The V5422L and V5422E Actuated Butterfly Valves are
suitable for heating and cooling applications as well as in
boiler management systems. They can also be employed for
general services, water treatment, etc.
The V5422L series is equipped with floating-control actuators
(230 V, three-point).
The V5422E series is equipped with modulating-control
actuators with a standard control signal of 0...10 V (2...10 V,
0...20 mA, and 4...20 mA also possible).
The actuators and valves are delivered factory-mounted. The
position control and the end stops are completely justified.
V5422L / V5422E
ACTUATED BUTTERFLY VALVES
SPECIFICATION DATA
FEATURES
• With factory-mounted electric actuator
• Centric butterfly valve with elastomer liner
• Wide DN range (DN250 through DN400)
• For heating water containing up to 50% glycol
• Wafer body
• For modulating and floating control
• Maintenance-free control drive
• Mechanical setting indicator
• Manual adjustment wheel and declutch button
• Ample reserve torque
• Sizable terminal compartment for cabling
• Long unit lifetime
SPECIFICATIONS
Valves
Sizes DN250...DN400
Nominal pressure rating PN10
Shut-off pressure 10 bar
Tightness bubble-tight
Temperature of medium -10...+120 °C
Body Wafer, ductile iron GGG40
Liner EPDM
Disc ductile iron GGG40
coating: DeltaMagni
Shaft Stainless steel 1.4021
Actuators
Motor voltage 230 Vac (±10%), 50 to 60 Hz
Current, running time See Table 1
Angle of rotation 90°
Duty cycles max. 30% (class S4 IEC60034)
Running noise 65 dBA
Ambient temperature -20...+70 °C
Motor insulation class F according to VDE 0530
Protection class IP67 as per DIN 40050
Cable gland M20, cable ∅ 9...16 mm
The actuator's position is indicated by a mechanical pointer
located behind a window on the actuator's cover.
The actuator's running status is indicated by three LED's
located on the main PCB:
•The green LED (Op) is lit when the valve has been
opened.
•The red LED (Cl) is lit when the valve has been closed.
Angle Limitation
The angle at the drive shaft can be
adjusted to between 0° and 90°.
The end position is limited both electrically and mechanically. The electrical
limitation can be adjusted by pressing
and turning (with a screwdriver) the
adjustment screws situated on the
white and black cams.
The end position is factory-set to -2°
and +92°. As a rule, it is not necessary
to alter this value.
Manually Adjusting Valve
CAUTION
Before manually adjusting the valve, you must first
disconnect the power supply!
The valve can be manually adjusted using the manual
adjustment wheel and declutch button (see Fig. 1).
Fig. 1. Manual adjustment wheel and declutch button
The manual safety wheel is disengaged automatically when
the motor is running. To use the manual safety wheel, it must
therefore first be re-engaged using the declutch button.
Motor and Gear Protection
The actuator motor is protected against overheating by a
bimetal temperature monitor.
The motor and gear train are also protected against
mechanical overload by a torque limiter switch. The yellow
LED (Tq) is lit when the torque limiter has been activated.
Maintenance
The actuators are maintenance-free. They are lubricated for a
minimum of 100,000 operations.
If it becomes necessary to renew the grease completely, use
a lubricant complying with the following specifications:
• temperature range: -30...+135 °C
• penetration: ASTM 265/295 at 25 °C
• drop point: 180 °C
E.g. ELF Expecta 250, TOTAL Multis EP2, SHELL alvania
EP2, MOBIL Mobilux EP2, or ESSO Beacon EP2.
The V5422L series is equipped with a main PCB (see Fig. 3)
located (together with the angle indicator) under the cover
(see Fig. 4). To access the main PCB, remove the cover.
Tr1Tr2
1
2
18
17
16
17
18
4
9
Dead
Band
P1
Cl Op Tq
red/green/yellow LEDs
feedback jacks
microswitches
A
B
7
654321
707172733132
70
71 72 73 31 32L N PE
Fig. 3. Main PCB of the V5422L
input
15
12 14 11
10
Tr1
R2
R1
LNPE
power supply
27 26 41 40 1 2 3 3
Ful
10000
5000
1000
0
5
500
400
300
250
3
flow (cubic meters per h)
100
50
20
0.10.5151050
velocity (m/s)
Fig. 2. Flow rate and valve pressure drop
EN0B-0319GE51 R0108
3
V5422L / V5422E ACTUATED BUTTERFLY VALVES
angle
indicator
main printed
circuit board
feedback
terminals
Fig. 4. Explosion view
Input Terminals
An external floating controller controls the actuator of the
V5422L. This controller transmits the phase to input 31 (for
closing the valve) or to input 32 (for opening the valve). See
also Fig. 12.
Feedback Terminals
The V5422L is equipped with two change-over switches (see
Fig. 5):
• terminals 20, 21, and 22 (provides a feedback signal that
the valve is in the OPEN position) and
• terminals 23, 24, and 25 (provides a feedback signal that
the valve is in the CLOSED position).
20
21
22
23
24
25
Fig. 5. Feedback terminals
NOTE: These change-over switches must be supplied with
power from an independent (external) power source
(maximum permissible load: 230 Vac, 16 A).
