Honeywell TB7100A1000 User Manual

63-2675-03
TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat
FOR CONVENTIONAL, HEAT PUMP, FAN COIL AND PTAC SYSTEMS
PRODUCT DATA

FEATURES

• Large, clear display with backlight shows the current and set temperature and time—even in the dark.
• Menu-driven programming make setup effortless.
• Beautiful ergonomic design is smart and sophisticated to match your customers’ lifestyle.
• Real-time clock keeps time during power failures and automatically updates to daylight savings.
• “Saving Changes” notification lets you know when the schedule changes have been saved.
• Change reminders let you know when to replace the batteries.
• Holiday Override options allow you to override the

APPLICATION

The TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat is an effortless, seven-day programmable or non­programmable thermostat that provides universal system compatibility, precise comfort control and is easy-to-program.
The TB7100 provides temperature control for gas, oil, electric, heat pumps, PTACs, and fan coil equipment for the following types of applications:
— 1H/1C conventional — Up to 2H/1C heat pump — 4 pipe fan coil (3 fan speeds) — 2 pipe fan coil (3 fan speeds) — 2 pipe fan coil with Auxiliary Heat (3 fan speeds) — PTAC (Hi, Lo fan speed)
program schedule, as desired.
• Speedy same-schedule programming—no need to copy multiple days.
• Armchair programming allows you to remove the thermostat from the wall for programming.
• Programmable or non-programmable modes.
• Remote setback input for occupancy sensors or timeclocks.
• VersaSpeed™ fan ramping algorithm and fan reset algorithm (fan coil and PTAC applications).
• Up to 3 fan speeds for fan coil and 2 speeds for PTAC applications.
• Remote indoor air sensing option (20K ohm or 10K ohm).
Contents
Application ........................................................................ 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Wiring ............................................................................... 5
Installer Setup .................................................................. 11
Operation .......................................................................... 17
Troubleshooting (Table 12) ............................................... 23
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT

SPECIFICATIONS

Thermostat Description: See Table 1.
Electrical Ratings: See Table 2.
Temperature:
Ratings:
Operating Ambient:
TB7100: 0°F to 120°F (-18°C to 49°C). C7189U: 5% to 95%.
Shipping: -30 °F to 150 °F (-34.4°C to 65.6°C). Display Accuracy: ±1°F (±0.5°C). Setpoint:
Range:
Heating: 40°F to 90°F (4°C to 32°C). Cooling: 50°F to 99°F (10°C to 37°C).
Default Settings: See Table 3.
Humidity Ratings (RH, non-condensing):
TB7100: 5% to 90%. C7189U: 5% to 95%.
Table 1. Thermostat Description.
Feature Description
Powering methods
System types Conventional (1 Heat, 1 Cool Stages)
Changeover Manual or Auto changeover selectable
System setting Heat-Off-Cool-Auto
Fan setting Auto-On
Fan Speeds Low, Medium, High
Remote Setback
Fan Ramping Algorithm
Battery only
24 Vac only
24 Vac with battery backup
Heat Pump (up to 2 Heat,
2 Pipe Fan Coil
2 Pipe Fan Coil with Auxiliary Heat
4 Pipe Fan Coil
PTAC (up to 2 Heat, 1 Cool)
Remote Setback Input for occupancy sensor or DDC Setback
VersaSpeed™ Fan Ramping Algorithm for Automatic Fan Speed Selection (fan coil and PTAC applications)
1 Cool Stages)
Table 2. Electrical Ratings
Voltage
Ter min al
W (Heating) 20 - 30 Vac 0.02 - 1.0A
Y (Cooling) 20 - 30 Vac 0.02 - 1.0A
G (Fan), G
Table 3. Energy-saving Default Program Settings.
Schedule
Period Time
Occ1 8:00am 70°F (21°C) 75°F (24°C)
Unocc1 10:00pm 55°F (10°C) 85°F (29.5°C)
Occ2
Unocc2
Cycle Rates (at 50% Load):
Heating: Selectable 1 - 12 cycles per hour. Cooling: Selectable 1 - 6 cycles per hour.
Interstage Differential:
Droopless control. Once the first stage is running at 90% load,
the thermostat energizes the second stage.
Cool Indication: Displays “Cool On” when Cool is activated.
Heat Indication: Displays “Heat On” when Heat is activated.
Auxiliary Heat Indication: Displays “Aux. Heat On” when
Auxiliary Heat is activated.
Clock Accuracy: ±1 minute per month.
Finish:
TB7100: Premier White® color. C7189U Wall Mount Remote Indoor Sensor: Premier White®
color.
TR21 Wall Mount Remote Indoor Sensor: Premier White®
color.
Batteries:
Two replaceable AA alkaline batteries: Power thermostat
when 24 Vac common is not used.
Non-replaceable lithium battery with ten-year life: Under nor-
mal conditions holds calendar and time settings.
, G
2
3
(50/60 Hz) Running Current
20 - 30 Vac 0.02 - 0.60A
Setpoints
Heat Cool
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2675—03 2
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
LARGE COVER PLATE
BRACKET
LEVEL
LEVEL
MEDIUM COVER PLATE
UP
6-7/8 IN. (175 MM)
UP
8-5/16 IN. (211 MM)
6 IN.
(152 MM)
M13669
BRACKET FOR MOUNTING ON JUNCTION BOX NOT INCLUDED WITH COVER PLATE
.
1
USE BOTTOM MOUNTING HOLES.
2
2
2
5 IN.
(127 MM)
1
2
2
3 (76)
M27480
4-9/16
(116)
7/8 (22)
NOTE: Alkaline batteries keep calendar and time if lithium
battery is no longer functional.
Resistance Characteristics of Remote Sensors:
C7189U Remote Indoor Sensor: 10K ohm NTC. C7772 Flush-Mount Remote Indoor Sensor: 20K ohm NTC. TR21 Wall-Mount Remote Indoor Sensor: 20K ohm NTC. TR21-A Wall-Mount Remote Indoor Sensor: 10K ohm NTC.
Calibration (TB7100, C7089U, C7189U, T7770A):
No field calibration required.
Mounting Means:
TB7100: Direct wall-mount using mounting screws and
anchors provided. Fits standard vertical or horizontal 2 in. x 4 in. junction box.
C7189U, TR21: Mounts directly on the wall using mounting
screws and anchors provided. Fits a vertical 2 x 4 in. junc­tion box.
Cover Plate:
32003796-001 Cover Plate is used to cover marks left on the
wall by the old thermostat.
Dimensions:
TB7100 Thermostat: See Fig. 1. C7189U Remote Indoor Sensor: see Fig. 4. TR21 Remote Indoor Sensor: See Fig. 3. 32003796-001 Cover Plate: See Fig. 2.
3-3/4
(95)
6 (152)
Fig. 1. TB7100 Thermostat
dimensions in in. (mm).
THERMOSTAT
AND WALLPLATE
1-3/8
(35)
M13668
Fig. 2. 32003796-001 Cover Plate dimensions in in. (mm).
Fig. 3. TR21 indoor sensor dimensions in in. (mm).
3 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
MERCURY NOTICE
CAUTION
M4465
4-5/8 (117)
2-3/4 (70)
1-1/8
(29)
FRONT VIEW SIDE VIEW
Fig. 4. C7189U Indoor Sensor dimensions in in. (mm).
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control.
NO
M22258
NO
NO
YES
5 FEET
[1.5 METERS]
Fig. 5. Select thermostat location.
Do not install the thermostat where it can be affected by: — Drafts or dead spots behind doors and in corners. — Hot or cold air from ducts. — Radiant heat from sun or appliances. — Concealed pipes and chimneys. — Unheated (uncooled) areas such as an outside wall behind
the thermostat.

