Honeywell V5050A, V5050B DATASHEET

Page 1
V5050A,B
FLANGED LINEAR VALVE PN16 AND PN25/40
SPECIFICATION DATA
These three-port mixing valves are used for modulating control of hot/chilled water or steam in heating, ventilation, and air conditioning systems and can be operated by electric linear actuators ML6420/ML6425, ML7420/ML7425, and ML6421/ML7421 or by pneumatic actuator MP953.
FEATURES
Cast iron body with flanged end connections
Low seat leakage rate
Metal-to-metal seating for long life span
Self-adjusting packing
Accurate positioning to ensure state-of-the-art
temperature control
Easy mounting of direct-coupled electric and
pneumatic actuators
Constant total flow throughout entire plug travel
SPECIFICATIONS
Action Stem up to close port A-AB Nominal pressure rating PN16, PN25/40
Flow characteristic linear for ports A-AB and B-AB Rangeability 50:1 Leakage rate 0.1 % of k
0.1 % of k Stroke 20 mm DN15...80
38 mm DN100...150
Valve body
End connections Flanged per ISO 7005-2 Material Cast iron (GG25) PN16 Cast steel (GS-C25) PN25/40
Dimensions See Fig. 1.
Trim
Seat Stainless steel, replaceable Plug Stainless steel, skirt guided Stem Stainless steel
Packing Spring-loaded PTFE V-rings
Medium temperature and max. pressure
PN16
120 ... 150 °C; max. 1440 kPa
150 ... 200 °C; max. 1280 kPa
200 ... 220 °C; max. 1200 kPa
PN25/40
120 ... 150 °C; max. 3920 kPa
150 ... 200 °C; max. 3800 kPa
200 ... 220 °C; max. 3720 kPa
Maximum temperature differential in alternating hot/cold water use 60 K
2 ... 120 °C; max. 1600 kPa
2 ... 120 °C; max. 4000 kPa
port A-AB
VS
port B-AB
VS
® U.S Registered Trademark EN0B-0413GE51 R0808 Copyright © 2008 Honeywell Inc. All Rights Reserved
Page 2
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
SIZES AND FLOW CAPACITIES
Order Number Valve Size kVS
V5050A1124 DN15 2.5 V5050A1132 DN15 4.0 V5050A1140 DN20 6.3 V5050A1157 DN25 10.0 V5050A1165 DN32 16.0 V5050A1173 DN40 25.0 V5050A1181 DN50 40.0 V5050A1199 DN65 63.0 V5050A1207 DN80 100.0 V5050A1215 DN100 160.0
V5050B1155*
V5050A1090 DN100 160.0 V5050A1108 DN125 250.0 V5050A1116 DN150 360.0
V5050B1064* DN100 160.0 V5050B1072* DN125 250.0 V5050B1080*
* Reverse acting valve, only available on special request.
PN25/40
DN100 160.0
PN16
DN150 360.0
INSTALLATION
Water should meet VDI 2035 requirements.
Do not install valve with stem below the horizontal.
Fluid flow must correspond with the arrow direction on
the valve body.
The installation of a strainer is strongly recommended.
