savings with your new Duracraft Programmable Thermostat.
Your new thermostat will automatically control
the temperature in your home, keeping you
comfortable while saving energy when programmed according to the instructions in this
manual.
RECYCLING THERMOSTAT
If this thermostat is replacing a thermostat that contains mercury in a sealed
tube, do not place your old thermostat in
the trash. Contact your local waste
management authority for instructions
regarding recycling and the proper
disposal of your old thermostat.
Direct any questions concerning the application
of this thermostat to Duracraft Consumer
Services at 1-800-554-4558, Monday-Friday
7:00 a.m.-5:30 p.m., Eastern time.
If you have questions, call Duracraft
at 1-800-554-4558.
Fig. 1.Typical
location of a
mercury switch in
a thermostat.
2
69-1119
Table Of Contents
Step 1. Prepare For Installation ..................................................................................................... 4
Step 2. Remove Old Thermostat .................................................................................................... 6
Step 3. Install The Batteries ........................................................................................................... 7
Step 4. Program The Thermostat ................................................................................................ 10
Step 5. Adjust Fan Operation Switch, as Required.................................................................... 18
Step 6. Adjust System On-Time,
Step 7. Mount Thermostat Mounting Plate ................................................................................. 20
Limited One-Year Warranty ................................................................................. Inside Back Cover
°F/°C, as Required .................................................................. 18
3
69-1119
Step 1. Prepare for Installation
❑ Check Table 1 to make sure this thermostat is compatible with your system. If not, return to
retailer. For more information, call Duracraft Consumer Services, toll-free 1-800-554-4558.
System TypeCompatible With TD2200
Gas—Standing PilotYes
Gas—Electronic IgnitionYes
Gas-Fired BoilersYes
Gas—MillivoltNo
Oil-Fired BoilersYes
Oil-Fired FurnaceYes
Electric FurnaceYes
Electric Air ConditioningYes
Baseboard Electric (120/240 Line Volt)No
Heat Pumps/Multistage EquipmentNo
Not compatible with any 120/240 volt circuit.
a
Compatible with 2-wire Honeywell zone valves. Isolating relay required for 3-wire thermostats for
zone valves. Not compatible with 2-wire White-Rodgers no. 1361 valves.
b
Compatible with hot water baseboard systems. Will not work efficiently on steam or gravity
systems.
Table 1. Compatibility Chart.
4
a,b
a,b
69-1119
❑ Acquire tools and items as needed (below). Also purchase two AA alkaline batteries; we
recommend Energizer® batteries.
CROSS-RECESSED
SCREWDRIVER
HAND OR POWER
DRILL WITH 3/16 INCH
DRILL BIT, IF NEEDED TO
DRILL HOLES IN WALL
WIRE CUTTER/STRIPPER OR SHARP
KNIFE, IF NEEDED TO STRIP WIRES
LEVEL, IF NEEDED TO LEVEL
THERMOSTAT FOR APPEARANCE
5
MASKING TAPE, IF
NEEDED TO LABEL WIRES
AS DISCONNECTED FROM
OLD THERMOSTAT
M878B
69-1119
Step 2. Remove Old Thermostat
WIRES THROUGH
WALL OPENING
M5136
❑ Test to make certain that your heating and
cooling systems are working properly. If
either does not work, contact your local
heating/air conditioning dealer. To avoid
compressor damage, do not operate the
cooling system when outdoor temperature is
below 50°F (10°C).
❑ TURN OFF POWER to system at the
furnace, or at the fuse/circuit breaker panel.
❑ Carefully unpack your new thermostat and
mounting plate; save package of screws,
instructions and receipt.
❑ Remove cover from old thermostat. If it
does not snap off when pulled firmly from
the bottom, check for a screw used to lock
on the cover.
❑ Loosen screws holding thermostat to
❑ Disconnect wires from old thermostat or
subbase, wallplate or wall, and lift away.
subbase. As you disconnect each wire, use
masking tape to label it with the old terminal
designation. If there are only two wires, they
do not need to be labeled. If there is an
extra wire that is not connected to your old
thermostat, you will also not be connecting it
to your new thermostat. Keep the wires from
falling back into the wall by wrapping them
around a pencil as shown.