Separate Wallplate from Thermostat

1. Separate the wallplate from the thermostat. See Fig. 6.
WALLPLATE

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.

Select Thermostat Location

Select a location for the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 5.
WIRE HOLE
THERMOSTAT
M22267
Fig. 6. Separate wallplate from thermostat.

Install Wallplate (See Fig. 7)

Mount the thermostat horizontally on the wall:
1. Pull the wires through the wire hole on the wallplate.
2. Position the wallplate on the wall with the arrow pointing
up. Level the wallplate for appearance only.
3. Use a pencil to mark the mounting holes.
4. Remove the wallplate from the wall and drill two 3/16 in.
holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 in. holes. Tap the wall anchors (provided) into the drilled holes until flush with the wall.
5. Pull the wires through the wire hole on the wallplate and position the wallplate over the wall anchors.
6. Insert the mounting screws into the wall anchors and tighten.
63-2675—03 4
Fig. 7. Install wallplate.
CAUTION
WALL
MOUNTING HOLES
M13665
MOUNTING SCREWS (2)
WALL ANCHORS (2)
WIRES THROUGH WALL AND WIRE SLOT
M27415
C
G
Y
O/B
RC
R
W1
G2
G3
S1
S2
SCREW
TERMINALS
M13666
WIRE HOLE
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Fig. 9. Insert wires into terminal block.
4. Push excess wire back into the wall opening and restrict
wires to the shaded area. See Fig. 10.
5. Plug the wall opening with nonflammable insulation to prevent drafts from affecting the thermostat.

WIRING

Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
IMPORTANT
— All wiring must agree with applicable codes,
ordinances and regulations.
— Use 18 gauge thermostat wire. Shielded cable is not
required.
NOTES:
Refer to Table 5 for terminal designation
descriptions.
See Fig. 11 through 17 for wiring diagrams for
specific equipment applications.
1. Select set of terminal identifications that correspond to your system type (conventional or heat pump). See Fig. 8.
Fig. 8. Terminal identifications for system type.
2. Loosen screw terminals used for the application.
3. Insert the wires into the terminal block and tighten each
screw terminal. See Fig. 9.
WIRE
WALL OPENING
SHADED AREA
WALLPLATE
M22266
Fig. 10. Restrict wires to shaded area of wire hole.
Table 4. Wiring Diagrams.
Wiring Diagram
System Type
Figure
Standard Heat/Cool (1H/1C) 11, 12
Heat Only 13
Heat Only with Fan 14
Cool only 15
Heat Pump (No Auxiliary Heat) (1H/1C) 16
Heat Pump (with Auxiliary Heat) (2H/1C) 17
4 Pipe Fan Coil 18
2 Pipe Fan Coil 19
2 Pipe Fan Coil with aux. heat 20
PTAC 1H/1C (High speed, Low speed fan) 21
PTAC 2H/1C (High speed, Low speed fan) 22
Multiple TR21 Sensors 25, 26, 27
Multiple C7189U Sensors 28
5 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
COMPRESSOR CONTACTOR
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
1
2
3
C G Y
O/B
RC
R
W1 G2 G3
S1 S2
2
3
L1 (HOT)
L2
1
24 VAC
M27416
HEAT RELAY
Table 5. Terminal Designation Descriptions. NOTES:
Terminal
Designation Description
Rc (see Note 1)
R (see Note 1)
Power for cooling—connect to secondary side of cooling system transformer.
Power for heating—connect to secondary side of heating system transformer.
Y Compressor output.
C (see Note 2)
Common wire from secondary side of cooling system transformer.
W1 Heat relay. Auxiliary heat relay for heat pump,
PTAC.
G Fan relay. Low fan speed for fan coil and PTAC.
G2 Fan relay. Medium fan speed for fan coil only.
G3 Fan relay. High fan speed for fan coil and
PTAC.
O/B
Changeover valve for heat pumps.
(see Note 3)
S1 (See Note 4)
S2 (See Note 4)
Indoor remote sensor, remote setback, or changeover input.
Indoor remote sensor, remote setback, or changeover input.

Conventional System Wiring

1. When used in a single-transformer system, leave metal jumper wire in place between Rc and R. If used on a two-transformer system, remove metal jumper wire between Rc and R.
2. Common wire is optional when thermostat is used with batteries. When using separate transformers for heating and cooling, the common must come from the cooling transformer.
3. If thermostat is configured for a heat pump in the Installer Setup, configure changeover valve for cool (O-factory setting) or heat (B).
4. Sensor wires must have a cable separate from the thermostat control cable.
Fig. 11. Typical wiring of single transformer 1H/1C system.
COMPRESSOR CONTACTOR
FAN RELAY
1
L1 (HOT)
24 VAC
L2
COOLING
TRANSFORMER
L1
1
(HOT)
24 VAC
L2
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
REMOVE FACTORY INSTALLED JUMPER.
3
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY.
C G Y
O/B
RC
R
HEAT RELAY
3
2
INDOOR TEMPERATURE
SENSOR/REMOTE
W1
G2 G3 S1 S2
SETBACK
M27417
Fig. 12. Typical hookup of dual transformer 1H/1C system.
63-2675—03 6
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
M27418
HEAT RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
1
2
3
L1 (HOT)
L2
1
24 VAC
C G Y
O/B
RC
R
2
W1 G2 G3
S1 S2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
3
M27419
HEAT RELAY
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
1
2
3
3
L1 (HOT)
L2
1
24 VAC
2
C G
Y
O/B
RC
R
W1
G2 G3 S1 S2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
COMPRESSOR CONTACTOR
M27422
CHANGEOVER VALVE
1
2
3
4
5
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
3
L1 (HOT)
L2
1
24 VAC
AUXILIARY HEAT RELAY
4
2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
5
C
G
Y
O/B
RC
R
W1 G2 G3
S1 S2

Heat Pump System Wiring

L1 (HOT)
3
W1 G2 G3
S1
2
S2
L2
24 VAC
1
C
G
Y
O/B
4
RC
R
Fig. 13. Typical hookup of heat-only system.
Fig. 14. Typical hookup of heat-only system with fan.
CHANGEOVER VALVE
COMPRESSOR CONTACTOR
FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
3
OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
M27421
5
Fig. 16. Typical hookup of single-stage heat pump with no
auxiliary heat (1H/1C).
1
L1 (HOT)
24 VAC
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
3
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
Fig. 15. Typical hookup of cool-only system.
COMPRESSOR CONTACTOR
C G Y
O/B RC
R
FAN RELAY
2
3
W1 G2 G3 S1 S2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
M27420
Fig. 17. Typical hookup of single-stage heat pump with
auxiliary heat (2H/1C).
7 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
COOLING RELAY
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
HEAT RELAY
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
1
2
3
C G Y
O/B
RC
R
W1 G2 G3
S1 S2
2
3
L1 (HOT)
L2
1
24 VAC
M27423
HIGH FAN RELAY
MEDIUM FAN RELAY
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK/CHANGEOVER
PIPE SENSOR
TWO PIPE HEAT/COOL RELAY
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
1
2
3
C G Y
O/B
RC
R
W1 G2 G3
S1 S2
2
3
L1 (HOT)
L2
1
24 VAC
M27424
HIGH FAN RELAY
AUXILIARY HEAT RELAY
MEDIUM FAN RELAY
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK/CHANGEOVER
PIPE SENSOR
TWO PIPE HEAT/COOL RELAY
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
1
2
3
C G Y
O/B
RC
R
W1 G2 G3
S1 S2
2
3
L1 (HOT)
L2
1
24 VAC
M27425
HIGH FAN RELAY
MEDIUM FAN RELAY

Fan Coil System Wiring

Fig. 20. Typical wiring of 2 pipe fan coil without reheat.
Fig. 18. Typical wiring of 4 pipe fan coil.
Fig. 19. Typical wiring of 2 pipe fan coil with reheat.
63-2675—03 8

