Honeywell V5050A, V5050B DATASHEET

Honeywell V5050A, V5050B DATASHEET

V5050A,B

FLANGED LINEAR VALVE PN16 AND PN25/40

SPECIFICATION DATA

FEATURES

GENERAL

These three-port mixing valves are used for modulating control of hot/chilled water or steam in heating, ventilation, and air conditioning systems and can be operated by electric linear actuators ML6420/ML6425, ML7420/ML7425, and ML6421/ML7421 or by pneumatic actuator MP953.

Cast iron body with flanged end connections

Low seat leakage rate

Metal-to-metal seating for long life span

Self-adjusting packing

Accurate positioning to ensure state-of-the-art temperature control

Easy mounting of direct-coupled electric and pneumatic actuators

Constant total flow throughout entire plug travel

SPECIFICATIONS

Action

Stem up to close port A-AB

Nominal pressure rating

PN16, PN25/40

Flow characteristic

linear for ports A-AB and B-AB

Rangeability

50:1

Leakage rate

≤0.1 % of kVS port A-AB

 

≤0.1 % of kVS port B-AB

Stroke

20 mm DN15...80

 

38 mm DN100...150

Valve body

 

End connections

Flanged per ISO 7005-2

Material

Cast iron (GG25) PN16

 

Cast steel (GS-C25) PN25/40

Dimensions

See Fig. 1.

Trim

 

Seat

Stainless steel, replaceable

Plug

Stainless steel, skirt guided

Stem

Stainless steel

Packing

Spring-loaded PTFE V-rings

Medium temperature and max. pressure

PN16

2 ... 120 °C; max. 1600 kPa

 

120 ... 150 °C; max. 1440 kPa

 

150 ... 200 °C; max. 1280 kPa

 

200 ... 220 °C; max. 1200 kPa

PN25/40

2 ... 120 °C; max. 4000 kPa

 

120 ... 150 °C; max. 3920 kPa

 

150 ... 200 °C; max. 3800 kPa

 

200 ... 220 °C; max. 3720 kPa

Maximum temperature

 

differential in alternating

 

hot/cold water use

60 K

® U.S Registered Trademark

EN0B-0413GE51 R0808

Copyright © 2008 Honeywell Inc.

• All Rights Reserved

V5050A,B FLANGED LINEAR VALVE PN16, PN25/40

SIZES AND FLOW CAPACITIES

Order Number

Valve Size

kVS

V5050A1124

 

DN15

2.5

V5050A1132

 

DN15

4.0

V5050A1140

 

DN20

6.3

V5050A1157

 

DN25

10.0

V5050A1165

 

DN32

16.0

V5050A1173

PN25/40

DN40

25.0

V5050A1181

 

DN50

40.0

V5050A1199

 

DN65

63.0

V5050A1207

 

DN80

100.0

V5050A1215

 

DN100

160.0

V5050B1155*

 

DN100

160.0

V5050A1090

 

DN100

160.0

V5050A1108

 

DN125

250.0

V5050A1116

PN16

DN150

360.0

V5050B1064*

DN100

160.0

 

V5050B1072*

 

DN125

250.0

V5050B1080*

 

DN150

360.0

* Reverse acting valve, only available on special request.

INSTALLATION

Water should meet VDI 2035 requirements.

Do not install valve with stem below the horizontal.

Fluid flow must correspond with the arrow direction on the valve body.

The installation of a strainer is strongly recommended.

REPAIR PACKING KIT

Part No.: R 43 176 755 - 004 (DN15...80)

R 43 176 755 - 005 (DN100...150)

ACTUATORS

Electric Actuators

 

 

 

 

600 N

 

 

 

 

 

 

 

600 N

spring

 

1800 N

 

 

 

 

 

return

 

 

 

 

 

valve

 

DN15-80

 

DN

DN

 

size

 

15-80

100-150

 

 

 

 

 

 

 

model

 

ML6420A

ML6425A,B

 

ML6421A

ML6421B

 

 

ML7420A

ML7425A,B

 

ML6421A

ML6421B

 

 

 

 

Pneumatic Actuators

 

valve

 

 

actuator

 

action

 

positioner

 

 

size

 

 

model

size

 

direct

reverse

 

 

 

 

 

 

 

 

 

 

 

 

 

MP953A

5“, 8“

 

x

 

 

yes

 

DN

 

MP953B

7“

 

 

x

 

 

 

 

 

 

 

 

15-80

 

 

MP953C

5“, 8“

 

x

 

 

no

 

 

 

 

MP953D

7“

 

 

x

 

 

 

 

 

 

 

 

 

 

 

DN

 

MP953A

13“

 

x

 

 

yes

100-150

 

 

MP953C

13“

 

x

 

 

no

EN0B-0413GE51 R0808

2

Loading...