Page 1
V5050A,B
FLANGED LINEAR VALVE PN16 AND PN25/40
SPECIFICATION DATA
GENERAL
These three-port mixing valves are used for modulating
control of hot/chilled water or steam in heating, ventilation,
and air conditioning systems and can be operated by electric
linear actuators ML6420/ML6425, ML7420/ML7425, and
ML6421/ML7421 or by pneumatic actuator MP953.
FEATURES
• Cast iron body with flanged end connections
• Low seat leakage rate
• Metal-to-metal seating for long life span
• Self-adjusting packing
• Accurate positioning to ensure state-of-the-art
temperature control
• Easy mounting of direct-coupled electric and
pneumatic actuators
• Constant total flow throughout entire plug travel
SPECIFICATIONS
Action Stem up to close port A-AB
Nominal pressure rating PN16, PN25/40
Flow characteristic linear for ports A-AB and B-AB
Rangeability 50:1
Leakage rate ≤ 0.1 % of k
≤ 0.1 % of k
Stroke 20 mm DN15...80
38 mm DN100...150
Valve body
End connections Flanged per ISO 7005-2
Material Cast iron (GG25) PN16
Cast steel (GS-C25) PN25/40
Dimensions See Fig. 1.
Trim
Seat Stainless steel, replaceable
Plug Stainless steel, skirt guided
Stem Stainless steel
Packing Spring-loaded PTFE V-rings
Medium temperature and max. pressure
PN16
120 ... 150 °C; max. 1440 kPa
150 ... 200 °C; max. 1280 kPa
200 ... 220 °C; max. 1200 kPa
PN25/40
120 ... 150 °C; max. 3920 kPa
150 ... 200 °C; max. 3800 kPa
200 ... 220 °C; max. 3720 kPa
Maximum temperature
differential in alternating
hot/cold water use 60 K
2 ... 120 °C; max. 1600 kPa
2 ... 120 °C; max. 4000 kPa
port A-AB
VS
port B-AB
VS
® U.S Registered Trademark EN0B-0413GE51 R0808
Copyright © 2008 Honeywell Inc. • All Rights Reserved
Page 2
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
SIZES AND FLOW CAPACITIES
Order Number Valve Size kVS
V5050A1124 DN15 2.5
V5050A1132 DN15 4.0
V5050A1140 DN20 6.3
V5050A1157 DN25 10.0
V5050A1165 DN32 16.0
V5050A1173 DN40 25.0
V5050A1181 DN50 40.0
V5050A1199 DN65 63.0
V5050A1207 DN80 100.0
V5050A1215 DN100 160.0
V5050B1155*
V5050A1090 DN100 160.0
V5050A1108 DN125 250.0
V5050A1116 DN150 360.0
V5050B1064* DN100 160.0
V5050B1072* DN125 250.0
V5050B1080*
* Reverse acting valve, only available on special request.
PN25/40
DN100 160.0
PN16
DN150 360.0
INSTALLATION
• Water should meet VDI 2035 requirements.
• Do not install valve with stem below the horizontal.
• Fluid flow must correspond with the arrow direction on
the valve body.
• The installation of a strainer is strongly recommended.