PTAC System Wiring

L1 (HOT)
2
(1H/1C).
3
W1 G2 G3
S1 S2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
HIGH FAN RELAY
5
M27426
24 VAC
L2
1
CHANGEOVER VALVE
COMPRESSOR CONTACTOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS
3
OPTIONAL.
4
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK.
5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
C
G
Y
O/B
4
RC
R
LOW FAN RELAY
Fig. 21. Typical hookup of PTAC with HI and LO fan speeds
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
COMPRESSOR CONTACTOR
M27427
CHANGEOVER VALVE
1
2
3
4
5
LOW FAN RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
FACTORY INSTALLED JUMPER.
WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL.
"O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.
3
L1 (HOT)
L2
1
24 VAC
AUXILIARY HEAT RELAY
4
2
INDOOR TEMPERATURE
SENSOR/REMOTE
SETBACK
5
C
G
Y
O/B
RC
R
W1 G2 G3
S1 S2
HIGH FAN RELAY

Installing Batteries

1. Install two AA alkaline batteries on the back of the ther­mostat as marked. See Fig. 23.
Fig. 22. Typical hookup of PTAC with HI and LO fan speeds
(2H/1C).

POWER THE THERMOSTAT

BATTERIES (2)
BACK OF THERMOSTAT
BATTERY HOLDER
M22259
Fig. 23. Installing batteries.
2. Locate and remove tab labeled Remove. See Fig. 24.
IMPORTANT
This tab must be removed in order to set the real-time clock.
REMOVE TAB
You can choose from three methods to power the thermostat:
• Batteries only (AAA alkaline).
• 24 Vac direct connection only.
• 24 Vac direct connection with battery backup (AAA alkaline).

Wiring 24 Vac Common

• Single-Transformer System—Connect the common side of the transformer to the C screw terminal of the thermostat wallplate. Leave the metal jumper wire in place between Rc and R.
• Two-Transformer System—Connect the common side of the cooling transformer to the C screw terminal of the thermostat wallplate. Remove the metal jumper wire between Rc and R.
INSTALLATION
REMOVE DURING
INSTALLATION
REMOVE DURING
M22260
Fig. 24. Remove tab labeled REMOVE from
thermostat back.

Locate and Mount TR21 or C7189U Remote Indoor Temperature Sensor (Optional)

Locate and mount the sensor in the same fashion as the thermostat. See the Select Thermostat Location section.
Consider the following as well:
1. Be sure wire distance between sensor and thermostat is less than 200 feet.
2. Mark the area on the wall selected for mounting the sensor or junction box.
3. Sensor wire must be separate from the thermostat cable.
4. Run wire cable to a hole at the selected wall location.
5. Pull approximately three inches of wire through the
opening.
NOTE: Color-coded, 18-gauge wire is recommended.
9 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
CAUTION
M27481
S1 S2
T T
SUBBASE
TR21
T T
TR21
T T
TR21
T T
TR21
M27482
S1
S2
SUBBASE
TR21-A
T4 T3
TR21-A
T4 T3
1
11
THE TR21-A IS A 10K OHM SENSOR.
M27483
T4
T3
TR21-A
1
1
THE TR21-A IS A 10K OHM SENSOR.
S1
S2
T
T
SUBBASE
TR21
TT
TR21

Wire Indoor Sensor

Electrical Interference (Noise) Hazard. Can cause erratic system operation.
Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels.
1. Check Installer Setup Number (ISU) 340 to ensure it is set to the desired value. (See Table 6.)
2. Wire sensor to S1 and S2 thermostat terminals.
3. Push excess wire back into the hole. Plug the hole using
nonhardening caulk, putty or insulation to prevent drafts from affecting performance.
4. Remove sensor cover.
5. Mount sensor to the wall or junction box using the
screws and anchors provided.
6. Level the sensor for appearance only. Device functions correctly even when not level.
7. Install sensor cover.
Fig. 27. Wiring two TR21 (20K ohm) Sensors and one
TR21-A (10K ohm) sensor to provide a temperature

Sensor Wiring for Temperature Averaging

averaging network
SUBBASE
S1
S2
Fig. 25. Wiring four TR21 (20K ohm) Sensors.
Fig. 26. Wiring two TR21-A (10K ohm) Sensors to provide a
63-2675—03 10
temperature averaging network.
1
C7189
C7189 C7189
WIRES MUST HAVE A CABLE SEPARATE
1
FROM THE THERMOSTAT CABLE.
C7189
M27432
Fig. 28. Wiring four C7189U (10K ohm) Sensors to provide
a temperature averaging network.

SET CALENDAR AND TIME

This thermostat is designed to, under normal use, automatically keep current time and day in memory for up to ten years once the calendar is set. There are two ways to set the calendar for this thermostat:

Setting Calendar Once Functioning

See steps 1 through 4, in the Advanced Settings section, to set year, month and day.

Setting Calendar When First Powered

When first powered, the thermostat proceeds through a sequence of screens to set the calendar. — When first powered, the thermostat proceeds through a
sequence of screens to set the calendar. See Fig. 29.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
M22302A
MONTH
YEAR
DAY
GO BACK BUTTON
GOES BACK TO LAST SETTING
NEXT BUTTON
ADVANCE TO NEXT SETTING
DONE
BUTTON
ADVANCES
TO TIME
SETTING
SCREEN
UP AND DOWN
BUTTONS
CHANGES
MONTH,
DAY AND
YEAR
DeSelect Day System & Fan
FanUseEdit
Schedule
View
Clock & More
Tue
DONE BUTTON
ADVANCES TO HOME SCREEN
UP AND DOWN BUTTONS
CHANGES TIME
M22303
View
Clock & More
m
&
an
S
e
C
k
&
e
o
ue
o
Cool
Se
o
M22304
m
&
an
an
UseEdit
C
e
o
o
Cool
M22305
3. The Setup Number displays to the center of the screen. It is a four-digit code beginning with zero. The current setting is displayed to the right.
NOTE: To cycle through the Setup Numbers, press the up or
down arrow.
Fig. 29. Setting calendar when thermostat is first powered.
T
System Aut
HeatOff
Syste
Fan Aut
F
chedul
t T
loc
Mor
Fig. 31. Entering Installer Setup.
User Settings (Simple Set)
Access to the user settings is obtained as follows:
1. From the main screen, press SYSTEM.
2. Press and hold the center key approximately five sec-
onds.
3. The Setup Number displays to the center of the screen. It is a four-digit code beginning with zero. The current setting is displayed to the right.
NOTE: To cycle through the Setup Numbers, press the up or
down arrow.
Fig. 30. Setting time when thermostat is first powered.

