Kombi-F-II
Design
• Valve body with flanges drilled to DIN
• Valve insert with handwheel and pre-setting display
• Pressure test cocks
Materials
• Valve housing made of cast iron GG25, painted blue
• Valve insert made of stainless steel with seat sealing
made of PTFE
• Pressure test cocks made of brass
• Handwheel made of steel, painted black
• Fairing made of plastic, black
PRODUCT DATA
CONTENTS
Design................................................................................... 1
Materials ............................................................................... 1
Application ........................................................................... 1
Features................................................................................ 1
Specifications ...................................................................... 2
Dimensions and Ordering Information .............................. 2
Accessories.......................................................................... 3
Measuring Equipment................................................. 3
Spare Parts................................................................. 3
Installation Example ............................................................ 3
Flow Data Kombi-F-II (DN15...DN200)........................ 4 to 15
Flow Data Kombi-F (DN250...DN400)....................... 16 to 19
Influence of Coolants on Flow Values ............................. 20
Correction Factor f.................................................... 20
Application
The hydronic balance is a significant requirement for the
efficient operation of a hydronic heating or cooling installation.
In an unbalanced system under or over provision of hot water
to individual radiators or circuits can occur. Apart from the
correct selection of radiator valves, regulation of individual
circuits is also necessary and in some cases, such as in
DIN 18 380, VOB part C, is required by national standards.
This requirement is met with Kombi-F-II and Kombi-F shutoff
and balancing valves.
Kombi-F-II and Kombi-F have functions shut-off, pre-setting
and measuring.
Features
• Balancing through stroke limitation with digital pre-
setting and visible pre-setting indicator
• Equipped with 2 pressure test cocks for differential
pressure measurement
• Non rising spindle with EDD
• Pre-setting isn`t altered when handwheel is turned
• Stroke limitation-screw protected by protection cap
• PTFE seat sealing
• Spindle made of stainless steel
• Valve body made of corrosion resistant cast iron
• Available in dimensions up to DN400
Copyright © 2003 Honeywell AG • All rights reserved EN0H-0050GE25 R0803
KOMBI-F-II, KOMBI-F (V6000)
Specifications
Medium Water, water-glycol mixture
Operating temperature -10...120°C (14...248°F)
short run 130°C (266°F
Operating pressure max. 16 bar (232 psi)
k
vs (cv)-values see table below and flow
diagrams
Dimensions and Ordering Information
DN15 – DN80 DN100 – DN200 DN250 – DN400
DN (R) kvs (cv)-value L H Ø D Ø K n x Ø d Weight OS-No.
15
20
25
32
40
50
65
80
100
125
150
200
1/2” 4,50 (5,27) 130 225 95 65 4 x 14 3,5 kg V6000D0015
3/4” 6,60 (7,72) 150 225 105 75 4 x 14 4,1 kg V6000D0020
1” 9,80 (11,5) 160 225 115 85 4 x 14 4,8 kg V6000D0025
1 1/4” 15,1 (17,7) 180 225 140 100 4 x 18 6,6 kg V6000D0032
1 1/2” 24,9 (29,1) 200 280 150 110 4 x 18 9,0 kg V6000D0040
2” 48,5 (56,7) 230 280 165 125 4 x 18 11,5 kg V6000D0050
2 1/2” 74,4 (87,0) 290 365 185 145 4 x 18 18,5 kg V6000D0065
3” 111 (130) 310 395 200 160 8 x 18 24,5 kg V6000D0080
4” 165 (193) 350 430 220 180 8 x 18 40,0 kg V6000D0100
5” 242 (283) 400 495 250 210 8 x 18 79,0 kg V6000D0125
6” 372 (435) 480 530 285 240 8 x 22 91,0 kg V6000D0150
8” 704 (824) 600 665 340 295 8 x 22 170 kg V6000D0200
DN (R) kvs (cv)-value L H Ø D Ø K n x Ø d Weight OS-No.
