Honeywell T7770A, T7770B, T7770C, T7770D, T7770E Installation Instructions Manual

...
Page 1
T7770A,B,C,D,E,F,G
Wall Modules
INSTALLATION INSTRUCTIONS
BEFORE INSTALLATION
Two locking mechanisms are used on the cover of the wall module. After installation, to disassemble the cover and the subbase see Fig. 1.
T7770E
STEP 2
65
70
60
75
55
80
85
auto
0
BUTTON HEAD SOCKET CAP SCREW
STEP 1
M11394
Fig. 1. Cover disassembly.
1
STEP 3
ALLEN TOOL
— Wall module wiring can be sized from 14 to 22 AWG
(2.0 to 0.34 sq mm) depending on the application.
— The maximum length of wire from a device to a wall
module is 1000 ft (305m).
— Twisted pair wire is recommended for wire runs longer than
100 ft (30.5m).
— The cover for the wall module is packed separately from
the subbase for ease of installation.
See Fig. 2 to release/replace the subbase terminal block.
PRESS SHADED AREA OF TAB WITH THUMB TO RELEASE TERMINAL BLOCK FOR EASIER WIRING
M17988
Fig. 2. Releasing/replacing terminal block.
INSTALLATION
CAUTION
Erratic System Operation Hazard. Failure to follow proper wiring practices can introduce disruptive electrical interference (noise).
Keep wiring at least one foot away from large inductive
loads such as motors line starters, lighting ballasts, and large power distribution panels.
Shielded cable is required in installations where these
guidelines cannot be met.
Ground shield only to grounded controller case.
IMPORTANT
All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams.
® U.S. Registered Trademark © 2004 Honeywell International Inc. All Rights Reserved
Mount the T7770A,B,C,D,E,F,G Wall Modules on an inside wall approximately 54 in. (1372 mm) from the floor (or in the specified location) to allow exposure to the average zone temperature. Do not mount the wall modules on an outside wall, on a wall containing waterpipes or near air ducts. Avoid locations that are exposed to discharge air from registers or radiation from lights, appliances, or the sun.
The wall modules can be mounted on a wall, on a standard utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm wall outlet box (see Fig. 3). When mounting directly on a wall, use the type of screws appropriate for the wall material.
95-7538—4
Page 2
T7770A,B,C,D,E,F,G WALL MODULES
STANDARD UTILITY CONDUIT BOX
SUBBASE
NO. 6 SCREW
FRONT COVER
6
5
7
0
6 0
7
5
5 5
8
0
8
5
auto
0
1
BUTTON HEAD SOCKET CAP SCREW
BUTTON HEAD SOCKET CAP SCREW
6
5
7
0
6
0
7
5
5
5
8
0
8
5
auto
0
1
3.5 mm SCREW
FRONT COVER
60 mm WALL OUTLET BOX
SUBBASE
M17989
Fig. 3. Mounting wall modules on standard utility
conduit box or 60 mm wall outlet box.
See Fig. 4 for subbase mounting dimensions.
Wiring
Attach the wires from the device sensor terminals to the appropriate wall module terminals. See Fig. 5 through 16.
NOTE: None of these wall modules are compatible with
W7751A,C,E,G Controllers.
NOTE: Unless otherwise noted, sensor and E-Bus
terminals are not polarized; reversing the two sensor leads does not affect the signal.
Wiring Modules With a Removable Terminal Block
Wire the terminal blocks as follows:
1. For single wires, strip 3/16 in. (5 mm); for multiple wires going into one terminal, strip 1/2 in. (13 mm) insulation from the conductor.
2. If two or more wires are being inserted into one terminal, twist the wires together before inserting.
NOTE: When two or more wires are being inserted
into one terminal, be sure to twist them together. Deviation from this rule can result in improper electrical contact. See Fig. 17.
3. Insert the wire in the required terminal location and tighten the screw to complete the termination.
4. Verify wall module wiring with Fig. 5 through 16.
NOTE: Wire the E-Bus using Level IV 22 AWG (0.34 sq mm)
plenum or non-plenum rated, unshielded, twisted pair, solid conductor wire.