INSTALLER SETUP

Advanced Settings

The thermostat has advanced settings to match the HVAC system. These settings can be adjusted to match specific needs.
There are two different groups of settings: — A complete set designed for the installation use. — A simple set to limit accessibility for typical users.
Installer Settings (Complete Set)
Access to the installer settings is obtained as follows:
1. From the main screen, press SYSTEM.
2. Press and hold the two keys on either side of the center
key for approximately five seconds. (See Fig. 31.)
System Aut
Fan Aut
Heat Off
Syste
F
F
ancelDon
Fig. 32. Entering User Setup.
11 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
CAUTION

INSTALLER SETUP NUMBERS (ISU), SETTINGS, AND TESTS (TABLE 6)

Use the Installer System Test to test the heating, cooling and fan. Refer to the latter portion of Table 6.
Equipment Damage Hazard. Minimum compressor off time is bypassed during Installer System Test
Avoid cycling compressor quickly.
Table 6. Installer Setup Menu.
Installer
Setup
Number
0120 Date (Year Upper) 20 20—21 Available year range: 2001 - 2178
0130 Date (Year Lower) 08 00-99 Available year range: 2001 - 2178
0140 Date (Month) 6 1-12
0150 Date (Day) 15 1-31 (Month Dependent)
0160 Schedule Options 4 0—Non-Programmable
0170 System Selection 1 1—1H/1C Conv
0180 Heat Fan Operation 0 0—Fossil
0185 Pre-occupancy
0190 Reversing Valve
0220 Cycles Per Hour
0240 CPH for first stage
0270 CPH for Em Heat 9 1-12 Only shown if HP with reheat, 2 pipe fan coil with
0280 Continuous
0300 Changeover 1 0—Manual
Installer Setup
Name
Purge Duration
O/B
(CPH) for first stage cooling/compressor
heat
Backlight
Default Setting All Settings Notes
4—Programmable
2—1H w/o fan 3—1H with fan 4—1C 5—1H/1C HP 6—2H/1C HP 7—4 pipe Fan Coil 8—2 pipe Fan Coil 9—2 pipe Fan Coil w/ Aux Heat 10—PTAC 1H/1C (Hi speed, Lo speed Fan) 11—PTAC 2H/1C (Hi speed, Lo speed Fan)
1—Electric
0 0—no duration
1—one hour 2—two hours 3—three hours
0 0—O (O/B On Cool)
1—B (O/B On Heat)
3 1-6 Only shown if system has cool stages (ISU 0170).
5 1-12 Only shown if system is conventional with heat
0 0—No
1—Yes
1—Auto
IMPORTANT
Use Installer System Test to test heating, cooling and fan. The setting chosen for System Type (ISU 0170) can prevent some System Test Numbers from appearing.
NOTE: Unless otherwise noted, setup items are accessible
through only the Installer setup and not the User setup.
Relay Y is used for 2 pipe fan coil output relay.
Only shows up if conventional system with heat stages and fan capability is selected (ISU 0170). If heat pump is selected, fan defaults to electric. If fan coil or PTAC modes are selected, fan defaults to electric (does not show up).
Shown only if system has fan and schedule is programmable (ISU 0160). Pre-occupancy purge is enabled by a nonzero duration.
Only shown if heat pump or PTAC system is selected.
Shown for heat pump, fan coil, PTAC, and conventional cooling stages.
stages, 4 pipe fan coil, 2 pipe fan coil (ISU 0170).
reheat, and PTAC with reheat (ISU 0170).
Always shown; however, if AC power is not present, the option is overridden and normal backlight operation occurs.
Only shown if system has both heat and cool stages (ISU 0170). Shown for CNV, HP, PTAC and 4 pipe fan coil (ISU 0170). Not shown for 2 pipe fan coil modes.
63-2675—03 12
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 6. Installer Setup Menu. (Continued)
Installer
Setup
Number
0310 Deadband 3°F
Installer Setup
Name
Default Setting All Settings Notes
2 (1.5)—2°F (1.5°C)
(2°C)
3 (2.0)—3°F (2.0°C) 4 (2.5)—4°F (2.5°C) 5 (3.0)—5°F (3.0°C) 6 (3.5)—6°F (3.5°C) 7 (4.0)—7°F (4.0°C) 8 (4.5)—8°F (4.5°C) 9 (5.0)—9°F (5.0°C)
0320 Temperature
Indication Scale
0 0—°F
1—°C
0330 Daylight Saving 1 0—Disabled
1—Enabled (US)
0340 Remote Temp
Sensor/Remote Setback/ Changeover Input
0 0—None
1—Remote 10K Indoor 2—Remote 20K Indoor 3—Changeover 2 pipe Fan Coil modes only 4—Changeover 2 pipe Fan Coil modes only
0340 (Non­program mable)
Remote Temp Sensor/Remote Setback/ Changeover Input
0 0—None
1—Remote 10K Indoor 2—Remote 20K Indoor 3—Changeover 2 pipe Fan Coil modes only 4—Changeover 2 pipe Fan Coil modes only 5—Remote Setback
6—Remote Setback
0341 Delay for Remote
Setback
0342 Override Option
(only available in
0 0—No Delay
2—2 Minute Delay
0 0—No Override
1—Override non-programmable mode)
0343 Unoccupied
Heating Setpoint
60°F 50-65°F
10-18°C (only when remote setback enabled)
0346 Unoccupied
Cooling Setpoint
80°F 75-90°F
24-30°C (only when remote setback is enabled)
0347 Fan Ramping 1 0—Disabled (Lo, Med, Hi)
1—Enabled
0348 Fan Mode 0 0—User can choose Cycle or
Constant 3 speed: Low->Med->
H ig h- >A ut o- > L ow
1—Cycle Only - Auto only
Only shown if Automatic Changeover selected (ISU
0300).
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
Hotel card NO, with 1 second software delay going from UnOcc to Occupied; 2 minute delay going from Occupied to UnOcc. Hotel Card NC, with 1 second software delay going from UnOcc to Occupied; 2 minute delay going from Occupied to UnOcc.
Only shown if Remote Setback (ISU 0340) is enabled.
This option is only available for non-programmable mode (ISU 0160)
To enable the fan ramping algorithm. Only available for fan coil or PTAC applications (ISU 0170)
To select a particular fan mode: Auto is the fan ramp mode. If ramping is not selected, fan mode automatically defaults to Low Med High (Constant only) and ISU 0348 is unavailable. Only available for fan coil or PTAC applications (ISU 0170)
13 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 6. Installer Setup Menu. (Continued)
Installer
Setup
Number
0349 Auto Fan Reset 0 0 —Ina ctiv e
Installer Setup
Name
Default Setting All Settings Notes
The timer will be set after the user selects the 1—Reset back to Auto after 2 hours 2—Reset back to Auto after 4 hours
constant fan speed. Fan will be set to Auto
automatically when time out. The start time is
calculated after initial call for heat/cool is satisfied,
then 2 hour timing begins.
The timer will be set after the user selects the
constant fan speed. Fan will be set to Auto
automatically when time out. The start time is
calculated after initial call for heat/cool is satisfied,
then 4 hour timing begins. Only available for fan coil
or PTAC applications (ISU 0170)
0535 Temporary
3 0–12 hours 0 means no limit. Occupied Duration Limit
0540 Number of Periods 4 2—2 Periods
4—4 Periods
Does not appear if Non-programmable is chosen (ISU
0160). Applies to all days of the week. If 2 is selected the Cancel Period option will not appear on the display.
0580 Minimum
Compressor Off Time
50Off
2—2 minutes 3—3 minutes
Only shown if system has cool stages in CNV, Heat Pump, PTAC (ISU 0170).
4—4 minutes 5—5 minutes
0600 Heat Temperature
90 40 to 90°F (4 to 32°C) Only shown if system has heat stages (ISU 0170). Range Stops
0610 Cool Temperature
50 50 to 99°F (10 to 37°C) Only shown if system has cool stages (ISU 0170). Range Stops
0640 Clock Format 12 12—12 Hour
24—24 Hour
0650 Extended Fan-on
time Heat
0660 Extended Fan-on
time Cool
0670 Keypad Lockout 0 0—Unlocked
00Off
90—90 seconds
00Off
40—40 seconds
1—Partial Lockout 1 2—Partial Lockout 2
Not displayed if fan set to fossil or cool only systems (ISU 0170)
Only shown if system has cool stages. (ISU 0170)
Unlocked: All functions accessible. Partial 1: Locks out schedule and system changes. Partial 2: Locks out schedule, system, and fan changes.
3—Partial Lockout 3
Partial 3: Locks out schedule, system, fan, and up/ down arrow changes. Full: Entire interface locked/non-functional.
Only shown if system has heat stages (ISU 0170). Only integral gains are affected by this setting. The setting affects control operation in all control regimes
0680 Temperature
Control Heat
4—Fully Locked
2 1—Less Aggressive
2—Standard 3—More Aggressive
(not just recovery or setpoint change).
0685 Recovery Heat
Ramp Rate
5 0-20°F/hour Only shown if system has heat stages (ISU 0170).
0 disables the ramped recovery (step setpoint change at period start time).
0690 Temperature
Control Cool
2 1—Less Aggressive
2—Standard 3—More Aggressive
Only shown if system has cool stages (ISU 0170). Only integral gains are affected by this setting. The setting affects control operation in all control regimes (not just recovery or setpoint change).
0695 Recovery Cool
Ramp Rate
3 0-20°F/hour Only shown if system has cool stages (ISU 0170).
0 disables the ramped recovery (step setpoint change at the period start time).
63-2675—03 14
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
M22316
UP ARROW BUTTON
RAISES TEMPERATURE SETTING OR
MAKES SELECTIONS IN OTHER SCREENS
DOWN BUTTON
LOWERS TEMPERATURE SETTING OR
MAKES SELECTIONS IN OTHER SCREENS
CLOCK &
MORE BUTTON
SELECTS TIME AND
FURNACE FILTER
INFORMATION
SYSTEM & FAN BUTTON
SELECTS FAN AUTO OR ON SELECTS HEAT, OFF, COOL AND EM HEAT
SCHEDULE BUTTON
SELECTS PROGRAMMING MODE
System
Cool
Fan Auto
System & Fan Schedule Clock & More
Set To
Table 6. Installer Setup Menu. (Continued)
Installer
Setup
Number
0700 Temperature
Installer Setup
Name
Display Offset
Default Setting All Settings Notes
0 -3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C) 0 (0.0)—0°F (0.0°C) 1 (0.5)—1°F (0.5°C) 2 (1.0)— 2°F (1.0°C) 3 (1.5)—3°F (1.5°C)
0710 Restore Factory
Defaults
0 0—No
1—Yes
0720 Screen Display 2 0—Display Room Temperature
1—Display Setpoint 2—Display Both
INSTALLER TESTS
Test 1 Installer Test
Cool
Test 2 Installer Test
Fan
00Off
1—Cool Stage 1
00Off
1—Fan Stage 1 2—Fan Stage 2 3—Fan Stage 3
Test 3 Installer Test
Heat
00Off
1—Heat Stage 1 2—Heat Stage 2
Test 4 Installer Test EM
Heat
0 0—EM Heat Off
1—EM Heat On
This offset applies to both the control temperature and to the display temperature for indoor sensor (and remote indoor sensor).
Resets all ISU parameters to default values and resets the schedule to default. Retains only calendar settings and time.
Only shown if system has cool stages.
Only shown if system has fan.
Only shown if system has fan. Systems with 2 Heat stages will have option 2 enabled for Installer Test 3.
Only shown if multi-stage HP is selected (heat pump with more heating than cooling stages).
NOTE: Press the Done button to exit the Installer System Test.

