Honeywell V5822A, V5823A, V5823C DATASHEET

V5822A/5823A,C
SMALL LINEAR VALVES PN16
FOR MODULATING AND ON/OFF-CONTROL
SPECIFICATION DATA
V5822A V5823A
V5823C
These small linear valves are used in combination with small electric linear valve actuators and thermoelectric actuators for the control of hot and/or chilled water for fan coil units and small reheaters/recoolers in electric/electronic temperature control systems.
FEATURES
Small size allows installation where space is limited
Range of fittings available for different connections
(compression, soldered, threaded)
Long stroke results in a high-quality characteristic
Soft seat provides low leakage rate and high
rangeability
Reduced k
hydronic balancing
Adjustment cap for manual operation
Valve inserts changeable without draining by using
insert replacement tool WV 108
Compatible with two-piece conex compression
fittings
Conical sealing connections
Flat surfaces on body to fit installation tools
40 mm distance between ports A/AB and the bypass
(V5823C, only)
values in the bypass to facilitate
VS
SPECIFICATIONS
Models Two-way V5822A Three-way V5823A Three-way with bypass V5823C
Operation Two-way stem up to open, port A to B; Three-way stem up to close, port A to AB
Nominal pressure rating PN16
Capacity index (k
Leakage rate 0.02% of k
Valve body Material Brass Size DN15 (1/2“), DN20 (3/4“)
) see tables on page 2 and 3
VS
VS
Trim Stem Stainless steel Plug Brass
Suitable medium Water, with max. 50% glycol
Controlled water temperature 2...120 °C
® U.S. Registered Trademark EN0B-0307GE51 R0209 Copyright © 2009 Honeywell Inc. • All rights reserved
V5822A/V5823A,C SMALL LINEAR VALVES PN16
Modulating valves Rangeability Two-way valves 100:1 Three-way valves 100:1 for controlled port
Flow characteristic Equal percentage port A-AB, n linear for bypass port B-AB Stroke 6.5 mm
On/Off valves Stroke 2.5 mm
Dimensions see Fig. 4 on page 5
=3.4,
gl
FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS
TWO-WAY VALVES
Valve Close-Off Pressure (kPa) with Actuators
DN kVS Order Number M6410C,L/M7410C,E
(180 N)
15 0.16 V5822A1006 1600 600 ­15 0.25 V5822A1014 1600 600 ­15 0.40 V5822A1022 1600 600 ­15 0.63 V5822A1030 1600 600 ­15 1.00 V5822A1048 1200 180 ­15 1.60 V5822A1055 1200 180 ­20 2.50 V5822A1063 400 50* ­20 4.00 V5822A1071 400 50* - 15 1.60 V5822A4000** 1200 180 180 20 2.50 V5822A4018** 400 50* 50*
*Up to 1000kPa system pressure. **In the case of on/off control, the stroke amounts to 2.5 mm.
THREE-WAY VALVES
Valve Close-Off Pressure (kPa) with Actuators
DN kVS Order Number M6410C,L/M7410C,E
(180 N)
15 0.25 V5823A2003 800 500 ­15 0.40 V5823A2011 800 500 ­15 0.63 V5823A2029 800 500 ­15 1.00 V5823A2037 250 150 ­15 1.60 V5823A2045 250 150 ­20 2.50 V5823A2151 240 - ­20 2.50 V5823A2052 100 50 ­20 4.00 V5823A2169 240 - ­20 4.00 V5823A2060 100 50 ­15 1.60 V5823A4009* 250 150 150 20 2.50 V5823A4017* 100 50 50
*In the case of on/off control, the stroke amounts to 2.5 mm.
M4450/M8450
(90 N)
M4450/M8450
(90 N)
Z100/M7410A
(90 N)
Z100/M7410A
(90 N)
EN0B-0307GE51 R0209 2
V5822A/V5823A,C SMALL LINEAR VALVES PN16
V
V
A
THREE-WAY VALVES WITH BYPASS
Valve Close-Off Pressure (kPa) with Actuators
k
DN
k
S
A-AB B-AB
S
Order Number
M6410C,L/M7410C,E
(180 N) (90 N) (90 N)
M4450/M8450 Z100/M7410
15 0.25 0.16 V5823C2009 800 500 ­15 0.40 0.25 V5823C2017 800 500 ­15 0.63 0.40 V5823C2025 800 500 ­15 1.00 0.63 V5823C2033 250 150 ­15 1.60 1.00 V5823C2041 250 150 ­20 2.50 1.60 V5823C2058 100 50 ­20 2.50 1.60 V5823C2157 240 - ­20 4.00 2.50 V5823C2066 100 50 ­20 4.00 2.50 V5823C2165 240 - ­15 1.60 1.60 V5823C4005* 250 150 150 20 2.50 2.50 V5823C4013* 100 50 50
*In the case of on/off control, the stroke amounts to 2.5 mm.
OPERATION
A built-in return spring in the two-way valve produces an opening force. In the three-way valve and the three-way valve with bypass, the spring produces a closing force on the A to AB ports.
The valves are supplied with a screwed-on adjustment cap for manual operation and for protection of the stem. This allows the stem to be set up for filling or initial heating/cooling during the building construction phase without the use of a controller or actuator.
The small electric valve actuators as well as the thermoelectric actuators provide automatic control over the opening and closing movement of the valve stem.
TYPICAL OPERATION
All types of valves should be mounted in the return flow. If the p-values exceed 60 kPa, attention should be paid to the development of noise.
Two-Way Valves
Direction of flow always from port A to port B Port B: Outlet
outlet
inlet
+
-
outlet
Fig. 1. Two-way valve operation
inlet
+
-
Three-Way Valves
These valves are preferably used as mixing valves, this means:
Port AB: Total flow outlet Port A: Controlled flow inlet Port B: Bypass inlet
inlet
AB A
B
+
-
inlet
AB A
B
Fig. 2. Three-way valve operation
Three-Way Valves with Bypass
These valves simplify the installation, which is depending on the layout of the pipework, as the bypass pipe is part of the valve. The information for the normal three-way valves is also valid for this type.
inlet
+
AB A
B
-
Fig. 3. Three-way valve with bypass
inlet
AB A
B
+
-
+
-
3 EN0B-0307GE51 R0209
V5822A/V5823A,C SMALL LINEAR VALVES PN16
MOUNTING
When installing the valve care must be taken that the flow direction is correct (see section "Typical Operation"). The valve must not be mounted with the stem pointing downward. The adjustment cap must be removed from the valve only when the actuator is fitted. The valve should be installed as stress-free as possible with a tightening torque of 25 to 30 Nm. The valve is supplied complete with mounting instructions. The water quality must meet VDI 2035 requirements.
ACCESSORIES
For valves V5822A, two connection sets are necessary; for valves V5823A, three connection sets are necessary; for valves V5823C, four connection sets are necessary.
Connection Pipe Size DN Order Number Connection Set Description
Compression
Soldering
External
Thread
Compression
(Conex)
*Cannot be purchased from Honeywell
15 mm 22 mm
12 mm 15 mm
R3/8" R1/2"
15 mm 22 mm
15 20
15 20
15 20
15 20
ACN-15C ACN-20C
ACN-15S ACN-20S
ACN-15T ACN-20T
63* 65*
Consisting of 1 union nut and 1 ferrule
Consisting of 1 union nut and 1 solder bush
Consisting of 1 union nut and 1 tailpiece
Capnut and compression ring
Dimensions of Connection Sets
a b c d
G1/2“
11/8“ x 14 BS 84
G1/2“
11/8“ x 14 BS 84
G1/2“
11/8“ x 14 BS 84
15 mm
22 mm
R3/8"
ACN-15C
12mm
15mm
R1/2"
Order Number
ACN-20C
ACN-15S
ACN-20S
ACN-15T
ACN-20T
EN0B-0307GE51 R0209 4
DIMENSIONS
A
A
A
A
A
*
Two-way valve
Three-way valve
6. 5 Str ok
18
6.5 Stroke* 6.5 Stroke* 6.5 Stroke*
*
6. 5 Str ok
18
e*
M30x1.5
M30x1.5
llow 130mm for the actuator and clearance for removal
llow 130mm for the actuator and clearance for removal
V5822A/V5823A,C SMALL LINEAR VALVES PN16
DN15 56 G1/2A 34
DN20 66 11/8“x14BS 84 33
DN15 56 G1/2A 24.5 34
DN20 66 11/8“x14BS 84 33 33
a b d
b d
DN15 56 G 1/2A 34 DN20 6 11/8" x 14 BS 84
a b c d
a b d
DN15 56 G1/2 DN20 66 11/8" x 14 BS 84
33
34
33
c
a
Three-way valve with bypass
6. 5 Str ok
*
18
M30x1.5
llow 130mm for the actuator and clearance for removal
Modulating valves, only (in the case of on/off valves, the stroke amounts to 2.5 mm and the closure distance to 14 mm).
DN15 56 G1/2
DN15 56 G1/2A 40 34
DN20 66 11/8" x 14 BS 84 40
DN20 66 11/8“x14BS 84 40 33
a b c d
a b c d
40 34
33
Fig. 4. Dimensions V5822A/V5823A,C in mm
5 EN0B-0307GE51 R0209
V5822A/V5823A,C SMALL LINEAR VALVES PN16
SPARE PARTS
Valve inserts are provided as spare parts for the V5822A and V5823A,C small linear valves. When the tool WV 108 is used, the valve inserts can be changed without draining the system.
Order Number DN kVS
V5822A1006 15 0.16 0902812 V5822A1014 15 0.25 0902811 V5822A1022 15 0.40 0902810 V5822A1030 15 0.63 0902809 V5822A1048 15 1.00 0902808 V5822A1055 15 1.60 0902807 V5822A1063 20 2.50 0902814
V5822A1071 20 4.00 0902815 V5822A4000* 15 1.60 0902813 V5822A4018* 20 2.50 0902816
* For on/off control
Order Number DN kVS
V5823A2003 / V5823C2009 15 0.25 0902821 V5823A2014 / V5823C2017 15 0.40 0902822 V5823A2029 / V5823C2025 15 0.63 0902823 V5823A2037 / V5823C2033 15 1.00 0902824 V5823A2045 / V5823C2041 15 1.60 0902825 V5823A2151 / V5823C2058 20 2.50 0902826 V5823A2052 / V5823C2157 20 2.50 0902818 V5823A2169 / V5823C2066 20 4.00 0902827
V5823A2060 / V5823C2165 20 4.00 0902819 V5823A4009* / V5823C4005* 15 1.60 0902817 V5823A4017* / V5823C4013* 20 2.50 0902820
* For on/off control
Order Number
Valve Insert
Order Number
Valve Insert
The following valve inserts are interchangeable
Two-way valves: k k k
Three-way valves: k k
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany
EN0B-0307GE51 R0209
0.16, 0.25, 0.40, and 0.63
VS
1.0 and 1.6
VS
2.5 and 4.0
VS
0.25, 0.40, 0.63, and 1.0
VS
2.5 and 4.0
VS
Loading...