Honeywell TB7220 CommercialPRO Product Information Sheet

TB7220 CommercialPRO™ Programmable Thermostat

FEATURES

• Large, clear display with backlight shows the current and set temperature and time—even in the dark.
• Menu-driven programming make setup effortless.
• Beautiful ergonomic design is smart and sophisticated to match your customers’ lifestyle.
• Real-time clock keeps time during power failures and automatically updates to daylight savings.
• “Saving Changes” notification lets you know when the schedule changes have been saved.
• Change reminders let you know when to replace the batteries.
• Holiday Override options allow you to override the
APPLICATION
The TB7220 COMMERCIALPRO™ 7000 Programmable Thermostat is an effortless, seven-day programmable thermostat that provides universal system compatibility, precise comfort control and is easy-to-program.
program schedule, as desired.
• Speedy same-schedule programming—no need to copy multiple days.
• Armchair programming allows you to remove the thermostat from the wall for programming.
PRODUCT DATA
The TB7220 provides temperature control for gas, oil, electric and heat pumps for up to 2 heat, 2 cool systems.
Contents
Application ........................................................................ 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Wiring ............................................................................... 5
Installer Setup .................................................................. 12
Operation .......................................................................... 17
Troubleshooting (Table 11) ............................................... 22
63-2635—2
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

SPECIFICATIONS

Thermostat Description: See Table 1.
Electrical Ratings: See Table 2.
Temperature:
Ratings:
Operating Ambient:
TB7220: 0°F to 120°F (-18°C to 49°C). C7089U, C7189U: 5% to 95%.
Shipping: -30 °F to 150 °F (-34.4°C to 65.6°C). Display Accuracy: ±1°F (±0.5°C). Setpoint:
Range:
Heating: 40°F to 90°F (4°C to 32°C). Cooling: 50°F to 99°F (10°C to 37°C).
Default Settings: See Table 3.
Humidity Ratings (RH, non-condensing):
TB7220 Thermostat: 5% to 90%. C7089U, C7189U: 5% to 95%.
Table 1. Thermostat Description.
Feature Description
Powering methods
System types (up to 2 heat/2 cool)
Changeover Manual or Auto changeover selectable
System setting Heat-Off-Cool-Auto
Fan setting Auto-On
Terminal
W (Heating) 20 - 30 Vac 0.02 - 1.0A
Y (Cooling) 20 - 30 Vac 0.02 - 1.0A
G (Fan) 20 - 30 Vac 0.02 - 0.60A
A (Economizer/TOD) 20 - 30 Vac 0.02 - 1.0A
Battery only
24 Vac only
24 Vac with battery backup
Gas or electric heat with air conditioning
Warm air, hot water, high-efficiency
furnaces, and heat pumps
Heat only
Heat only with fan
Cool only
Table 2. Electrical Ratings
Voltage
(50/60 Hz) Running Current
Table 3. Energy Star Default Program Settings.
Schedule
Period Time
Occ1 8:00am 70°F (21°C) 75°F (24°C)
Unocc1 10:00pm 55°F (10°C) 85°F (29.5°C)
Occ2
Unocc2
Cycle Rates (at 50% Load):
Heating: Selectable 1 - 12 cycles per hour. Cooling: Selectable 1 - 6 cycles per hour.
Interstage Differential:
Droopless control. Once the first stage is running at 90% load,
the thermostat energizes the second stage.
Cool Indication: Displays “Cool On” when Cool is activated.
Heat Indication: Displays “Heat On” when Heat is activated.
Auxiliary Heat Indication: Displays “Aux. Heat On” when
Auxiliary Heat is activated.
Clock Accuracy: ±1 minute per month.
Finish:
TB7000: Premier White® color. C7189U Wall Mount Remote Indoor Sensor: Premier White®
color.
T7770A Wall Mount Remote Indoor Sensor: Premier White®
color.
Batteries:
Two replaceable AA alkaline batteries: Power thermostat when
24 Vac common is not used.
Non-replaceable lithium battery with ten-year life: Under nor-
mal conditions holds calendar and time settings.
NOTE: Alkaline batteries keep calendar and time if lithium
battery is no longer functional.
Resistance Characteristics of Remote Sensors:
C7089U Outdoor Sensor: 10K ohm NTC. C7189U Remote Indoor Sensor: 10K ohm NTC. C7772 Flush-Mount Remote Indoor Sensor: 20K ohm NTC. T7770A1006 Wall-Mount Remote Indoor Sensor: 20K ohm
NTC.
T7770A3002 Wall-Mount Remote Indoor Sensor: 10K ohm
NTC.
Setpoints
Heat Cool
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2635—2 2
Calibration (TB7220, C7089U, C7189U, T7770A):
No field calibration required.
Mounting Means:
TB7220: Direct wall-mount using mounting screws and
anchors provided. Fits standard vertical or horizontal 2 in. x 4 in. junction box.
C7089U: Mounts outside of living space with mounting clip and
screws provided.
C7189U, T7770A: Mounts directly on the wall using mounting
screws and anchors provided. Fits a vertical 2 x 4 in. junc­tion box.
Cover Plate:
32003796-001 Cover Plate is used to cover marks left on the
wall by the old thermostat.
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
1
LEVEL
BRACKET
LEVEL
5 IN.
(127 MM)
6-7/8 IN. (175 MM)
UP
2
2
Dimensions:
TB7220 Thermostat: See Fig. 1. C7089U Outdoor Sensor Mounting Clip: See Fig. 3. C7189U Remote Indoor Sensor: see Fig. 5. T7770A: See Fig. 4. 32003796-001 Cover Plate: See Fig. 2.
THERMOSTAT
AND WALLPLATE
6 (152)
3-3/4
(95)
1-3/8
(35)
MEDIUM COVER PLATE
8-5/16 IN. (211 MM)
UP
6 IN.
(152 MM)
1
BRACKET FOR MOUNTING ON JUNCTION BOX NOT INCLUDED WITH COVER PLATE
2
USE BOTTOM MOUNTING HOLES.
.
2
LARGE COVER PLATE
2
M13669
Fig. 2. 32003796-001 Cover Plate dimensions in in. (mm).
1-1/2 (38)
Fig. 1. TB7220 Thermostat
dimensions in in. (mm).
M13668
M4488
Fig. 3. C7089U Outdoor Sensor Mounting Clip
dimensions in in. (mm).
3 63-2635—2
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
KNOCKOUTS FOR EUROPEAN APPLICATIONS
2-3/8
(60)
STANDARD
UTILITY
CONDUIT BOX (2 X 4) MOUNTING
HOLES
5-1/16
(128)
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.