MAIN SCREEN

SHOWS CURRENT DAY OF WEEK
CURRENT SYSTEM SETTING
CURRENT FAN SETTING
Mon
System Auto
System & Fan
TEMPERATURE SETTING
CURRENT TIME
Aux Heat On
Fan Auto
Schedule Clock & More
INDICATES THERMOSTAT IS "CALLING FOR COOL OR HEAT"
M22317
Fig. 33. Main screen selections.
Fig. 34. Main screen display.
15 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
M22332
Mon Tue Wed Thu Fri Sat Sun
Select Day
Next Step
Cancel
M23041
DAYS SELECTED
NEXT STEP KEY
ADVANCES PERIOD,TIME, HEAT AND COOL TEMPERATURES
SCHEDULE PERIOD
HEAT OR COOL TEMPERATURES
GO BACK KEY
GOES BACK TO THE LAST SCHEDULE STEP
DONE KEY
EXITS AND SAVES CHANGES MADE TO SCHEDULE
DOWN ARROW
CHANGES TIME
AND
TEMPERATURES
UP ARROW
CHANGES TIME
AND
TEMPERATURES
AM
Go Back Next Done
Mon Tue Wed Thu Fri
Period
Occupied1 Unocc1 Occupied2 Unocc2

PROGRAMMING

Table 7 shows default program settings.
Table 7. Energy-saving Default Program Settings.
Schedule
Period Time
Occ1 8:00am 70°F (21°C) 75°F (24°C)
Unocc1 10:00pm 55°F (10°C) 85°F (29.5°C)
Occ2
Unocc2

Fan Settings

Auto: Fan runs only when heating/cooling system is on.
See the Fan Schedule section for more information.
On: Fan runs continuously.

System Settings

Heat: Thermostat controls the heating system. Off: Both heating and cooling systems are off. Fan is turned
off.
Cool: Thermostat controls the cooling system. Auto: Thermostat automatically changes between heat and
cool operation, depending on indoor temperature.
Setpoints
Heat Cool
Fig. 35. Initial schedule edit screen.
6. OCCUPIED 1 flashes, denoting the period that is about
to be edited.
7. Press NEXT, and the start time for that period flashes.
8. Change the start time by pressing the Up and Down
arrow keys.
9. Press NEXT to edit the heating and cooling setpoints.
10. Continue to cycle through the remaining periods and
make changes by pressing the NEXT key.

Programming Heating and Cooling Schedule

The thermostat can control up to four different schedule periods per day: OCC 1: Work arrival time. Period to keep space at a
comfortable temperature.
UNOCC1: Work exit time. Period to keep space at an
energy-saving temperature.
OCC 2: Second occupied period. UNOCC2: Second unoccupied period.
NOTE: Available schedule times are at 15-minute intervals.

Editing Schedule

1. Press MORE
2. Press SCHEDULE.
3. Press EDIT.
4. Press SELECT DAY to select the days you wish to
5. Press NEXT when finished selecting days
NOTES:
63-2675—03 16
schedule.
Multiple days can be selected. — To skip over a day, press the Up or Down arrow
keys.
Checkmarks appear next to selected days. These
are scheduled with identical times and tempera­tures.
Fig. 36. Screen to edit existing settings.
11. When complete, press DONE. SAVING CHANGES
appears on the screen to indicate changes are being saved to the day(s) modified.
12. To exit schedule without saving changes, press CANCEL any time.

Setting Time

1. Press CLOCK.
2. Use arrows to set current time.
3. Press DONE.
IMPORTANT
The current day of the week should already be set correctly. If not, see the Advanced Settings section to set the day.
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT

OPERATION

Fan Sequence Operations (ISU 347, 348, 349)

If heat pump or conventional application modes are enabled in ISU 170, then ISU 347 is not available for fan ramp algorithm. The fan operates as a default ON/AUTO selection that works the same way as our CommercialPRO TB7220 thermostat. There is only one fan relay output that is activated.
If PTAC or fan coil thermostat application modes are enabled in ISU 170, then ISU 347 fan ramp algorithm is available for installer setup selection. The fan ramp algorithm will automatically calculate the appropriate fan speed that is needed to meet the proportional band requirements to speed up setpoint satisfaction. When the setpoint is satisfied it will revert to the lowest fan speed setting to conserve energy.
The thermostat comes factory default with the fan ramping algorithm enabled (ISU 347). This gives the user the ability to select Auto-Lo-Med-Hi option in ISU 348 or Auto only option in ISU 348. Auto sets the thermostat into the fan ramping algorithm mode and automatically sets the sufficient speed for PI control. Auto also automatically shuts the fan off when there is not a call for heating or cooling. If the user decides to disable ISU 347, then the fan will only have Lo-Med-Hi option available.
If ISU 347 is not enabled, then ISU 348 does not appear as a user selection choice.
If ISU 347 is enabled, then ISU 349 is available as a selection choice. The user can select either a 2 hour or 4 hour timer fan reset function. The fan will reset from a constant on speed to Auto mode after the time period expires. If ISU 347 is not enabled, then ISU 349 does not appear as a user selection choice.