KNOCKOUTS FOR EUROPEAN APPLICATIONS
UTILITY
CONDUIT
HOLES
5-1/16
(128)
2-3/8
(60)
STANDARD
BOX (2 X 4) MOUNTING
CAUTION
Improper Electrical Contact Hazard. Screw type terminal blocks are designed to accept no more than one 14 AWG (2.5 sq mm) conductor.
Connect multiple wires that are 14 AWG (2.5 sq mm) with a wire nut. Include a pigtail with this wire group and attach the pigtail to the individual terminal block.
Wiring Modules Without a Removable Terminal Block
Attach the wires as follows:
1. Connect controller sensor leads to the sensor screw terminals.
NOTE: T7770A1006 have a 20K ohm sensor,
T7770A3002 have a 10K ohm sensor. They are for use in averaging for the T7350. They do not have E-bus network terminals.
2. If the module has E-bus terminals, connect the controller E-bus leads to these screw terminals.
NOTE: Wire the E-Bus using Level IV 22 AWG
(0.34 sq mm) plenum or non-plenum rated, unshielded, twisted pair, solid conductor wire.
95-7538—4 2
2-3/8 (60)
3-3/16 (80)
15/16
(23)
1-1/4 (32)
M17990
Fig. 4. T7770A,B,C,D,E,F,G Subbase
dimensions in in. (mm).
SENSOR SENSOR E-BUS E-BUS
SENSOR
SENSOR
NETWORK
BUS
E-BUS TERMINALS ARE NOT USED FOR C-BUS DEVICES.
NETWORK
BUS
M20359
Fig. 5. Wiring diagram for T7770A20XX Wall Modules.
Page 3
T7770A,B,C,D,E,F,G WALL MODULES
E-BUS TERMINALS
ARE NOT USED FOR
C-BUS DEVICES.
M11400
SETPT
AI COM
(OR) GND
SENSOR
E-BUS
123456789
E-BUS
Fig. 6. Wiring diagram for T7770B10XX Wall Modules.
PRINTED WIRING BOARD DIP SWITCH POSITIONS
LED
BYPASS
SETPT
SENSOR
E-BUS
AI COM
(OR) GND
(S4-1,2,3,4=ON; 5=OFF)
E-BUS
123456789
S4
1
2345
ON
M11401
Fig. 7. Wiring diagram for T7770C10XX Wall Modules
wired to Excel 10 W7750, W7751, W7752.
2
1
BYPASS
LED
1
2
LED
RETURN
BYPASS
RETURN
USING AN EXCEL 20 WITH THIS WALLMODULE REQUIRES WIRING (AT CONTROLLER) THE 1500 OHM BAG ASSEMBLY RESISTOR IN SERIES WITH TERMINAL 7.
TERMINAL 5 IS USED ONLY WITH T7770C MODEL SENSORS.
SETPT
AI COM
SENSOR
NOTE: CHANGE AND VERIFY DIP SWITCH POSITIONS FOR THESE EXCEL CONTROLLERS (S4-1,4=ON; 2,3,5=OFF)
S4
1
123456789
2345
ON
M11402
Fig. 8. Wiring diagram for T7770C10XX, D10XX
Wall Modules wired to Excel 600/500/100/80/20.
NOTE: VERIFY DIP SWITCH POSITIONS
LED
BYPASS
1
1
TERMINAL 5 IS USED ONLY WITH T7770C MODEL SENSORS.
SETPT
SENSOR
GND
E-BUS
(S4-1,3,5=ON; 2,4=OFF)
E-BUS
123456789
S4
1
2345
ON
M11403
NOTES: —T7770E HAS A SINGLE-SPEED FAN
LED
FAN SPEED SWITCH
BYPASS/FAN
SETPT
GND
SENSOR
—T7770F HAS A THREE-SPEED FAN
E-BUS
E-BUS
—VERIFY DIP SWITCH POSITIONS (S4-1,2,3,4=ON; 5=OFF)
123456789
2345
S4
1
ON
Fig. 11. Wiring diagram for T7770E10XX, F10XX
Wall Modules wired to Excel 10 W7752.
