V5050A,B
FLANGED LINEAR VALVE PN16 AND PN25/40
SPECIFICATION DATA
GENERAL
These three-port mixing valves are used for modulating
control of hot/chilled water or steam in heating, ventilation,
and air conditioning systems and can be operated by electric
linear actuators ML6420/ML6425, ML7420/ML7425, and
ML6421/ML7421 or by pneumatic actuator MP953.
FEATURES
• Cast iron body with flanged end connections
• Low seat leakage rate
• Metal-to-metal seating for long life span
• Self-adjusting packing
• Accurate positioning to ensure state-of-the-art
temperature control
• Easy mounting of direct-coupled electric and
pneumatic actuators
• Constant total flow throughout entire plug travel
SPECIFICATIONS
Action Stem up to close port A-AB
Nominal pressure rating PN16, PN25/40
Flow characteristic linear for ports A-AB and B-AB
Rangeability 50:1
Leakage rate ≤0.1 % of k
≤0.1 % of k
Stroke 20 mm DN15...80
38 mm DN100...150
Valve body
End connections Flanged per ISO 7005-2
Material Cast iron (GG25) PN16
Cast steel (GS-C25) PN25/40
Dimensions See Fig. 1.
Trim
Seat Stainless steel, replaceable
Plug Stainless steel, skirt guided
Stem Stainless steel
Packing Spring-loaded PTFE V-rings
Medium temperature and max. pressure
PN16
120 ... 150 °C; max. 1440 kPa
150 ... 200 °C; max. 1280 kPa
200 ... 220 °C; max. 1200 kPa
PN25/40
120 ... 150 °C; max. 3920 kPa
150 ... 200 °C; max. 3800 kPa
200 ... 220 °C; max. 3720 kPa
Maximum temperature
differential in alternating
hot/cold water use 60 K
2 ... 120 °C; max. 1600 kPa
2 ... 120 °C; max. 4000 kPa
port A-AB
VS
port B-AB
VS
® U.S Registered Trademark EN0B-0413GE51 R0808
Copyright © 2008 Honeywell Inc. • All Rights Reserved
V5050A,B FLANGED LINEAR VALVE PN16, PN25/40
SIZES AND FLOW CAPACITIES
Order Number Valve Size kVS
V5050A1124 DN15 2.5
V5050A1132 DN15 4.0
V5050A1140 DN20 6.3
V5050A1157 DN25 10.0
V5050A1165 DN32 16.0
V5050A1173 DN40 25.0
V5050A1181 DN50 40.0
V5050A1199 DN65 63.0
V5050A1207 DN80 100.0
V5050A1215 DN100 160.0
V5050B1155*
V5050A1090 DN100 160.0
V5050A1108 DN125 250.0
V5050A1116 DN150 360.0
V5050B1064* DN100 160.0
V5050B1072* DN125 250.0
V5050B1080*
* Reverse acting valve, only available on special request.
PN25/40
DN100 160.0
PN16
DN150 360.0
INSTALLATION
• Water should meet VDI 2035 requirements.
• Do not install valve with stem below the horizontal.
• Fluid flow must correspond with the arrow direction on
the valve body.
• The installation of a strainer is strongly recommended.
REPAIR PACKING KIT
Part No.: R 43 176 755 - 004 (DN15...80)
R 43 176 755 - 005 (DN100...150)
ACTUATORS
Electric Actuators
600 N
valve
size
model
Pneumatic Actuators
valve
size
MP953A 5“, 8“ x
MP953B 7“ x
DN
15-80
100-150
MP953C 5“, 8“ x
MP953D 7“ x
MP953A 13“ x yes
DN
MP953C 13“ x no
600 N
spring
return
DN15-80
ML6420A
ML7420A
actuator action
model size direct reverse
ML6425A,B
ML7425A,B
1800 N
DN
15-80
ML6421A
ML6421A
DN
100-150
ML6421B
ML6421B
positioner
yes
no
EN0B-0413GE51 R0808 2