Equipment Sequence Operations (ISU 170)

Heat Pump and Conventional
Heat Pump and conventional use a single fan speed. The single fan speed label is the G terminal relay output. Display on the thermostat for these modes will give the Fan On/Auto option. There is no fan ramping algorithm, ISU 347, 348, 349 are not available.
PTAC
PTAC modes 10 and 11 will have the same selection options available as the heat pump selection options. The only difference is that the PTAC options have a Lo and Hi speed fan output instead of single speed output and that it follows the fan sequencing described above with ISU 347, 348, 349.
4 Pipe
4 pipe is treated similar to 1H/1C conventional. It follows the fan sequencing described above with ISU 347, 348, 349.
2 Pipe There are two different 2 pipe modes - 2 pipe only and 2 pipe with reheat.
2 pipe only - 2 pipe modes do not contain the ability to have
automatic changeover. They are manual changeover only. The thermostat will have a priority when choosing a system mode (heat or cool). When ISU #340 has a 2 pipe changeover
sensor enabled, the thermostat screen system mode will lock on heat or cool (whatever the changeover sensor is communicating to the thermostat). If ISU #340 does not have a changeover sensor enabled, then the system mode from the thermostat screen can manually be adjusted between heat or cool. It follows the fan sequencing described above with ISU 347, 348, 349.
2 pipe with reheat - 2 pipe modes do not contain the ability to have automatic changeover. They are manual changeover only. The thermostat will have a priority when choosing a system mode (heat or cool). When ISU #340 has a 2 pipe changeover sensor enabled, the thermostat screen system mode will lock on heat only. When the 2 pipe changeover sensor is sensing cool mode, the user can adjust to heating mode which will bring on the auxiliary heat. If ISU #340 does not have a changeover sensor enabled, then the system mode from the thermostat screen can manually be adjusted between heat or cool. It follows the fan sequencing described above with ISU 347, 348, 349.
Operating Sequence
The thermostat energizes specific terminal(s), depending on the demand for heating, cooling or fan. The thermostat screen shows the time, inside temperature, system and fan selections. Additional indicators are shown when the heating, cooling or fan is energized. See Tables 8 and 9 for specification information.
Table 8. Sequence of Operation for Conventional Systems.
System
Setting
Off Auto
Cool Auto
Cool or Auto
Heat Auto
Heat or Auto
a
If Installer Setup System type is set to two stages of cooling.
b
G energizes only if Installer Setup 0180 is set to Electric.
Table 9. Sequence of Operation for Heat Pump Systems.
System
Setting
Off Auto
Cool
Cool or Auto
Heat Auto
Heat or Auto
a
Configure O/B in Installer Setup. Based on last piece of equipment called (cooling = O; heating = B).
b
If Installer Setup System Type is set to 2Heat/1Cool Heat Pump with Auxiliary Heat.
Fan
Setting Call for Action
Auto Stage 1
Cooling
Auto Stage 1
Heating
Fan
Setting Call for Action
Auto Stage 1 Cooling
Auto Stage 1 Heating
Stages 1 and 2 Heating
Energize
Ter min als
Screen
Message
Y, G Cool On
b
W, G
Energize
Terminals
a
O/B
Y, G, O/B
a
O/B
Y, G, O/B
Y, W 1
a
O/B
b
, G,
a
a
Heat On
Screen
Message
Cool On
Heat On
Auxiliary Heat On
17 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 10. Sequence of Operations for Fan Coil Systems.
System Setting Fan Setting Call for Action Energize Terminals Screen Message
Off/Cool/Heat/Em Heat/Auto Auto -- --
Cool or Auto Auto 4 Pipe Cooling
Y, G
b
, G2b, G3
b
Cool On
Cool or Auto LO 4 Pipe Cooling Y, G Cool On
Cool or Auto MED 4 Pipe Cooling Y, G2 Cool On
Cool or Auto HIGH 4 Pipe Cooling Y, G3 Cool On
Heat or Auto Auto 4 Pipe Heating
Heat or Auto LO 4 Pipe Heating
Heat or Auto MED 4 Pipe Heating
Heat or Auto HIGH 4 Pipe Heating
Cool or Heat Auto
Cool or Heat LO
Cool or Heat MED
Cool or Heat HIGH
2 Pipe Cooling/Heating
2 Pipe Cooling/Heating
2 Pipe Cooling/Heating
2 Pipe Cooling/Heating
a
a
a
a
Em Heat Auto 2 Pipe Call for Auxiliary Heat
Em Heat LO 2 Pipe Call for Auxiliary Heat
Em Heat MED 2 Pipe Call for Auxiliary Heat
Em Heat HIGH 2 Pipe Call for Auxiliary Heat
a
If Installer Setup (0170) System Type is set to 2 pipe Fan Coil (8) or 2 pipe Fan Coil w/Aux Heat (9), the Y terminal will be used
c
W1
, Gb, G2b, G3
c
, G
W1
W1c, G2
c
, G3
W1
Ya, Gb, G2b, G3
Ya, G
Ya, G2
Ya, G3
Ya, W1c, Gb, G2b, G3
a
, W1c, G
Y
Ya, W1c, G2
Ya, W1c, G3
b
Heat On
Heat On
Heat On
Heat On
b
Cool On or Heat On
Cool On or Heat On
Cool On or Heat On
Cool On or Heat On
b
Heat On
Heat On
Heat On
Heat On
for cooling and heating. If Installer Setup (0170) System Type is set to 4 pipe Fan Coil (7), the Y terminal will be used for cooling only.
b
When fan is in AUTO, it automatically selects the fan speed based on how far away the temperature is from the setpoint.
c
If Installer Setup (0170) System Type is set to 2 pipe Fan Coil with Auxiliary Heat (9), the W1 terminal will be used for reheat. If Installer Setup (0170) System Type is set to 4 pipe Fan Coil (7),the W1 terminal will be used for heating.
Table 11. Sequence of Operations for PTAC Systems.
System Setting Fan Setting Call for Action Energize Terminals Screen Message
Off/Cool/Heat/
Auto --
Em Heat/Auto
Cool or Auto Auto Stage 1 Cooling
Cool or Auto LO Stage1 Cooling
Cool or Auto HIGH Stage 1 Cooling
Heat or Auto Auto Stage 1 Heating
Heat or Auto LO Stage 1 Heating
Heat or Auto HIGH Stage 1 Heating
Em Heat Auto Stage 1 and 2 Heating
Em Heat LO Stage 1 and 2 Heating
Em Heat HIGH Stage 1 and 2 Heating
a
When the fan is in AUTO, it automatically selects the fan speed based on how far away the temperature is from the setpoint.
b
Configure O/B in Installer Setup. Based on last piece of equipment called (cooling=O; heating=B).
c
If Installer Setup (1070) System Type is set to 2Heat/1 Cool PTAC.
b
O/B
a
, G3a, O/B
Y, G
Y, G, O/B
Y, G3, O/B
a
, G3a, O/B
Y, G
Y, G, O/B
Y, G3, O/B
c
, Ga, G3a, O/B
Y, W 1
c
, G, O/B
Y, W 1
c
, G3, O/B
Y, W 1
--
b
b
b
b
b
b
b
b
b
Cool On
Cool On
Cool On
Heat On
Heat On
Heat On
Heat On
Heat On
Heat On
63-2675—03 18
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT

Special Programmable Mode Functions

Installer Setup 160 allows the thermostat to be configured for either a mode with a programmable 7 day schedule or as a non-programmable thermostat.
Preoccupancy purge (ISU 185)
This feature is available only when the thermostat is configured as a programmable schedule and when a fan is used. The fan will run 1-3 hours before the occupied schedule starting time to circulate air.
Override Button, Temporary Override (Duration Limit ISU
535)
While in the programmable schedule mode, an override button is available to perform temporary override control. The default override time can be configured through ISU 535. Lockout configuration via ISU 670 can provide restrictions on access to setpoint changes, system changes, and schedule changes.
No remote setback
The remote setback feature only works in the non­programmable mode.

