V8043A,E,F 5000 Series
APPLICATION
These valves consist of a motorized
actuator and valve assembly for controlling
the flow of hot water to a heat exchanger
such as a radiator, convector, finned
baseboard radiator, or infloor radiant coil
for space temperature control. The V8043
5000 series valves provide two-position,
straight through control of supply water at
up to 300 psi operating pressure.
Quick Fit actuator provides easy snap on and
off connection to the valve assembly.
SPECIFICATION
Actuator Electrical Rating:
24Vac 60 Hz, 0.30 A Current Draw,
5 W, 7.2 VA maximum
Electrical Connection:
18” leads or screw terminal board
Auxiliary Switch Rating:
120V, 4.4A running, 26.4A Inrush (60 Hz);
50 VA Pilot duty at 24 V.
Fluid Temperature:
Standard models (class F motor):
200° F (93° C) Max.
Ambient Temperature:
125°F (52° C) Max.
Humidity Limits:
95% Relative Humidity, Non-condensing
Shipping and Storage Temperature:
-40°F to 150°F (-40°C to 65°C).
Atmosphere:
Non-corrosive, non explosive.
Maximum Soldering Temperature:
500°F (260°C). Rubber ball plug must be
moved away from the seat for soldering.
Maximum System Pressure Rating:
300 psi (2000 kPa), PN20.
Flow Characteristics:
Quick opening for on-off application.
Slow return for water hammer resist.
Maximum Close-off Rating (@ Flow
Capacity Rating) :
20 psi (@ 3.5 Cv)
8 psi (@ 8 Cv)
ZONE V ALVES
Patent Pending
Actuator Materials:
Case:galvanized steel.
Cover : zinc plated steel.
Sector gear: Brass
Valve Material:
Body of forged brass; drive shaft stem of
stainless steel; ball plug of Buna-N rubber;
o-ring seals of EPDM rubber.
Service Medium:
Suitable for glycol/water mix up to 50:50
use in closed hydronic systems. Not for
use with oxygenated water, potable water
or steam.
Use this valve in hydronic systems which
do not contain dissolved oxygen in the
system water. The dissolved oxygen,
which is found in systems that have a
frequent source of make-up water, causes
the rubber plug inside the valve to
deteriorate and eventually fail.
Approvals:
CSA C/US Certified to Canadian Standards
Association and Underwriter's Laboratories
Standards.
MODELS
V8043 (Straight through, Normally Closed)
V8043A: Leadwires
V8043E: Leadwires and End Switch
V8043F: Terminal Board and End Switch
V4043, V8043 SWEAT COPPER CONNECTION MODELS
7/8 DIA.
(22)
8
1-1/2
(38)
1
HEIGHT NEEDED TO REMOVE COVER.
2
DIMENSIONS FOR 1/2 IN. COPPER TUBING.
DIMENSIONS FOR 3/4 IN COPPER TUBING.
3
DIMENSIONS FOR 1 IN. COPPER TUBING.
4
4-7/8 IN. (124) MAX ON V8034F WITH TERMINAL
5
BOARD ENCLOSURE.
V4034B AND V8043B VAL VES THAT ARE
6
NORMALLY OPEN IN THE DE-ENERGIZED
POSITION HAVE NO MANUAL LEVER.
REFER TO MOUNTING INSTRUCTIONS.
7
OPENING FOR 1/2 IN. CONDUIT ON MANUAL
8
LEVER SIDE FOR V4043, V8043.
Fig. 1 - Mounting Dimensions in in. (mm in Brackets)
M10175.A4
15/32
(12)
CAUTION
1. Disconnect power supply before
connecting wiring to prevent electrical
shock or equipment damage.
2. Normally it is not necessary to remove
the actuator from the valve body during
installation. If the valve must be
disassembled, be certain that it is
reassembled with the water flow in the
direction of the arrow. Reversal of the
actuator results in damage to the gear
train.
3. On 24V systems, never jumper the
valve coil terminals even tempor arily.
This can burn out the heat anticipator in
the thermostat.
INSTALLATION
When Installing this Product…
1. Read these instructions carefully. Failure
to follow them could damage the product
or cause a hazardous condition.
2. Check the ratings given in the
instructions and on the product to make
sure the product is suitable for your
application.
3-1/2 (89)
1-3/4
(44)
AB
1-5/16
(33)
1-3/8
(35)
1-11/16
(43)
AUTO
2-3/8
(60)
MAN OPEN
5-1/4
(133)
1
3/8
(10)
IN
3. Installer must be a trained, experienced
service technician.
4. After installation is complete, check out
product operation as provided in these
instructions.
Location
Install the valve in an area with adequate
clearance to:
- Move the manual opening lever on the
side of the actuator
- Remove the actuator cover
- Wire the actuator
- Replace the actuator motor
The valve location should be in an area
where the temperature does not exceed the
maximum valve operating ambient
temperature and fluid temperatuare.
