Honeywell V5833A, V5833C, V5832A User Manual

V5832A V5833A
V5832A/5833A,C
SMALL LINEAR VALVES PN16
FOR MODULATING AND ON/OFF-CONTROL
SPECIFICATION DATA

FEATURES

Small size allows installation where space is limited
Long stroke results in a high quality characteristic
Soft seat provides low leakage rate and high
rangeability
Reduced k
hydronic balancing
Range of fittings available for different connections
(soldered, threaded)
Adjustment cap for manual operation
Flat surfaces on body to fit installation tools
Flat sealing connections in standard sizes
Valve inserts changeable without draining by using
insert replacement tool WV 108
40 mm distance between ports A/AB and the bypass
(V5833C, only)
values in the bypass to facilitate
VS
V5833C

GENERAL

These small linear valves are used in combination with small electric linear valve actuators and thermoelectric actuators for the control of hot and/or chilled water for fan coil units and small reheaters/recoolers in electric/electronic temperature control systems.

SPECIFICATIONS

Models Two-way V5832A
Three-way V5833A Three-way with bypass V5833C
Operation Two-way stem up to open,
port A to B; Three-way stem up to close, port A to AB
Nominal pressure rating PN16
Capacity index (k
Leakage rate 0.02% of k
Valve body
Material Brass Size DN15 (1/2“), DN20 (3/4“)
Trim
Stem Stainless steel Plug Brass
Suitable medium Water, with max. 50% glycol
Controlled water temperature 2...120 °C
) see tables on page 2 and 3
VS
VS
® U.S. Registered Trademark EN0B-0308GE51 R1002 Copyright © 2002 Honeywell Inc. • All rights reserved
V5832A/V5833A,C SMALL LINEAR VALVES PN16
A
Modulating valves
Rangeability Two-way valves 100:1 Three-way valves 100:1 for controlled port Flow characteristic Equal percentage port A-AB,
linear for bypass port B-AB
Stroke 6.5 mm
On/Off valves
Stroke 2.5 mm
Dimensions see Fig. 4 on page 5

FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS

TWO-WAY VALVES

Valve Close-Off Pressure (kPa) with Actuators
DN k
15 0.16 V5832A1004 1600 600 ­15 V5832A1012 1600 600 ­15 V5832A1020 1600 600 ­15 V5832A1038 1600 600 ­15 V5832A1046 1200 180 ­15 V5832A1053 1200 180 ­20 V5832A1061 400 50* - 20 V5832A1079 400 50* ­15 V5832A4008** 1200 180 180 20 2.50 V5832A4016** 400 50* 50*
*Up to 1000kPa system pressure. **For on/off control, stroke 2.5mm.
VS
Order number
M6410C,L/M7410C,E
(180 N)
M4450/M8450
(90 N)
Z100/M7410A
(90 N)

THREE-WAY VALVES

Valve Close-Off Pressure (kPa) with Actuators
k
DN
15 15 0.40 0.25 V5833A1011 800 500 ­15 0.63 0.40 V5833A1029 800 500 ­15 1.00 0.63 V5833A1037 250 150 ­15 1.60 1.00 V5833A1045 250 150 ­20 2.50 1.60 V5833A1052 100 50 ­20 2.50 1.60 V5833A3009 240 - ­20 4.00 2.50 V5833A1060 100 50 ­20 4.00 2.50 V5833A3017 240 - ­15 1.60 1.60 V5833A4007* 250 150 150 20 2.50 2.50 V5833A4015* 100 50 50
*For on/off control, stroke 2.5mm.
VS
A-AB B-AB
0.25
k
VS M6410C,L/M7410C,E M4450/M8450 Z100/M7410
0.16 V5833A1003 800 500 -
Order Number
(180 N) (90 N) (90 N)
EN0B-0308GE51 R1002 2
V5832A/V5833A,C SMALL LINEAR VALVES PN16
A

THREE-WAY VALVES WITH BYPASS

Valve Close-Off Pressure (kPa) with Actuators
DN
k
VS
A-AB B-AB
k
VS M6410C,L/M7410C,E M4450/M8450 Z100/M7410
Order Number
(180 N) (90 N) (90 N)
15 0.25 0.16 V5833C1066 800 500 ­15 0.40 0.25 V5833C1009 800 500 ­15 0.63 0.40 V5833C1017 800 500 ­15 1.00 0.63 V5833C1025 250 150 ­15 1.60 1.00 V5833C1033 250 150 ­20 2.50 1.60 V5833C1041 100 50 ­20 2.50 1.60 V5833C1140 240 - ­20 4.00 2.50 V5833C1058 100 50 ­20 4.00 2.50 V5833C1152 240 - ­15 1.60 1.60 V5833C4003* 250 150 150 20 2.50 2.50 V5833C4011* 100 50 50
*For on/off control, stroke 2.5mm.

OPERATION

A built-in return spring in the two-way valve produces an opening force. In the three-way valve and the three-way valve with bypass, the spring produces a closing force on the A to AB ports.
The valves are supplied with a screwed-on adjustment cap for manual operation and for protection of the stem. This allows the stem to be set up for filling or initial heating/cooling during the building construction phase without the use of a controller or actuator.
The small electric valve actuators as well as the thermoelectric actuators provide automatic control over the opening and closing movement of the valve stem.

TYPICAL OPERATION

All types of valves should be mounted in the return flow. If the p-values exceed 60 kPa, attention should be paid to the development of noise.

