TB7200 Series Communicating
TB7200 Series
Thermostat
TB7200 Series
Thermostat with
Occupancy Sensor
Zone Thermostats
SPECIFICATION DATA
present or not. This advanced occupancy functionality
provides advantageous energy savings during occupied hours
without sacrificing occupant comfort. All thermostats are PIR
ready and can be ordered with or without Honeywell
occupancy sensor. The occupancy sensor cover is available to
order separately if a PIR is needed at a later time.
FEATURES
• Available in BACnet MS/TP and ZigBee wireless
protocols
• Backlit LCD display with dedicated function menu keys
for simple operation
• Fully integrated advanced occupancy functionality
with a PIR cover provides energy savings opportunity
on select models; all other models are PIR ready and
can have an optional occupancy sensor cover added at
any time
• Pre-configured sequences of operation means one
model meets more application needs
APPLICATION
The TB7200 Series PI thermostat family is specifically
designed for zoning applications. The TB7200 Series are
communicating thermostats with models available in BACnet®
MS/TP and ZigBee® wireless mesh protocols and can be
easily integrated into a WEBs-AX building automation system
based on the Niagara
Typical applications include local hydronic reheat valve control
and pressure dependent VAV with or without local reheat.
Accurate temperature control is achieved due to the product’s
PI proportional control algorithm, which virtually eliminates
temperature offset associated with traditional, differentialbased thermostats. Models are available for 3 point floating
and analog 0 to 10 Vdc control. In addition remote room
sensing is available.
Thermostats equipped with an occupancy sensor cover
provide advanced active occupancy logic, which will
automatically switch occupancy levels from Occupied to
Stand-By and Unoccupied as required by local activity being
AX
® platform.
• Password protection to minimize parameter tampering
• Four levels of keypad lockout to limit access to change
user parameters such as setpoints, system mode, etc.
• Available in 24 Vac on/off, floating or 0-10 Vdc analog
control to meet advanced applications requirements
• Three configurable inputs for monitoring and
advanced functions
• SPST auxiliary output that can be used for lighting or
reheat
• All wiring connections are made to removable terminal
blocks simplifying installation
More Information
To learn about additional products in this family visit
http://customer.honeywell.com.
• TB7600 Series Communicating RTU/Heat Pump
Thermostats (Form No. 63-2706)
• TB7300 Series Communicating Fan Coil Unit Thermostats
Specification Data (Form No. 63-2709)
• Sensors Product Overview Brochure (Form No. 63-9285)
63-2708-04
TB7200 SERIES COMMUNICATING ZONE THERMOSTATS
ON/OFF THERMOSTATS WASTE ENERGY
SETPOINT
(COMFORT TEMPERATURE)
TIME
PI ELECTRONIC CONTROLS DO NOT WASTE ENERGY
TEMPERATURE
M16927
TB7200 Series Models
Occupancy
Product Number Description Outputs
Sensor
BACnet Models
TB7200C5014B Modulating with Reheat 2 floating or on/off + 1 Aux Ready
TB7200C5514B Modulating with Reheat 2 floating or on/off + 1 Aux Ye s
TB7200F5014B Modulating with Reheat 2 0-10Vdc + 1 Aux Ready
TB7200F5514B Modulating with Reheat 2 0-10Vdc + 1 Aux Ye s
Wireless Models
TB7200C5014W Modulating with Reheat 2 floating or on/off + 1 Aux Ready
TB7200C5514W Modulating with Reheat 2 floating or on/off + 1 Aux Yes
TB7200F5014W Modulating with Reheat 2 0-10Vdc + 1 Aux Ready
TB7200F5514W Modulating with Reheat 2 0-10Vdc + 1 Aux Yes
Accessories
TB-PIR-ZN Zone Occupancy Sensor Cover
TB-RA-1014 Wireless Remote Antenna Base
TB-RP5000W Wireless Repeater for TB7XXX Series Wireless
Thermostats
TBST-5014W ZigBee Wireless Survey Toolkit
TB-VWG-APP-1014 TB7XXX Series Wireless Communication Card
TB-WALL-1014 Room Sensor 10K NTC Type 2
TB-WALLOVR-1014 Room Sensor with Override 10K NTC Type 2
1Thermostats ordered without an occupancy sensor cover can be retrofitted with the cover at a later time if required
1
Theory of Operation
The TB7200 uses a proprietary adaptive logic algorithm to
control the space temperature. This algorithm controls the
heating / air conditioning system to minimize overshoot while
still providing comfort. It provides exceptional accuracy due to
its unique PI time proportioning control algorithm, which
virtually eliminates temperature offset associated with
traditional, differential-based on/off thermostats.
Fig. 1. On/Off mechanical control vs. PI electronic control.
63-2708—04 2