Honeywell TB7100A1000 MultiPRO Product Information Sheet

TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat
FOR CONVENTIONAL, HEAT PUMP, FAN COIL AND PTAC SYSTEMS
PRODUCT DATA

FEATURES

• Large, clear display with backlight shows the current and set temperature and time—even in the dark.
• Menu-driven programming make setup effortless.
• Beautiful ergonomic design is smart and sophisticated to match your customers’ lifestyle.
• Real-time clock keeps time during power failures and automatically updates to daylight savings.
• “Saving Changes” notification lets you know when the schedule changes have been saved.
• Change reminders let you know when to replace the batteries.
• Holiday Override options allow you to override the

APPLICATION

The TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat is an effortless, seven-day programmable or non­programmable thermostat that provides universal system compatibility, precise comfort control and is easy-to-program.
The TB7100 provides temperature control for gas, oil, electric, heat pumps, PTACs, and fan coil equipment for the following types of applications:
— 1H/1C conventional — Up to 2H/1C heat pump — 4 pipe fan coil (3 fan speeds) — 2 pipe fan coil (3 fan speeds) — 2 pipe fan coil with Auxiliary Heat (3 fan speeds) — PTAC (Hi, Lo fan speed)
program schedule, as desired.
• Speedy same-schedule programming—no need to copy multiple days.
• Armchair programming allows you to remove the thermostat from the wall for programming.
• Programmable or non-programmable modes.
• Remote setback input for occupancy sensors or timeclocks.
• VersaSpeed™ fan ramping algorithm and fan reset algorithm (fan coil and PTAC applications).
• Up to 3 fan speeds for fan coil and 2 speeds for PTAC applications.
• Remote indoor air sensing option (20K ohm or 10K ohm).
Contents
Application ........................................................................ 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Wiring ............................................................................... 5
Installer Setup .................................................................. 11
Operation .......................................................................... 17
Troubleshooting (Table 12) ............................................... 23
63-2675-01
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT

SPECIFICATIONS

Thermostat Description: See Table 1.
Electrical Ratings: See Table 2.
Temperature:
Ratings:
Operating Ambient:
TB7100: 0°F to 120°F (-18°C to 49°C). C7189U: 5% to 95%.
Shipping: -30 °F to 150 °F (-34.4°C to 65.6°C). Display Accuracy: ±1°F (±0.5°C). Setpoint:
Range:
Heating: 40°F to 90°F (4°C to 32°C). Cooling: 50°F to 99°F (10°C to 37°C).
Default Settings: See Table 3.
Humidity Ratings (RH, non-condensing):
TB7100: 5% to 90%. C7189U: 5% to 95%.
Table 1. Thermostat Description.
Feature Description
Powering methods
System types Conventional (1 Heat, 1 Cool Stages)
Changeover Manual or Auto changeover selectable
System setting Heat-Off-Cool-Auto
Fan setting Auto-On
Fan Speeds Low, Medium, High
Remote Setback
Fan Ramping Algorithm
Battery only
24 Vac only
24 Vac with battery backup
Heat Pump (up to 2 Heat,
2 Pipe Fan Coil
2 Pipe Fan Coil with Auxiliary Heat
4 Pipe Fan Coil
PTAC (up to 2 Heat, 1 Cool)
Remote Setback Input for occupancy sensor or DDC Setback
VersaSpeed™ Fan Ramping Algorithm for Automatic Fan Speed Selection (fan coil and PTAC applications)
1 Cool Stages)
Table 2. Electrical Ratings
Voltage
Ter min al
W (Heating) 20 - 30 Vac 0.02 - 1.0A
Y (Cooling) 20 - 30 Vac 0.02 - 1.0A
G (Fan), G
Schedule
Period Time
Occ1 8:00am 70°F (21°C) 75°F (24°C)
Unocc1 10:00pm 55°F (10°C) 85°F (29.5°C)
Occ2
Unocc2
Cycle Rates (at 50% Load):
Heating: Selectable 1 - 12 cycles per hour. Cooling: Selectable 1 - 6 cycles per hour.
Interstage Differential:
Droopless control. Once the first stage is running at 90% load,
the thermostat energizes the second stage.
Cool Indication: Displays “Cool On” when Cool is activated.
Heat Indication: Displays “Heat On” when Heat is activated.
Auxiliary Heat Indication: Displays “Aux. Heat On” when
Auxiliary Heat is activated.
Clock Accuracy: ±1 minute per month.
Finish:
TB7100: Premier White® color. C7189U Wall Mount Remote Indoor Sensor: Premier White®
color.
TR21 Wall Mount Remote Indoor Sensor: Premier White®
color.
Batteries:
Two replaceable AA alkaline batteries: Power thermostat
when 24 Vac common is not used.
Non-replaceable lithium battery with ten-year life: Under nor-
mal conditions holds calendar and time settings.
, G
2
3
Table 3. Energy Star Default Program Settings.
(50/60 Hz) Running Current
20 - 30 Vac 0.02 - 0.60A
Setpoints
Heat Cool
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2675—01 2
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
NOTE: Alkaline batteries keep calendar and time if lithium
battery is no longer functional.
Resistance Characteristics of Remote Sensors:
C7189U Remote Indoor Sensor: 10K ohm NTC. C7772 Flush-Mount Remote Indoor Sensor: 20K ohm NTC. TR21 Wall-Mount Remote Indoor Sensor: 20K ohm NTC. TR21-A Wall-Mount Remote Indoor Sensor: 10K ohm NTC.
Calibration (TB7100, C7089U, C7189U, T7770A):
No field calibration required.
Mounting Means:
TB7100: Direct wall-mount using mounting screws and
anchors provided. Fits standard vertical or horizontal 2 in. x 4 in. junction box.
C7189U, TR21: Mounts directly on the wall using mounting
screws and anchors provided. Fits a vertical 2 x 4 in. junc­tion box.
Cover Plate:
32003796-001 Cover Plate is used to cover marks left on the
wall by the old thermostat.
Dimensions:
TB7100 Thermostat: See Fig. 1. C7189U Remote Indoor Sensor: see Fig. 4. TR21 Remote Indoor Sensor: See Fig. 3. 32003796-001 Cover Plate: See Fig. 2.
LEVEL
1
BRACKET
(152 MM)
6 IN.
LEVEL
5 IN.
(127 MM)
6-7/8 IN. (175 MM)
UP
2
MEDIUM COVER PLATE
8-5/16 IN. (211 MM)
UP
2
2
2
3-3/4
(95)
6 (152)
Fig. 1. TB7100 Thermostat
dimensions in in. (mm).
THERMOSTAT
AND WALLPLATE
1-3/8
(35)
M13668
LARGE COVER PLATE
1
BRACKET FOR MOUNTING ON JUNCTION BOX NOT INCLUDED WITH COVER PLATE
2
USE BOTTOM MOUNTING HOLES.
.
M13669
Fig. 2. 32003796-001 Cover Plate dimensions in in. (mm).
3 (76)
4-9/16
(116)
7/8 (22)
M27480
Fig. 3. TR21 indoor sensor dimensions in in. (mm).
3 63-2675—01
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
4-5/8 (117)
1-1/8
(29)
M4465
2-3/4 (70)
FRONT VIEW SIDE VIEW
Fig. 4. C7189U Indoor Sensor dimensions in in. (mm).
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.
NO
M22258
NO
NO
YES
5 FEET
[1.5 METERS]
Fig. 5. Select thermostat location.
Do not install the thermostat where it can be affected by: — Drafts or dead spots behind doors and in corners. — Hot or cold air from ducts. — Radiant heat from sun or appliances. — Concealed pipes and chimneys. — Unheated (uncooled) areas such as an outside wall behind
the thermostat.

Separate Wallplate from Thermostat

1. Separate the wallplate from the thermostat. See Fig. 6.
WALLPLATE

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.

Select Thermostat Location

Select a location for the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 5.
WIRE HOLE
THERMOSTAT
M22267
Fig. 6. Separate wallplate from thermostat.