REPAIR PACKING KIT
Part No.: R 43 176 755 - 004 (DN15...80)
R 43 176 755 - 005 (DN100...150)
ACTUATORS
Electric Actuators
600 N
valve
size
model
Pneumatic Actuators
valve
size
MP953A 5“, 8“ x
MP953B 7“ x
DN
15-80
100-150
MP953C 5“, 8“ x
MP953D 7“ x
MP953A 13“ x yes
DN
MP953C 13“ x no
600 N
spring
return
DN15-80
ML6420A
ML7420A
actuator action
model size direct reverse
ML6425A,B
ML7425A,B
1800 N
DN
15-80
ML6421A
ML6421A
DN
100-150
ML6421B
ML6421B
positioner
yes
no
EN0B-0413GE51 R0808 2
Page 3
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
CLOSE OFF PRESSURE RATINGS in kPa
Electric Actuators
actuator valve size
model
ML6420A, ML6425A,B
ML7420A, ML7425A,B
ML6421A,B ML7421A,B
Pneumatic Actuators
actuator valve size
force DN15 DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100 DN125 DN150
600 N 1000 1000 1000 600 350 200 120 50 - - -
1800 N 2500 2500 2500 2000 1300 750 500 230 230 90 90
model
MP953 A,C;
(5“)
MP953 C;
(5“)
MP953C;
(8“)
MP953A,C;
(8“)
MP953C;
(8“)
MP953C;
(13“)
MP953A,C;
(13“)
MP953D;
(7“)
MP953B,D;
(7“)
actuator
spring
range
27-76 kPa
(4-11 PSI)
55-83 kPa
(8-12 PSI)
14-48 kPa
(2-7 PSI)
27-76 kPa
(4-11 PSI)
55-83 kPa
(8-12 PSI)
14-48 kPa
(2-7 PSI)
27-76 kPa
(4-11 PSI)
27-76 kPa
(4-11 PSI)
55-90 kPa
(8-13 PSI)
air
pressure
in
actuator
0 kPa
115 kPa
closed
valve
seat
upper
lower
DN
15 DN20 DN25 DN32 DN40 DN50
160
160
160
410
410
410 70230
550
550
550
310
220
220
220
110
370
370
370
200
1600
1600
1600
1600
980
980
980
570
1500
1500
1500
1600
1600
1600
1100
1100
1100
- - - - - - - -
- - - - - - - -
880
880
530
530
680
680
1300
1300
1300
880
530
680
890
1300
700
510
300
390
800
- - - - - - -
180
50
110
100 40570
340
540
820
420
300
170
230
440
DN
DN
65
80 DN100 DN125 DN150
- - - - - -
- - - - -
180
290
450
220
160
80
110
260
100
180
280
130
160
90
40
60
40
80
140
60
- - - -
20
70
- - -
- - -
90
620 30250 30250
230
320 90120 90120
- - -
3 EN0B-0413GE51 R0808
Page 4
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
DIMENSIONS
Valve
3
stroke
1,2,3
Y
2
1
Y
Y
Y
Electric Actuators
135x(161)
67.4
135x(161)
67.4
Without stem
extension for
ML6420/25
B C
ML7420/25
M6421, M7421
MP953A,C 5”
MP953B,D
A
Fig. 1. V5050A,B (dimensions in mm)
valve
size
A B C Y1 * Y2 * Y3 *
DN15 130
DN20 150
DN25 160
126
DN32 180
120
135
DN40 200 140
DN50 230 150
DN65 290
DN80 310 181
DN100 350 184
DN125 400 245
DN150 480
* = Adjustment dimension. Port A-AB closed.
155
219
165
220
170.5 - 227
270
With stem
extension for
MP953A,C 8”
With stem
extension for
MP953A,C 13
107 151 -
100
0 100
100 0
ML6420A / ML7420A
Fig. 2. ML6420A / ML7420A, ML6425A,B / ML7425A,B
233
322 (with High-Temperature Kit: 402 mm)
141
ML6425A,B / ML7425A,B
178x (178)
64
284
0
100 0
364 (with High-Temperature Kit: 444 mm)
141
360
264
Two knock-outs
are provided for
cable fitting:
21.2 (PG13.5) /
22.8 (PG16),
18.9 (PG11)
Fig. 3. ML6421A/ML7421A (dimensions in mm)
EN0B-0413GE51 R0808 4
239
142
Page 5
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
Pneumatic Actuators
178x (178)
64
Two knock-outs
are provided for
cable fitting:
21.2 (PG13.5) /
22.8 (PG16),
18.9 (PG11)
204
301
326
E
0
50
100
MP953A,C MP953B,D
H
F
G
E
100
50
0
H K
70
F
G
Fig. 5. MP953A,C/MP953B,D (dimensions in mm)
430
model ∅ E F G H K
MP953A, 5“ 192 - MP953C, 5“
MP953A, 8“ 237 - MP953C, 8“
MP953A, 13“ 327 - MP953A, 13“
MP953B 242 - 107
MP953D
130
210
343
180
- 120
- 165
- 255
- 137
120
140
200
120
-
-
-
-
Fig. 4. ML6421B/ML7421B (dimensions in mm)
5 EN0B-0413GE51 R0808
Page 6
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich
Germany
Phone: (49) 7031 63701
Fax: (49) 7031 637493
http://ecc.emea.honeywell.com
Subject to change without notice. Printed in Germany
EN0B-0413GE51 R0808