Honeywell V5329A, V5329C User Manual

APPLICATION

These three port mixing valves are used for modulating control of hot or chilled water in heating, ventilation and air conditioning systems and can be operated by electric linear actuators as ML6420/6425, ML7420/7425, M6421/7421 or by pneumatic actuators MP953.

V5329A,C

FLANGED LINEAR VALVE PN6/16

SPECIFICATION DATA

FEATURES

Cast iron body with flanged end connections

Metal to metal seating for long life span

Self adjusting packing

Accurate positioning to ensure state of the art temperature control

Direct coupled electric and pneumatic actuators for easy mounting

Constant total flow throughout full plug travel

SPECIFICATIONS

Action

Stem up to close port A-AB

Nominal pressure rating

V5329A - PN16

 

 

V5329C - PN6

 

Flow characteristic

Equal percentage port A-AB,

 

linear port B-AB

 

Rangeability

50:1

 

 

 

Leakage rate

0.5 % of kVS port A-AB

 

1 % of kVS port B-AB

Stroke

20 mm

 

 

Valve body

 

 

 

 

End connections

Flanged per ISO 7005-2

Material

Cast iron (GG25)

Dimensions

See Fig. 1

 

 

Trim

 

 

 

 

Seat

Body integrated

 

Plug

Stainless steel, skirt guided

Stem

Stainless steel

 

Packing

Spring loaded PTFE cone rings

Medium temperature

 

 

 

 

and max. pressure

 

 

 

 

PN16

2

... 120

°C; 1600 kPa

 

120

... 150

°C; 1440 kPa

 

150

... 170

°C; 1370 kPa

PN6

2

... 120

°C;

600 kPa

 

120

... 150

°C;

540 kPa

 

150

... 170

°C;

510 kPa

Maximum temperature

 

 

 

 

differential in alternating

 

 

 

 

hot/cold water use

60 K

 

 

EN0B-0434GE02 R0299

Honeywell V5329A, V5329C User Manual

V5329A,C FLANGED LINEAR VALVE PN6/16

SIZES AND FLOW CAPACITIES

Order Number

Valve Size

kVS

V5329A1004

DN15

2.5

 

 

 

V5329A1012

DN15

4.0

 

 

 

V5329A1020

DN20

6.3

 

 

 

V5329A1038

DN25

10.0

 

 

 

V5329A1046

DN32

16.0

 

 

 

V5329A1053

DN40

25.0

 

 

 

V5329A1061

DN50

40.0

 

 

 

V5329A1079

DN65

63.0

 

 

 

V5329A1087

DN80

100.0

 

 

 

V5329C1000

DN15

2.5

 

 

 

V5329C1018

DN15

4.0

 

 

 

V5329C1026

DN20

6.3

 

 

 

V5329C1034

DN25

10.0

 

 

 

V5329C1042

DN32

16.0

 

 

 

V5329C1059

DN40

25.0

 

 

 

V5329C1067

DN50

40.0

 

 

 

V5329C1075

DN65

63.0

 

 

 

V5329C1083

DN80

100.0

 

 

 

INSTALLATION

Water should meet VDI 2035 requirements.

Do not install valve with stem below the horizontal.

Fluid flow must correspond with the arrow direction on the valve body.

The installation of a strainer is strongly recommended.

REPAIR PACKING KIT

Part No.: R 43 176 754 - 001 (DN15… 32)

R 43 176 754 - 002 (DN40… 80)

CLOSE OFF PRESSURE RATINGS IN kPa

Pneumatic actuators

 

 

 

 

 

 

 

 

 

 

Valve Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Actuator

Size

Acting

Actuator

Air

Positi-

Closed

DN15

DN20

DN25

DN32

DN40

DN50

DN65

DN80

 

Model

(in)

dir. rev.

Spring

Pressure

oner

Valve

 

 

 

 

 

 

 

 

 

MP953

 

Range

in

 

Seat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A5005,

5

x

27-76kPa

 

yes

 

150

150

150

90

40

-

-

-

 

C5027

 

 

(4-11PSI)

 

no

 

370

370

370

240

130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C5019

5

x

55-83kPa

 

no

 

500

500

500

330

190

-

-

-

 

 

 

 

(8-12PSI)

 

 

 

200

200

200

120

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C5068

8

x

14-48kPa

 

no

upper

3402)

3402)

3402)

220

120

50

-

-

 

 

 

 

(2-7PSI)

 

 

lower

16002)

16002)

16002)

16001)

10001)

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A5039,

8

x

27-76kPa

0kPa

yes

 

9802)

9802)

9802)

6002)

360

200

120

70

 

C5084

 

 

(4-11PSI)

115kPa

no

 

14002)

14002)

14002)

9202)

570

320

200

120

 

C5076

8

x

55-83kPa

 

no

 

16002)

16002)

16002)

13002)

8502)

480

300

190

 

 

 

 

(8-12PSI)

 

 

 

10002) 10002) 10002)

7302)

4402)

240

150

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D5025

7

x

27-76kPa

 

no

 

480

480

480

320

180

90

50

20

 

 

 

 

(4-11PSI)

 

 

lower

7901)

7901)

7901)

540

320

170

100

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B5003,

7

x

55-90kPa

 

yes

upper

12001)

12001)

12001)

8301)

510

280

170

100

 

D5009

 

 

(8-13PSI)

 

no

 

600

600

600

410

240

120

70

40

 

1) For V5329C maximum 600 kPa