Select Thermostat Location

Select a location for the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 6.
2-3/8 (60)
3-3/16 (80)
15/16
(23)
M22936
Fig. 4. T7770A dimensions in in. (mm).
4-5/8 (117)
1-1/8
(29)
M4465
2-3/4 (70)
FRONT VIEW SIDE VIEW
Fig. 5. C7189U Indoor Sensor dimensions in in. (mm).
NO
M22258
NO
NO
YES
5 FEET
[1.5 METERS]
Fig. 6. Select thermostat location.
Do not install the thermostat where it can be affected by: — Drafts or dead spots behind doors and in corners. — Hot or cold air from ducts. — Radiant heat from sun or appliances. — Concealed pipes and chimneys. — Unheated (uncooled) areas such as an outside wall behind
the thermostat.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.
INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
63-2635—2 4

Separate Wallplate from Thermostat

1. Separate the wallplate from the thermostat. See Fig. 7.
WALLPLATE
WIRE HOLE
THERMOSTAT
M22267
Fig. 7. Separate wallplate from thermostat.
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

Install Wallplate (See Fig. 8)

Mount the thermostat horizontally on the wall:
1. Pull the wires through the wire hole on the wallplate.
2. Position the wallplate on the wall with the arrow pointing
up. Level the wallplate for appearance only.
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and drill two 3/16 in.
holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 in. holes. Tap the wall anchors (provided) into the drilled holes until flush with the wall.
5. Pull the wires through the wire hole on the wallplate and position the wallplate over the wall anchors.
6. Insert the mounting screws into the wall anchors and tighten.
WALL
WIRES THROUGH WALL AND WIRE SLOT
WALL ANCHORS (2)
MOUNTING HOLES
NOTES:
Refer to Table 5 for terminal designation
descriptions.
See Fig. 12 through 21 for wiring diagrams for
specific equipment applications.
1. Select set of terminal identifications that correspond to your system type (conventional or heat pump). See Fig. 9.
HEAT PUMP
CONVENTIONAL
1
SCREW
W2
Y2
S1 S2
W1
Y2
A
S1
S2
M13663
C
G
Y
O/B
RC
R
1
C G Y W RC R
TERMINALS
FACTORY INSTALLED JUMPER.
Fig. 9. Terminal identifications for system type.
2. Loosen screw terminals used for the application.
3. Insert the wires into the terminal block and tighten each
screw terminal. See Fig. 10.
MOUNTING SCREWS (2)
Fig. 8. Install wallplate.
WIRING
CAUTION
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
IMPORTANT
— All wiring must agree with applicable codes,
ordinances and regulations.
— Use 18 gauge thermostat wire. Shielded cable is not
required.
M13665
M13666
WIRE HOLE
Fig. 10. Insert wires into terminal block.
4. Push excess wire back into the wall opening and restrict
wires to the shaded area. See Fig. 11.
5. Plug the wall opening with nonflammable insulation to prevent drafts from affecting the thermostat.
5 63-2635—2
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
WIRE
WALL OPENING
SHADED AREA
WALLPLATE
M22266
Fig. 11. Restrict wires to shaded area of wire hole.
Table 4. Wiring Diagrams.
System Type
Wallplate Terminal
Identifications
Wiring Diagram
Standard Heat/Cool Conventional 12, 13
Heat Only Conventional 14
Cool only Conventional 15
Standard Multistage
Conventional 16, 17
up to 2 Heat/2 Cool
Heat Pump
Heat Pump 18, 19
(No Auxiliary Heat)
Heat Pump
Heat Pump 20, 21
(with Auxiliary Heat)
Multiple T7770A
26, 27, 28
Sensors
Multiple C7189U
—29
Sensors
Figure
Table 5. Terminal Designation Descriptions.
Terminal
Designation Description
Rc (see Note 1)
R (see Note 1)
Power for cooling—connect to secondary side of cooling system transformer.
Power for heating—connect to secondary side of heating system transformer.
Y Compressor output.
C (see Note 2)
Common wire from secondary side of cooling system transformer.
W Heat relay.
GFan relay.
W2 Second stage heat relay.
Y2 Second stage cooling.
O/B
Changeover valve for heat pumps.
(see Note 3)
A (see Note 4)
S1
Economizer/Time-Of-Day (TOD) output— powered via R terminal.
Optional outdoor or indoor remote sensor.
(See Note 5)
S2
Optional outdoor or indoor remote sensor.
(See Note 5)
NOTES:
1. When used in a single-transformer system, leave metal jumper wire in place between Rc and R. If used on a two-transformer system, remove metal jumper wire between Rc and R.
2. Common wire is optional when thermostat is used with batteries. When using separate transformers for heating and cooling, the common must come from the cooling transformer.
3. If thermostat is configured for a heat pump in the Installer Setup, configure changeover valve for cool (O-factory setting) or heat (B).
4. Reference economizer literature for wiring details. When set for economizer operation, the A terminal provides the occupancy signal. (Power indicates occupied.)
5. Sensor wires must have a cable separate from the thermostat control cable.
63-2635—2 6
Terminal “A” Wiring Details for Economizers
— Wire the A terminal to the W7212 “N” terminal, or the
W7459 “TR” terminal.
— When using dual transformers at the thermostat, the cooling
transformer must power the economizer.
— The A signal is powered from the R terminal and energizes
the economizer to signal occupied status and drive the damper to the set minimum position.