Replacing a Clock Thermostat that has
C or C1 Clock Terminals?
If you are replacing a Honeywell
Chronotherm® Thermostat, you may find one
or two wires that go to the C or C1 clock
6
69-1119
terminals on the Chronotherm® Thermostat
wiring wallplate. Do not allow them to touch, or
you may damage your transformer. Disconnect
the wires and wrap them separately, using
electrical tape. Do not wrap them together.
Place the wires where they will not interfere
with the operation of the new thermostat.
Record the colors and terminal designation
labels of the remaining wires.
Six or more wires?
If there are six or more wires (excluding clock
wires attached to terminals), you most likely
have a variation of a heat pump or multistage
system. The thermostat is not compatible with
such systems so return the product to the
place of purchase. If you would like information
about which programmable thermostats will
work with your system, call Duracraft Consumer Services at 1-800-554-4558.
Three thermostat wires?
If you have three wires for heating only and
can operate the fan using the fan ON switch,
this thermostat will work with your system.
However, some hot water (zoned) heating
systems have three thermostat wires. The
thermostat will not work without installing an
isolating relay on these systems. For details,
call Duracraft Consumer Servicies at
1-800-554-4558.
Step 3. Install the Batteries
IMPORTANT
Batteries must be installed for programming and operation of the thermostat
and heating/cooling system.
7
69-1119
❒ Purchase two AA alkaline batteries; non-
M1719C
REMOVING
BATTERY
DOOR
alkaline batteries will not last as long, and
may leak, causing damage to the thermostat or the wall surface. We recommend
Energizer® batteries.
❒ Open top cover of thermostat to access
control panel and battery compartment.
❒ Make sure the thermostat is set in the Off
position.
❒ Use a coin to remove battery cover.
❒ Install the fresh batteries as shown, making
sure positive and negative terminals are
oriented correctly.
❒ Replace battery cover.
As the batteries are running low, a bAt Lo
indicator will flash for 1 to 2 months before
batteries run out completely. Replace the
batteries as soon as possible after the indicator
starts flashing. If you do not replace the
batteries sometime during the flashing bAt Lo,
the indicator will eventually stop flashing.
bAt Lo will stay on without flashing to indicate
the thermostat and heating/cooling system
have stopped working when the batteries are
almost completely dead.
8
69-1119
After the batteries are completely dead, the bAt
Lo indicator will disappear, leaving a completely
blank display. Press down on left ends of
batteries to remove. If you insert the new
batteries within 20 to 30 seconds of removing
the old ones, you will not have to reprogram the
thermostat. However, if the display is blank, the
INSTALL TWO AA ALKALINE
BATTERIES AS SHOWN
M1713
batteries are dead or incorrectly installed and
you will have to reprogram. See pages 14 to 17
to reprogram.
IMPORTANT
Although the thermostat has a low
battery indicator, replace the batteries
once a year to prevent the thermostat
and heating/cooling system from
shutting down due to lack of battery
power.
As a precaution, when leaving home for longer
than a month, change batteries before you
leave to prevent the system from shutting down
due to lack of battery power.
9
69-1119
Step 4. Program the Thermostat
After the batteries are installed, the thermostat
can be easily programmed in your hand before
it is installed on the wall.
If you would prefer to program the thermostat
after it is installed on the wall, skip to page 14,
and return later to this programming section.
The personal programming chart on pages 12
and 13 may be helpful for planning your
program schedule of time and temperature
settings for various times of the day.
Four time periods are available during weekdays — WAKE, LEAVE, RETURN, and
SLEEP; these periods can be seen individually
on the display as you press the Schedule key.
WAKE is the time period you want the house at
a comfortable temperature when you get up
and while you get ready for work or school.
(This will be a higher temperature during
heating season, or a lower temperature during
cooling season.)
LEAVE is the time period you can set for an
energy-saving temperature while you are away
at work or school. (This will be a lower temperature during heating season, or a higher
temperature during cooling season.)
