Two-way on-off low voltage valves consist of an actuator and valve
assembly for controlling the flow of hot water.
• Manual opener (on all models, except straight-through, normally
open valves) for valve operation on power failure; valve returns to
automatic position when power is restored.
• All models may be installed without disassembling the valve.
• Compact construction for easy installation.
• Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
• Actuator motor may be replaced without removing the valve body or
draining the system.
Application: Hydronic Control
Typ e: Two position
Body Pattern: Two-way, Straight-through
Valve Action: Spring return to close
Volt ag e: 24 Vac
Frequency: 50 Hz; 60 Hz
Power Consumption: 7.7 VA
De-energized Position: Normally Closed
Fluid Temperature Range: 50 F to 200 F (10 C to 93 C)
Maximum Ambient Temperature: 125 F (52 C)
Comments: Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water.
Valve designed for cycling (not constantly powered on) applications.
On-off and two way low voltage valves consist of an actuator and
valve assembly for controlling the flow of low pressure steam.
• All models may be installed without disassembling the valve.
• Compact construction for easy installation.
• Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
• Actuator motor may be replaced without removing the valve body or
draining the system.
• Suitable for use 15 psi low pressure steam application.
Application: Steam (low pressure) Control
Typ e: Two position
Body Pattern: Two-way, Straight-through
Valve Action: Spring return to open
Volt ag e: 24 Vac
Frequency: 50 Hz; 60 Hz
Power Consumption: 7.7 VA
Nominal Timing (sec, min): De-energized Position: Normally Open
Electrical Connections: 18 in. leads (457 mm leads)
Fluid Temperature Range: 50 F to 240 F (10 C to 116 C)
Maximum Ambient Temperature: 125 F (52 C)
Approvals
Underwriters Laboratories, Inc: UL Listed: File MH11826
Replacement Parts:
802360UA-24V, 50/60 Hz Replacement motor for steam and heating
Zone Valves
Maximum Closeoff Pressure
De-energized
Position
Current Draw
(A)
Manual
Opener(Cv)(Kv)inchDN(psi)(kPa)
Controls
Hydronic
70-6910207
Motorized Zone Valves
NPT Connection
Sweat Connection
V8043 Low Voltage Normally Open Zone Valves
On-off and two-way low voltage valves consist of an actuator and
valve assembly for controlling the flow of hot water.
• All models may be installed without disassembling the valve.
• Compact construction for easy installation.
• Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
• Actuator motor may be replaced without removing the valve body or
draining the system.
• No Manual opener
Application
Hydronic Control
Typ e: Two position
Body Pattern: Two-way, Straight-through
Valve Action: Spring return to open
Volt ag e: 24 Vac
Power Consumption: 7.7 VA
Nominal Timing (sec, min): De-energized Position: Normally Open
Electrical Connections: 18 in. leads (457 mm leads)
Fluid Temperature Range: 40 F to 200 F (5 C to 93 C)
Maximum Ambient Temperature: 125 F (52 C)
Comments: Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water.
Valve designed for cycling (not constantly powered on) applications.
DIMENSIONS FOR 3/4 IN COPPER TUBING.
DIMENSIONS FOR 1 IN. COPPER TUBING.
4-7/8 IN. (124) MAX ON V8034F WITH TERMINAL BOARD ENCLOSURE.
V8043B VALVES THAT ARE NORMALLY OPEN IN THE DE-ENERGIZED
POSITION HAVE NO MANUAL LEVER. THE VALVES ALSO HAVE A
REVERSED POWERHEAD WHERE THE LEADWIRES EXIT THE
POWERHEAD ABOVE THE B (OUTLET) PORT RATHER THAN ABOVE
THE A (INLET) PORT.
OPENING FOR 1/2 IN. CONDUIT ON MANUAL LEVER SIDE FOR V8043
1
7
1
6
5
2
3
4
2
3
4
5
6
7
M23257
V8043 SWEAT QUICKFIT CONNECTION MODELS
2-3/8
(60)
7/8 DIA.
(22)
1-1/2
(38)
5-3/4
(146)
15/32
(12)
IN
OUT
3-1/2 (89)
1-3/4
(44)
3/8
(10)
1-3/4
(44)
1-9/16
(40)
1-3/4
(44)
3-1/8
(79)
3-1/2
(89)
1-7/8
(47)
3-11/16 (94)
®
V8043 Low Voltage Series 5000 QuickFit® Zone Valves
Two-way on-off low voltage valves consist of an actuator and valve
assembly for controlling the flow of hot water.
• All models may be installed without disassembling the valve.
• Compact construction for easy installation.
• Manual opener (on all models, except straight-through, normally
open valves) for valve operation on power failure; valve returns to
automatic position when power is restored.
• Complete powerhead may be removed or replaced without breaking
plumbing line connections or draining the system.
• “Quick Fit” pushbutton powerhead makes it easy to remove for
service.
• Series 5000 replacement powerhead is backward compat ble with
series 1000 zone valves.
• Innovative motor technology offers silent operation, water hammer
resist and longer life.
Dimensions in inches (millimeters)Application: Hydronic Control
Typ e: Two position
Body Pattern: Two-way, Straight-through
Valve Action: Spring return to close
Volt ag e: 24 Vac
Frequency: 60 Hz
Power Consumption: 7.2 VA
De-energized Position: Normally Closed
Fluid Temperature Range: 50 F to 200 F (10 C to 93 C)
Maximum Ambient Temperature: 125 F (52 C)
Materials
(Body): Brass
(Stem): Stainless Steel
(Seat): Brass
(Packing O-Ring): EPDM rubber
(Ball Plug): Buna-N (NBR) Rubber Ball
Comments: Use this valve in closed loop hydronic systems that do not
contain dissolved oxygen in system water, such as fresh water from
frequent source of makeup water.
Valve designed for cycling (not constantly powered on) applications.