Conventional System Wiring

TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
3
1
L1 (HOT)
24 VAC
L2
HEAT RELAY
COMPRESSOR CONTACTOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
C G Y W RC
2
R
W2
Y2
A S1 S2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
ECONOMIZER
M23011
Fig. 12. Typical wiring of single transformer 1H/1C system.
1
L1 (HOT)
L2
COOLING
TRANSFORMER
1
L1 (HOT)
L2
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
REMOVE FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY.
24 VAC
FAN RELAY
COMPRESSOR CONTACTOR
24 VAC
HEAT RELAY
3
C G Y W RC
2
R
W2
Y2
A S1 S2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
ECONOMIZER
M23012
1
L1 (HOT)
L2
24 VAC
HEAT RELAY
ECONOMIZER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
3
C G Y W RC
2
R
W2
Y2
A S1 S2
OUTDOOR/INDOOR
TEMPERATURE
Fig. 14. Typical hookup of heat-only system.
2
3
C G Y W RC R
ECONOMIZER
W2
Y2
A S1 S2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
L1 (HOT)
24 VAC
L2
COMPRESSOR CONTACTOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
Fig. 15. Typical hookup of cool-only system.
SENSOR
M23013
M23015
Fig. 13. Typical hookup of dual transformer 1H/1C system.
7 63-2635—2
TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
1
L1 (HOT)
24 VAC
L2
COOL RELAY 1
HEAT RELAY 1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
COOL RELAY 2
FAN RELAY
3
C G Y W RC
2
R
W2
Y2
A S1 S2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT RELAY 2
ECONOMIZER
M23016
Fig. 16. Typical hookup of single transformer multistage
system (up to 2H/2C).

Heat Pump System Wiring

3
1
L1 (HOT)
L2
TRANSFORMER
TRANSFORMER
24 VAC
COOLING
FAN RELAY
1
L1 (HOT)
L2
HEATING
1
2
3
COOL RELAY 1
24 VAC
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
REMOVE FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY.
HEAT RELAY 1
C G Y W RC
2
R
COOL RELAY 2
W2
Y2
A S1 S2
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT RELAY 2
ECONOMIZER
M23017
Fig. 17. Typical hookup of dual transformer multistage
system (up to 2H/2C).
L1 (HOT)
2
FAN RELAY
3
OUTDOOR/INDOOR
ECONOMIZER
W1
Y2
A
S1
S2
TEMPERATURE
SENSOR
5
M23018
24 VAC
L2
1
CHANGEOVER VALVE
COMPRESSOR CONTACTOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
3
IS OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
C
G
Y
O/B
4
RC
R
Fig. 18. Typical hookup of single-stage heat pump with no
auxiliary heat (1H/1C).
L1 (HOT)
24 VAC
L2
1
FAN RELAY
COMPRESSOR 1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
3
IS OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
C
G
Y
O/B
4
RC
R
CHANGEOVER VALVE
2
COMPRESSOR 2
3
OUTDOOR/INDOOR
W1
Y2
A
S1
S2
TEMPERATURE
SENSOR
ECONOMIZER
5
M23019
Fig. 19. Typical hookup of multistage heat pump with no
auxiliary heat (2H/2C).
63-2635—2 8
Loading...
+ 16 hidden pages