RETURN is the time period you want the
house at a comfortable temperature for
activities before bedtime. (Again, higher heat or
lower cool.)
10
69-1119
SLEEP is the time period you can set for an
energy-saving temperature while you are
sleeping. (Again, lower heat or higher cool. For
more comfortable sleeping, some people
choose not to raise the cool temperature during
the night.)
You will set one schedule for weekdays and
another for weekends, because your requirements will probably be different for each. Also,
during weekends, only the WAKE and SLEEP
time periods are available.
Fill in the times and temperatures you desire
for weekdays and weekends. If you decide not
to program the thermostat, it will automatically
control heating at 68°F (20°C), and cooling at
78°F (26°C), 24 hours a day. Also, you do not
need to enter a time and temperature program
for all periods if your schedule does not require
it. For example, a house that is occupied
during weekdays would only require programs
for WAKE and SLEEP.
If no program is entered for the weekends, the
thermostat will operate on the weekday SLEEP
program all weekend.
Before programming, remove the clear plastic
overlay covering the display.
When pressing the keys, use the ball of your
finger or a soft pencil eraser. Using sharp
fingernails or pencil points can damage the
keypad.
If you make an error at any time during
programming, just press the Run Program key,
and continue again at the step where you left
off.
11
69-1119
Personal Programming Chart
WeekdaysStart TimeHeating Temperature
WAKE
LEAVE
RETURN
SLEEP
Heating Program
a
Weekends
b
WAKE
SLEEP
a
The temperatures cannot be set any higher than 88°F (31°C) or any lower than 45°F (7°C).
b
If you decide not to enter weekend programs, the SLEEP from the weekday program will copy to
the weekend schedule.
12
69-1119
WAKE
LEAVE
RETURN
SLEEP
WeekdaysStart TimeCooling Temperature
Cooling Program
a
Weekends
b
WAKE
SLEEP
a
The temperatures cannot be set any higher than 88°F (31°C) or any lower than 45°F (7°C).
b
If you decide not to enter weekend programs, the SLEEP from the weekday program will copy to
the weekend schedule.
NOTE: If you decide not to program the thermostat, it will automatically control heating at 68°F
(20°C), and cooling at 78°F (26°C), 24 hours a day.
13
69-1119
This guide can be used for programming your new thermostat.
NOTE: Batteries are required for operation and programming. When inserting batteries, set the
system switch to OFF. Remove battery door (on thermostat left side) using a coin at the
bottom. Follow instructions on pages 6 and 7. Also note that the label inside the battery
cover contains an abbreviated set of procedures for programming the thermostat.
Set Current Time/Day
Clock/Day
Time
To set time, press and releaseonce, pressuntil current time shows. To set day, press and
Clock/Day
Clock/Day
Run Program
releaseagain, continue to pressuntil current day shows; then press.
Heating Program
With System switch at Heat, press and releaseonce. WAKE, MO FR (Monday-Friday),
and SET appears on display.
Schedule
14
69-1119
Time
TEMP
Useto program WAKE time andto program WAKE temperature for MO FR
(Monday-Friday).
Repeat sequence for LEAVE, RETURN, SLEEP.
Time
Pressuntil WAKE, SA SU (Saturday-Sunday), and SET appears on display. Useto
Schedule
TEMP
program WAKE time andto program WAKE temperature for SA SU (Saturday-Sunday).
Run Program
Repeat sequence for SLEEP. Press and releaseto start the program.
15
69-1119
Cooling Program
With System switch at Cool, follow the same instructions as for the Heating Program.
After programming, adjust the fan and system switches as desired. Press and releaseto
start the program.
A quick guide for operating or making changes follows.
NOTE: System switch must be set to Heat or Cool to perform the following:
TEMP
Temporarily Change temperature for current period only—Press; TEMPORARY indicator will
show on display and will cancel itself at the next scheduled change; or to cancel sooner
Run Program
press.
Run Program
16
69-1119
Clear
TEMP
Hold a temperature indefinitely (such as if on vacation)—Pressand; HOLD will appear
Run Program
Hold T emp
on display; to cancel, press.