250
300
350
400
10” 812 (950) 730 600 405 355 12 x 22 265 kg V6000D0250
12” 1.380 (1.615) 850 685 460 410 12 x 26 360 kg V6000D0300
14” 1.651 (1.932) 980 775 520 470 16 x 26 535 kg V6000D0350
16” 2.389 (2.795) 1.100 790 580 525 16 x 30 765 kg V6000D0400
NOTE: All dimensions in mm if not stated otherwise.
Fig. 1. Dimensions
Table 1. Dimensions Kombi-F-II
Table 2. Dimensions Kombi-F
EN0H-0050GE25 R0803 2 Honeywell AG • All rights reserved
Accessories
KOMBI-F-II, KOMBI-F (V6000)
Measuring Equipment
Set of 2 measuring adapters
for all dimensions VA3600A008
Extension piece for pressure test cocks, length 45 mm, for insulated
Kombi-F-II and Kombi-F
for all dimensions VA2601A008
‘BasicMES’ handheld measuring computer
for all dimensions;
computer is supplied with
case and accessories
VM241A1002
Installation Example
Spare Parts
Spare set of 2 pressure test cocks G1/4”
for all dimensions VA2600A008
Fig. 3. Kombi-F in a cooling system
Honeywell AG • All rights reserved 3 EN0H-0050GE25 R0803
KOMBI-F-II, KOMBI-F (V6000)
Flow Data Kombi-F-II, DN15
Pre-setting
kv -value
cv-value
EN0H-0050GE25 R0803 4 Honeywell AG • All rights reserved
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 6,6 = open
0,13 0,26 0,37 0,55 0,80 1,10 1,50 1,90 2,30 2,60 2,90 3,30 4,20 kvs = 4,50
0,15 0,30 0,43 0,64 0,94 1,29 1,76 2,22 2,69 3,04 3,39 3,86 4,91 5,27
Flow Data Kombi-F-II, DN20
KOMBI-F-II, KOMBI-F (V6000)
Pre-setting
kv -value
cv-value
Honeywell AG • All rights reserved 5 EN0H-0050GE25 R0803
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 6,6 = open
0,22 0,43 0,65 0,90 1,15 1,60 2,06 2,60 3,26 4,00 4,79 5,60 6,43 kvs = 6,60
0,26 0,50 0,76 1,05 1,35 1,87 2,41 3,04 3,81 4,68 5,60 6,55 7,52 7,72
KOMBI-F-II, KOMBI-F (V6000)
Flow Data Kombi-F-II, DN25
Pre-setting
kv -value
cv-value
EN0H-0050GE25 R0803 6 Honeywell AG • All rights reserved
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 6,6 = open
0,22 0,49 0,84 1,30 1,85 2,50 3,25 4,10 5,07 6,20 7,50 8,70 9,63 kvs = 9,80
0,26 0,57 0,98 1,52 2,16 2,93 3,80 4,80 5,93 7,25 8,78 10,2 11,3 11,5
Flow Data Kombi-F-II, DN32
KOMBI-F-II, KOMBI-F (V6000)
Pre-setting
kv -value
cv-value
Honeywell AG • All rights reserved 7 EN0H-0050GE25 R0803
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 6,6 = open
0,28 0,60 1,06 1,68 2,48 3,54 4,91 6,46 7,97 9,47 11, 0 12,8 14,7 kvs = 15,1
0,33 0,70 1,24 1,97 2,90 4,14 5,74 7,56 9,32 11,1 12,9 15,0 17,2 17,7
KOMBI-F-II, KOMBI-F (V6000)
Flow Data Kombi-F-II, DN40
Pre-setting
kv -value
cv-value
Pre-setting
kv -value
cv-value
EN0H-0050GE25 R0803 8 Honeywell AG • All rights reserved
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0
0,88 1,80 2,80 4,00 5,42 6,90 8,31 9,90 11,9 14,3 16,8 18,8 20,4 22,2
1,03 2,11 3,28 4,68 6,34 8,07 9,72 11,6 13,9 16,7 19,7 22,0 23,9 26,0
7,5 = open
kvs = 2 4 , 9
2 9 , 1
Flow Data Kombi-F-II, DN50