Special Non-Programmable Mode Functions

Override (Optional)
The override feature is optional in the non-programmable mode. The override can be configured through ISU 342. When the override is activated in the non-programmable mode it will temporarily override to a new setpoint until the end time expires.
OVERRIDE
Changes temperature setting until the next period takes effect. For use during Unoccupied periods.
1. Press OVERRIDE. The settings change by default to the next Occupied period.
NOTE: Changes are limited to those allowed by the
lockout level.
2. Press Up or Down arrow to change the override temper­ature, and NEXT to adjust override time.
HOLIDAY
Changes temperature setting for a designated number of days. Press MORE and then HOLIDAY. The screen shows “Hold Until 1 DAYS”.
1. Press Up or Down arrow to change the temperature desired for the thermostat to override the schedule.
2. Press NEXT to change the desired days for the duration of the holiday.
3. To cancel the Holiday Override early, press CANCEL.
Fan Status Displayed on Main Screen
When the thermostat is running the fan, the fan blade symbol
appears next to FAN to indicate the thermostat has the fan
on.
NOTE: If the thermostat is not controlling the fan—typical for
many gas, forced-air heating systems—the fan blade symbol will not appear even though the fan may be running.
Remote Setback
Remote Setback is available (ISU 340). Occupancy sensors, manual time clock inputs, and DDC night setback can be used to provide inputs to setback the thermostat. Unoccupied heating (ISU 343) and unoccupied cooling (ISU 346) setpoints are available to configure the setback setpoints.
Setting Temperature Overrides
There are three temperature override options: — Hold Temperature Until — Override, and — Holiday.
HOLD TEMPERATURE UNTIL
Holds the temperature temporarily until the time set by the user, or the next scheduled period time.
1. Press the Up or Down arrow next to the temperature to adjust. The Hold Until time appears on the screen. The time defaults to the next scheduled period start time
2. Press NEXT to adjust the time for the thermostat to resume schedule.
NOTE: The installer setup can limit the length of time
for an override to 1, 2, 3, or 4 hours beyond the current time.
3. Press DONE or wait 5 seconds.
4. Press CANCEL or SCHEDULE to cancel “Hold Tempera-
ture Until” and resume the schedule.
Replacing Batteries
Not all thermostat models require batteries. If the thermostat has batteries, a low battery warning (see Fig. 38) flashes on the main screen for approximately 30 days.
NOTE:
If batteries are not replaced when the Low Battery
warning is flashing, the LO batt screen displays continuously and the thermostat stops operating until batteries are replaced.
The thermostat has a low battery indicator.
However, it is recommended that the batteries be replaced once each year. Do this to prevent leakage and prevent the thermostat and HVAC system from shutting down due to lack of thermostat battery power.
M22322
Fig. 37. Low battery signal.
19 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
WALL
M23024
WALLPLATE
M22299
TERMINAL SCREW BLOCK
PINS ON
BACK OF
THERMOSTAT
Replace the batteries as follows:
1. Remove the thermostat from the base by pulling it straight out. (See Fig. 39.)
2. Install two new AA alkaline batteries with proper polar­ization.
NOTES:
Always use AA alkaline batteries. — All programming (Schedule, Date and Time)
information is retained during battery replacement.
3. Place thermostat back on subbase by aligning terminal screw blocks with the pins on the back of the thermostat. (See Fig. 40.)
4. Push the thermostat straight onto the base.
NOTE: If connected to an installed remote indoor temperature
sensor, the thermostat internal sensor is not used.
ONE REMOTE INDOOR SENSOR INSTALLED
If one remote indoor temperature sensor is used, the screen showing the Inside temperature reading displays the temperature at the indoor remote sensor location.
MULTIPLE REMOTE INDOOR SENSORS INSTALLED
If more than one remote indoor sensor is used, the screen showing the Inside temperature reading displays the average of all the remote indoor sensors.

Screen Locked

Portions of the touch screen interface can be fully or partially locked. See the Advanced Settings section for information to use these features. When the thermostat displays LOCKED, the buttons are either fully or partially locked.
Fully Locked Screen
In this mode, the entire interface is locked and not functional. To unlock screen, see the Advanced Settings section. The screen continuously displays SCREEN LOCKED.
Partially Locked Screen
When partially locked:
Fig. 38. Removing thermostat from subbase.
Fig. 39. Placing thermostat back onto subbase.
Reading Remote Indoor Temperature
If connected to an installed remote indoor temperature sensor, the thermostat displays the indoor temperature from the remote sensor(s).
— Pressing a locked key prompts the screen to indicate
LOCKED for five to seven seconds.
— Pressing an unlocked key with LOCKED shown removes
LOCKED from the display.
— HOLIDAY and OVERRIDE options are available in all partial
lockout levels.
— Pressing HOLIDAY sets the temperature to the Unoccupied
setting for the selected period of time. The next Occupied period switches back to the program settings.
— Pressing OVERRIDE sets the temperature to the Occupied
setting for the selected period of time. The next Unoccupied period switches back to the program settings.
— To cancel the temperature override and follow the
programmed schedule, press CANCEL.
PARTIAL LOCKOUT 1
This mode locks out schedule and system changes.
— User can change the temperature setpoint and fan settings,
but cannot change schedule or system settings.
— The temporary changes last until next scheduled period.
The screen displays that time.
— To unlock the screen, see Advanced Settings section.
PARTIAL LOCKOUT 2
This mode locks out schedule, system and fan changes.
— User can change the temperature setpoint, but cannot
change schedule, system, or fan settings.
— The temporary temperature change lasts until next
scheduled period. The screen displays that time.
— To unlock the screen, see Advanced Settings section.
PARTIAL LOCKOUT 3
This mode locks out schedule, system, fan, and temperature setpoint settings.
63-2675—03 20
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
TEMPERATURE (DEGREES)
o
F
-40
-20 0 20 40
60
80
100
120
-20
-30
-40
-10
40
RESISTANCE (OHMS)
10K OHM AT 77
o
F (25oC)
220K
190K
160K
130K
100K
90K
60K
30K
o
C
M22823
0
10 20
30
50
0K
— Users cannot make changes to the temperature setpoint or
any schedule, system, or fan settings. — The only features available are HOLIDAY and OVERRIDE. — To unlock the screen, see Advanced Settings section.
Temperature Recovery
The thermostat is equipped with a feature to eliminate guesswork when setting a schedule. That is, the user need not know the amount of time for the HVAC system to bring the space to temperature (without overshoot) prior to the scheduled time.The thermostat manages that automatically.
Simply set the program schedule to the desired time to have the space at comfort temperature. In addition, program the temperature to this comfort temperature. The thermostat activates the heating or cooling at the proper time to reach the scheduled temperature at the scheduled time.
NOTE: The setpoint changes gradually to use economical
stages and avoid overshoot.
For example—the space will be occupied at 8:00 AM and the desired temperature is 70°F. Set the OCC 1 period for 8:00 AM and 70°F. The thermostat turns on the heat prior to 8:00 AM to raise the temperature to 70°F by 8:00 AM.
The thermostat provides an alert that the heating or cooling system is coming on before a scheduled time by displaying “Recovery” on the screen.
The C7189U can be used to provide one remote sensor input or as a temperature averaging network with multiple TR21 Sensors connected, as shown in Fig. 28.
Checkout
For best results, allow C7189U Wall Mount Temperature Sensor to absorb the air moving through the room for a minimum of twenty minutes before taking a resistance measurement.
With an accurate thermometer (±1°F [0.5°C]) measure the temperature at the sensor location, allowing time for the thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of C7189U wiring terminals. Use an ohmmeter to measure the resistance across the sensor. Then compare sensor accuracy with the temperature/resistance curve in Fig. 40.