Run Program
Check Current Temperature Setting—Press. (If using TEMPORARILY CHANGE or HOLD,
pressing this will cancel your change.)
Check Programs—Pressrepeatedly to see each time and temperature; then press.
Schedule
Time
Cancel Program—Pressuntil program to cancel shows; then presstogether.
Schedule
Permanently Change Program—Repeat steps under Heating Program or Cooling Program (page
14 and 16) as applicable.
Return to normal program or start program—Press.
17
Run Program
69-1119
Step 5. Adjust Fan Operation Switch, As Required
❑ The thermostat fan operation switch, labeled FUEL SWITCH (see illustration on page 19) is
factory-set in the F position. This is the correct setting for most systems. If your system is an
electric heat system, set the switch to E. The E setting will allow the fan to turn on immediately
with the heating or cooling in a system where the G terminal is connected.
Step 6. Adjust System On-Time, °F/°C, As Required
❑ The thermostat on-time is factory-set for a warm air, gas or oil heating system. If you are
installing it on another type of system, adjust the on-time accordingly by setting screws A and B
on the back of the thermostat. use the heating system table shown in the illustration (page 19)
as a guide. The system on-time should be optimized according to the type of system to minimize
room temperature swings. Setting the screw “out one turn” means turning the screw approximately 360° counterclockwise, or about one complete turn.
In the unlikely event that you want a longer furnace on-time, readjust screws A and/or B as
follows:
18
69-1119
First, turn in both screws completely, then
adjust for system type:
• Warm Air Furnace—Set at the Hot Water
setting (A—out one turn, B—leave in).
• Electric Furnace—leave at the Warm Air
Furnace setting (A—leave in, B—leave in).
NOTE: This thermostat does not have a
setting for steam/gravity air. Cycles
would not be long enough for accurate temperature control.
IMPORTANT
When using a high efficiency furnace
such as a 90% or greater AFUE
(Average Fuel Utilization Efficiency)
unit, adjust screw A out one turn and
leave screw B in.
❑ The thermostat is set to read the tempera-
ture in degrees Fahrenheit. If readings are
desired in degrees Celsius, adjust screw C
out one turn, as shown in illustration.
THERMOSTAT BACK
DISPLAY °F
C–IN
DISPLAY
°
C
C–OUT
1 TURN
FOR HIGH EFFICIENCY FURNACE (90%+ AFUE)
ADJUST: SCREW A–OUT ONE TURN
SCREW B–IN
FUEL SWITCH – F POSITION
FUEL SWITCH
F
A C
B D
E
ADJUST SCREWS THROUGH HOLES
TO SELECT OPERATION DESIRED
HEATING SYSTEM
WARM AIR
FURNACE
HOT WATER
BOILER
ELECTRIC
FURNACE
W Y G
A–IN
A–OUT
1 TURN
A–IN
B–IN
B–IN
B–OUT
1 TURN
FUEL SWITCH
POSITION
R
F
F
E
Rc
M1708B
19
69-1119
Step 7. Mount Thermostat Mounting Plate
LEVEL
M1714A
(2)
❑ Position mounting plate on wall. Use level to
make sure mounting plate is level. Use a
pencil to mark the two mounting holes.
❑ Remove mounting plate from wall, and drill
3/16-inch holes in wall (if drywall) as
marked. For firmer material such as plaster
or wood, drill
7/32-inch
holes.
Gently
tap
WALL
anchors
(provided)
WALL ANCHORS (2)
WIRES THROUGH
WALL OPENING
into
drilled holes
until flush
MOUNTING
PLATE
with the wall.
MOUNTING
SCREWS
M1718
❑ Reposition mounting plate over holes,
❑ Level for appearance only; thermostat will
pulling wires through wiring opening.
Loosely insert two mounting screws into
holes.
function properly even when not level.
Tighten mounting screws.
20
69-1119
Step 8. Wire Thermostat Terminals
NOTE: All wiring must comply with local
codes and ordinances. If unsure
about household wiring procedures,
call your local heating/air conditioning
contractor.
Refer to masking tape labels you placed on
wires when you removed your old thermostat.
