: 32°F to 100°F (0°C to 38°C) Fixed Temperature Rating: 135°F (57°C ) WSK-HEAT and WSK-HEAT-ROR Rate-of-Rise Detection: Responds to greater than 15°F/minute WSK-HEAT-ROR Battery Type: 4 Panasonic CR123A or 4 Duracell DL123A Battery Life: 2 year minimum Battery Replacement: Upon TROUBLE BATTERY LOW display and/or during annual maintenance Height: 2.4˝ (61 mm) installed in B501W Base Diameter: 4.0˝ (102 mm) installed in B501W Base Weight: 8.1 oz. (230 g) installed in B501W base with 4 batteries
This sensor must be installed in compliance with the control panel system installation manual and the SWIFT Wireless Manual. The installation must meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with the National Fire Protection Association (NFPA); see NFPA 72.
GENERAL DESCRIPTION
Models WSK-HEAT and WSK-HEAT-ROR are intelligent sensors that utilize a state-of-the-art thermistor sensing circuit for fast response. These sensors are designed to provide open area protection with 50 foot spacing capability as approved by UL 521. Model WSK-HEAT is a fixed temperature sensor with 135°F fixed temperature alarm. Model WSK-HEAT-ROR is a rate-of-rise tem­perature sensor with 135° F fixed temperature alarm. Rotary dial switches are provided for setting the sensor’s address. (Figure 1). Two LEDs on the sensor are controlled by the panel to indicate sensor status.
Silent Knight panels offer different features sets across different models. As a result, certain features of the WSK-HEAT and WSK-HEAT-ROR may be avail­able on some control panels, but not on others. The possible features available in the WSK-HEAT and WSK-HEAT-ROR, if supported by the control panel are:
• The panel controls the LED operation on the sensor. Operational modes include red, green and amber colors in various solid or blink patterns.
Please refer to the operation manual for the UL listed control panel for specific operation of the WSK-HEAT and WSK-HEAT-ROR .
The WSK-HEAT and WSK-HEAT-ROR require compatible addressable com­munications to function properly. Connect these sensors to listed-compatible control panels only.
SPACING
Wireless technologies can exhibit communication disruption if devices are spaced too close together. To avoid this form of disruption, SWIFT devices should not be placed closer than 2 feet (60 cm) apart without an intervening structure.
NOTE: Do not attach the base and detectors to temporary structures such as removable ceiling tiles such that the placement could be altered. To prevent changes in device placement, permanently secure the structure or mount the detector across the ceiling panel support as shown in Figure 2.
BATTERY REPLACEMENT
Low battery levels on the wireless devices are displayed as a trouble on an annunciator. Therefore when the message “TROUBLE BATTERY LOW” is dis­played, replace the battery in the device. This message is an indication that approximately one week of battery life remains.
To replace the batteries in a wireless device use the following steps:
1. Have 4 CR123A (or DL123A) batteries available
2. Remove the detector from the base.
3. Open the battery compartment refer to Figure 3. Note: The battery compart­ment cover may be left attached at the hinges during battery replacement.
4. Remove the used batteries and replace with new batteries. The battery compartment is designed such that the batteries can only align in the ap­propriate direction. Do not force the batteries into the openings.
5. Replace the battery compartment cover.
6. Return the device to its original location.
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling or construction.
TAMPER RESISTANCE
Models WSK-HEAT and WSK-HEAT-ROR include a tamper-resistant capability that prevents their removal from the base without the use of a tool. Refer to the base manual for details on making use of this capability. The base also includes a magnet for tamper resistance. The magnet activates a supervisory tamper fault at the panel if the detector is removed from the base.
TESTING
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to
FIGURE 1. ROTARY ADDRESS SWITCHES:
Phone: 203-484-7161 Fax: 203-484-7118
www.silentknight.com
1 I56-4270-000 03-02
C0162-00
Page 2
BATTERY COMPARTMENT COVER
FIGURE 2. CEILING PANEL SUPPORT:
FIGURE 3. BATTERY COMPARTMENT:
Disable the zone or system undergoing maintenance to prevent unwanted alarms.
It is recommended that the sensor be removed from its mounting base for easier cleaning and that sensors be cleaned at least once a year. Use a vacuum cleaner to remove dust from the sensing chamber (Figure 5).
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina­tion has been evaluated and found suitable for that purpose.
C2016-00
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer max­imum performance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
1. Place the optional test magnet against the cover in the magnet test
2. The LEDs should latch on within 10 seconds, indicating alarm and an-
3. Reset the detector at the system control panel.
B. Direct Heat Method (Hair dryer of 1000 – 1500 watts).
1. From the side of the detector, direct the heat toward the sensor. Hold
2. The LEDs on the detector should light when the temperature at the
3. Reset the detector at the system control panel.
A sensor that fails any of these tests should be cleaned as described under CLEANING, and retested. If the sensor fails after cleaning, it must be replaced and returned for repair.
When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke de­tector system is undergoing maintenance and will be temporarily out of service.
C1092-00
area, as shown in Figure 4, to activate the test feature.
nunciating the panel.
the heat source about 6 inches (15 cm) away to prevent damage to the cover during testing.
detector reaches the alarm setpoint. If the LEDs fail to light, check the power to the detector and the wiring in the detector base.
2 I56-4270-000 03-02
Page 3
CHAMBER
LED
TEST MAGNET MARKER
LED
TEST MAGNET MARKER
FIGURE 4. MAGNET TEST MARKERS:
FIGURE 5. DETECTOR COMPONENTS:
WSK-HEAT &
WSK-HEAT- ROR
C0152-00
COVER
REMOVAL
TABS
FM CLASSIFICATION
RTI ratings are for installations which must comply with FM 3210.
WSK-HEAT RTI: FAST
WSK-HEAT-ROR RTI: V2-FAST
SENSOR
COVER
SENSING
C2014-01
3 I56-4270-000 03-02
Page 4
Please refer to insert for the Limitations of Fire Alarm Systems
Use of these products in combination with non-Honeywell products in a wireless mesh network, or to access, monitor or control devices in a wireless mesh nework via the inter­net or another external wide area network, may require a separate license from Sipco, LLC.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation. WARNING: Do not make changes to the equipment. Changes or modifications not expressly approved by the manufacturer could void the user’s authority to operate the equipment.
Silent Knigh® and Honeywell® are registered trademarks of Honeywell International, Inc.
LICENSING STATEMENT
For more information, contact Sipco, LLC or Ipco, LLC at 8215 Roswell Rd., Building 900, Suite 950, Atlanta, GA 303350, or at www.sipocollc.com or www.intusiq.com.
FCC STATEMENT
4 I56-4270-000 ©2017 Honeywell. 03-02
Loading...