FLANGED LINEAR VALVE PN16
SPECIFICATION DATA
FEATURES
Pressure-balanced plug
Nodular iron body with flanged end connections
Low seat leakage rate
Metal-to-metal seating for long life span
Self-adjusting packing
Accurate positioning to ensure state-of-the-art
temperature control
GENERAL
These single-seated valves are suitable for use in conjunction with the modulating control of hot / chilled water or steam in closed heating, ventilating, and air conditioning systems. They are designed especially for use in high differential pressure applications (e.g. district heating) and can be operated by linear actuators ML6420/ML6425, ML7420/ML7425, or M6421/M7421 or by pneumatic actuators MP953.
Easy mounting of direct-coupled electric and
pneumatic actuators
Approved according to DIN EN 14597 in DN15...80 in
combination with ML6425/ML7425
SPECIFICATIONS
Action Stem down to close
Nominal pressure rating PN16
Flow characteristic Equal percentage
Rangeability 50:1
Leakage rate 0.05% of kVS (DN15...80)
0.1% of k
Stroke 20 mm (DN15...80) 38 mm (DN100...150)
Valve body
End connections Flanged per ISO 7005-2 Material Nodular iron (GGG40.3)
Dimensions See Fig. 1 on page 3
Trim
Seat Stainless steel Stem Stainless steel Plug Stainless steel, skirt-guided
Packing Spring-loaded PTFE cone rings
Medium temperature and pressure
Max. temp. differential 60 K (alternating hot/coldwater)
Medium water, water-glycol (max. 50%),
steam
2...180 °C (max. 1600 kPa)
(DN100...150)
VS
Copyright © 2009 Honeywell Inc. • All Rights Reserved EN0B-0440GE51 R0709
V5016A FLANGED LINEAR VALVE PN16
SIZES AND FLOW CAPACITIES
Order Number Valve Size kVS
V5016A1010 DN15 0.40
V5016A1028 DN15 0.63
V5016A1036 DN15 1.0
V5016A1044 DN15 1.6
V5016A1051 DN15 2.5
V5016A1069 DN15 4.0
V5016A1077 DN20 6.3
V5016A1085 DN25 10.0
V5016A1093 DN32 16.0
V5016A1101 DN40 25.0
V5016A1119 DN50 40.0
V5016A1127 DN65 63.0
V5016A1135 DN80 100.0
V5016A1143 DN100 160.0
V5016A1150 DN125 250.0
V5016A1168 DN150 360.0
CLOSE-OFF PRESSURE RATINGS (in kPa)
INSTALLATION
Water should meet VDI 2035 requirements.
Do not install valve with stem below the horizontal.
Fluid flow must correspond with the arrow direction on the
valve body.
The installation of a strainer is strongly recommended.
REPAIR PACKING KIT
Part No.: R43176755004 (DN15...80) R43176755005 (DN100...150)
ACTUATORS
Electric Actuators
600 N (20 mm)
ML6420A ML6425A,B ML6421B ML7420A ML7425A,B ML7421B
Pneumatic Actuators
actuator stroke acting
model size direct reverse
MP953A
MP953B 7" 20 mm X
MP953C
MP953D 7" 20 mm X
5", 8" 20 mm
13" 38 mm
5", 8" 20 mm
13" 38 mm
600 N (20 mm),
spring return
X
X
1800 N (38 mm)
positioner
yes
no
Electric Actuators
actuator valve size
model stroke force DN15 DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100 DN125 DN150
ML6420A, ML6425A,B, ML7420A, ML7425A,B
ML6421B, ML6421B 38 mm 1800 N -- -- -- -- -- -- -- -- 1600 1600 1600
20 mm 600 N 1600 1600 1600 1600 1600 1600 1600 1600 -- -- --
Pneumatic Actuators
actuator valve size
model
MP953A,C (5")
MP953A,C (8")
MP953B,D (7")
MP953A,C (13")
spring
range
28...77 kPa (4...11 psi)
28...77 kPa (4...11 psi)
55...90 kPa (8...13 psi)
28...77 kPa (4...11 psi)
air
pressure
115 kPa 1600 1600 1600 1600 1600 1200 -- -- -- -- --
115 kPa 1600 1600 1600 1600 1600 1600 1600 1600 -- -- --
0 kPa 1600 1600 1600 1600 1600 1600 1600 1600 -- -- --
115 kPa -- -- -- -- -- -- -- -- 1600 1600 1600
DN15 DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100 DN125 DN150
EN0B-0440GE51 R0709 2
V5016A FLANGED LINEAR VALVE PN16
2
2
DIMENSIONS
Valve
valve size A B Y1 * Y2 * Y3 *
DN15 130
stroke
Y3
Y2
Y1*
with stem
B
A
extension for
MP953A,C 8”
*without stem extension for
ML6420/25, ML7420/25
M6421, M7421,
MP953A,C 5”, and MP953B,D 7”
with stem
extension for
MP953A,C 13
Fig. 1. V5016A with stem extensions (dimensions in mm)
Electric Actuators
DN20 150 DN25 160 DN32 180 DN40 200 DN50 230 101 DN65 290 106
DN80 310 DN100 350 DN125 400 156 DN150 480 157
* = Adjustment dimension. Valve in closed position.
95
99
150
89 133 --
133 -- 190
135x(161)
67.4
135x(161)
67.4
4
100
0 100
1000
ML6420A / ML7420A
233
322 (with High-Temperature Kit: 402 mm)
141
0
1000
141
ML6425A,B / ML7425A,B
Fig. 2. ML6420A / ML7420A and ML6425A,B / ML7425A,B
178x (178)
64
430
Two knock-outs are provided for cable fitting:
21.2 (PG13.5) /
284
364 (with High-Temperature Kit: 444 mm)
22.8 (PG16),
18.9 (PG11)
326
301
204
Fig. 3. M6421B / M7421B (dimensions in mm)
3 EN0B-0440GE51 R0709
V5016A FLANGED LINEAR VALVE PN16
C
Pneumatic Actuators
E
MP953A,
0
50
100
H
F
G
E
MP953B,D
100
50
0
Fig. 4. MP953A,C / MP953B,D (dimensions in mm)
Model
MP953A, 5” 192 -- -­MP953C, 5” MP953A, 8" 237 -- -­MP953C, 8" MP953A, 13" 327 -- -­MP953C, 13" MP953B, 7" 242 -- 107 MP953D, 7"
E
130
210
343
180
F G H K
- 120
-- 165
-- 255
-- 137
120
140
200
120
NOTE: V5016A valves in combination with the following
actuators are approved according to DIN EN 14597:
Actuator O.S. No. DIN Registration No.
ML6425A3006 ML6425A3014
1F139/08
ML7425A6008
HK
70
F
G
--
--
--
--
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany
EN0B-0440GE51 R0709