Install Wallplate (See Fig. 7)

Mount the thermostat horizontally on the wall:
1. Pull the wires through the wire hole on the wallplate.
2. Position the wallplate on the wall with the arrow pointing
up. Level the wallplate for appearance only.
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and drill two 3/16 in.
holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 in. holes. Tap the wall anchors (provided) into the drilled holes until flush with the wall.
5. Pull the wires through the wire hole on the wallplate and position the wallplate over the wall anchors.
6. Insert the mounting screws into the wall anchors and tighten.
63-2675—01 4
WALL
SC
WIRES THROUGH WALL AND WIRE SLOT
WALL ANCHORS (2)
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
MOUNTING HOLES
MOUNTING SCREWS (2)
Fig. 7. Install wallplate.

WIRING

CAUTION
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
IMPORTANT
— All wiring must agree with applicable codes,
ordinances and regulations.
— Use 18 gauge thermostat wire. Shielded cable is not
required.
NOTES:
Refer to Table 5 for terminal designation
descriptions.
See Fig. 11 through 17 for wiring diagrams for
specific equipment applications.
M13665
M13666
WIRE HOLE
Fig. 9. Insert wires into terminal block.
4. Push excess wire back into the wall opening and restrict
wires to the shaded area. See Fig. 10.
5. Plug the wall opening with nonflammable insulation to prevent drafts from affecting the thermostat.
WIRE
WALL OPENING
SHADED AREA
WALLPLATE
M22266
Fig. 10. Restrict wires to shaded area of wire hole.
1. Select set of terminal identifications that correspond to
your system type (conventional or heat pump). See Fig. 8.
REW
TERMINALS
C
G
Y
O/B
RC
R
Fig. 8. Terminal identifications for system type.
W1
G2
G3
S1
S2
M27415
2. Loosen screw terminals used for the application.
3. Insert the wires into the terminal block and tighten each
screw terminal. See Fig. 9.
Table 4. Wiring Diagrams.
Wiring Diagram
System Type
Figure
Standard Heat/Cool (1H/1C) 11, 12
Heat Only 13
Heat Only with Fan 14
Cool only 15
Heat Pump (No Auxiliary Heat) (1H/1C) 16
Heat Pump (with Auxiliary Heat) (2H/1C) 17
4 Pipe Fan Coil 18
2 Pipe Fan Coil 19
2 Pipe Fan Coil with aux. heat 20
PTAC 1H/1C (High speed, Low speed fan) 21
PTAC 2H/1C (High speed, Low speed fan) 22
Multiple TR21 Sensors 25, 26, 27
Multiple C7189U Sensors 28
5 63-2675—01
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 5. Terminal Designation Descriptions. NOTES:
Terminal
Designation Description
Rc (see Note 1)
R (see Note 1)
Power for cooling—connect to secondary side of cooling system transformer.
Power for heating—connect to secondary side of heating system transformer.
Y Compressor output.
C (see Note 2)
Common wire from secondary side of cooling system transformer.
W1 Heat relay. Auxiliary heat relay for heat pump,
PTAC.
G Fan relay. Low fan speed for fan coil and PTAC.
G2 Medium fan speed. Fan coil.
G3 High fan speed. Fan coil and PTAC.
O/B
Changeover valve for heat pumps.
(see Note 3)
S1 (See Note 4)
S2 (See Note 4)
Indoor remote sensor, remote setback, or changeover input.
Indoor remote sensor, remote setback, or changeover input.