❑ Match the letter of your old thermostat wire
with the terminal of the corresponding letter
on the back of your new thermostat. Refer
to illustrations on pages 23 and 24. Hold the
thermostat as shown to minimize need for
wire extenders. If wires are still too short,
use wire connectors (purchased locally) to
extend wires. See figure for guidelines on
using wire extenders.
❑ In 5-wire installations only, be sure to
remove the factory-installed jumper connecting terminals R and Rc.
METHOD TO INCREASE WIRE LENGTH
M1715A
21
WIRE NUT SIZE FOR
TWO 18-GAUGE WIRES
WIRE
FROM
WALL
6 IN. (152 MM)
OF 18-GAUGE
THERMOSTAT
WIRE. MATCH
INSULATION
COLORS
OR MARK
WIRE ENDS.
69-1119
❑ Loosen the terminal screws and slip each
M1712A
JUMPER (FACTORYINSTALLED) REMOVE
IF 5-WIRE SYSTEM
INSERT
STRAIGHT
UNDER
SCREW HEAD
5/16 in.
(8 mm)
STRIP
END OF WIRE
VISIBLE HERE
R
R
c
WY G
M3002A
wire beneath its matching terminal. See
illustration (lower right) for wire insertion
technique. securely tighten terminals.
❑ Plug the hole in the wall with insulation to
help prevent drafts from adversely affecting
thermostat operation.
22
69-1119
2-WIRE HEAT-ONLY (JUMPER INTACT)
R
Rc
W Y G
B D
A C
4-WIRE HEAT/COOL (JUMPER INTACT)
L1
(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
1
JUMPER
HEATING
RELAY OR
VALVE COIL
M1710B
COOLING
CONTACTOR
COIL
FAN
RELAY
A C
B D
HEATING
RELAY OR
VALVE COIL
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
W Y G
R
L1
(HOT)
L2
Rc
1
JUMPER
M1709B
23
69-1119
5-WIRE HEAT/COOL (JUMPER REMOVED)
A C
B D
W Y G
Rc
R
3-WIRE COOL-ONLY (JUMPER INTACT)
A C
B D
W Y G
Rc
R
JUMPER
HEATING
RELAY OR
VALVE COIL
COOLING
11
L1
(HOT)
CONTACTOR
COIL
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
FAN
RELAY
L1
(HOT)
L2
M1711B
24
COOLING
CONTACTOR
COIL
FAN
RELAY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
L1
(HOT)
L2
M848A
69-1119
Step 9: Mount The Thermostat
NOTE: To remove thermostat from wall, first pull out at bottom of thermostat, then remove top.
ENGAGE TABS AT TOP OF
A. B. C.
THERMOSTAT AND SUBBASE.
PRESS LOWER EDGE
OF CASE TO LATCH.
SWING OPEN COVER TO
CHECK OPERATION.
AM
TU
LEAVE
Clock/Day
Time TEMP Run Program
Schedule
Fan
OnAuto
Cool Off Heat
System On
Temporary
Hold Temp
System
M12491
25
69-1119
Step 10. Check Thermostat Operation After Programming and Installing
HeatCoolOff
Heating
Do not check heating system operation
by jumpering thermostat terminals,
such as the gas valve, zone valve, oil
burner control at the primary control.
This will damage the thermostat;
instead, jumper R and W wires at the
thermostat.
AutoOn
TEMP
Move the System switch to Heat and
the fan switch to Auto.
Press TEMP key until the setting is
about 10°F (6°C) above room temperature. Heating should start and the
fan should run after a short delay
(immediately if fan operation switch is
set in E position).
Press TEMP key until setting is about
10°F (6°C) below room temperature.
The heating equipment should shut off.
26
69-1119
Cooling
To avoid possible compressor damage, do not operate the cooling system
when outside temperature is below
50°F (10°C). See compressor manufacturer instructions for further
information.
NOTE: When cooling setting is
changed, thermostat may
delay up to five minutes
before turning on the air
conditioner. This delay
protects the compressor.
