Honeywell WS8B2WB User Manual

Page 1
WS8SERIES WALL MODULE
FOR USE WITH FAN COIL UNITS
Extra-large LCD display and operating interface
Temperature display selection (room temperature or set
temperature)
Manual or automatic fan speed selection
Anti-freeze protection
Operating buttons lock / unlock
Temperature range setting
Standard 86 wall-mount installation box
SCOPE OF APPLICATION
WS8 Series wall modules are designed for indoor temperature control. It has large LCD display providing real time display of room temperature or set temperature. With temperature set, it will provide on/off control signal to the fan coil valve for temperature regulation to the occupant’s desired comfort. WS8 Series wall modules provide selectable automatic or manual control of fan speeds. It also provides anti-freeze function.
Ordering Part Numbers
Model
Number
WS8B2WB
/U
Backlight
White
Application
2-pipe
Ventilation Mode
Technical Specification
Operating Voltages
Load Capacity
Temperature Setting Range
Emperature Display Range
Operating Temperature
Relative Humidity
Protection rating
Operating Voltages
Yes
100-240Vac
100VAC-240VAC 50-60Hz
Resistive – Fan unit 3A; valve 2A
Inductive – Fan unit 1A; valve 0.6A
10~30°C 50~86°F
-10~50°C 14~99°F
-30~60°C
-22~140°F
5-90%RH, non condensating
IP20
WS8B4WB
/U
White
2/4-pipe
Yes
100-240Vac
Page 2
Product Design
Function
Outlook Design
LCD Display
KeyLock Indicator
Freeze Protection
SetUp
Temperature Display
Valve And Fan Control
The wall module reads indoor temperature through integrated temperature sensor and command valve to be opened or closed to achieve set temperature. There are three fan speeds which can be set manually or automatically. Under manual mode, fan speed is adjusted by FH, FM and FL outputs. Under automatic mode, the fan speed will depend on the difference between the room temperature and set temperature. The fan will shut down when the valve is not operating.
Highfanspeed
room
1°C
0.5°C
Medium fan
Low fan speed
speed
Settingvalue
between
temperature
-0.5°C
Difference
and set
Figure 1.
-1°C
Low fan speed
Medium fan
speed
Highfanspeed
Automatic Fan Speed Control Algorithm
Cooling
Heating
SetPoint
Power Off
OperationModes
ValveStatus
(flickerwhen open)
Fan Status
Temperature Display
Room temperature or set temperature can be set to be displayed during the installation of the wall module.
Backlight
The Backlight will be activated when any button is pressed and will last for 8 seconds upon the last button pressed. In setting mode, the backlight will remain turn on for 60 seconds upon the last button pressed.
Keypad Lockout
It is possible to lock or unlock the keypad while the device is not in setting mode. When in lockth mode, the keypad will be inactive when pressing any button.
Page 3
Dimensions (mm)
Anti-freeze mode
Anti-freeze mode is an option under the heating mode. When selected, if room temperature falls below 6C, the wall module (in off status) will be activated in heating mode until it reaches 8C.
Operating Mode
Comfort Mode
In the comfort mode, press the Up or DownIn the button to set the temperature. The comfort mode is included in cooling, heating and automatic
Ventilation Mode
Press the mode key to enter the ventilation mode.Pr In ventilation mode, the fan speed will run as manually set with the valve st
PRODUCT WIRING DIAGRAM
Part number: WS3B2WB/U Two-Pipe Application
220Vac, motorized valve wiring diagram
Wiring diagram 2
Hot/cold water
valve
Fan unit
Hot/cold water
valve
Fan
unit
Neutral wire
Live wire
Neutral wire
Live wire
3-wire motorized valve
Page 4
Part number: WS8B4WB/U 2-pipe Application
Wiring diagram 1
2-wire motorized valve
Hot/cold water
Wiring diagram 2
3-wire motorized valve
Hot/cold water
erminal Designations
T
valve
Fan unit
valve
Fan unit
Neutral wire
Live wire
Neutral wire
Live wire
4-pipe Application
Wiring diagram 1
wire motorized valve
2-
Wiring diagram 2
3-wire motorized valve
Troubleshooting
Cold water
valve
Hot water
valve
Fan unit
Cold water
valve
Hot water
valve
Fan
it
un
Neutral wire
Live wire
Neutral wire
Live wire
SYMBOL
vC2
vO2
N
vC1
vO1
FH
FM
L
FL
Description
Cooling valve is closed (for quadrup
le-pipe only)
Cooling valve is open (for quadruple-pipe only)
Power source neutral wire
Heating/cooling valve is closed
Heating/cooling valve is open
High fan speed
Medium fan speed
Power source live wire
Low fan speed
Symtoms
Fails To
ctivate
A
Fails To Activate
Fails to work
Fails to work
Solution
Pressing to set the operation mode to
( heating mode). Check whether the setting temperature
than the room temperature.
igher
Check whether the valve status ind icator
flickering.
Wait for 5 minutes, check whether the
system starts.
Pressing to set the operating mode to ( cooling mode).
C heck whether the setting temperature is
lower than the room temperature.
whether the valve status ind icator
Check
is
flickering.
Wait for 5 minutes, check whether the cooling system starts.
Check if the button is locked.
Check if the device is in OFF mode
Check whether the buttons is locked.
Check whether is in
Check whether is in the OFF state.
mode
is
is
heating
For more information,
https://honeywellbuildings.in Call: 1-800-103-0339 Email: HBT-Indiabuildings@honeywell.com
Honeywell HBT India Buildings
Unitech Trade Center, 5th Floor, Sector-43, Block C, Sushant Lok Phase - I, Gurgaon - 122 002
www.honeywell.com