Honeywell V5329A, V5329C User Manual

APPLICATION
These three port mixing valves are used for modulating control of hot or chilled water in heating, ventilation and air conditioning systems and can be operated by electric linear actuators as ML6420/6425, ML7420/7425, M6421/7421 or by pneumatic actuators MP953.
V5329A,C
FLANGED LINEAR VALVE PN6/16
SPECIFICATION DATA
FEATURES
Cast iron body with flanged end connections
Metal to metal seating for long life span
Self adjusting packing
Accurate positioning to ensure state of the art
temperature control Direct coupled electric and pneumatic actuators for
easy mounting Constant total flow throughout full plug travel
SPECIFICATIONS
Action Stem up to close port A-AB Nominal pressure rating V5329A - PN16
Flow characteristic Equal percentage port A-AB,
Rangeability 50:1 Leakage rate
Stroke 20 mm Valve body
End connections Flanged per ISO 7005-2 Material Cast iron (GG25) Dimensions See Fig. 1
Trim
Seat Body integrated Plug Stainless steel, skirt guided Stem Stainless steel
Packing Spring loaded PTFE cone rings Medium temperature
and max. pressure
PN16 2 ... 120 °C; 1600 kPa
PN6 2 ... 120 °C; 600 kPa
Maximum temperature differential in alternating hot/cold water use 60 K
V5329C - PN6
linear port B-AB
0.5 % of k
1 % of k
120 ... 150 °C; 1440 kPa 150 ... 170 °C; 1370 kPa
120 ... 150 °C; 540 kPa 150 ... 170 °C; 510 kPa
port A-AB
VS
port B-AB
VS
EN0B-0434GE02 R0299
V5329A,C FLANGED LINEAR VALVE PN6/16
SIZES AND FLOW CAPACITIES
Order Number Valve Size k
V5329A1004 DN15 2.5 V5329A1012 DN15 4.0 V5329A1020 DN20 6.3 V5329A1038 DN25 10.0 V5329A1046 DN32 16.0 V5329A1053 DN40 25.0 V5329A1061 DN50 40.0 V5329A1079 DN65 63.0 V5329A1087 DN80 100.0 V5329C1000 DN15 2.5 V5329C1018 DN15 4.0 V5329C1026 DN20 6.3 V5329C1034 DN25 10.0 V5329C1042 DN32 16.0 V5329C1059 DN40 25.0 V5329C1067 DN50 40.0 V5329C1075 DN65 63.0 V5329C1083 DN80 100.0
INSTALLATION
VS
Water should meet VDI 2035 requirements.
Do not install valve with stem below the horizontal.
Fluid flow must correspond with the arrow direction on the valve body.
The installation of a strainer is strongly recommended.
REPAIR PACKING KIT
Part No.: R 43 176 754 - 001 (DN1532)
R 43 176 754 - 002 (DN4080)
CLOSE OFF PRESSURE RATINGS IN kPa
Pneumatic actuators
Actuator
Model
MP953
A5005, C5027
C5019 5 x 55-83kPa
C5068 8 x 14-48kPa
A5039, C5084
C5076 8 x 55-83kPa
D5025 7 x 27-76kPa
B5003, D5009
)
1
For V5329C maximum 600 kPa
2)
For V5329A only
Size
(in)
Acting
dir. rev.
Actuator
Spring Range
5 x 27-76kPa
(4-11PSI)
(8-12PSI)
(2-7PSI)
8 x 27-76kPa
(4-11PSI)
(8-12PSI)
(4-11PSI)
7 x 55-90kPa
(8-13PSI)
Air
Pressure
in
Actuator
0kPa
115kPa
Positi­oner
Closed
Valve
Seat
yes
no no 500
no upper
lower
yes
no no
no
lower
yes
upper
no
Valve Size
DN15 DN20 DN25 DN32 DN40 DN50 DN65 DN80
150
150
370
200
340
1600
980
1400 1600
1000
480
790
1200
600
150
370
3709024040130
500
500
200
200
2)
2)
340
980
480
790
600
340
2)
1600
2)
980
2)
1400
2)
1600
2)
1000
480
1)
790
1)
1200
600
2)
1600
2)
2)
1400
2)
1600
2)
1000
1)
1)
1200
330
190
120
2)
220
2)
1600
2)
600
2)
920
2)
1300
2)
730
320
1)
540
1)
830
410
60
120
1)
1000
2)
360
2)
570
2)
850
2)
440
180 32090170501002060
1)
510 240
---
---
50
1)
600 200
320
2)
480
2)
240
280
--
120 20070120
300 150
17070100
120
190
90
40
EN0B-0434GE02 R0299 2