Honeywell V8043, V8043A, V8043E, V8043F User Manual

4.4 (11)

V8043A,E,F 5000 Series

ZONE VALVES

APPLICATION

These valves consist of a motorized actuator and valve assembly for controlling the flow of hot water to a heat exchanger such as a radiator, convector, finned baseboard radiator, or infloor radiant coil for space temperature control. The V8043 5000 series valves provide two-position, straight through control of supply water at up to 300 psi operating pressure.

Quick Fit actuator provides easy snap on and off connection to the valve assembly.

Patent Pending

SPECIFICATION

Actuator Electrical Rating:

Actuator Materials:

24Vac 60 Hz, 0.30 A Current Draw, 5 W, 7.2 VA maximum

Electrical Connection:

18” leads or screw terminal board

Auxiliary Switch Rating:

120V, 4.4A running, 26.4A Inrush (60 Hz); 50 VA Pilot duty at 24 V.

Fluid Temperature:

Standard models (class F motor):

200° F (93° C) Max.

Ambient Temperature:

125°F (52° C) Max.

Humidity Limits:

95% Relative Humidity, Non-condensing

Shipping and Storage Temperature:

-40°F to 150°F (-40°C to 65°C).

Atmosphere:

Non-corrosive, non explosive.

Maximum Soldering Temperature:

500°F (260°C). Rubber ball plug must be moved away from the seat for soldering.

Maximum System Pressure Rating:

300 psi (2000 kPa), PN20.

Case:galvanized steel. Cover : zinc plated steel. Sector gear: Brass

Valve Material:

Body of forged brass; drive shaft stem of stainless steel; ball plug of Buna-N rubber; o-ring seals of EPDM rubber.

Service Medium:

Suitable for glycol/water mix up to 50:50 use in closed hydronic systems. Not for use with oxygenated water, potable water or steam.

Use this valve in hydronic systems which do not contain dissolved oxygen in the system water. The dissolved oxygen, which is found in systems that have a frequent source of make-up water, causes the rubber plug inside the valve to deteriorate and eventually fail.

Approvals:

CSA C/US Certified to Canadian Standards Association and Underwriter's Laboratories Standards.

Flow Characteristics:

MODELS

 

Quick opening for on-off application.

Slow return for water hammer resist.

 

V8043 (Straight through, Normally Closed)

Maximum Close-off Rating (@ Flow

 

 

V8043A: Leadwires

Capacity Rating) :

 

 

V8043E: Leadwires and End Switch

20 psi (@ 3.5 Cv)

 

 

V8043F: Terminal Board and End Switch

8 psi (@ 8 Cv)

 

 

 

 

 

 

 

 

 

2004.09 Printed in Canada

1

Form No. 95C-10932

V4043, V8043 SWEAT COPPER CONNECTION MODELS 6

7/8 DIA.

 

2-3/8

(22)

 

(60)

8

 

 

1-1/2

 

 

(38)

AUTO

MAN OPEN

 

1HEIGHT NEEDED TO REMOVE COVER.

2DIMENSIONS FOR 1/2 IN. COPPER TUBING.

3DIMENSIONS FOR 3/4 IN COPPER TUBING.

4

DIMENSIONS FOR 1 IN. COPPER TUBING.

15/32

(12)

 

 

5

4-7/8 IN. (124) MAX ON V8034F WITH TERMINAL

 

BOARD ENCLOSURE.

 

6

V4034B AND V8043B VALVES THAT ARE

 

NORMALLY OPEN IN THE DE-ENERGIZED

 

 

POSITION HAVE NO MANUAL LEVER.

 

7

REFER TO MOUNTING INSTRUCTIONS.

 

8

OPENING FOR 1/2 IN. CONDUIT ON MANUAL

 

LEVER SIDE FOR V4043, V8043.

 

5

1 3-1/2 (89)

1-3/4 1-3/4

(44)(44)

5-1/4

 

 

 

(133)

 

 

 

3/8

 

 

 

(10)

 

 

 

IN

A

B

OUT

 

 

 

7

1-5/16

(33)2

2-5/8 (66)

1-3/8

(35)3

2-3/4 (70)

1-11/16

(43)4

3-3/8

(86)

M10175.A4

Fig. 1 - Mounting Dimensions in in. (mm in Brackets)

CAUTION

1.Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.

2.Normally it is not necessary to remove the actuator from the valve body during installation. If the valve must be disassembled, be certain that it is reassembled with the water flow in the direction of the arrow. Reversal of the actuator results in damage to the gear train.

3.On 24V systems, never jumper the valve coil terminals even temporarily. This can burn out the heat anticipator in the thermostat.

INSTALLATION

When Installing this Product…

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

2

3.Installer must be a trained, experienced service technician.

4.After installation is complete, check out product operation as provided in these instructions.

Location

Install the valve in an area with adequate clearance to:

-Move the manual opening lever on the side of the actuator

-Remove the actuator cover

-Wire the actuator

-Replace the actuator motor

The valve location should be in an area where the temperature does not exceed the maximum valve operating ambient temperature and fluid temperatuare.

Manual Lever

The V8043 normally closed valves can be opened manually by moving the manual lever slowly and firmly to the MAN. OPEN position and pushing up to the stop. The stop permits the valve to be locked in the open position.

The valve returns to automatic position when it is energized.

Honeywell V8043, V8043A, V8043E, V8043F User Manual
Parallel flat surfaces align with Notch on side of valve body

MOUNTING

The valve can be mounted in any position on a vertical line. See Fig. 2. If the valve is mounted horizontally; the actuator must be even with or above the center line of the piping. Make sure to leave enough room above the actuator to remove the cover for servicing.

Mount the valve directly in the tube or pipe after the coil. Make sure that the flow through the valve is in the direction indicated by the arrow stamped on the valve body.

HORIZONTIAL

PIPING

VERTICAL

PIPING

M10162

thermostat or controller connected to the valve so that the valve runs through its cycle. Make sure the valve runs smoothly and positively from closed to open to closed again. (See Operation and Checkout Sections.)

TO REMOVE THE ACTUATOR FROM THE VALVE BODY (See Fig. 3)

NOTE!

It is not necessary to drain the hydronic system if the valve body assembly remains in the pipe line.

1.Switch power supply OFF. Disconnect electrical leads carefully, noting the position and colour of each lead.

2.Place the manual lever in the MAN. OPEN position.

3.Remove actuator by fully depressing spring release button and lift it straight off of the body.

Fig. 2 - Mounting Positions

Sweat Copper Models

1.Use new, properly reamed pipe, free from dents or corrosion.

2.Place the valve on the pipe. Set the manual opening lever to MAN. OPEN position before applying heat. This protects the plug inside the valve by removing it from the seat.

3.Sweat the joints, keeping the outer surface free from solder. DO NOT use silver solder because of the high melting temperature required.

TO INSTALL A COMPLETE VALVE (V8043):

1.Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.

2.Install valve into pipe on the return side of the coil. (See Mounting Section.)

3.Make wiring connections to valve. (Refer to Wiring section for proper instructions.)

4.Inspect the valve installation to ensure that all connections and adjustments have been correctly made. Adjust the

 

1. PLACE MANUAL

AUTO

LEVER IN OPEN

OPEN

 

POSITION

2. DEPRESS

 

LOCKING

 

BUTTON

3. LIFT ACTUATOR

 

STRAIGHT UP

Fig. 3 - Removing Actuator from Valve Body

TO INSTALL REPLACEMENT ACTUATOR ON THE VALVE BODY

1.Align the parallel flat surfaces in

double-D shaft of valve body with notch in side of body (i.e. 90° to water flow.) See Fig. 4. This makes actuator attachment easier.

2.Wiring connections may be made either before or after actuator installed on valve body.

3.Place the manual lever on the actuator in the MAN. OPEN position.

4.Line up motor coupling to the parallel flat surfaces in double-D shaft of body and fit the actuator onto the valve body, ensuring that the shaft seats correctly. (See Fig. 5)

5.Snap actuator onto body by pressing down.

6.The manual lever may be released manually, but it is also automatically released when the valve is operated electrically.

Double-D

Shaft

Notch

Fig. 4 - Shaft Position

Actuator

Coupling

Notch Tab

Notch

Fig. 5 - Installing Actuator

WIRING

Disconnect the power supply before connecting wiring to prevent electrical shock or equipment damage.

All wiring must comply with local codes and ordinances. Connections to the individual valves are shown in Fig. 6 and 7. See Fig. 8 through 14 for typical hookups.

If replacing a Taco, Dole, Flair or White Rodgers 3-wire valve with a 2-wire V8043E or F, see Fig. 15 through 27. Check that the pressure rating of the new valve is appropriate for the application.

 

 

THERMOSTAT

TO

 

(TYPICALLY T87F)

LINE

 

 

 

 

TO CIRCULATOR

 

YELLOW

OR ANOTHER VALVE

 

 

 

LEADS

 

 

 

RED LEADS

 

MOTOR

 

 

 

AUXILIARY

 

 

SWITCH

M5953

Fig. 6 - Typical wiring for V8043E, V8044E.

R

THERMOSTAT (TYPICALLY T87F)

TO CIRCULATOR

OR ANOTHER

VALVE

END SWITCH

TH TR TH

TR

1

L1

(HOT)

L2

24V TRANSFORMER

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M5952

Fig. 7 - Typical wiring for V8043F.

T822

 

T822

 

T822

 

 

 

 

 

L1

(HOT)

L2

1

2

2

2

V8043A

V8043A

V8043A

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 CONNECT V8043A BLACK LEADWIRE TO THERMOSTAT.

M10168

Fig. 8 - T822 Thermostat, V8043A valve hookup.

3