Minimum-Off Timer Compressor Protection

The thermostat has an adjustable Minimum-Off Timer that can be set from zero to five minutes (Factory Setting—five minutes). The Minimum-Off Timer can be bypassed through the Installer System Test or it can be bypassed permanently by setting the Minimum-Off Timer to 0 minutes in the Installer Setup. The Minimum-Off Timer is activated after the compressor turns off: — If the thermostat is system powered (common wire), the
Minimum-Off Timer is also activated upon initial startup and
after power interruptions. — If there is a call for cooling or heating during the Minimum-
Off Time, the thermostat displays “Wait.” — When the Minimum Off Timer expires, “Cool On” or “Heat
On” (heat pumps only)” appears solidly in the display and
the compressor and fan turn on.

Temperature Sensor Operation and Checkout

Allow outdoor or indoor temperature sensor to absorb the air for a minimum of five minutes before taking a reading. See the Sensor instructions for more information.
NOTE: The C7189U, TR21 and TR21-A Temperature
Sensors are calibrated at the factory and cannot be recalibrated in the field.

C7189U Remote Indoor Temperature Sensor

Operation
When installed with Thermostat ISU 0340 set to 3, the remote inside temperature is displayed on the Thermostat Home Screen as Inside Temperature. The thermostat internal temperature sensor is not used.
Fig. 40. 10K ohm sensor resistance versus temperature.

TR21 Remote Temperature Sensor

Operation
When installed with Thermostat ISU 0340 set to 3 or 4, the remote inside temperature is displayed on the Thermostat Home Screen as Inside Temperature. The thermostat internal temperature sensor is not used.
The TR21 can be used to provide one remote sensor input or as a temperature averaging network with multiple TR21 Sensors connected, as shown in Fig. 25 through 27.
Checkout
For best results, allow TR21 Wall Mount Temperature Sensor to absorb the air moving through the room for a minimum of twenty minutes before taking a resistance measurement.
With an accurate thermometer (±1°F [0.5°C]) measure the temperature at the sensor location, allowing time for the thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of the wiring terminals. Use an ohmmeter to measure the resistance across the sensor. Then verify the sensor accuracy with the temperature/resistance in Fig. 41.
21 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
80K
70K
60K
50K
40K
30K
RESISTANCE (OHMS)
20K
10K
20K OHM AT
o
F (25oC)
77
40 50 60 70
30
0
80
10
20
TEMPERATURE (DEGREES)
90
30
100
110
40
M5874A
o
F
o
C
Fig. 41. 20K ohm sensor resistance versus temperature.
63-2675—03 22
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT

TROUBLESHOOTING (TABLE 12)

Table 12. Troubleshooting.
Symptom Possible Cause Action
Display does not come on. Thermostat is not being powered. Check for 24 Vac between C and Rc.
Check that AAA batteries are installed correctly and are good.
Temperature settings do not change.
Heating or cooling does not come on.
Thermostat is calling for Heat (Heat on) or Cool (Cool on) but no heating or cooling is running.
Heat does not turn on (Heat On is solid in the display).
The upper or lower temperature limits were reached.
The keypad is fully locked. Check ISU 0670 to change keypad locked
Thermostat minimum off-time is activated. Wait up to five minutes for the system to respond.
System selection is not set to Heat or Cool. Set system Selection to correct position.
System type Selection is incorrect. Check ISU 0170 and make sure correct System
Heating or cooling equipment is not operating.
Heating equipment failure. Check for 24 Vac at the equipment on the
Check temperature setpoints. Check ISU 0600 and 0610; modify as needed.
options.
type is chosen.
Check wiring. Check ISU 0170 and make sure correct system type is chosen. Verify operation of equipment in System Test mode.
secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to find the cause of the problem.
Cooling does not turn on (Cool On is solid in the display).
Fan does not turn on in a call for heat (electric furnace).
Heat pump puts out cool air in the heat mode and warm air in the cool mode.
Both the heating and cooling equipment are running at the same time.
Check for 24 Vac between the heat terminal (W) and transformer common. If 24 Vac is present, the thermostat is functional. Check the heating equipment to find the cause of the problem.
Loose or broken wire connection between thermostat and heating equipment.
Cooling equipment failure. Check for 24 Vac at the equipment on the
Loose or broken wire connection between thermostat and cooling equipment.
Fan Control in Heating is set to System Controls Fan (Setting 0180).
Changeover Valve (ISU 0190) is not configured to match the changeover required by the installed heat pump.
The heating equipment is not a heat pump but the System Type (ISU 0170) is set to Heat Pump.
Heating and cooling wires are shorted together.
Check for 24 Vac between the heat terminal (W) and transformer common. If voltage is not present, check wire connection (loose or broken) between the thermostat and the heating equipment.
secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment to find the cause of the problem.
Check for 24 Vac between the cool terminal (Y) and transformer common. If 24 Vac is present, the thermostat is functional. Check the cooling equipment to find the cause of the problem.
Check for 24 Vac between the cool terminal (Y) and transformer common. If voltage is not present, check the wire connection (loose or broken) between the thermostat and the cooling equipment.
Set Fan Control in Heating to Thermostat Controls Fan (Setting 0180).
Set Changeover Valve (ISU 0190) to match the changeover required by the installed heat pump.
Set System Type (ISU 0170) to match the installed heating and/or cooling equipment.
Separate the shorted heating and cooling wires.
23 63-2675—03
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
Table 12. Troubleshooting. (Continued)
Symptom Possible Cause Action
Heating equipment is running in the cool mode.
Heating equipment is not a heat pump but System Type (ISU 0170) is set to Heat
Set System Type (ISU 0170) to match the installed heating and/or cooling equipment.
Pump.
Heating equipment does not turn off and heat temperature setting is set below room temperature
Heating equipment is not a heat pump but System Type (ISU 0170) is set to Heat Pump.
Set System Type (ISU 0170) to match the installed heating and/or cooling equipment.
(Heat On is not in the display).
Cannot set the system setting to Heat.
System Type (ISU 0170) is set to Cool Only.
Set System Type (ISU 0170) to match the installed heating and/or cooling equipment.
Cannot set the system setting to Cool.
Heat On is not in the display. System setting is not set to Heat and/or
System Type (ISU 0170) is set to Heat Only or Heat Only with Fan.
temperature setting is not set above room
Set System Type (ISU 0170) to match the installed heating and/or cooling equipment.
Set the system setting to Heat and set the temperature setting above the room temperature.
temperature.
Cool On is not in the display. System setting is not set to Cool and/or the
temperature setting is not set below room
Set the system setting to Cool and set the temperature setting below the room temperature.
temperature.
Wait is in the display. Compressor minimum off timer is active. Wait up to five minutes for the cooling or heating
(heat pump) equipment to turn on.
“Screen Locked” appears on the screen and all or some of the
The keypad is fully or partially locked. Check ISU 0670 to change keypad locked
options.
keys do not respond.
Perchlorate Material
This thermostat contains a Lithium battery which may contain Perchlorate material.
The following statement is required: Perchlorate Material—special handling may apply. See www.dtsc.ca.gov/hazardouswaste/perchlorate
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2011 Honeywell International Inc. 63-2675—03 M.S. Rev. 03-11
Printed in U.S.A.
Loading...