AutoOn
TEMP
AutoOn
Move the System switch to Cool and
HeatCoolOff
the fan switch to Auto.
Press TEMP key until setting is about
10°F (6°C) below room temperature.
The cooling equipment and fan should
start.
Press TEMP key until the setting is
about 10°F (6°C) above room temperature. The cooling equipment and
fan should stop.
HeatCoolOff
Move the System switch to Off, with
the fan switch still at Auto. The system
and fan should be off.
27
69-1119
Step 11. Set The Fan and System Switches
AutoOn
First set the Fan switch.
Fan Auto: Normal setting for most homes. A
single-speed fan will turn on automatically
with the air conditioner or furnace. A twospeed fan will usually run on high with the air
conditioner and on low with the furnace.
Exception: If Fan Operation Switch on back of
thermostat is set to E position (see page
19), fan will operate only with the furnace.
Fan On: The fan runs continuously. Use for
improved air circulation during special
occasions or for more efficient electronic air
cleaning. (In a heat-only system, fan will run
continuously only if fan relay is connected to
the thermostat.)
AutoOn
28
69-1119
Then set the System switch.
Cool: The thermostat controls your air
conditioning system.
Off: Both the heating and air conditioning
systems are off.
Heat: The thermostat controls your heating
system.
HeatCoolOff
HeatCoolOff
HeatCoolOff
29
69-1119
Troubleshooting Guide
IF…THEN…
Display will not come on.❑ Set the System switch to Off. Remove batteries.
Temperature display will not go
lower than 45°F (7°C) or higher than
88°F (31°C) during programming.
Temperature change occurs at the
wrong times.
Insert backward for at least 5 seconds to reset
thermostat. Replace batteries correctly. Display
should come on.
❑ Make sure batteries are fresh and installed
correctly.
❑ Gently clean battery contacts using a soft pencil
eraser. Do not use anything abrasive on the clips.
❑ You have reached the temperature setting limit. The
setting range is 45°F to 88°F (7°C to 31°C).
❑ Check the program times for the period in question.
Be sure that AM and PM indications are correct.
Make sure the current day and time are correct.
Reprogram if necessary.
30
69-1119
Heating will not come on.❑ Check that switch on thermostat is set to Heat.
❑ Check the system fuse or circuit breaker and
replace or reset if necessary.
❑ Check for correct wiring and good connections.
❑ Jumper wires R and W. If heat does not come on,
contact your heating dealer.
❑ If display is blank or says bAt Lo, install fresh
batteries.
❑ If temperature setting is higher than current
temperature, and System On indicator is lit, contact
Duracraft Consumer Services at 1-800-554-4558.
Cooling will not come on.❑ Check that switch on thermostat is set to Cool.
❑ Check the system fuse or circuit breaker and
replace or reset if necessary.
❑ Check for correct wiring and good connections.
❑ Jumper wires Rc and Y. If cooling does not come
on, contact your cooling dealer.
❑ If display is blank or says bAt Lo, install fresh
batteries.
31
69-1119
Cooling will not come on.
(continued)
❑ The thermostat has a built-in time delay on cooling.
Allow 5 to 10 minutes after changing the setting
before the air conditioner starts.
❑ Make sure outdoor disconnect is energized (on).
❑ If temperature setting is lower than current
temperature,and SYSTEM ON indicator is lit, move
system switch from Cool to Off for 10 minutes. After
10 minutes, return switch to Cool position. If air
conditioner comes on, compressor may have
reached its high limit temperature protection and
shut down. If air conditioner does not come on after
the 10 minutes and the SYSTEM ON indicator is lit,
contact Duracraft Consumer Services at 1-800-554-
4558.
❑ If 2- or 4-wire installation, verify R-Rc jumper is
installed.
The house is too warm or too cool.❑ Press Run Program key to check the current
temperature setting.
❑ If desired, change the temperature setting. See
page 17.
32
69-1119
SYSTEM ON indicator is lit, but no
heat is coming from the registers.
The furnace cycles too frequently or
the system cycle length is too short
or too long.
The thermostat's current setting
does not match the display
temperature to within ±1°.
❑ Allow time for the furnace to heat up and the fan to
come on before checking for heat at the register.
(Check to make sure system on-time is set correctly
according to page 18 and 19.)
❑ Readjust system on-time according to instructions
on pages 18 and 19.
❑ Check that the wiring hole in the wall behind the
wallplate has been plugged with insulation to
prevent drafts that might adversely affect thermostat
operation.
❑ Be aware that it is normal for the current setting and
display temperature to differ on occasion.
❑ During recovery from setback or setup, setting and
display temperatures may differ for up to 30 minutes
after recovery period.
33
69-1119
Incorrect room temperature showing
on thermostat display.
❑ Make sure the hole behind the thermostat is
plugged with insulation to help prevent drafts from
adversely affecting the thermostat operation.
❑ The thermostat is factory-calibrated and cannot be
adjusted.
Toll-free Customer Assistance
For all questions concerning this thermostat, please read and follow the instructions. If additional
assistance is needed, call Duracraft Consumer Services toll-free at 1-800-554-4558, Monday Friday, 7:00 a.m. - 5:30 p.m. Eastern time.
Before you call, please have the following information available—thermostat model number and
date code, kind of heating/cooling system (i.e., hot water, warm air, oil, gas, etc.), number of wires
connected to the thermostat.
This equipment is a Class B digital apparatus, which complies with Canadian Radio Interference
NOTICE
Regulations, CRC c.1374.
34
69-1119
Limited One-Year Warranty
Duracraft Corporation warrants this product, excluding battery, to be free from defects in the workmanship or materials, under normal use and service, for a period of one (1) year
from the date of purchase by the consumer. If, at any time during the warranty period, the product is defective or malfunctions, Duracraft shall repair or replace it (at Duracraft’s
option) within a reasonable period of time.
If the product is defective,
(i) return it, with a bill of sale or other dated proof of purchase, to the retailer from which you purchased it, or
(ii) package it carefully, along with proof of purchase (including date of purchase) and a short description of the malfunction, and mail it, postage prepaid, to the following
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Duracraft that the defect or malfunction was caused by damage which
occurred while the product was in the possession of a consumer.
Duracraft’s sole responsibility shall be to repair or replace the product within the terms stated above. DURACRAFT SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF
ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY,
EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some states do not allow the exclusion or limitation of incidental or consequential damages, so this
limitation may not apply to you.
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY DURACRAFT MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE ONE YEAR DURATION OF THIS WARRANTY. Some
states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
This warranty gives you specific legal rights, and you may have other rights which vary from state to state.
If you have any questions concerning this warranty, please write Duracraft Corporation, Consumer Services, 250 Turnpike Road, Southborough, MA 01772 or call 1-800-554-4558,
Monday-Friday, 7:00 a.m. to 5:30 p.m., Eastern time.
35
69-1119
TYPICAL ENERGY SAVINGS FOR REPRESENTATIVE CITIES IN THE U.S. AND CANADA
Savings for Once-A-Day
10°F (5°C) decrease
30%
28%
26%
24%
22%
20%
18%
16%
14%
12%
10%
8%
6%
Approximate percentage of energy cost savings
4%
2%
Edmonton
Regina
Winnipeg
Calgary
HalifaxVancouverDenver
Moncton
North Bay
Quebec
St. John's
Minneapolis
St. Paul
Montreal
Ottawa
Toronto
Buffalo
Cleveland
Milwaukee
Savings for Twice-A-Day
10°F (5°C) decrease*
Cincinnati
Kansas City
St. Louis
Columbus
New York
Philadelphia
Seattle
Boston
Chicago
Des Moines
Detroit
Omaha
Pittsburgh
Salt Lake
Indianapolis
City
*Based on 10°F (5°C) decrease—(5°F [3°C] decrease
gives approximately 55 percent of these savings).
Savings for 5°F (3°)
summer increase
Louisville
Portland
Wash., D C
San
Francisco
Dallas
Atlanta
Los Angeles
San Diego
M2416A
® U.S. Registered Trademark
69-1119 7-97 R.T.
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
36
69-1119
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.