Manual Lever
The V8043 normally closed valves can be
opened manually by moving the manual lever
slowly and firmly to the MAN. OPEN position
and pushing up to the stop. The stop permits
the valve to be locked in the open position.
The valve returns to automatic position when
it is energized.
1-3/4
(44)
2-5/8
(66)
2-3/4
(70)
3-3/8
(86)
6
5
OUT
7
2
3
4
2004.09 Printed in Canada
1
Form No. 95C-10932
2
MOUNTING
R
L1
(HOT)
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
END SWITCH
TO CIRCULATOR
OR ANOTHER
VALVE
TH
TR
24V
TRANSFORMER
THERMOSTAT
(TYPICALLY T87F)
TH TR
M5952
The valve can be mounted in any position
on a vertical line. See Fig. 2. If the valve is
mounted horizontally; the actuator must be
even with or above the center line of the
piping. Make sure to leave enough room
above the actuator to remove the cover for
servicing.
Mount the valve directly in the tube or pipe
after the coil.
through the valve is in the direction
indicated by the arrow stamped on the
valve body.
VERTICAL
PIPING
Make sure that the flow
HORIZONTIAL
PIPING
M10162
thermostat or controller connected to the
valve so that the valve runs through its
cycle. Make sure the valve runs
smoothly and positively from closed to
open to closed again. (See Operation
and Checkout Sections.)
TO REMOVE THE ACTUATOR FROM THE
VALVE BODY (See Fig. 3)
NOTE!
It is not necessary to drain the hydronic
system if the valve body assembly remains in
the pipe line.
1. Switch power supply OFF. Disconnect
electrical leads carefully, noting the
position and colour of each lead.
2. Place the manual lever in the MAN.
OPEN position.
3. Remove actuator by fully depressing
spring release button and lift it straight
off of the body .
4. Line up motor coupling to the parallel flat
surfaces in double-D shaft of body and fit
the actuator onto the valve body,
ensuring that the shaft seats correctly .
(See Fig. 5)
5. Snap actuator onto body by pressing
down.
6.The manual lever may be released
manually, but it is also automatically
released when the valve is operated
Double-D
Shaft
Notch
Actuator
Coupling
electrically.
Fig. 4 - Shaft Position
Parallel flat surfaces
align with Notch on
side of valve body
LINE
YELLOW
LEADS
MOTOR
Fig. 6 - Typical wiring for V8043E, V8044E.
AUXILIARY
SWITCH
THERMOSTAT
(TYPICALLY T87F)TO
TO CIRCULATOR
OR ANOTHER VALVE
RED LEADS
M5953
Fig. 2 - Mounting Positions
Sweat Copper Models
1. Use new, properly reamed pipe, free
from dents or corrosion.
2. Place the valve on the pipe. Set the
manual opening lever to MAN. OPEN
position before applying heat. This
protects the plug inside the valve by
removing it from the seat.
3. Sweat the joints, keeping the outer
surface free from solder. DO NOT use
silver solder because of the high
melting temperature required.
TO INSTALL A COMPLETE V ALVE (V8043):
1. Disconnect power supply before
connecting wiring to prevent electrical
shock or equipment damage.
2. Install valve into pipe on the return side
of the coil. (See Mounting Section.)
3. Make wiring connections to valve. (Refer
to Wiring section for proper instructions.)
4. Inspect the valve installation to ensure
that all connections and adjustments
have been correctly made. Adjust the
Notch Tab
1. PLACE MANUAL
AUTO OPEN
2. DEPRESS
LOCKING
BUTTON
Fig. 3 - Removing Actuator from Valve Body
TO INSTALL REPLACEMENT ACTUATOR
ON THE VAL VE BODY
1.
Align the parallel flat surfaces in
double-D shaft of valve body with
notch in side of body (i.e. 90° to water
flow.) See Fig. 4.
attachment easier.
2. Wiring connections may be made either
before or after actuator installed on
valve body.
3.
Place the manual lever on the
actuator in the MAN. OPEN position.
3
LEVER IN OPEN
POSITION
3. LIFT ACTUATOR
STRAIGHT UP
This makes actuator
Notch
Fig. 5 - Installing Actuator
WIRING
Disconnect the power supply before
connecting wiring to prevent electrical shock
or equipment damage.
All wiring must comply with local codes and
ordinances. Connections to the individual
valves are shown in Fig. 6 and 7. See Fig. 8
through 14 for typical hookups.
If replacing a Taco, Dole, Flair or White
Rodgers 3-wire valve with a 2-wire V8043E or
F, see Fig. 15 through 27. Check that the
pressure rating of the new valve is
appropriate for the application.
Fig. 7 - Typical wiring for V8043F.
T822 T822 T822
L1
(HOT)
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
CONNECT V8043A BLACK LEADWIRE TO THERMOSTAT.
2
V8043A V8043A V8043A
Fig. 8 - T822 Thermostat, V8043A valve hookup.
2 2
4
M10168