Conventional System Wiring

1. When used in a single-transformer system, leave metal jumper wire in place between Rc and R. If used on a two-transformer system, remove metal jumper wire between Rc and R.
2. Common wire is optional when thermostat is used with batteries. When using separate transformers for heating and cooling, the common must come from the cooling transformer.
3. If thermostat is configured for a heat pump in the Installer Setup, configure changeover valve for cool (O-factory setting) or heat (B).
4. Sensor wires must have a cable separate from the thermostat control cable.
1
L1 (HOT)
24 VAC
L2
COMPRESSOR CONTACTOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
C G Y
O/B
RC
R
FAN RELAY
HEAT RELAY
2
3
INDOOR TEMPERATURE
SENSOR/REMOTE
W1 G2 G3
S1 S2
SETBACK
M27416
Fig. 11. Typical wiring of single transformer 1H/1C system.
COMPRESSOR CONTACTOR
FAN RELAY
1
L1 (HOT)
24 VAC
L2
COOLING
TRANSFORMER
L1
1
(HOT)
24 VAC
L2
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
REMOVE FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY.
C G Y
O/B
RC
R
HEAT RELAY
3
2
INDOOR TEMPERATURE
SENSOR/REMOTE
W1 G2 G3
S1 S2
SETBACK
M27417
Fig. 12. Typical hookup of dual transformer 1H/1C system.
63-2675—01 6
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
1
L1 (HOT)
L2
24 VAC
C G Y
O/B
RC
R
HEAT RELAY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
3
W1 G2 G3
S1
2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
S2
M27418
Fig. 13. Typical hookup of heat-only system.
1
L1 (HOT)
L2
24 VAC
C G
Y
O/B
RC
R
HEAT RELAY
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
3
W1 G2 G3
S1
2
INDOOR TEMPERATURE
SENSOR/REMOTE
S2
SETBACK
M27419
Fig. 14. Typical hookup of heat-only system with fan.
1
L1 (HOT)
L2
24 VAC
C G Y
O/B
RC
R
COMPRESSOR CONTACTOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
3
W1 G2 G3
S1
2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
S2
M27420
Fig. 15. Typical hookup of cool-only system.

Heat Pump System Wiring

L1 (HOT)
2
FAN RELAY
2
3
INDOOR TEMPERATURE
3
INDOOR TEMPERATURE
AUXILIARY HEAT RELAY
W1 G2 G3
S1 S2
SENSOR/REMOTE
SETBACK
W1 G2 G3
S1 S2
SENSOR/REMOTE
SETBACK
5
M27421
5
M27422
24 VAC
L2
1
CHANGEOVER VALVE
COMPRESSOR CONTACTOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
3
OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
C
G
Y
O/B
4
RC
R
Fig. 16. Typical hookup of single-stage heat pump with no
auxiliary heat (1H/1C).
L1 (HOT)
24 VAC
L2
1
COMPRESSOR CONTACTOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION
3
IS OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
C
G
Y
O/B
4
RC
R
CHANGEOVER VALVE
Fig. 17. Typical hookup of single-stage heat pump with
auxiliary heat (2H/1C).
7 63-2675—01
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT

Fan Coil System Wiring

1
1
L1 (HOT)
24 VAC
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
C G Y
O/B
RC
2
R
HEAT RELAY
COOLING RELAY
LOW FAN RELAY
MEDIUM FAN RELAY
3
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
HIGH FAN RELAY
W1 G2 G3
S1 S2
M27423
L1 (HOT)
24 VAC
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
Fig. 20. Typical wiring of 2 pipe fan coil without reheat.
C G Y
O/B
RC
2
R
TWO PIPE HEAT/COOL RELAY
LOW FAN RELAY
MEDIUM FAN RELAY
3
INDOOR TEMPERATURE
SETBACK/CHANGEOVER
W1 G2 G3
S1 S2
SENSOR/REMOTE
PIPE SENSOR
HIGH FAN RELAY
M27425
Fig. 18. Typical wiring of 4 pipe fan coil.
1
L1 (HOT)
24 VAC
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
C G Y
O/B
RC
2
R
TWO PIPE HEAT/COOL RELAY
LOW FAN RELAY
MEDIUM FAN RELAY
AUXILIARY HEAT RELAY
3
INDOOR TEMPERATURE
SETBACK/CHANGEOVER
W1 G2 G3
S1 S2
SENSOR/REMOTE
PIPE SENSOR
HIGH FAN RELAY
M27424
Fig. 19. Typical wiring of 2 pipe fan coil with reheat.

PTAC System Wiring

L1 (HOT)
2
(1H/1C).
3
W1 G2 G3
S1 S2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
HIGH FAN RELAY
5
M27426
24 VAC
L2
1
CHANGEOVER VALVE
COMPRESSOR CONTACTOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
3
OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
C
G
Y
O/B
4
RC
R
LOW FAN RELAY
Fig. 21. Typical hookup of PTAC with HI and LO fan speeds
63-2675—01 8
Loading...
+ 16 hidden pages