NOTES:
1
BYPASS/FAN
LED
LED
RETURN
1
USING AN EXCEL 20 WITH THIS WALL MODULE REQUIRES WIRING (AT CONTROLLER) THE 1500 OHMBAG ASSEMBLY RESISTOR IN SERIES WITH TERMINAL 7.
SETPT
FAN SPEED SWITCH
AI COM
SENSOR
—T7770E HAS A SINGLE-SPEED FAN —T7770F HAS A THREE-SPEED FAN —CHANGE AND VERIFY DIP SWITCH POSITIONS FOR THESE EXCEL CONTROLLERS (S4-2,4=ON; 1,3,5=OFF)
123456789
S4
1
2345
ON
Fig. 12. Wiring diagram for T7770E10XX, F10XX Wall Modules wired to Excel 600/500/100/80/20.
1
FAN
BYPASS
LED
1 TERMINAL 5 IS USED ONLY WITH T7770E,F MODEL SENSORS.
SETPT
FAN SPEED SWITCH
GND
SENSOR
NOTE: —T7770E HAS A SINGLE-SPEED FAN —T7770F HAS A THREE-SPEED FAN —VERIFY DIP SWITCH POSITIONS
E-BUS
E-BUS
(S4-1,3,5=ON; 2,4=OFF)
123456789
S4
1
2345
ON
Fig. 13. Wiring diagram for T7770E10XX, F10XX,
G10XX Wall Modules wired to Excel 10 W7753.
M11407
M11408
M11409
Fig. 9. Wiring diagram for T7770C10XX, D10XX
Wall Modules wired to Excel 10 W7753.
NOTE: VERIFY DIP SWITCH POSITIONS
LED
BYPASS
GND
SENSOR
E-BUS
(S4-1,2,3,4=ON; 5=OFF)
E-BUS
123456789
S4
1
2345
ON
M11404
Fig. 10. Wiring diagram for T7770D10XX Wall Modules
wired to Excel 10 W7750, W7751, W7752.
NOTES:
LED
BYPASS/FAN
FAN SPEED SWITCH
GND
SENSOR
—T7770G HAS A THREE-SPEED FAN
E-BUS
E-BUS
—VERIFY DIP SWITCH POSITIONS (S4-1,2,3,4=ON; 5=OFF)
123456789
S4
1
2345
ON
M11410
Fig. 14. Wiring diagram for T7770G10XX Wall
Modules wired to Excel 10 W7752.
3 95-7538—4
Page 4
T7770A,B,C,D,E,F,G WALL MODULES
1
BYPASS/
FAN
LED
LED
RETURN
1
USING AN EXCEL 20 WITH THIS WALL MODULE REQUIRES WIRING (AT CONTROLLER) THE 1500 OHM BAG ASSEMBLY RESISTOR IN SERIES WITH TERMINAL 7.
FAN SPEED SWITCH
AI COM
SENSOR
NOTES: —T7770G HAS A THREE-SPEED FAN —CHANGE AND VERIFY DIP SWITCH POSITIONS FOR THESE EXCEL CONTROLLERS (S4-2,4=ON; 1,3,5=OFF)
123456789
S4
1
2345
ON
Fig. 15. Wiring diagram for T7770G10XX Wall
Modules wired to Excel 600/500/100/80/20.
T7350 SUBBASE
T4 T3
T3
T4
T7770A3002
THE T7771A3002 IS A 10K OHM SENSOR.
1
T4
11
T7770A3002
T3
M22408
M11411
1.
1/2
(13)
STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
2.
TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
CONTROLLER OR WALL MODULE E-BUS CONNECTOR TERMINALS
3.
CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M11413
Fig. 17. Attaching two wires at wall module terminals.
When all wiring is complete, attach the cover of the T7770A,B,C,D,E,F,G Wall Module by reversing step 3 of Fig. 1. Insert and tighten locking screw by reversing step 1 on Fig. 1.
NOTE: The locking screw must be installed and tight for
a secure T7770 installation.
Fig. 16. Two T7770A3002 Wall Modules wired to a T7350
for temperature averaging.