Adjusting the V5422L for Floating Control
A
B
7
Fig. 6. Default microswitch settings of the V5422L
• To adjust the V5422L for floating control, microswitches 5
and 6 (located on the main PCB; see Fig. 3) must both be
set to position "B" (see Fig. 6).
NOTE: In the case of the V5422L, microswitches 1, 2, 3,
and 4 have no function/effect.
5
6
3
4
ON
221
1
Adjusting the Direction of Rotation of the V5422L
• To adjust the direction of rotation so that the V5422L
closes in the clockwise (right) direction, microswitch 7
must be set to position "A".
• To set the direction of rotation so that the V5422L closes
in the counterclockwise (left) direction, microswitch 7 must
be set to position "B".
EN0B-0319GE51 R0108 4
V5422L / V5422E ACTUATED BUTTERFLY VALVES
V5422E (Modulating Control)
The V5422E series is equipped with a main PCB (see Fig. 7)
located (together with a feedback potentiometer and the angle
indicator) under the cover (see Fig. 4). To access the main
PCB, remove the cover.
Tr1Tr2
1
2
18
17
16
17
feedback jacks
18
microswitches
4
A
adjustment
9
Dead
Band
Cl Op Tq
red/green
/yellow LEDs
B
7
654321
707172733132
70
71 72 73 31 32L N PE
analog
input/output
P1
P2 offset
Fig. 7. Main PCB of the V5422E
Adjusting the V5422E for Modulating Control
A
B
7
6
Fig. 8. Default microswitch settings of the V5422E
• To adjust the V5422E for modulating control, microswitches 5 and 6 (located on the main PCB; see Fig. 7)
must both be set to position "A" (see Fig. 8).
Adjusting the Direction of Rotation of the V5422E
• To adjust the direction of rotation so that the V5422E
closes in the clockwise (right) direction, microswitch 7
must be set to position "A".
• To set the direction of rotation so that the V5422E closes
in the counterclockwise (left) direction, microswitch 7 must
be set to position "B".
See also section "Reversing Direction of Rotation of the
V5422E".
Adjusting the Input Signal Range of the V5422E
The input signal range (0/2...10 V or 0/4...20 mA) and the
corresponding output signal are set using microswitches 1, 2,
3, and 4 (see Table 3).
15
12 14 11
10
Tr1
R2
R1
LNPE
power supply
27 26 41 40 1 2 3 3
Ful
1
ON
5
3
4
221
Table 3. Adjusting the input signal range (V5422E)
Input
signal
output
signal
microswitch positions
1 2 3 4 5 6 7*
0…10 V 0…10 V B B B B A A A/B
2…10 V 2…10 V B B B A A A A/B
4…20 mA 4…20 mA A A A A A A A/B
0…20 mA 0…20 mA A A A B A A A/B
0…10 V 0…20 mA B B A B A A A/B
2…10 V 4…20 mA B B A A A A A/B
4…20 mA 2…10 V A A B A A A A/B
0…20 mA 0…10 V A A B B A A A/B
*Depends upon desired direction of rotation.
Terminals for Input/Output Signals
An external modulating controller controls the actuator of the
V5422E by means of an analog signal provided at terminal
70/71. An analog output signal for position indication is
provided at terminal 71/72.
Adjusting the Input/Output Signal Offset
The offset of modulating actuators is adjusted at the factory
and should not be changed. If you wish to change the offset
(using offset potentiometer P2; see Fig. 7), note that an
excessively small offset will result in oscillation of the
actuator.
Reversing Direction of Rotation of the V5422E
In the case of the V5422E, it is possible to reverse the
direction of rotation of the valve by adjusting the feedback
signals. The feedback signals are adjusted by resetting the
microswitches and replugging the feedback potentiometer's
cables. To do this, proceed as follows:
1. Turn the power off.
2. Reset the microswitches as shown in Table 3, but with
microswitch 7 in position B.
3. Replug the feedback potentiometer's cables as shown in
Fig. 9.
Fig. 9. Replugging the feedback potentiometer's cables
4. Apply the desired control signal (10 V or 20 mA, as the
case may be) for the closing position.
5. Turn the power back on.
6. Using a small screwdriver, adjust the potentiometer P1
(located on the main PCB; see Fig. 7) until the valve
closes completely.
EN0B-0319GE51 R0108
5
V5422L / V5422E ACTUATED BUTTERFLY VALVES
VALVE MOUNTING
Install the actuated valve in the pipe according the following
steps (see also Fig. 10).
1. Spread the valve's flanges to facilitate installation. The
valve's disc must be partially open.
2. Set all stay-bolts while keeping the valve's disc slightly
open and without tightening the nuts.
3. Open the valve's disc completely. Ensure that the piping is
aligned. Tighten diagonally opposite the nuts until the
flanges are in contact with the body of the valve. Never
use gaskets or grease. Never weld the flanges after the
valve has been installed.
Step 1Step 2Step 3
Fig. 10. Installing the valve
Bolting
Table 4 lists the number of bolts and nuts required for
mounting. The number is dependent upon the size (DN).
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative: