Honeywell TP970-72, TP970-74, TP9600, TP9630 Installation Instructions

TP970-72, TP970-74, TP9600, and TP9630
Pneumatic Sensors, Humidistats,
and Thermostats
INSTALLATION INSTRUCTIONS
Contents
INTRODUCTION ............................................................................................................................ 2
BEFORE INSTALLATION ............................................................................................................................ 2
INSTALLATION ............................................................................................................................ 9
CALIBRATION .......................................................................................................................... 45
General ............................................................................................................... 2
Dimensions ......................................................................................................... 4
Covers ................................................................................................................ 5
General ............................................................................................................... 5
Removing and Replacing Covers ....................................................................... 6
Installing Cover Inserts ....................................................................................... 7
Painting (Beige Plastic Covers Only).................................................................. 7
Installation with Recessed Tubing ...................................................................... 9
Hollow-Core Studded Wall ................................................................................. 9
Block or Brick Wall ............................................................................................ 28
Mullion .............................................................................................................. 38
Installation with Surface-Mounted Tubing ........................................................ 40
Piping................................................................................................................ 45
Humidistat/Humidity Sensor ............................................................................. 45
General ............................................................................................................. 45
Setpoint Lock .................................................................................................... 46
Throttling Range Adjustment (HP970 and HP972) ........................................... 46
Calibration Check ............................................................................................. 46
Recalibration .................................................................................................... 46
Thermostat/Temperature Sensor ...................................................................... 47
General ............................................................................................................. 47
Throttling Range Adjustment ............................................................................ 47
Calibration Check ............................................................................................. 47
Recalibration .................................................................................................... 47
APPENDIX: BACKPLATES .......................................................................................................................... 48
® U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • All Rights Reserved
General ............................................................................................................. 48
Removing Stat from Conventional Backplate ................................................... 48
Removing Stat from Quick-Mount Backplate.................................................... 48
95-5597-1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
INTRODUCTION
The BEFORE INSTALLATION section shows tools and accessories used during installation and calibration, dimensions of major accessories, and procedures for preparing thermostat and humidistat covers. The INSTALLATION section shows how to install thermostats, humidistats, sensors, and fittings and shows connections for one- and two-pipe applications. The CALIBRATION section describes calibration and adjustment procedures.
For information on how to remove a stat body from a stat backplate, refer to APPENDIX: BACKPLATES.
BEFORE INSTALLATION
Tools and Accessories
General
Figure 1 shows tools used for stat installation. Figure 2 shows tools used during calibration check. Figures 3 through 8 show accessories used for several mounting methods.
10
5 0
GAGE 305965 0-30 PSI (0-207 kPa)
TEST THERMOMETER CCT902
20
15
25
30
GAGE PORT NEEDLE (CCT729A CAN BE USED TO CONNECT TO 5/32 IN. AND 1/4 IN. POLYETHYLENE TUBING)
120
140
100
160
80
180
60
200
40
220
20
0
THERMOSTAT TOOL
POCKET LEVEL CCT348
C3150-1
Fig. 1. Installation Tools Used for All Mounting Methods.
DIGITAL RELATIVE HUMIDITY INDICATOR PEN CCT915
Fig. 2. Calibration Tools.
LEVEL
TAPE MEASURE
1—1/2 IN. (38 MM) FROM BOTTOM OF TAPE MEASURE TO
1
CENTER MARK CORRESPONDING TO CENTER OF STAT.
BACK VIEW
C
L
THERMOSTAT MOUNTING GUIDE TOOL
C3928
1
C3151
95-5597—1
Fig. 3. Tape Measure CCT422 and Thermostat
Mounting Guide Tool CCT690.
2
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
PROTECTIVE SLEEVE FOR BORE
REPLACEMENT PROTECTIVE SLEEVES ARE AVAILABLE. ORDER CCT691A.
THERMOSTAT STEP/BORING TOOL
CORDLESS DRILL
WARNING
! !
TO AVOID BODILY INJURY AND PROTECT BORE, LEAVE PROTECTIVE SLEEVE ON STEP/BORING TOOL EXCEPT WHEN DRILLING WITH BORE.
Fig. 4. Thermostat Step/Boring Tool CCT691
and Cordless Drill CCT713.
C3152
1/2
(13)
REMOVABLE WEB (CUT AWAY WITH POCKET KNIFE)
3-17/32
(90)
2-5/16
(59)
C3153
Fig. 6. Wall Mounting Ring 14004458-001 for Flush or
Surface Mounting to Brick or Block Wall or to Wall
with Surface-Mounted Tubing.
SEE CHART FOR BARB SIZE
REMOTE RESTRICTORS
PART NO. ORIFICE BODY
14002913– SIZE IN INCHES COLOR
–001* 0.005 Blue 1/4 (6) –004 0.005 Blue 5/32 (4)
* ONE BARB CAP 14003567-001 FURNISHED WITH RESTRICTOR
BA
FILTER
INLET
ALL INLET BARBS
1/4 IN. (6 MM)
BARB SIZE
IN INCHES (MM)
A B
5/32 (4) 5/32 (4)
C3931-1
Fig. 5. Remote Restrictors Used for Piping.
NOTE: USE FOR APPLICATION WITH RECESSED TUBING WHEN
STAT IS TO BE MOUNTED AT A LATER DATE
C3154
Fig. 7. Wall Plate Bag Assembly 14001905-001.
3
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
Dimensions
Figures 9 through 13 show dimensions of major installation accessories.
4-1/2 (115)
4-5/8 (117)
2-3/4 (70)
C5532
Fig. 7A. Wall Plate Bag Assembly 14002136-004.
TWIN TUBE AK3240 (5/32 IN. O.D. X 0.030 IN. WALL) OR AK3241 (1/4 IN. O.D. X 0.040 IN. WALL)
BUNDLED TUBING AK3168 (5/32 IN. O.D. X 0.030 IN. WALL)
2-7/8
(73)
1-11/16
(43)
NO. 6-32 X 1/2 IN. MOUNTING SCREW (2) PROVIDED WITH SHALLOW WALLPLATE
Fig. 9. Shallow Wall Plate 14001614-001
Dimensions in Inches (Millimeters).
KNOCKOUT FOR 1/2 IN. CONDUIT OR
FITTING SNAP RING (BOTH SIDES,
BACK, TOP AND BOTTOM)
3/16 (5)
(6 PLACES)
TAPPED HOLE
8 x 32 (2 PLACES)
GUIDES FOR
MOUNTING
BRACKET
TAPPED HOLE (2) 6 x 32
MOUNTING SCREWS
6 x 32 - 1/2 (PROVIDED)
ALIGNMENT
FOR FINISHED WALL
3/4 (19)
1/2 (13)
1/4 (6)
2-1/4
(57)
C3180
C3155
Fig. 8. Twin Tube AK3240 (5/32 in. O.D. x 0.030 in. wall)
or AK3241 (1/4 in. O.D. x 0.040 in. wall) and Bundled
Tubing AK3168 (5/32 in. O.D. x 0.030 in. wall).
95-5597—1
2-5/8
(67)
2-9/16 (65)
1-7/16
(37)
C3930
Fig. 10. Deep Wall Box 14001355-001
Dimensions in Inches (Millimeters).
4
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
1 IN. (25 MM) OFFSET FOR BOX
2 IN. (51 MM) OFFSET FOR BOX
1-1/2
(38)
3-1/16 (78)
1-7/16 (37)
C3179
STUD-MOUNTED STAT PLATE (ALIGN OVER ELECTRICAL BOX)
NO. 6-32 X 1/2 IN. MOUNTING SCREW (2) PROVIDED WITH STUD-MOUNTED STAT PLATE
EXTENSION PLATE
3-15/16
(100)
Fig. 11. Deep Wall Box Mounting Bracket 14001354-001
Dimensions in Inches (Millimeters).
1/2
(13)
REMOVABLE WEB (CUT AWAY WITH POCKET KNIFE)
3-17/32
(90)
2-5/16
(59)
C3153
3-15/16
(100)
1-1/16
(27)
3-1/16
(78)
3-9/16
(91)
C3933
Fig. 13. Stud-Mounted Stat Plate 14004610-001
and Extension Plate 14004656-001
Dimensions in Inches (Millimeters).
Covers
General
This section shows how to remove and replace thermostat and humidistat covers and how to install Inserts over the setpoint and DAY/AUTO slots at the bottom of covers. This section also lists recommended paints for covers that can be painted and describes painting procedures.
Cover assembly and disassembly differs between conventional and Quick-Mount stats. On a conventional stat the cover mounts to setscrews in the backplate, while on a Quick-Mount stat the cover mounts to setscrews in the stat body (Fig. 14).
Fig. 12. Wall Mounting Ring 14004458-001
Dimensions in Inches (Millimeters).
CONVENTIONAL STAT SETSCREWS
5
QUICK-MOUNT STAT SETSCREWS
STAT BACKPLATE
STAT BODY
C3569
Fig. 14. Setscrew Locations for Conventional
and Quick-Mount Stats.
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
R
To determine the cover mounting method, look at the holes at the top of the cover (Fig. 15). If the setscrews are raised against the back pair of slots (toward the wall), the setscrews are in the backplate and the stat is a conventional stat. If the setscrews are raised into the front pair of holes, the setscrews are in the stat body and the stat is a Quick-Mount stat.
CONVENTIONAL STAT
SETSCREWS VISIBLE
THERMOSTAT TOOL
CONVENTIONAL STAT SETSCREW SLOT (2)
SETSCREWS VISIBLE
SETSCREWS VISIBLE
QUICK-MOUNT STAT
SPECIAL COVER
STANDARD COVE
QUICK-MOUNT STAT SETSCREW HOLE (2)
COVER
60
70
80
Honeywell
Fig. 16. Removing Cover.
Use the following procedure to replace a cover:
1. Hook slots at bottom of cover over two bottom tabs of stat (Fig. 17). Setpoint adjustment will align with setpoint slot.
CONVENTIONAL STAT SETSCREW LOCATION (2)
STAT BACKPLATE
70
60
QUICK-MOUNT STAT SETSCREW LOCATION (2)
STAT
90
80
90
C3158
STANDARD COVER
C3157
Fig. 15. Conventional and Quick-Mount Stats.
Removing and Replacing Covers
Cover assembly/disassembly requires Thermostat Tool CCT735A (MQT735A). Use the following procedure to remove a cover:
1. Locate setscrews in cover (back pair of slots for conven­tional stat, front pair of holes for Quick-Mount stat).
2. Place Allen wrench end of Thermostat Tool through slot/ hole and into setscrew (Fig. 16).
3. Rotate Thermostat Tool clockwise until setscrew no longer touches cover. Repeat for other setscrew.
4. Pull Cover out and down.
95-5597—1
CONVENTIONAL STAT MOUNTING SLOT (2)
QUICK-MOUNT STAT MOUNTING SLOT (2)
6
CONVENTIONAL STAT TAB (2)
COVER
CONVENTIONAL STAT SETSCREW SLOT (2)
Fig. 17. Replacing Cover.
QUICK-MOUNT STAT TAB (2)
QUICK-MOUNT STAT SETSCREW HOLE (2)
C4110
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
COVER
SETPOINT SLOT
SETPOINT COVER
M10827
INSERT
2. Swing cover up and over stat.
3. Place Allen wrench end of Thermostat Tool through
setscrew slot and into setscrew.
4. Rotate Thermostat Tool counterclockwise until setscrew holds cover securely onto stat backplate (conventional stat) or stat body (Quick-Mount stat). Repeat for other setscrew.
Installing Cover Inserts
The following Cover Inserts are available for the setpoint and DAY/AUTO lever slots on stat covers:
Part No. Finish
14004437 -001 Satin
Chrome
-002 Beige Plastic
14004438 -001 Satin
Chrome
-002 Beige Plastic
14004442 -001 Black 14002132-XXX
Covers Slot
14004406-XXX Standard Covers*
14004407-XXX Standard Covers*
14004406-XXX Standard Covers*
14004407-XXX Standard Covers*
Special Covers†
DAY/AUTO
Setpoint
DAY/AUTO Setpoint
* See HP970 and TP970 Series Standard Covers and
Accessories Specification Data 77-1003.
† See HP970 and TP970 Series Standard Covers
Specification Data 77-9828.
Cover Inserts are removable. Covers ship with setpoint and DAY/AUTO lever slots “open” (without Insert) or “closed” (with Insert present) as follows: — Setpoint slot: Open or closed as ordered (see HP970
and TP970 Series Standard Covers and Accessories Specification Data 77-1003 and HP970 and TP970 Series Special Covers and Accessories Specification Data 77-9828)
— DAY/AUTO lever slot:
• No Insert on vertical stat covers
• Insert present on horizontal stat covers
Applicable
Fig. 19. Installing Setpoint Cover Insert
14004438-001/-002.
Painting (Beige Plastic Covers Only)
Beige Plastic Covers can be painted with recommended paints before or after Covers are installed.
Recommended Paints
If a non-latex paint is required, use Rust-Oleum Enamel (a fish-oil type enamel). No primer is needed.
If a latex paint is required, use one of the following as a primer and follow with any latex wall paint: — Sears Anti-Rust Enamel (a soya-alkyd type enamel in a
spray can)
— True Value Tru-Test X-O Stain Primer/Sealer Stain Killer
XOS-1 White (a white-pigmented, shellac type primer)
Painting Procedures
Painting Cover before Window is Installed
Order the following equipment: — Cover Assembly 14004402-002 — DAY/AUTO Cover Insert 14004437-002 (optional) — Setpoint Cover Insert 14004438-002 (optional) — Window 14004405-XXX according to the following table:
Figures 18 and 19 show how to install Inserts.
COVER
SLOT COVER INSERT
UNUSED SLOT
Fig. 18. Installing DAY/AUTO Cover Insert
14004437-001/-002.
M10828
1. Remove or add Inserts to Cover Assembly as required (see INSTALLING COVER INSERTS).
2. Wash Cover Assembly with mild dish detergent solution.
3. Dry with paper towel.
4. Paint with approved paint.
5. Allow to dry.
6. When Window has been assembled to Cover,
disassembly may damage Window. Before installing Window, note the following:
a. Check that Window display is correct for job
requirements.
b. Check Window orientation to cover. Cover
setpoint and DAY/AUTO lever slots should be on the bottom (vertical mounting) or to the right (horizontal mounting).
7. Remove liner from adhesive on back of Window. Slide Window into Cover opening (Fig. 20) and press in place.
7
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
Painting Cover after Window is Installed
Order the following equipment: — Cover Assembly 14004407-XXX (select from HP970 and
COVER
0
9
0
8
0
7
0
6
0
9
0
8
0
7
0
6
WINDOW CURVED FOR INSTALLATION
Fig. 20. Installing Window.
C3156
TP970 Series Standard Covers and Accessories Spec
Data 77-1003) — Paint Mask 14002193-001 — DAY/AUTO Cover Insert 14004437-002 (optional) — Setpoint Cover Insert 14004438-002 (optional)
1. Remove or add Inserts to Cover Assembly as required (see INSTALLING COVER INSERTS).
2. Wash Cover Assembly with mild dish detergent solution. Do not immerse.
3. Dry with paper towel.
4. Apply Paint Mask to window. Trim around window as
needed.
5. Paint with approved paint.
6. Allow to dry.
7. Remove Paint Mask.
Window 14004405-XXX
Stat
Orientation Honeywell Display (Unit)Silver Beige
Background Background
Vert. Horiz.
Logo
Setpoint Thermometer
-001 -101 X X None None
-002 -102 X X None None
-003 -112 X X None None
-004 -113 X 60-90 (F) 60-90 (F)
-005 -103 X X 60-90 (F) 60-90 (F)
-006 N/A X X 40-70 (F) 40-70 (F)
-007 -104 X X 15-30 (C) 15-30 (C)
-008 -106 X X 60-90 (F) None
-009 N/A X X 40-70 (F) None
-010 N/A X X 15-30 (C) None
-011 N/A X X None 60-90 (F)
-012 N/A X X None 15-30 (C)
-013 N/A X 60-90 (F) 60-90 (F)
-014 N/A X X 60-90 (F) 60-90 (F)
-015 -105 X X 15-30 (C) 15-30 (C)
-016 -107 X X 20-80 (% rh) None
-017 N/A X X 20-80 (% rh) None
-018 N/A X X COOLER/WARMER None
-019 N/A X X HEAT RANGE/COOL RANGE 60-90 (F)
N/A -110 X X 15-30 (C) 60-90 (F)
-021 N/A X X 40-70 (F) 40-70 (F)
60-90 (F)
95-5597—1
8
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
C3181
INSTALLATION
This section categorizes stat installation according to the following factors: — Location of tubing: recessed or surface-mounted — Type of wall: hollow-core studded, block or brick,
concrete, or mullion
— Condition of wall: rough-in or finished
Installation with Recessed Tubing
Examples of installations with recessed tubing include: hollow-core stud walls, block or brick walls, concrete walls, and mullions.
Hollow-Core Studded Wall
A hollow-core studded wall requires either rough-in mounting or finished-wall installation.
Rough-In Installation
Rough-in installation is done to a stud before the wall is drywalled or to lath before the wall is plastered.
NOTE: If the wall is already drywalled or plastered, see
FINISHED WALL INSTALLATION.
Mounting to Stud with Stud-Mounted Stat Plate
Mounting to a stud using a Stud-Mounted Stat Plate requires the following equipment: — Stud-Mounted Stat Plate 14004610-001 (Fig. 21) — Extension Plate 14004656-001 (optional) (Fig. 21) — Tape Measure CCT422 — No. 8 sheet metal screws — Cordless Drill CCT713 (Fig. 22) — TEK Drill Adapter Screwdriver CCT240 (Fig. 22) — No. 8 x 1/2 in. TEK Screws CCT2444 (two per stat) — Stud Mount Box Clip CCT2642 for mounting Stud-
Mounted Stat Plate to metal stud (Fig. 23) (optional)
— Thermostat Tool CCT735A (MQT735A)
TEK DRILL ADAPTER SCREWDRIVER
CORDLESS DRILL
C3167
Fig. 22. TEK Drill Adapter Screwdriver and Cordless Drill.
Fig. 23. Stud Mount Box Clip.
SCREWS
PROVIDED
STUD-MOUNTED STAT PLATE
NOTE: MAXIMUM EXTENSION IS 2-3/4 IN. (70 MM) USING
ONE PLATE, 5-3/8 IN. (137MM) USING TWO PLATES.
Fig. 21. Stud-Mounted Stat Plate and
Optional Extension Plate.
EXTENSION PLATE
C3932
TAPE MEASURE
C3162
1. Measure and mark approximate stat location on stud.
9
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
HORIZONTAL MOUNTING TO HORIZONTAL STUD
HORIZONTAL MOUNTING TO VERTICAL STUD OR VERTICAL MOUNTING TO HORIZONTAL STUD
OR
VERTICAL MOUNTING TO VERTICAL STUD
TEK SCREW (2)
EXTENSION PLATE
SHEET METAL SCREW (2)
EXTENSION PLATE BUTTON (2)
STUD-MOUNTED STAT PLATE
STUD MOUNT BOX CLIP
MOUNTING TO METAL STUD (REQUIRES STUD MOUNT BOX CLIP CCT2642)
NOTE:
TO ATTACH STUD-MOUNTED STAT PLATE TO EXTENSION PLATE:
A. FIT TWO BUTTONS ON EXTENSION PLATE INTO SLOTS
ON STUD-MOUNTED STAT PLATE. ALIGN TWO OUTER HOLES AND/OR SINGLE CENTER
B.
HOLES ON TWO PLATES. FASTEN PLATES TOGETHER WITH NO. 8 x 1/2 IN.
C.
SHEET METAL SCREWS. FASTEN EXTENSION PLATE TO STUD USING
D.
NO. 8 x 1/2 IN. TEK SCREWS.
TYPICAL MOUNTING WITH EXTENSION PLATE
C3937
2. Attach Stud-Mounted Stat Plate, using Extension Plate if required to center stat over electrical box. Use Cordless Drill and TEK Screwdriver Drill Adapter to drive No. 8 x 1/2 in. TEK screws, or use Stud Mount Box Clip as required.
95-5597—1
10
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
STAT BACKPLATE
STAT
C3573
TUBING
STUD-MOUNTED STAT PLATE
STUD MOUNTED STAT PLATE
TAB
STAT BACKPLATE
C3934
3. Fish tubing through Stud-Mounted Stat Plate. Anchor tubing in upper-right or lower-left corner of Plate by crimping Plate tab with pliers.
TUBING
STAT BACKPLATE
C3936
5. Hook keyhole slots of stat backplate over backed-out screws on Stud-Mounted Stat Plate. Level stat backplate and tighten screws.
C3935
4. After drywall or plaster is up, release tubing from corner of Plate. Connect tubing to barbs on stat backplate.
6. Mount stat to stat backplate.
11
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
Mounting to Stud with Deep Wall Box
Mounting to a stud using a Deep Wall Box requires the following equipment:
SETSCREWS
STAT BACKPLATE
STAT
TAB (2)
COVER
SETSCREW SLOTS
C4116
7. Hook slots on stat cover over bottom tabs on stat backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
— Deep Wall Box Assembly 14001492-001 (includes two-
pipe plastic cable assembly, see Fig. 24) or separate parts for one- and three-pipe applications as follows:
• Deep Wall Box 14001355-001
• Fitting Finder 14000706-001 (optional)
• One of the following: 14001491-001 one-pipe or -003 three-pipe Plastic Cable Assembly
or 14001494-001 one-pipe, -002 two-pipe, or -003 three-pipe Copper Cable Assembly
— Barb Couplings CCT1606B (MJP1606B) (5/32 x 1/4 in.)
or CCT1628B (MJP1628B) (5/32 x 5/32 in.) for plastic tubing (one, two, or three Couplings required according
to application) — Tape Measure CCT422 — Cordless Drill CCT713 (Fig. 25) — TEK Drill Adapter Screwdriver CCT240 (Fig. 25) — The following items according to mounting method:
• Directly to stud: Two No. 8 x 2 in. Pan Head Sheet Metal Screws CCT2310 (MVH2310)
or
Two 6d 2 in. (51 mm) nails
• Between two studs: Universal Strap CCT2630 (MVP2630) (Fig. 26) Two No. 8 x 1/2 in. TEK Screws CCT2444 One No. 8-32 x 1/2 in. Round Head Screw CCT2410
• Offset from stud (e.g., to center over electrical box): Deep Wall Box Mounting Bracket 14001354-001 One No. 8-32 x 1/4 in. Round Head Screw CCT2408 Two No. 8 x 1/2 in. TEK Screws CCT2444
— Thermostat Tool CCT735A (MQT735A)
DEEP WALL BOX
ALIGNMENT GUIDE FOR FINISHED WALL
NO. 6–32 X 1/2 IN. SCREW (2) PROVIDED WITH DEEP WALL BOX
BUSHING
PROTECTOR CAP
PLASTIC CABLE ASSEMBLY 8 FT (2.5 M)
BUSHING
FITTING FINDER
CABLE ASSEMBLY
Fig. 24. Deep Wall Box Assembly and Cable Assemblies.
MAIN
BARB CAP
BRANCH
ONE-PIPE ASSEMBLY
SWITCH
MAIN
BRANCH
BARB TEE
THREE - PIPE ASSEMBLY
PROTECTOR CAP
BARB COUPLINGS FOR PLASTIC TUBING
C3562
95-5597—1
12
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
TEK DRILL ADAPTER SCREWDRIVER
CORDLESS DRILL
C3167
Fig. 25. TEK Drill Adapter Screwdriver and Cordless Drill.
1 (25)
NO. 8–32
3/4 (19)
MOUNTING BRACKET
DEEP WALL BOX
NO. 8–32 X 1/4 IN. SCREW
MOUNTING BRACKET
NO. 6–32 X 1/2 IN. SCREW (2) PROVIDED
DEEP WALL BOX
NO. 8–32 X 1/4 IN. SCREW
C3566
24 (610)
Fig. 26. Universal Strap.
TAPE MEASURE
C3161
2. If offset from stud is required (e.g., to center stat over electrical box), attach Deep Wall Box to Deep Wall Box Mounting Bracket with No. 8-32 x 1/4 in. Round Head Screw.
C3162
1. Measure and mark approximate stat location on stud.
13
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
STUD
CABLE ASSEMBLY
PROTECTOR CAP
PLASTIC CABLE ASSEMBLY 8 FT (2.5 M)
DEEP WALL BOX
NO. 8 x 2 IN. SHEET METAL SCREWS OR 6d 2 IN. (51 MM) NAILS
MOUNTING DEEP WALL BOX DIRECTLY TO STUD
BARB COUPLINGS
NO. 8 x 1/2 IN. TEK SCREW
UNIVERSAL STRAP
8-32 x 1/2 IN. ROUND HEAD SCREW
(INSTALL FROM INSIDE BOX)
NO. 8 x 1/2 IN. TEK SCREW
MOUNTING DEEP WALL BOX BETWEEN STUDS USING UNIVERSAL STRAP
DEEP WALL BOX DEEP WALL BOX
NO. 8 TEK SCREWS (2)
DEEP WALL BOX
NO. 8 TEK SCREWS (2)
FITTING FINDER (IF WALL IS TO BE PLASTERED)
C3561
4. Remove protector cap from Cable Assembly. Attach tubing to Cable with 5/32 x 1/4 in. or 5/32 x 5/32 in. Barb Couplings. If wall is to be plastered, snap Fitting Finder onto Deep Wall Box.
TUBING
STAT BACKPLATE
1 (25) OFFSET
DEEP WALL BOX MOUNTING BRACKET
2 (51) OFFSET
ALIGN BRACKET NOTCH WITH EDGE OF STUD
DEEP WALL BOX MOUNTING BRACKET
C3939
USING DEEP WALL BOX MOUNTING BRACKET
3. Mount Deep Wall Box to stud so that front of Box will be flush with finished wall.
95-5597—1
C3590
5. After drywall or plaster is up, remove Fitting Finder, if used, from box. Cut elbow from end of Cable Assembly. Connect tubing to barbs on stat backplate.
14
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
SETSCREWS
STAT BACKPLATE
DEEP WALL BOX
STAT BACKPLATE
KEYHOLE SLOTS
C3587
6. Back screws out of Deep Wall Box. Hook stat backplate keyhole slots onto backed-out screws. Level stat backplate and tighten screws.
STAT
TAB (2)
COVER
SETSCREW SLOTS
C4115
8. Hook slots on stat cover over bottom tabs on stat backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
7. Mount stat onto stat backplate.
STAT BACKPLATE
STAT
C3575
Mounting to Stud with Standard Electrical Box
Mounting to a stud using a standard electrical box requires the following equipment: — Standard Utility Conduit Box CCT2967 (MVE2967) or
Standard 4 x 4 in. Electrical Box CCT2960 (Fig. 27)
— One of the following (Fig. 28):
• Plastic Cable Assembly 14001491-001 (one pipe),
-002 (two pipe), or -003 (three pipe) and Barb Couplings CCT1606B (MJP1606B) (5/32 x 1/4 in.) or CCT1628B (MJP1628B) (5/32 x 5/32 in.)
• Copper Cable Assembly 14001494-001 (one pipe),
-002 (two pipe), or -003 (three pipe)
• 1/2 in. emt conduit and 1/2 in. TW Setscrew Connector CCT2900 (MVE2900)
— Tape Measure CCT422 — No. 10 x 3 Pan Head Sheet Metal Screws CCT2317
(MVH2317) or 2-1/2 in. (64 mm) nails (two per stat)
— Stud Mount Box Clip CCT2642 for Standard Utility
Conduit Box (Fig. 29)
— MFS Clip CCT2649E for Standard 4 x 4 in. Electrical Box
(Fig. 29)
— If wall is to be plastered:
• Standoff Ring 14000885-001
• Fitting Finder 14000706-001
— Thermostat Tool CCT735A (MQT735A)
15
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
STUD MOUNT BOX CLIP (FOR STANDARD UTILITY CONDUIT BOX)
STANDARD UTILITY
CONDUIT BOX
4 X 2-1/8 X 1-7/8 IN.
(102 X 55 X 48 MM)
STANDARD
ELECTRICAL BOX
4 X 4 X 2-1/8 IN.
(102 X 102 X 54 MM)
Fig. 27. Standard Utility Conduit Box and
Standard 4 x 4 in. Electrical Box.
MAIN
SWITCH
BRANCH
MAIN
BRANCH
ONE-PIPE ASSEMBLY
THREE-PIPE ASSEMBLY
BARB CAP
BUSHING
MAIN
BRANCH
TWO-PIPE ASSEMBLY
C3938
BARB TEE
ELBOW
MFS CLIP (FOR STANDARD 4 X 4 ELECTRICAL BOX)
C3182
Fig. 29. Stud Mount Box Clip and MFS Clip.
TAPE MEASURE
PROTECTOR CAP
BARB COUPLINGS
CABLE ASSEMBLY
FOR PLASTIC TUBING
OR
1/2 IN. EMT CONDUIT
1/2 IN. TW SETSCREW CONNECTOR
C3563
Fig. 28. One-, Two-, or Three-Pipe Plastic
or Copper Cable Assembly
or
1/2 in. EMT Conduit with 1/2 in. TW Setscrew Connector.
95-5597—1
C3162
1. Measure and mark approximate stat location on stud.
16
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
CABLE
STANDARD UTILITY CONDUIT BOX
NO. 10 X 3 PAN HEAD SHEET METAL SCREWS OR 6d 2 IN. (64 MM) NAILS
ASSEMBLY
BUSHING
PUSH BUSHING INTO KNOCKOUT
MOUNTING STANDARD UTILITY CONDUIT BOX
DIRECTLY TO STUD
STANDARD UTILITY CONDUIT BOX
MOUNTING STANDARD UTILITY CONDUIT BOX
TO STUD USING STUD MOUNT BOX CLIP
STANDARD 4 x 4 ELECTRICAL BOX
STUD MOUNT BOX CLIP
1/2 IN. TW SETSCREW CONNECTOR
OR
1/2 IN. EMT CONDUIT
MOUNTING STANDARD 4 x 4 ELECTRICAL BOX
TO STUD USING MFS CLIP
2. Mount box to stud.
MFS CLIP
C3186
3. Place elbow end of Cable Assembly through knockout and push Cable Assembly bushing into knockout.
or Attach 1/2 in. TW Setscrew Connector to appropriate knockout in box, place conduit into Connector, and tighten Connector setscrew.
17
C3188
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
TUBING
BARB COUPLINGS
CABLE ASSEMBLY
STANDARD UTILITY CONDUIT BOX
STANDOFF RING
(EARS BROKEN OFF)
OR
OR
TUBING
CONDUIT
C3189
4. Remove protector cap from Cable Assembly and attach plastic tubing to Cable Assembly with 5/32 x 1/4 in. or 5/32 x 5/32 in. Barb Couplings.
or
Run plastic tubing through conduit.
STANDARD 4 x 4 ELECTRICAL BOX
IF WALL IS TO BE PLASTERED:
STANDOFF RING
STANDOFF RING
95-5597—1
18
FITTING FINDER
5.
Mount Standoff Ring to box with screws provided. For
C3940
standard utility conduit box, break ears off Standoff Ring before mounting. If wall is to be plastered, snap Fitting Finder onto Standoff Ring.
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
STAT BACKPLATE
STAT
C3579
STANDOFF RING IN WALL
TUBING
STAT BACKPLATE
C3592
6. After drywall or plaster is up, remove elbow from end of Cable Assembly, if used. Connect tubing to barbs on stat backplate.
STANDOFF RING IN WALL
STAT BACKPLATE
KEYHOLE SLOTS
8. Mount stat onto stat backplate.
TAB (2)
COVER
SETSCREWS
STAT BACKPLATE
STAT
C3586
7. Back screws out of Standoff Ring. Hook keyhole slots of stat backplate over screws. Level stat backplate and tighten screws.
9. Hook slots on stat cover over bottom tabs on stat backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
19
SETSCREW SLOTS
C4117
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
Mounting to Lath
Mounting to lath requires the following equipment: — Shallow Wall Plate Assembly 14001615-001/-002 or
14001616-001/-002 (Fig. 30). Includes the following:
• Shallow Wall Plate 14001614-001
• Plaster Ring 14001609-001
• Fitting Finder 14000706-001
TAPE MEASURE
NOTE: Shallow Wall Plate Assembly 14001615-001 (one
pipe) or -002 (two pipe) has copper tubing. Assembly 14001616-001 (one pipe) or -002 (two pipe) has 5/32 in. (4 mm) O.D. plastic tubing.
— Tape Measure CCT422 — Barb Couplings CCT1606B (MJP1606B) (5/32 x 1/4 in.)
or CCT1628B (MJP1628B) (5/32 x 5/32 in.) for plastic tubing (one, two, or three Couplings required according to application)
— Soft Copper Tie Wire CCT2643 or Plastic Covered Wire
Ties CCT2663 (MVE2663) — Wall Mounting Ring 14004458-001 — Thermostat Tool CCT735A (MQT735A)
SHALLOW WALL PLATE BOTH ENDS ARE REMOVABLE
PROTECTOR CAP
8 FT (2.5 M)TUBING AND TWIN ELBOW ASSEMBLY
1
PLASTER RING
C3170
1. Measure and mark approximate stat location on lath.
1
FITTING FINDER PRESS TO SNAP IN PLACE
1
AVAILABLE SEPARATELY
Fig. 30. Shallow Wall Plate Assembly.
C3597
SOFT COPPER TIE WIREOR PLASTIC COVERED WIRE TIES
C3187
2. At approximate stat location, anchor corners of Shallow Wall Plate to lath with Soft Copper Tie Wire or Plastic Covered Wire Ties.
95-5597—1
20
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
FITTING FINDER
PLASTER RING
C3599
TUBING
BARB
C3948
COUPLINGS
TUBING AND TWIN ELBOW ASSEMBLY
SHALLOW WALL PLATE
3. Connect tubing to Tubing and Twin Elbow Assembly with 5/32 x 1/4 in. or 5/32 x 5/32 in. Barb Couplings.
SHALLOW WALL PLATE
BREAK­OUT TAB
PLASTER RING
SCREWS PROVIDED WITH SHALLOW WALL PLATE
C3598
5. Remove break-out tab from top of Plaster Ring. Push Plaster Ring onto Shallow Wall Plate brackets and lower screw receptacle. Attach Plaster Ring to Shallow Wall Plate with screws provided.
SOFT COPPER TIE WIRE OT PLASTIC COVERED WIRE TIE
SHALLOW WALL PLATE
TWIN TUBE
TUBING AND TWIN ELBOW ASSEMBLY
UPPER SCREW RECEPTACLE
C3949
4. Remove screws from screw receptacles on Shallow 6. Snap Fitting Finder onto Plaster Ring. Wall Plate. Push Tubing and Twin Elbow Assembly onto upper screw receptacle. Anchor tubing to lath with Soft Copper Tie Wire or Plastic Covered Wire Ties.
21
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
STAT BACKPLATE
TWIN ELBOW CONNECTOR
STAT BACKPLATE
PLASTER RING IN WALL
C3595
7. After plaster is up, remove Fitting Finder from Plaster Ring. Remove protector from end of tubing, leaving Twin Elbow Connector. Connect Twin Elbow Connector to barbs on stat backplate.
STAT BACKPLATE
BACKED-OUT SCREW (2)
KEYHOLE SLOTS
C3596
STAT
9.
Mount Stat to stat backplate.
TAB (2)
COVER
SETSCREWS
STAT BACKPLATE
STAT
C3578
8. Back screws out of Plaster Ring. Slip stat backplate keyhole slots over screws. Level stat backplate and tighten screws.
95-5597—1
SETSCREW SLOTS
C4118
10. Hook slots on stat cover over bottom tabs on stat backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
22
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
GUIDE
TAPE MEASURE
WALL
C3172
LEVEL ON
FLOOR
Finished Wall Installation
In a finished wall installation, the studs are covered with drywall or plaster and the tubing is behind the wall. Finished wall installation is done with a Quick-Mount Thermostat, anchors, or a Shallow Wall Plate.
Quick-Mount Thermostat
Installing a Quick-Mount Thermostat requires the following tools: — Tape Measure CCT422 (Fig. 31) — Thermostat Mounting Guide Tool CCT690 (Fig. 31) — Cordless Drill CCT713 (Fig. 32) — Thermostat Step/Boring Tool CCT691 (Fig. 32) — Fish Chain CCT417 — Wire hook for pulling Fish Chain (see Step 3)
BACK VIEW
C
L
1
TAPE MEASURE
LEVEL
THERMOSTAT MOUNTING GUIDE TOOL
1—1/2 IN. (38 MM) FROM BOTTOM OF TAPE MEASURE TO
1
CENTER MARK CORRESPONDING TO CENTER OF STAT.
C3151
Fig. 31. Tape Measure and Thermostat Mounting Guide Tool.
PROTECTIVE SLEEVE FOR BORE
REPLACEMENT PROTECTIVE SLEEVES ARE AVAILABLE. ORDER CCT691A.
THERMOSTAT STEP/BORING TOOL
CORDLESS DRILL
1. Measure thermostat location on wall. Use level on Mounting Guide to ensure that Mounting Guide is plumb. Tap Tape Measure to mark hole locations.
STEP
3/4 INCH
(19 MM)
1/4 INCH
(6 MM)
BORE
CORDLESS DRILL
WARNING
! !
TO AVOID BODILY INJURY AND PROTECT BORE, LEAVE PROTECTIVE SLEEVE ON STEP/BORING TOOL EXCEPT WHEN DRILLING WITH BORE.
C3152
Fig. 32. Thermostat Step/Boring Tool and Cordless Drill.
C3174
2. Drill holes where marked on wall. For top and bottom holes, drill until the step of the Thermostat Step/Boring Tool meets wall. For center hole, remove protective sleeve from bore, force Thermostat Step/Boring Tool beyond the step, and drill the hole with the bore. Replace protective sleeve over bore.
23
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
TWIN TUBE
WIRE HOOK
FISH CHAIN
C3175
3. Use Fish Chain to fish tubing through center hole.
ANCHORS
BARBS
BACKPLATE
BACKPLATE ASSEMBLY
CONE
ASSEMBLY
C3942
5. Cut tubing. Use cone on Backplate Assembly to flare cut ends of tubing. Connect tubing to barbs on Backplate Assembly.
BACKPLATE ASSEMBLY
THERMOSTAT AND COVER ASSEMBLY
PACKING SHELL
4.
Remove Backplate Assembly from packing shell.
C3941
BACKPLATE ASSEMBLY
Place Backplate Assembly anchors through top and
6.
C3173
bottom holes.
95-5597—1
24
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
PHILLIPS END
THERMOSTAT STEP/BORING
BACKPLATE ASSEMBLY
C3183
TOOL
CORDLESS DRILL
SHIPPING STOP(S)
C3178
9. Remove shipping stop(s) from Thermostat and Cover Assembly. Place packing shell and shipping stop(s) back in carton.
7. Hold Backplate Assembly to appear plumb. With protective sleeve over bore of Thermostat Step/Boring Tool, drive anchors with Phillips end of Tool.
BACKPLATE ASSEMBLY
THERMOSTAT AND
COVER ASSEMBLY
C3176
BACKPLATE ASSEMBLY
THERMOSTAT AND COVER ASSEMBLY
C3176
8. Remove Thermostat and Cover Assembly from packing shell. Align top of Thermostat and Cover Assembly with top of Backplate. Snap Thermostat and Cover Assembly onto Backplate Assembly.
10. After painting is complete, use tear strip to remove outer paint mask. Peel off inner paint mask.
25
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
WALL
LEVEL ON GUIDE
TAPE MEASURE
FLOOR
C3172
Anchors
Drywall installation with anchors requires the following equipment: — Tape Measure CCT422 (Fig. 33) — Thermostat Mounting Guide Tool CCT690 (Fig. 33) — Cordless Drill CCT713 (Fig. 34) — Thermostat Step/Boring Tool CCT691 (Fig. 34) — Fish Chain CCT417 — Wire hook for pulling Fish Chain (see Step 3) — Molly Anchors CCT2260 (MVH2260) (2 per stat) — Thermostat Tool CCT735A (MQT735A)
BACK VIEW
C
L
THERMOSTAT MOUNTING GUIDE TOOL
1
TAPE MEASURE
LEVEL
1—1/2 IN. (38 MM) FROM BOTTOM OF TAPE MEASURE TO
1
CENTER MARK CORRESPONDING TO CENTER OF STAT.
C3151
Fig. 33. Tape Measure and Thermostat Mounting Guide Tool.
PROTECTIVE SLEEVE FOR BORE
REPLACEMENT PROTECTIVE SLEEVES ARE AVAILABLE. ORDER CCT691A.
THERMOSTAT STEP/BORING TOOL
CORDLESS DRILL
1. Measure thermostat location on wall. Use level on Mounting Guide to ensure that Mounting Guide is plumb. Tap Tape Measure to mark hole locations on wall.
STEP
3/4 INCH
(19 MM)
1/4 INCH
(6 MM)
BORE
CORDLESS DRILL
!
WARNING
TO AVOID BODILY INJURY AND PROTECT BORE, LEAVE PROTECTIVE SLEEVE ON STEP/BORING TOOL EXCEPT WHEN DRILLING WITH BORE.
!
C3152
Fig. 34. Thermostat Step/Boring Tool and Cordless Drill.
95-5597—1
C3174
2. Drill holes where marked on wall. For top and bottom holes, drill until the step of the Thermostat Step/Boring Tool meets wall. For center hole, remove protective sleeve from bore, force Thermostat Step/Boring Tool beyond the step, and drill the hole with the bore. Replace protective sleeve over bore.
26
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
PHILLIPS END
STAT BACKPLATE
ANCHOR (2)
THERMOSTAT STEP/BORING TOOL
C3171
CORDLESS DRILL
TWIN TUBE
WIRE HOOK
TUBING
M3944
FISH CHAIN
C3175
3. Use Fish Chain to fish tubing through center hole.
STAT BACKPLATE
5.
Cut tubing and connect to barbs on stat backplate.
STAT BACKPLATE
MOLLY ANCHORS
KEYHOLE SLOTS
4. Push Molly anchor heads through stat backplate keyhole slots. Tighten anchors slightly to secure them to stat backplate.
C3943
6. Push anchors into holes in wall. Level backplate. With protective sleeve over bore of Thermostat Step/Boring Tool, tighten anchors with Phillips end of Tool.
27
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
STAT BACKPLATE
STAT
7. Mount stat onto stat backplate.
SETSCREWS
STAT BACKPLATE
C3170
Block or Brick Wall
A stat should be mounted according to the steps shown in ROUGH-IN INSTALLATION. Use the procedure in FINISHED WALL INSTALLATION only if the stat cannot be roughed in as part of the wall. If the wall is to be plastered, see INSTALLATION WITH SURFACE-MOUNTED TUBING.
Rough-In Installation
Rough-in is done by the mason as the wall is laid. The installer hangs the stat at its approximate final location and the mason cuts the hole where needed in the block course.
Rough-in installation may require some or all of the following equipment: — Deep Wall Box 14001355-001 (Fig. 35) — One of the following (Fig. 36):
• Plastic Cable Assembly 14001491-001 (one pipe),
-002 (two pipe), or -003 (three pipe) and Barb Couplings CCT1606B (MJP1606B) (5/32 x 1/4 in.) or CCT1628B (MJP1628B) (5/32 x 5/32 in.)
• Copper Cable Assembly 14001494-001 (one pipe),
-002 (two pipe), or -003 (three pipe)
• 1/2 in. emt conduit and 1/2 in. TW Setscrew Connector CCT2900 (MVE2900)
— Tape Measure CCT422 — Thermostat Tool CCT735A (MQT735A)
STAT
SETSCREW SLOTS
TAB (2)
COVER
8. Hook slots on stat cover over bottom tabs on stat backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew holes on top of cover.
C4114
ALIGNMENT GUIDE FOR FINISHED WALL
NO. 6–32 X 1/2 IN. SCREW (2) PROVIDED WITH DEEP WALL BOX
Fig. 35. Deep Wall Box.
C3185
95-5597—1
28
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
MAIN
BRANCH
THREE-PIPE ASSEMBLY
ONE-PIPE ASSEMBLY
BUSHING
CABLE ASSEMBLY
OR
MAIN
BRANCH
BARB CAP
MAIN
BRANCH
SWITCH
BARB TEE
ELBOW
TWO-PIPE ASSEMBLY
PROTECTOR CAP
BARB COUPLINGS FOR PLASTIC TUBING
CABLE ASSEMBLY
PUSH BUSHING INTO KNOCKOUT
DEEP WALL BOX
1/2 IN. TW SETSCREW CONNECTOR
OR
1/2 IN. EMT CONDUIT
1/2 IN. EMT CONDUIT
1/2 IN. TW SETSCREW CONNECTOR
C3563
Fig. 36. One-, Two-, or Three-Pipe Plastic
or Copper Cable Assembly
or
1/2 in. EMT Conduit with 1/2 in. TW Setscrew Connector.
DEEP WALL BOX
C3564
1. Place elbow end of Cable Assembly through knockout and push Cable Assembly bushing into knockout.
or Attach 1/2 in. TW Setscrew Connector to appropriate knockout in box, place conduit into Connector, and tighten Connector setscrew.
29
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
TUBING
BARB COUPLINGS
CABLE ASSEMBLY
CONDUIT
OR
TUBING
HOLLOW BLCOK OR BRICK WALL
DEEP WALL BOX
C4101
3. Measure approximate location of stat. Hang or position Deep Wall Box at measured location.
C3565
2. Remove protector cap from Cable Assembly and attach plastic tubing to Cable Assembly with 5/32 x 1/4 in. or 5/32 x 5/32 in. Barb Couplings.
or
Run plastic tubing through conduit.
PLASTIC CABLE
COPPER TUBING
CONDUIT
DEEP WALL BOX ASSEMBLIES
C4102
4. Mason lays block or brick course and cuts hole where indicated by stat position. Place Deep Wall Box Assembly into hole so that conduit or Cable Assembly runs through openings inside blocks or bricks.
95-5597—1
30
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
7. Mount stat to stat backplate.
8. Hook slots on stat cover over bottom tabs on stat
DEEP WALL BOX IN BLOCK BRICK WALL
backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
Finished Wall Installation
This section describes finished wall installation with tubing recessed in the openings inside the block or brick. To install a stat where tubing is surface mounted, see SURFACE­MOUNTED TUBING.
C3582
5. If Cable Assembly is used, cut elbow from end of tubing. Connect tubing to barbs on stat backplate.
DEEP WALL BOX SCREW (2)
STAT BACKPLATE
Finished wall installation requires the following equipment: — Tape Measure CCT422 (Fig. 37) — Thermostat Mounting Guide Tool CCT690 (Fig. 37) — Fish Chain CCT417 — Wire hook for pulling Fish Chain through wall (see Step 4) — 1/2 in. Hammer Drill CCT717 (MQG717) (Fig. 38) — Masonry Drills CCT773 (MQG773) (3/16-in. bit) and
CCT786 (7/8-in. bit) (Fig. 38)
— 3/4 in. Plastic Screw Anchors CCT2230 (MVH2230)
(2 per stat) — No. 8 sheet metal screws (2 per stat) — Thermostat Tool CCT735A (MQT735A)
BACK VIEW
C
L
THERMOSTAT MOUNTING GUIDE TOOL
1
TAPE MEASURE
LEVEL
KEYHOLE SLOT (2)
STAT BACKPLATE
C3583
6. Back screws out of Deep Wall Box. Hook keyhole slots on stat backplate over backed out screws. Level stat backplate and tighten screws.
1—1/2 IN. (38 MM) FROM BOTTOM OF TAPE MEASURE TO
1
CENTER MARK CORRESPONDING TO CENTER OF STAT.
C3151
Fig. 37. Tape Measure and Thermostat Mounting Guide Tool.
31
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
MASONRY DRILL
MASONRY DRILL (7/8 -IN. BIT)
HAMMER DRILL
C3191
Fig. 38. Hammer Drill and 3/16-in. or 7/8-in. Masonry Drill.
TAPE MEASURE
THERMOSTAT MOUNTING GUIDE TOOL
HAMMER DRILL
C3196
2. Use 7/8-in. Masonry Drill and Hammer Drill to Drill 7/8-in. (22.2-mm) center hole.
1. Measure approximate stat location on wall. Turn Tape Measure sideways and mark center, top, and bottom hole locations according to points on back of Thermostat Mounting Guide Tool.
95-5597—1
C3195
32
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
MASONRY DRILL
3/16 IN. (4.8 MM)
PLASTIC SCEW ANCHOR (2)
(3/16-IN. BIT)
PLASTIC SCREW ANCHOR (2)
HAMMER DRILL
C3199
3. Use 3/16-in. Masonry Drill to drill 3/16-in. (4.8-mm) top and bottom holes.
WIRE HOOK
NO. 8 SHEET METAL SCREWS (2)
C3197
5. Knot tubing. Tap 3/4 in. Plastic Screw Anchors into top and bottom holes. Screw No. 8 sheet metal screws partway into Plastic Screw Anchors.
STAT BACKPLATE
FISH CHAIN
4. Use Fish Chain to fish tubing through center hole.
C4104
6. Unknot tubing and connect to barbs on stat backplate.
33
C4107
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
9. Hook slots on stat cover over bottom tabs on stat backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
Concrete Pour
Mounting in preparation for a concrete pour requires the following equipment:
STAT BACKPLATE
KEYHOLE SLOTS
— Deep Wall Box 14001355-001 (Fig. 39) — One of the following (Fig. 40):
• Plastic Cable Assembly 14001491-001 (one pipe),
-002 (two pipe), or -003 (three pipe) and Barb Couplings CCT1606B (MJP1606B) (5/32 x 1/4 in.) or CCT1628B (MJP1628B) (5/32 x 5/32 in.)
• Copper Cable Assembly 14001494-001 (one pipe),
-002 (two pipe), or -003 (three pipe)
• 1/2 in. emt conduit and 1/2 in. TW Setscrew Connector CCT2900 (MVE2900)
— Tape Measure CCT422 — Soft Copper Tie Wire CCT2643 or Plastic Covered Wire
Ties CCT2663 (MVE2663) — 2 in. Duct Tape CCT3349B — Thermostat Tool CCT735A (MQT735A)
C4108
7. Hook keyhole slots of stat backplate over screws. Level stat backplate and tighten screws.
STAT BACKPLATE
STAT
ALIGNMENT GUIDE FOR FINISHED WALL
NO. 6–32 X 1/2 IN. SCREW (2) PROVIDED WITH DEEP WALL BOX
Fig. 39. Deep Wall Box.
C3185
8. Mount stat to stat backplate.
95-5597—1
C3572
34
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
MAIN
BRANCH
THREE-PIPE ASSEMBLY
ONE-PIPE ASSEMBLY
BUSHING
CABLE ASSEMBLY
OR
MAIN
BRANCH
BARB CAP
MAIN
BRANCH
SWITCH
BARB TEE
ELBOW
TWO-PIPE ASSEMBLY
PROTECTOR CAP
BARB COUPLINGS FOR PLASTIC TUBING
STEEL REINFORCEMENT ROD
TAPE MEASURE
C3164
1. Measure and mark stat location on steel reinforcement rods.
1/2 IN. EMT CONDUIT
1/2 IN. TW SETSCREW CONNECTOR
C3563
Fig. 40. One-, Two-, or Three-Pipe Plastic
or Copper Cable Assembly
or
1/2 in. EMT Conduit with 1/2 in. TW Setscrew Connector.
35
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
CABLE ASSEMBLY OR CONDUIT
TAPE
DEEP WALL BOX
C3166
CABLE ASSEMBLY
PUSH BUSHING INTO KNOCKOUT
DEEP WALL BOX
1/2 IN. TW SETSCREW CONNECTOR
OR
1/2 IN. EMT CONDUIT
TUBING
BARB COUPLINGS
CABLE ASSEMBLY
CONDUIT
OR
TUBING
DEEP WALL BOX
C3564
2. Place elbow end of Cable Assembly through knockout and push Cable Assembly bushing into knockout.
or Attach 1/2 in. TW Setscrew Connector to appropriate knockout in box, place conduit into Connector, and tighten Connector setscrew.
C3565
3. Run plastic tubing through conduit, or remove protector cap from Cable Assembly and attach plastic tubing to Cable Assembly with 5/32 x 1/4 in. or 5/32 x 5/32 in. Barb Couplings.
95-5597—1
4. Wrap Deep Wall Box with 2 in. Duct Tape.
36
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
SOFT COPPER TIE WIRE OR PLASTIC COVERED WIRE TIE
STEEL REINFORCEMENT ROD
TAPED DEEP WALL BOX POSITION SO THAT FRONT OF BOX WILL BE FLUSH WITH WALL
C3165
5. Attach conduit or Cable Assembly to steel reinforcement rods with Soft Copper Tie Wire or Plastic Covered Wire Ties so that front of Deep Wall Box will be flush with wall.
DEEP WALL BOX
STAT BACKPLATE
C3585
7. Back screws out of Deep Wall Box. Hook stat backplate keyhole slots onto backed-out screws. Level stat backplate and tighten screws.
DEEP WALL BOX
STAT BACKPLATE
C3584
6. After concrete is poured and set, cut tape from front of Deep Wall Box. Cut elbow from Cable Assembly, if used. Connect tubing to barbs on stat backplate.
STAT BACKPLATE
C3577
8. Mount stat onto stat backplate.
37
STAT
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
SETSCREWS
STAT BACKPLATE
STAT
TAB (2)
UNI-BIT
1/8 IN. HIGH SPEED DRILL BIT
CORDLESS DRILL
COVER
SETSCREW SLOTS
C4119
9. Hook slots on stat cover over bottom tabs on stat backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
Mullion
Mounting to a standard metal mullion requires the following equipment: — Tape Measure CCT422 (Fig. 41) — Thermostat Mounting Guide Tool CCT690 (Fig. 41) — Fish Chain CCT417 — Wire hook for pulling Fish Chain through wall (see Step 4) — Cordless Drill CCT713 (Fig. 42) — Uni-Bit CCT230 (Fig. 42) — 1/8 in. High-Speed Drill Bit CCT166 (MQG166) (Fig. 42) — No. 8 x 3/4 in. Sheet Metal Screws CCT2306 (MVH2306) — Thermostat Tool CCT735A (MQT735A)
BACK VIEW
TAPE MEASURE
LEVEL
C3168
Fig. 42. Unit-Bit, 1/8 in. High-Speed Drill Bit,
and Cordless Drill.
MULLION
THERMOSTAT MOUNTING GUIDE TOOL
TAPE MEASURE
C
L
1
THERMOSTAT MOUNTING GUIDE TOOL
1—1/2 IN. (38 MM) FROM BOTTOM OF TAPE MEASURE TO
1
CENTER MARK CORRESPONDING TO CENTER OF STAT.
C3151
Fig. 41. Tape Measure and Thermostat Mounting Guide Tool.
95-5597—1
C3192
1. Measure approximate stat location on mullion. Turn Tape Measure sideways and mark center, top, and bottom hole locations according to points on back of Thermostat Mounting Guide Tool.
38
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
WIRE HOOK
C4103
FISH CHAIN
TUBING
STAT BACKPLATE
C4106
7/8 IN. (22 MM)
UNI-BIT
CORDLESS DRILL
C3193
2.
Use Uni-Bit and Cordless Drill to drill 7/8-in. (22-mm) center hole.
1/8 IN. (3.2 MM)
1/8 IN. HIGH SPEED DRILL BIT
4.
Use Fish Chain to fish tubing through center hole.
CORDLESS DRILL
C3194
3. Use 1/8 in. High-Speed Drill Bit to drill 1/8-in. (3.2-mm) top and bottom holes.
5. Attach tubing to barbs on stat backplate.
39
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
STAT BACKPLATE
NO. 8 x 3/4 SHEET METAL SCREW (2)
C4105
6. Position stat backplate against mullion. Level stat backplate. Screw No. 8 x 3/4 in. Sheet Metal Screws through stat backplate keyhole slots into mullion.
STAT BACKPLATE
SETSCREWS
STAT BACKPLATE
STAT
TAB (2)
COVER
SETSCREW SLOTS
C4111
8. Hook slots on stat cover over bottom tabs on stat backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
7. Mount stat to stat backplate.
STAT
C3574
Installation With Surface-Mounted Tubing
Installation with surface-mounted tubing requires the following equipment: — Shallow Wall Plate Assembly 14001615-001/-002 or
14001616-001/-002 (Fig. 43). Includes the following:
• Shallow Wall Plate 14001614-001
• Plaster Ring 14001609-001
• Fitting Finder 14000706-001
NOTE: Shallow Wall Plate Assembly 14001615-001 (one
pipe) or -002 (two pipe) has copper tubing. Assembly 14001616-001 (one pipe) or -002 (two pipe) has 5/32 in. (4 mm) O.D. plastic tubing.
— Tape Measure CCT422 — Wall Mounting Ring 14004458-001 (Fig. 44) — Cordless Hammer Drill CCT712 (MQG773) (Fig. 45) — If wall is block, brick, or concrete:
• Masonry Drill CCT773 (MQG773) (Fig. 45)
• Plastic Screw Anchors CCT2230 (MVH2230) (two per stat)
• No. 8 x 3/4 in. Sheet Metal Screws CCT2306 (MVH2306) (two per stat)
— If wall is drywall, Sheetrock, or plaster:
Thermostat Step/Boring Tool CCT691 (Fig. 45)
Molly Anchors CCT2260 (MVH2260) (two per stat)
— Pocket knife — Thermostat Tool CCT735A (MQT735A)
95-5597—1
40
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
THERMOSTAT STEP/BORING TOOL
CORDLESS HAMMER DRILL
C3190
MASONARY DRILL
SHALLOW WALL PLATE BOTH ENDS ARE REMOVABLE
1
AVAILABLE SEPARATELY
Fig. 43. Shallow Wall Plate Assembly.
PROTECTOR CAP
8 FT (2.5 M)TUBING AND TWIN ELBOW ASSEMBLY
1
FITTING FINDER PRESS TO SNAP IN PLACE
1
PLASTER RING
C3597
REMOVABLE WEB (CUT AWAY WITH POCKET KNIFE)
2-5/16
(59)
1/2
(13)
3-17/32
(90)
C3153
Fig. 45. Masonry Drill, Thermostat Step/Boring Tool,
and Cordless Hammer Drill.
TAPE MEASURE
C3163
Fig. 44. Wall Mounting Ring.
1. Measure and mark stat location on wall.
41
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
3. If wall is: a. Block, brick, or concrete, use Cordless Hammer
Drill and Masonry Drill to drill 3/16-in. (4.8-mm) holes where marked. Tap Plastic Screw Anchors into holes.
STEP
THERMOSTAT STEP/BORING TOOL
SAMPLE ANCHOR LOCATIONS
CORDLESS DRILL
SHALLOW WALL PLATE (ENDS BROKEN OFF)
C3184
2. Break off ends of Shallow Wall Plate. Center Shallow Wall Plate over mark on wall. Mark anchor locations at two opposite corners of Shallow Wall Plate.
3/16 IN. (4.8 MM)
PLASTIC SCREW
MASONRY DRILL BIT
ANCHOR (2)
C3169
b. Drywall, Sheetrock, or plaster, leave protective
sleeve over bore of Thermostat Step/Boring Tool and use Drill and Tool to drill 1/4 in. (6 mm) holes where marked (drill up to step on Tool).
PLASTIC SCREW ANCHOR (2)
SHALLOW WALL PLATE
95-5597—1
CORDLESS HAMMER DRILL
C3196
C3200
4. If wall is: a. If wall is block, brick, or concrete, screw No. 8 x 3/4
in. Sheet Metal Screws through stat backplate and into Plastic Screw Anchors.
42
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
TUBING AND TWIN ELBOW ASSEMBLY
SHALLOW WALL PLATE
WALL MOUNTING RING
C3951
TUBING AND TWIN ELBOW ASSEMBLY
PHILLIPS END
THERMOSTAT STEP/BORING TOOL
CORDLESS HAMMER DRILL
SHALLOW WALL PLATE
C3947
MOLLY ANCHORS (2)
b. If wall is drywall, Sheetrock, or plaster,
disassemble Molly anchors and reassemble through appropriate corner holes of Shallow Wall Plate (see inset). Tighten anchors slightly to secure them to Shallow Wall Plate. Push anchors through holes in wall. With protective sleeve over bore of Thermostat Step/Boring Tool, use Phillips end of Tool to tighten anchors.
STRAIN RELIEF
SHALLOW WALL PLATE
C3950
6. Remove screw from Shallow Wall Plate upper screw receptacle. Push strain relief of Tubing and Twin Elbow Assembly onto screw receptacle. Replace screw, leaving it slightly backed out. Back out bottom screw.
TUBING
BARB COUPLINGS
TUBING AND TWIN ELBOW ASSEMBLY
PROTECTOR CAP
PROTECTOR ASSEMBLY
C3591
5. Remove protector cap and protector assembly from Tubing and Twin Elbow Assembly. Attach tubing.
7. Use pocket knife to cut away web where indicated inside Wall Mounting Ring (see inset). Place Wall Mounting Ring over Shallow Wall Plate and Tubing and Twin Elbow Assembly.
43
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
TUBING AND TWIN ELBOW ASSEMBLY
STAT BACKPLATE
STAT BACKPLATE
STAT
C3593
8. Connect Twin Elbow Connector to barbs on stat backplate.
BACKED-OUT SCREW (2)
STAT BACKPLATE
KEYHOLE SLOTS
C3594
10. Mount stat onto stat backplate.
SETSCREWS
C3581
STAT BACKPLATE
STAT
9. Hook keyhole slots of stat backplate over backed-out screws. Level stat backplate and tighten screws.
95-5597—1
44
TAB (2)
COVER
11.
Hook slots on stat cover over bottom tabs on stat
SETSCREW SLOTS
backplate. Swing stat cover up and over stat. Use Thermostat Tool to raise stat backplate setscrews into setscrew slots on top of cover.
C4113
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
Piping
Figures 46 and 47 show typical one-pipe and two-pipe applications.
STAT
THERMOSTAT TOOL
M
VALVE
C3159
Fig. 46. Typical One-Pipe Application.
STAT
20
15
10
5
0
25
30
TEST THERMOMETER
GAGE PORT NEEDLE
120
140
100
160
80
180
60
200
40
220
20
0
BM
M
VALVE
C3160
Fig. 47. Typical Two-Pipe Application.
CALIBRATION
Tools Required
Calibration requires the following tools, shown in Figure 48: — Thermostat Tool CCT735A (MQT735A) — Gage 305965 (0 to 30 psi [0 to 210 kPa]) — Gage Port Needle CCT729 (MQP729) — Digital Relative Humidity Indicator Pen CCT915 for
humidistats and humidity sensors
— Test Thermometer CCT902 (MQT902) for thermostats
and temperature sensors
GAGE
DIGITAL RELATIVE HUMIDITY INDICATOR PEN
C3929
Fig. 48. Humidistat/Humidity Sensor Calibration Tools.
Humidistat/Humidity Sensor
General
After installing the humidistat, set the humidistat to the desired setpoint and let the system operate long enough to stabilize. The length of time required for stabilization depends on system response time and could be only a few minutes or as long as several hours. Verify that the system has stabilized before checking calibration.
NOTE: Humidistats and humidity sensors are factory
calibrated and should require only a bleed-off check to ensure correct operation. The throttling range is factory set and should not require adjustment under normal operating conditions.
45
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
Figure 49 shows humidistat components.
GAGE TAP
BIAS SPRING
THROTTLING RANGE ADJUSTMENT
SETPOINT INDICATOR
CALIBRATION SCREW
SETPOINT LOCK SCREW
757065 80 85 90 95
SETPOINT LOCKING STOPS
SETPOINT ADJUSTMENT
ELEMENT SPRING
THROTTLING RANGE SCALE
SCALE PLATE
NYLON ELEMENT
C3945
Fig. 49. Humidistat Front View, Cover Off.
Setpoint Lock
To set the minimum and maximum setpoint, refer to Figure 49 and use the following procedure:
1. Loosen setpoint lock screw.
2. Move locking stop to desired position.
3. Tighten setpoint lock screw.
4. Move setpoint adjustment to check stop positioning.
Throttling Range Adjustment (HP970 and HP972)
Use the following procedure if a change in the throttling range (TR) is required:
1. Slide TR indicator to desired setting on TR scale (see table).
2. Recalibrate humidistat (see RECALIBRATION).
Throttling Range Adjustment.
Humidistat
Setpoint
Model (% RH)
Range
Minimum Maximum
Throttling Range
Indication Lines (% RH)
HP970 12-75 3 5 10 15 HP970 65-95 3 5 10 15 HP972 15-75 8 12 20 35
Calibration Check
Direct-Acting Humidistat (HP970A)
1. Use Thermostat Tool to remove humidistat cover.
2. Use Digital Relative Humidity Indicator Pen to measure
actual relative humidity (rh) of space.
3. Turn setpoint indicator down 10 percent below measured rh.
4. Allow humidistat to build up branchline pressure.
5. Turn setpoint indicator up slowly.
6. If humidistat bleeds off at ±3 percent rh of measured
humidity, no further calibration is necessary. Remove Gage and replace humidistat cover.
7. If humidistat does not operate as described in Step 6, recalibrate humidistat (see RECALIBRATION).
Reverse-Acting Humidistats (HP970B and HP972)
1. Use Thermostat Tool to remove humidistat cover.
2. Use Digital Relative Humidity Indicator Pen to measure
actual relative humidity (rh) of space.
3. Turn setpoint indicator up 10 percent above measured rh.
4. Allow humidistat to build up branchline pressure.
5. Turn setpoint indicator down slowly.
6. If humidistat bleeds off at ±3 percent rh of measured
humidity, no further calibration is necessary. Remove Gage and replace humidistat cover.
7. If humidistat does not operate as described in Step 6, recalibrate humidistat (see RECALIBRATION).
Recalibration
CAUTION
Humidistats are extremely sensitive. Handle humidistats carefully during recalibration.
HP970 and HP972
The procedure in this section assumes that a calibration check has been performed (see CALIBRATION CHECK) and that the humidistat has not operated correctly.
1. Start with main air pressure at 18 psi (124 kPa) nominal or system pressure between 13 and 18 psi (91 and 124 kPa).
2. Assemble Gage and Gage Port Needle.
3. Insert Gage Port Needle in humidistat gage tap.
4. Set humidity setpoint indicator at humidity measured
during CALIBRATION CHECK procedure.
5. Turn calibration screw until Gage reads 0 psi.
6. Turn calibration screw in opposite direction until Gage
reads 8 psi (55 kPa) ±1 psi (±7 kPa).
7. Allow 5 to 10 seconds for HP970, 30 to 60 seconds for HP972, for complete response. Setpoint and actual rh should be within acceptable limits.
8. Repeat appropriate procedure under CALIBRATION CHECK to verify calibration.
9. Remove Gage and replace cover.
10. Adjust humidistat setpoint indicator to desired setpoint.
HP971 Humidity Sensor
1. Supply sensor with 18 psi (124 kPa) air through 0.007-in. internal or external restriction. The HP971A1024 (15 to 85% range) also has a 0.005-in. bleed restriction in the output line.
2. Assemble Gage and Gage Port Needle.
3. Insert Gage Port Needle in sensor gage tap (same
location as humidistat gage tap shown in Fig. 49).
4. Allow sensor to acclimate to ambient conditions at least 20 minutes.
5. Use Digital Relative Humidity Indicator Pen to measure actual relative humidity (rh) of space.
6. Adjust calibration screw (same location as humidistat calibration screw shown in Fig. 49) until branchline pressure is below that specified in the following table:
95-5597—1
46
TP970-72, TP970-74, TP9600, AND TP9630 PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
Output Pressure in psi (kPa)
% rh
Range:
15 to 75%
15 to 85%
HP971A1024* 65 to 95%
15 3.0 (21) 3.0 (21) — 20 3.5 (24) 3.9 (27) — 25 4.2 (29) 4.7 (32) — 30 4.9 (34) 5.6 (39) — 35 5.8 (40) 6.4 (44) — 40 6.8 (47) 7.3 (50) — 45 7.8 (54) 8.1 (56) — 50 8.9 (61) 9.0 (62) — 55 10.0 (69) 9.9 (68) — 60 11.1 (77) 10.7 (74) — 65 12.3 (85) 11.6 (80) 3.0 (21) 70 13.6 (94) 12.4 (85) 4.0 (28) 75 15.0 (103) 13.3 (92) 5.3 (37) 80 14.1 (97) 7.5 (52) 85 15.0 (103) 10.3 (71) 90 13.1 (90) 95 15.0 (103)
* Has a 0.007-in. restriction, and a 0.05-in. bleed restriction in
output line.
7. Readjust calibration screw slowly until pressure is
correct ±0.5 psi for the measured ambient humidity.
8. Remove Gage and replace cover.
Thermostat/Temperature Sensor
General
After installing the thermostat, set the thermostat to the desired setpoint and let the system operate long enough to stabilize. The length of time required for stabilization depends on system response time and could be only a few minutes or as long as several hours. Verify that the system has stabilized before checking calibration.
NOTE: Thermostats and temperature sensors are factory
Figure 50 shows thermostat components.
calibrated and should require only a bleed-off check to ensure correct operation. The throttling range is factory set and should not require adjustment under normal operating conditions.
GAGE TAP
BIAS SPRING
Throttling Range Adjustment
1. Use Thermostat Tool to remove cover. Assemble Gage and Gage Port Needle.
2. Insert Gage Port Needle in thermostat gage tap.
3. Slide throttling range (TR) adjustment to desired
position on TR scale.
4. Mechanically check TR by moving setpoint indicator to determine difference in setpoint indication when branchline pressure reads 3 psi (21 kPa) and 13 psi (91 kPa).
NOTE: If required, turn calibration screw to adjust TR into
thermostat range.
5. Reset TR to within ±2 degrees F (±1 degrees C) of required setting.
6. Follow applicable procedure under CALIBRATION CHECK.
Calibration Check
Direct-Acting Thermostat
1. Use Test Thermometer to measure actual temperature of space.
2. Turn setpoint indicator down to 5 degrees F (2.8 degrees C) below room temperature.
3. Wait 5 to 10 seconds (30 to 60 seconds for TP973) to allow thermostat to build up branchline pressure.
4. Turn setpoint indicator up slowly.
5. If thermostat begins to bleed off between 1 degree F
(0.6 degrees C) and 3 degrees F (1.7 degrees C) below room temperature, no recalibration is necessary. If recalibration is needed, see RECALIBRATION.
Reverse-Acting Thermostat
1. Use Test Thermometer to measure actual temperature of space.
2. Turn setpoint indicator up to 5 degrees F (2.8 degrees C) above room temperature.
3. Wait 5 to 10 seconds (30 to 60 seconds for TP973) to allow thermostat to build up branchline pressure.
4. Turn setpoint indicator down slowly.
5. If thermostat begins to bleed off between 1 degree F
(0.6 degrees C) and 3 degrees F (1.7 degrees C) above room temperature, no further calibration is necessary. If recalibration is needed, see RECALIBRATION.
THROTTLING RANGE ADJUSTMENT
SETPOINT INDICATOR
CALIBRATION SCREW
SETPOINT LOCK SCREW
SETPOINT LOCKING STOPS
757065 80 85 90 95
SETPOINT ADJUSTMENT
Fig. 50. Thermostat Front View, Cover Off.
ELEMENT SPRING
THROTTLING RANGE SCALE
SCALE PLATE
NYLON ELEMENT
C3945
Recalibration
The procedures in this section assume that a calibration check has been performed (see CALIBRATION CHECK) and that the thermostat has not operated correctly.
NOTE: Thermostats have either an adhesive paper dot or
an antihum spring, as shown in Figure 50. Verify that either the adhesive paper dot is in place or the antihum spring just touches the throttling plate and is not wedged against it. If the antihum spring needs adjustment, see TP970 Series Pneumatic Thermostats Service Data 75-7134.
CAUTION
Excessive handling during calibration can heat the thermostat and cause an inaccurate reading.
47
95-5597—1
TP970-72, TP970-74, TP9600, AND PNEUMATIC SENSORS, HUMIDISTATS, AND THERMOSTATS
General Procedure (All Thermostats)
1. Use Test Thermometer to measure actual temperature of space.
2. Use Thermostat Tool to remove thermostat cover. Assemble Gage and Gage Port Needle.
3. Insert Gage Port Needle into thermostat gage tap.
4. Turn setpoint adjustment until setpoint indicator reads
measured room temperature.
5. Proceed to appropriate section following.
TP970 and TP9600 Thermostats
1. Turn calibration screw until Gage reads 0 psi.
2. Turn calibration screw in opposite direction until Gage
reads 8 psi (56 kPa) ±1 psi (±7 kPa).
3. Remove Gage. Set thermostat at desired temperature. Replace thermostat cover.
TP971 and TP9610 Thermostats
1. With main air at pressure specified for DAY operation, turn DAY calibration screw until Gage reads 0 psi.
2. Turn calibration screw in opposite direction until Gage reads 8 psi (56 kPa) ±1 psi (±7 kPa).
3. With main air at pressure specified for NITE operation, rotate NITE setpoint dial until setting agrees with measured temperature.
4. Repeat Steps 1 and 2 using NITE calibration screw.
5. Remove Gage. Turn setpoint adjustment until setpoint
indicator reads desired room temperature.
6. Replace thermostat cover.
TP972 and TP9620 Thermostats
1. With main air at pressure specified for SUMMER operation, turn SUMMER calibration screw until Gage reads 0 psi.
2. Turn calibration screw in opposite direction until Gage reads 8 psi (56 kPa) ±1 psi (±7 kPa).
3. With main air at pressure specified for WINTER operation, rotate WINTER setpoint dial until setting agrees with measured temperature.
4. Repeat Steps 1 and 2 using WINTER calibration screw.
4. Remove Gage. Turn setpoint adjustment until setpoint
indicator reads desired room temperature.
5. Replace thermostat cover.
TP973 and TP9630 Room Thermostat
Follow procedure under TP970 AND TP9600 THERMOSTATS.
TP974 Temperature Sensor
Field calibration is not recommended.
Removing Stat from Conventional Backplate
1. Move backplate tab outward (Fig. 51), using Thermostat Tool CCT735A (MQT735A) if necessary.
STAT BACKPLATE
SHALLOW WALL PLATE
STAT BACKPLATE TAB
60
90
80
70
PUSH
C3568
Fig. 51. Loosening Stat Body from
Conventional Backplate.
2. Pull stat body from backplate.
Removing Stat from Quick-Mount Backplate
Use Thermostat Tool CCT735A (MQT735A) and the following procedure to remove a stat from a Quick-Mount backplate:
1. Insert blade of Thermostat Tool between stat body and backplate tab. Push in about 1/4 in. (Fig. 52).
2. Move Tool outward to lever stat body from backplate.
STAT BACKPLATE
STAT BODY
90
1
THERMOSTAT TOOL
STAT BACKPLATE TAB
80
70
60
APPENDIX: BACKPLATES
General
Backplates differ between conventional and Quick-Mount stats. A conventional stat backplate has setscrews at the top and holds the stat body with tabs at the sides. A Quick-Mount stat backplate does not have setscrews and holds the stat body with tabs at the top and sides.
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524
95-5597—1 R.F. Rev. 1-98
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
2
Fig. 52. Loosening Stat Body from
Quick-Mount Stat Backplate.
3. Pull stat body from backplate.
C3567
www.honeywell.com
Loading...