KOMBI-F-II, KOMBI-F (V6000)
Pre-setting
kv -value
cv-value
Pre-setting
kv -value
cv-value
Honeywell AG • All rights reserved 9 EN0H-0050GE25 R0803
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0
1,07 2,20 3,46 5,10 7,36 10,3 13,9 18,1 22,7 28,0 34,1 39,3 42,8 45,6
1,25 2,57 4,05 5,97 8,61 12,1 16,3 21,2 26,6 32,8 39,9 46,0 50,1 53,4
7,5 = open
kvs = 4 8 , 5
5 6 , 7
KOMBI-F-II, KOMBI-F (V6000)
Flow Data Kombi-F-II, DN65
Pre-setting
kv -value
cv-value
Pre-setting
kv -value
cv-value
EN0H-0050GE25 R0803 10 Honeywell AG • All rights reserved
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 8,0
2,98 5,30 6,64 7,80 9,60 12,1 15,2 19,0 23,6 29,1 35,2 41,3 47,0 52,1 60,7
3,49 6,20 7,77 9,13 11,2 14,2 17,8 22,2 27,6 34,0 41,2 48,3 55,0 61,0 71,0
9,0 10,0 = open
67,9 kvs = 7 4 , 4
79,4 87,0
Flow Data Kombi-F-II, DN80
KOMBI-F-II, KOMBI-F (V6000)
Pre-setting
kv -value
cv-value
Pre-setting
kv -value
cv-value
Honeywell AG • All rights reserved 11 EN0H-0050GE25 R0803
0,5 1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 6,0 7,0 8,0 9,0 10,0
3,65 6,60 8,52 10,0 11,7 13,7 16,1 19,2 23,2 28,1 40,4 55,4 70,9 84,8 96,1
4,27 7,72 9,97 11,7 13,7 16,0 18,8 22,5 27,1 32,9 47,3 64,8 83,0 99,2 112
11,0 12,0 = open
104 kvs = 111
122 130
KOMBI-F-II, KOMBI-F (V6000)
Flow Data Kombi-F-II, DN100
Pre-setting
kv -value
cv-value
Pre-setting
kv -value
cv-value
EN0H-0050GE25 R0803 12 Honeywell AG • All rights reserved
1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5 8,0 9,0
3,80 6,20 9,60 13,4 17,3 21,8 27,6 35,7 47,2 62,4 79,3 96,6 110 121 137
4,45 7,25 11,2 15,7 20,2 25,5 32,3 41,8 55,2 73,0 92,8 113 129 142 160
10,0 11,0 12,0 = open
148 157 kvs = 165
173 184 193
Flow Data Kombi-F-II, DN125
KOMBI-F-II, KOMBI-F (V6000)
Pre-setting
kv -value
cv-value
Pre-setting
kv -value
cv-value
Honeywell AG • All rights reserved 13 EN0H-0050GE25 R0803
1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5 8,0 9,0
8,30 11,3 14,4 17,7 21,1 24,6 28,2 32,3 37,4 44,9 56,1 72,5 93,2 120 162
9,71 13,2 16,8 20,7 24,7 28,8 33,0 37,8 43,8 52,5 65,6 84,8 109 140 190
10,0 11,0 12,0 13,0 13,5 = o p e n
192 211 225 236 k
225 247 263 276 283
vs = 242
KOMBI-F-II, KOMBI-F (V6000)
Flow Data Kombi-F-II, DN150
Pre-setting
kv -value
cv-value
Pre-setting
kv -value
cv-value
EN0H-0050GE25 R0803 14 Honeywell AG • All rights reserved
1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5 8,0 9,0
16,2 20,4 23,8 26,7 29,5 33,0 37,6 42,3 48,0 54,5 61,5 69,6 80,0 92,9 136
19,0 23,9 27,8 31,2 34,5 38,6 44,0 49,5 56,2 63,8 72,0 81,4 93,6 109 159
10,0 11,0 12,0 13,0 14,0 15,0 16,0 17,0 17,5 = open
193 240 274 300 320 337 352 365 k
226 281 321 351 374 394 412 427 435
vs = 372
Flow Data Kombi-F-II, DN200
KOMBI-F-II, KOMBI-F (V6000)
Pre-setting
kv -value
cv-value
Pre-setting
kv -value
cv-value
Honeywell AG • All rights reserved 15 EN0H-0050GE25 R0803