Two-Way Valves

Direction of flow always from port A to port B Port B: Outlet
outlet
inlet
+
-
outlet
inlet
+
-

Three-Way Valves

These valves are preferably used as mixing valves, this means:
Port AB: Total flow outlet Port A: Controlled flow inlet Port B: Bypass inlet
inlet
+
AB A
B
-
AB A
B
Fig. 2. Three-way valve operation

Three-Way Valves with Bypass

These valves simplify the installation, which is depending on the layout of the pipework, as the bypass pipe is part of the valve. The information for the normal three-way valves is also valid for this type.
inlet
+
AB A
B
-
AB A
B
inlet
+
-
inlet
+
-
Fig. 1. Two-way valve operation
Fig. 3. Three-way valve with bypass
3 EN0B-0308GE51 R1002
V5832A/V5833A,C SMALL LINEAR VALVES PN16

MOUNTING

When installing the valve care must be taken that the flow direction is correct (see section "Typical Operation"). The valve must not be mounted with the stem pointing downward.
The adjustment cap must be removed from the valve only when the actuator is fitted. The valve should be installed as stress-free as possible with a tightening torque of 25 to 30 Nm.
The valve is supplied complete with mounting instructions. The water quality must meet VDI 2035 requirements.

ACCESSORIES

Valves V5832A need two connection sets, valves V5833A three connection sets, and valves V5833C four connection sets.
Connection Pipe Size DN Order Number Connection Set Description
Soldering
External
Thread
*Cannot be purchased from Honeywell
12 mm 15 mm
R3/8" R1/2"
Dimensions of Connection Sets Order Number
G1/2“
G3/4“
G1/2“
G3/4“
15 20
15 20
a c d
AC-15FS AC-20FS
AC-15FT AC-20FT
12 mm
15 mm
R3/8“
R1/2“
Consisting of 1 union nut, 1 solder bush, and 1 gasket
Consisting of 1 union nut, 1 tailpiece, and 1 gasket
AC-15FS
AC-20FS
AC-15FT
AC-20FT
EN0B-0308GE51 R1002 4

DIMENSIONS

A
r
A
r
A
r
A
A
*
Two-way valve
Three-way valve
6. 5 Str ok
6. 5 Str ok e *
V5832A/V5833A,C SMALL LINEAR VALVES PN16
M30x1.5
18
6.5 Stroke*
*
M30x1.5
18
6.5 Stroke*
llow 130mm fo the actuator and clearance for removal
llow 130mm fo the actuator and clearance for removal
a b d
abd
DN15 56 G1/2A 34
DN15 56 G1/2A 34
DN20 66 11/8" x 14 BS 84
DN20 66 G3/4A 33
a b d
ab cd
DN15 56 G1/2
DN15 56 G1/2A 24.5 34
DN20 66 11/8" x 14 BS 84
DN20 66 G3/4A 33 33
33
34
33
c
c
a
a
Three-way valve with bypass
6. 5 Str ok
*
6.5 Stroke*
M30x1.5
18
llow 130mm fo the actuator and clearance for removal
ab cd
a b c d
DN15 56 G1/2
DN15 56 G1/2A 40 34
DN20 66 11/8" x 14 BS 84 40
DN20 66 G3/4A 40 33
40 34
33
Modulating valves, only (in the case of on/off valves, the stroke amounts to 2.5 mm and the closure distance to 14 mm).
Fig. 4. Dimensions V5832A/V5833A,C in mm
5 EN0B-0308GE51 R1002
V5832A/V5833A,C SMALL LINEAR VALVE PN16

SPARE PARTS

Valve inserts are provided as spare parts for the V5832A and V5833A,C small linear valves. When the tool WV 108 is used, the valve inserts can be changed without draining the system.
Order Number DN k
VS
V5832A1004 15 0.16 0902812 V5832A1012 15 0.25 0902811 V5832A1020 15 0.40 0902810 V5832A1038 15 0.63 0902809 V5832A1046 15 1.00 0902808 V5832A1053 15 1.60 0902807 V5832A1061 20 2.50 0902814
V5832A1079 20 4.00 0902815 V5832A4008* 15 1.60 0902813 V5832A4016* 20 4.00 0902816
*For on/off control
Order Number DN k
VS
V5833A1003 / V5833C1066 15 0.25 0902821 V5833A1011 / V5833C1009 15 0.40 0902822 V5833A1029 / V5833C1017 15 0.63 0902823 V5833A1037 / V5833C1025 15 1.00 0902824 V5833A1045 / V5833C1033 15 1.60 0902825 V5833A1052 / V5833C1041 20 2.50 0902826 V5833A3009 / V5833C1140 20 2.50 0902818 V5833A1060 / V5833C1058 20 4.00 0902827
V5833A3017 / V5833C1152 20 4.00 0902819 V5833A4007* / V5833C4003* 15 1.60 0902817 V5833A4015* / V5833C4011* 20 2.50 0902820
*For on/off control
Order Number
Valve Insert
Order Number
Valve Insert
The following valve inserts are interchangeable
Two-way valves: k
Three-way valves: k
Control Products
Honeywell AG Hardhofweg D-74821 Mosbach Phone: (49) 6261 810 Fax: (49) 6261 81309 http://europe.hbc.honeywell.com
Subject to change without notice. Printed in Germany Manufacturing location certified to
0.16, 0.25, 0.40, and 0.63
VS
k
1.0 and 1.6
VS
k
2.5 and 4.0
VS
0.25, 0.40, 0.63, and 1.0
VS
k
2.5 and 4.0
VS
EN0B-0308GE51 R1002
Loading...