V5049A
FLANGED LINEAR VALVE PN25/40
SPECIFICATION DATA
GENERAL
These single seated valves are used for modulating control of
hot or chilled water or steam in heating, ventilating, and air
conditioning systems and can be operated by electric linear
actuators as ML6420/25 or ML7420/25 and ML6421/ML7421,
or by pneumatic actuators MP953.
FEATURES
• Cast iron or cast steel body with flanged end
connections
• Low seat leakage rate
• Metal-to-metal seating for long life span
• Self-adjusting packing
• Accurate positioning to ensure state-of-the-art
temperature control
• Direct-coupled electric and pneumatic actuators for
easy mounting
• Approved according to DIN EN 14597
SPECIFICATIONS
Action Stem down to close
Nominal pressure rating PN25/40
Flow characteristic Equal percentage
Rangeability 50:1
Leakage rate ≤0.05% of kVS up to DN50
≤0.1% of k
Stroke 20 mm up to DN65
38 mm for DN80 to DN100
Valve body
End connections Flanged per ISO 7005-2
Material Cast steel (GS-C25)
Dimensions See Fig. 1 on page 3
Trim
Seat Stainless steel, replaceable
Plug Stainless steel, skirt-guided
Stem Stainless steel
Packing Spring-loaded PTFE V-rings
Medium temperature
and pressure 2 ... 120 °C: max. 4000 kPa
120 ... 150 °C: max. 3920 kPa
150 ... 200 °C: max. 3800 kPa
200 ... 220 °C: max. 3720 kPa
Maximum temperature
differential in alternating
hot cold water use 60 K
for DN65 to DN100
VS
Copyright © 2008 Honeywell Inc. • All Rights Reserved EN0B-0238GE51 R0508
V5049A FLANGED LINEAR VALVE 25/40
SIZES AND FLOW CAPACITIES
order number valve size kVS
V5049A2027 DN15 0.25
V5049A2035 DN15 0.40
V5049A2043 DN15 0.63
V5049A1425 DN15 1.00
V5049A1433 DN15 1.60
V5049A1441 DN15 2.50
V5049A1458 DN15 4.00
V5049A1508 DN20 6.30
V5049A1565 DN25 10.00
V5049A1573 DN32 16.00
V5049A1581 DN40 25.00
V5049A1599 DN50 40.00
V5049A1607 DN65 63.00
V5049A1615 DN80 100.00
V5049A1623 DN100 160.00
INSTALLATION
• Water should meet VDI 2035 requirements.
• Do not install valve with stem below the horizontal.
• Fluid flow must correspond with the arrow direction on the
valve body.
• The installation of a strainer is strongly recommended.
REPAIR PACKING KIT
Part no. R 43 176 755 – 004 (DN 15 to 65)
R 43 176 755 – 005 (DN 80 to 100)
ACTUATORS
Electric Actuators
force 600 N
model
stroke 20 mm 38 mm
size DN15-65 DN80-100
ML6420A
ML7420A
Pneumatic Actuators
valve
size
DN
15-65
DN
80-100
pneumatic
actuator
model size direct reverse
MP953A
MP953B
MP953C
MP953D
MP953A
MP953C
600 N
spring return
ML6425A,B
ML7425A,B
5“, 8“
7“
5“, 8“
7“
13“
x x
x x
x -
M6421A
M7421A
action
1800 N
M6421B
M7421B
positioner
yes
no
yes
no
CLOSE-OFF PRESSURE RATINGS (in kPa)
Electric Actuators
actuator valve size
model force
ML6420A, ML6425A,B
ML7420A, ML7425A,B
M6421A,B, M7421A,B 1800 N - 2500 2500 2000 1300 750 500 230
EN0B-0238GE51 R0508 2
600 N 1600 1000 1000 600 350 200 120 -
DN15
kVS 0.25 -1.0
DN15
kVS 2.5 -4.0
DN20/25 DN32 DN40 DN50 DN65 DN80/100