APPLICATION
These three port mixing valves are used for modulating control of hot or chilled water in heating, ventilation and air conditioning systems and can be operated by electric linear actuators as ML6420/6425, ML7420/7425, M6421/7421 or by pneumatic actuators MP953.
V5329A,C
FLANGED LINEAR VALVE PN6/16
SPECIFICATION DATA
FEATURES
•Cast iron body with flanged end connections
•Metal to metal seating for long life span
•Self adjusting packing
•Accurate positioning to ensure state of the art temperature control
•Direct coupled electric and pneumatic actuators for easy mounting
•Constant total flow throughout full plug travel
SPECIFICATIONS
Action |
Stem up to close port A-AB |
|||
Nominal pressure rating |
V5329A - PN16 |
|
||
|
V5329C - PN6 |
|
||
Flow characteristic |
Equal percentage port A-AB, |
|||
|
linear port B-AB |
|
||
Rangeability |
50:1 |
|
|
|
Leakage rate |
≤ 0.5 % of kVS port A-AB |
|||
|
≤ 1 % of kVS port B-AB |
|||
Stroke |
20 mm |
|
|
|
Valve body |
|
|
|
|
End connections |
Flanged per ISO 7005-2 |
|||
Material |
Cast iron (GG25) |
|||
Dimensions |
See Fig. 1 |
|
|
|
Trim |
|
|
|
|
Seat |
Body integrated |
|
||
Plug |
Stainless steel, skirt guided |
|||
Stem |
Stainless steel |
|
||
Packing |
Spring loaded PTFE cone rings |
|||
Medium temperature |
|
|
|
|
and max. pressure |
|
|
|
|
PN16 |
2 |
... 120 |
°C; 1600 kPa |
|
|
120 |
... 150 |
°C; 1440 kPa |
|
|
150 |
... 170 |
°C; 1370 kPa |
|
PN6 |
2 |
... 120 |
°C; |
600 kPa |
|
120 |
... 150 |
°C; |
540 kPa |
|
150 |
... 170 |
°C; |
510 kPa |
Maximum temperature |
|
|
|
|
differential in alternating |
|
|
|
|
hot/cold water use |
60 K |
|
|
EN0B-0434GE02 R0299
V5329A,C FLANGED LINEAR VALVE PN6/16
SIZES AND FLOW CAPACITIES
Order Number |
Valve Size |
kVS |
V5329A1004 |
DN15 |
2.5 |
|
|
|
V5329A1012 |
DN15 |
4.0 |
|
|
|
V5329A1020 |
DN20 |
6.3 |
|
|
|
V5329A1038 |
DN25 |
10.0 |
|
|
|
V5329A1046 |
DN32 |
16.0 |
|
|
|
V5329A1053 |
DN40 |
25.0 |
|
|
|
V5329A1061 |
DN50 |
40.0 |
|
|
|
V5329A1079 |
DN65 |
63.0 |
|
|
|
V5329A1087 |
DN80 |
100.0 |
|
|
|
V5329C1000 |
DN15 |
2.5 |
|
|
|
V5329C1018 |
DN15 |
4.0 |
|
|
|
V5329C1026 |
DN20 |
6.3 |
|
|
|
V5329C1034 |
DN25 |
10.0 |
|
|
|
V5329C1042 |
DN32 |
16.0 |
|
|
|
V5329C1059 |
DN40 |
25.0 |
|
|
|
V5329C1067 |
DN50 |
40.0 |
|
|
|
V5329C1075 |
DN65 |
63.0 |
|
|
|
V5329C1083 |
DN80 |
100.0 |
|
|
|
INSTALLATION
•Water should meet VDI 2035 requirements.
•Do not install valve with stem below the horizontal.
•Fluid flow must correspond with the arrow direction on the valve body.
•The installation of a strainer is strongly recommended.
REPAIR PACKING KIT
Part No.: R 43 176 754 - 001 (DN15… 32)
R 43 176 754 - 002 (DN40… 80)
CLOSE OFF PRESSURE RATINGS IN kPa
Pneumatic actuators
|
|
|
|
|
|
|
|
|
|
Valve Size |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Actuator |
Size |
Acting |
Actuator |
Air |
Positi- |
Closed |
DN15 |
DN20 |
DN25 |
DN32 |
DN40 |
DN50 |
DN65 |
DN80 |
|
Model |
(in) |
dir. rev. |
Spring |
Pressure |
oner |
Valve |
|
|
|
|
|
|
|
|
|
MP953 |
|
Range |
in |
|
Seat |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
Actuator |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A5005, |
5 |
x |
27-76kPa |
|
yes |
|
150 |
150 |
150 |
90 |
40 |
- |
- |
- |
|
C5027 |
|
|
(4-11PSI) |
|
no |
|
370 |
370 |
370 |
240 |
130 |
|
|||
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C5019 |
5 |
x |
55-83kPa |
|
no |
|
500 |
500 |
500 |
330 |
190 |
- |
- |
- |
|
|
|
|
(8-12PSI) |
|
|
|
200 |
200 |
200 |
120 |
60 |
|
|||
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C5068 |
8 |
x |
14-48kPa |
|
no |
upper |
3402) |
3402) |
3402) |
220 |
120 |
50 |
- |
- |
|
|
|
|
(2-7PSI) |
|
|
lower |
16002) |
16002) |
16002) |
16001) |
10001) |
600 |
|
||
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A5039, |
8 |
x |
27-76kPa |
0kPa |
yes |
|
9802) |
9802) |
9802) |
6002) |
360 |
200 |
120 |
70 |
|
C5084 |
|
|
(4-11PSI) |
115kPa |
no |
|
14002) |
14002) |
14002) |
9202) |
570 |
320 |
200 |
120 |
|
C5076 |
8 |
x |
55-83kPa |
|
no |
|
16002) |
16002) |
16002) |
13002) |
8502) |
480 |
300 |
190 |
|
|
|
|
(8-12PSI) |
|
|
|
10002) 10002) 10002) |
7302) |
4402) |
240 |
150 |
90 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
D5025 |
7 |
x |
27-76kPa |
|
no |
|
480 |
480 |
480 |
320 |
180 |
90 |
50 |
20 |
|
|
|
|
(4-11PSI) |
|
|
lower |
7901) |
7901) |
7901) |
540 |
320 |
170 |
100 |
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
B5003, |
7 |
x |
55-90kPa |
|
yes |
upper |
12001) |
12001) |
12001) |
8301) |
510 |
280 |
170 |
100 |
|
D5009 |
|
|
(8-13PSI) |
|
no |
|
600 |
600 |
600 |
410 |
240 |
120 |
70 |
40 |
|
1) For V5329C maximum 600 kPa
2) For V5329A only
EN0B-0434GE02 R0299 |
2 |