These small linear valves are used in combination with small
electric linear valve actuators and thermoelectric actuators for
the control of hot and/or chilled water for fan coil units and
small reheaters/recoolers in electric/electronic temperature
control systems.
FEATURES
• Small size allows installation where space is limited
• Range of fittings available for different connections
(compression, soldered, threaded)
• Long stroke results in a high-quality characteristic
• Soft seat provides low leakage rate and high
rangeability
• Reduced k
hydronic balancing
• Adjustment cap for manual operation
• Valve inserts changeable without draining by using
insert replacement tool WV 108
• Compatible with two-piece conex compression
fittings
• Conical sealing connections
• Flat surfaces on body to fit installation tools
• 40 mm distance between ports A/AB and the bypass
(V5823C, only)
values in the bypass to facilitate
VS
SPECIFICATIONS
Models Two-way V5822A
Three-way V5823A
Three-way with bypass V5823C
Operation Two-way stem up to open,
port A to B; Three-way stem up
to close, port A to AB
Nominal pressure rating PN16
Capacity index (k
Leakage rate ≤0.02% of k
Valve body
Material Brass
Size DN15 (1/2“), DN20 (3/4“)
*In the case of on/off control, the stroke amounts to 2.5 mm.
OPERATION
A built-in return spring in the two-way valve produces an
opening force. In the three-way valve and the three-way valve
with bypass, the spring produces a closing force on the A to
AB ports.
The valves are supplied with a screwed-on adjustment cap for
manual operation and for protection of the stem. This allows
the stem to be set up for filling or initial heating/cooling during
the building construction phase without the use of a controller
or actuator.
The small electric valve actuators as well as the
thermoelectric actuators provide automatic control over the
opening and closing movement of the valve stem.
TYPICAL OPERATION
All types of valves should be mounted in the return flow. If the
∆p-values exceed 60 kPa, attention should be paid to the
development of noise.
Two-Way Valves
Direction of flow alwaysfrom port A to port B
Port B: Outlet
outlet
inlet
+
-
outlet
Fig. 1. Two-way valve operation
inlet
+
-
Three-Way Valves
These valves are preferably used as mixing valves, this
means:
Port AB: Total flow outlet
Port A: Controlled flow inlet
Port B: Bypass inlet
inlet
ABA
B
+
-
inlet
ABA
B
Fig. 2. Three-way valve operation
Three-Way Valves with Bypass
These valves simplify the installation, which is depending on
the layout of the pipework, as the bypass pipe is part of the
valve. The information for the normal three-way valves is also
valid for this type.
inlet
+
ABA
B
-
Fig. 3. Three-way valve with bypass
inlet
ABA
B
+
-
+
-
3 EN0B-0307GE51 R0209
V5822A/V5823A,C SMALL LINEAR VALVES PN16
MOUNTING
When installing the valve care must be taken that the flow
direction is correct (see section "Typical Operation"). The
valve must not be mounted with the stem pointing downward.
The adjustment cap must be removed from the valve only
when the actuator is fitted. The valve should be installed as
stress-free as possible with a tightening torque of 25 to
30 Nm.
The valve is supplied complete with mounting instructions.
The water quality must meet VDI 2035 requirements.
ACCESSORIES
For valves V5822A, two connection sets are necessary; for valves V5823A, three connection sets are necessary; for valves
V5823C, four connection sets are necessary.
Connection Pipe Size DN Order NumberConnection Set Description
Compression
Soldering
External
Thread
Compression
(Conex)
*Cannot be purchased from Honeywell
15 mm
22 mm
12 mm
15 mm
R3/8"
R1/2"
15 mm
22 mm
15
20
15
20
15
20
15
20
ACN-15C
ACN-20C
ACN-15S
ACN-20S
ACN-15T
ACN-20T
63*
65*
Consisting of 1 union nut
and 1 ferrule
Consisting of 1 union nut
and 1 solder bush
Consisting of 1 union nut
and 1 tailpiece
Capnut and compression ring
Dimensions of Connection Sets
a b c d
G1/2“
11/8“ x 14 BS 84
G1/2“
11/8“ x 14 BS 84
G1/2“
11/8“ x 14 BS 84
15 mm
22 mm
R3/8"
ACN-15C
12mm
15mm
R1/2"
Order Number
ACN-20C
ACN-15S
ACN-20S
ACN-15T
ACN-20T
EN0B-0307GE51 R0209 4
DIMENSIONS
A
A
A
A
A
*
Two-way valve
Three-way valve
6.5Strok
18
6.5 Stroke* 6.5 Stroke* 6.5 Stroke*
*
6.5Strok
18
e*
M30x1.5
M30x1.5
llow 130mm for
the actuator and
clearance for
removal
llow 130mm for
the actuator and
clearance for
removal
V5822A/V5823A,C SMALL LINEAR VALVES PN16
DN15 56 G1/2A 34
DN20 66 11/8“x14BS 84 33
DN15 56 G1/2A 24.534
DN20 66 11/8“x14BS 84 33 33
a b d
b d
DN15 56 G1/2A 34 DN20 6 11/8" x 14 BS 84
a b c d
a b d
DN15 56 G1/2 DN20 66 11/8" x 14 BS 84
33
34
33
c
a
Three-way valve with bypass
6.
5Strok
*
18
M30x1.5
llow 130mm for
the actuator and
clearance for
removal
Modulating valves, only (in the case
of on/off valves, the stroke amounts
to 2.5 mm and the closure distance
to 14 mm).
DN15 56 G1/2
DN15 56 G1/2A 40 34
DN20 66 11/8" x 14 BS 84 40
DN20 66 11/8“x14BS 84 40 33
a b c d
a b c d
40 34
33
Fig. 4. Dimensions V5822A/V5823A,C in mm
5 EN0B-0307GE51 R0209
V5822A/V5823A,C SMALL LINEAR VALVES PN16
SPARE PARTS
Valve inserts are provided as spare parts for the V5822A and V5823A,C small linear valves. When the tool WV 108 is used, the
valve inserts can be changed without draining the system.
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich
Germany
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0307GE51 R0209
0.16, 0.25, 0.40, and 0.63
VS
1.0 and 1.6
VS
2.5 and 4.0
VS
0.25, 0.40, 0.63, and 1.0
VS
2.5 and 4.0
VS
Loading...