REPAIR PACKING KIT
Part No.: R 43 176 755 - 004 (DN15...80) R 43 176 755 - 005 (DN100...150)
ACTUATORS
Electric Actuators
600 N
valve
size
model
Pneumatic Actuators
valve
size
MP953A 5“, 8“ x
MP953B 7“ x
DN
15-80
100-150
MP953C 5“, 8“ x
MP953D 7“ x
MP953A 13“ x yes
DN
MP953C 13“ x no
600 N
spring
return
DN15-80
ML6420A ML7420A
actuator action
model size direct reverse
ML6425A,B ML7425A,B
1800 N
DN
15-80
ML6421A ML6421A
DN
100-150
ML6421B ML6421B
positioner
yes
no
EN0B-0413GE51 R0808 2
Page 3
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
CLOSE OFF PRESSURE RATINGS in kPa
Electric Actuators
actuator valve size
model
ML6420A, ML6425A,B ML7420A, ML7425A,B
ML6421A,B ML7421A,B
Pneumatic Actuators
actuator valve size
force DN15 DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100 DN125 DN150
600 N 1000 1000 1000 600 350 200 120 50 - - -
1800 N 2500 2500 2500 2000 1300 750 500 230 230 90 90
model
MP953 A,C; (5“)
MP953 C; (5“)
MP953C; (8“)
MP953A,C; (8“)
MP953C; (8“)
MP953C; (13“)
MP953A,C; (13“)
MP953D; (7“)
MP953B,D; (7“)
actuator
spring
range
27-76 kPa (4-11 PSI)
55-83 kPa (8-12 PSI)
14-48 kPa
(2-7 PSI)
27-76 kPa (4-11 PSI)
55-83 kPa (8-12 PSI)
14-48 kPa
(2-7 PSI)
27-76 kPa (4-11 PSI)
27-76 kPa (4-11 PSI)
55-90 kPa (8-13 PSI)
air
pressure
in
actuator
0 kPa
115 kPa
closed
valve
seat
upper lower
DN
15 DN20 DN25 DN32 DN40 DN50
160
160
160
410
410
410 70230
550
550
550
310
220
220
220
110
370
370
370
200
1600
1600
1600
1600
980
980
980
570
1500
1500
1500
1600
1600
1600
1100
1100
1100
- - - - - - - -
- - - - - - - -
880
880
530
530
680
680
1300
1300
1300
880 530
680
890
1300
700
510 300
390 800
- - - - - - -
180
50
110 100 40570
340 540
820 420
300 170
230 440
DN
DN
65
80 DN100 DN125 DN150
- - - - - -
- - - - -
180 290
450 220
160
80
110 260
100 180
280 130
160
90 40
60
40 80
140
60
- - - -
20 70
- - -
- - -
90
620 30250 30250
230 320 90120 90120
- - -
3 EN0B-0413GE51 R0808
Page 4
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
242
DIMENSIONS
Valve
3
stroke
1,2,3
Y
2
1
Y
Y
Y
Electric Actuators
135x(161)
67.4
135x(161)
67.4
Without stem
extension for
ML6420/25
BC
ML7420/25
M6421, M7421
MP953A,C 5”
MP953B,D
A
Fig. 1. V5050A,B (dimensions in mm)
valve
size
A B C Y1 * Y2 * Y3 *
DN15 130 DN20 150 DN25 160
126
DN32 180
120
135 DN40 200 140 DN50 230 150 DN65 290 DN80 310 181 DN100 350 184 DN125 400 245 DN150 480
* = Adjustment dimension. Port A-AB closed.
155
219
165
220
170.5 - 227
270
With stem
extension for
MP953A,C 8”
With stem
extension for
MP953A,C 13
107 151 -
100
0 100
1000
ML6420A / ML7420A
Fig. 2. ML6420A / ML7420A, ML6425A,B / ML7425A,B
233
322 (with High-Temperature Kit: 402 mm)
141
ML6425A,B / ML7425A,B
178x (178)
64
284
0
1000
364 (with High-Temperature Kit: 444 mm)
141
360
264
Two knock-outs are provided for cable fitting:
21.2 (PG13.5) /
22.8 (PG16),
18.9 (PG11)
Fig. 3. ML6421A/ML7421A (dimensions in mm)
EN0B-0413GE51 R0808 4
239
142
Page 5
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
Pneumatic Actuators
178x (178)
64
Two knock-outs are provided for cable fitting:
21.2 (PG13.5) /
22.8 (PG16),
18.9 (PG11)
204
301
326
E
0
50
100
MP953A,C MP953B,D
H
F
G
E
100
50
0
HK
70
F
G
Fig. 5. MP953A,C/MP953B,D (dimensions in mm)
430
model E F G H K
MP953A, 5“ 192 - ­MP953C, 5“ MP953A, 8“ 237 - ­MP953C, 8“ MP953A, 13“ 327 - ­MP953A, 13“ MP953B 242 - 107 MP953D
130
210
343
180
- 120
- 165
- 255
- 137
120
140
200
120
-
-
-
-
Fig. 4. ML6421B/ML7421B (dimensions in mm)
5 EN0B-0413GE51 R0808
Page 6
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany
EN0B-0413GE51 R0808
Loading...