1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5 8,0 9,0
32,5 41,3 48,9 55,5 62,1 69,3 77,8 88,1 101 115 133 154 179 208 284
38,0 48,3 57,2 64,9 72,7 81,1 91,0 103 118 135 156 180 209 243 332
10,0 11,0 12,0 13,0 14,0 15,0 16,0 17,0 18,0 = open
364 435 489 537 575 613 646 677 kvs = 704
426 509 572 628 673 717 756 792 824
KOMBI-F-II, KOMBI-F (V6000)
Flow Data Kombi-F, DN250
Pre-setting
kv -value
cv-value
EN0H-0050GE25 R0803 16 Honeywell AG • All rights reserved
1 2 3 4 5 6 7 8 9 11,0 = open
66 178 297 410 514 587 649 731 800 kvs = 812
77 208 347 480 601 687 759 855 936 950
Flow Data Kombi-F, DN300
KOMBI-F-II, KOMBI-F (V6000)
Pre-setting
kv -value
cv-value
Honeywell AG • All rights reserved 17 EN0H-0050GE25 R0803
1 2 3 4 5 6 7 8 9 10 11 12 13 14,0 = open
109 248 411 560 696 825 944 1044 1138 1226 1291 1324 1345 kvs = 1380
128 290 481 655 814 965 1104 1221 1331 1434 1510 1549 1573 1615
KOMBI-F-II, KOMBI-F (V6000)
Flow Data Kombi-F, DN350
Pre-setting
kv -value
cv-value
EN0H-0050GE25 R0803 18 Honeywell AG • All rights reserved
1 2 3 4 5 6 7 8 9 10 11 12,0 = open
128 300 495 677 851 1019 1163 1272 1386 1513 1606 kvs = 1651
150 351 579 792 996 1192 1361 1488 1622 1770 1879 1932
Flow Data Kombi-F, DN400
KOMBI-F-II, KOMBI-F (V6000)
Pre-setting
kv -value
cv-value
Honeywell AG • All rights reserved 19 EN0H-0050GE25 R0803
1 2 3 4 5 6 7 8 9 10 11 12 13.0 = open
201 430 690 946 1182 1409 1612 1752 1874 1991 2092 2256 kvs = 2389
235 503 807 1107 1383 1649 1886 2050 2193 2329 2448 2640 2795
KOMBI-F-II, KOMBI-F (V6000)
Influence of Coolants on Flow Values
The flow through a valve is defined by the kv -value. The kv -value is the flow m through a valve in [m³/h] at a differential pressure
of 1 bar (14,5 psi) and is only valid for fluids with a density of σ
20°C (68°F). For fluids with another density the following formula can be applied:
= 1000 kg/m³. This condition is met by water at a temperature of
0
Kv ×
Medium
m
=
p
∆
ρ
Medium
ρ
0
Correction Factor f
When the density σ is expressed in t/m³ instead of kg/m³ the correction factor f is the result. The correction factor f can be used
to re-calculate kv-value, pressure drop and flow:
1
Kv Kv
Medium
Medium
Normal water 100% 1,000 0,998 0,994 0,988 0,981 0,972
Ethylen glycol 70% 1,052 1,047 1,041 1,033 10,24 1,015
e.g. Antifrogen N 50% 1,086 1,079 1,070 1,061 1,052 1,042
Propylen glycol 70% 1,035 1,029 1,021 1,012 1,002 0,991
e.g. Antifrogen L 50% 1,053 1,044 1,035 1,025 1,014 1,002
× =
0
water part 5°C (41°F) 20°C (68°F) 35°C (95°F) 50°C (122°F) 65°C (149°F) 80°C (176°F)
f p p
f
Table 1. Values for correction factor f
Medium
0
Correction factor f
Medium
m m
1
× =
0
f
Automation and Control Products
Honeywell AG Phone: (49) 2932 9880
Zu den Ruhrwiesen 3 Fax: (49) 2932 988224
D-59755 Arnsberg-Neheim mng@honeywell.com http://europe.hbc.honeywell.com