Mount the T7770A,B,C,D,E,F,G Wall Modules on an inside
wall approximately 54 in. (1372 mm) from the floor (or in the
specified location) to allow exposure to the average zone
temperature. Do not mount the wall modules on an outside
wall, on a wall containing waterpipes or near air ducts. Avoid
locations that are exposed to discharge air from registers or
radiation from lights, appliances, or the sun.
The wall modules can be mounted on a wall, on a standard
utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm
wall outlet box (see Fig. 3). When mounting directly on a wall,
use the type of screws appropriate for the wall material.
95-7538—4
Page 2
T7770A,B,C,D,E,F,G WALL MODULES
STANDARD UTILITY
CONDUIT BOX
SUBBASE
NO. 6 SCREW
FRONT COVER
6
5
7
0
6
0
7
5
5
5
8
0
8
5
auto
0
1
BUTTON
HEAD
SOCKET
CAP SCREW
BUTTON
HEAD
SOCKET
CAP SCREW
6
5
7
0
6
0
7
5
5
5
8
0
8
5
auto
0
1
3.5 mm SCREW
FRONT COVER
60 mm WALL
OUTLET BOX
SUBBASE
M17989
Fig. 3. Mounting wall modules on standard utility
conduit box or 60 mm wall outlet box.
See Fig. 4 for subbase mounting dimensions.
Wiring
Attach the wires from the device sensor terminals to the
appropriate wall module terminals. See Fig. 5 through 16.
NOTE: None of these wall modules are compatible with
W7751A,C,E,G Controllers.
NOTE: Unless otherwise noted, sensor and E-Bus
terminals are not polarized; reversing the two sensor
leads does not affect the signal.
Wiring Modules With a Removable Terminal Block
Wire the terminal blocks as follows:
1. For single wires, strip 3/16 in. (5 mm); for multiple wires
going into one terminal, strip 1/2 in. (13 mm) insulation
from the conductor.
2. If two or more wires are being inserted into one
terminal, twist the wires together before inserting.
NOTE: When two or more wires are being inserted
into one terminal, be sure to twist them
together. Deviation from this rule can result
in improper electrical contact. See Fig. 17.
3. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
4. Verify wall module wiring with Fig. 5 through 16.
NOTE: Wire the E-Bus using Level IV 22 AWG (0.34 sq mm)
plenum or non-plenum rated, unshielded, twisted
pair, solid conductor wire.
KNOCKOUTS FOR
EUROPEAN APPLICATIONS
UTILITY
CONDUIT
HOLES
5-1/16
(128)
2-3/8
(60)
STANDARD
BOX (2 X 4)
MOUNTING
CAUTION
Improper Electrical Contact Hazard.
Screw type terminal blocks are designed to accept
no more than one 14 AWG (2.5 sq mm) conductor.
Connect multiple wires that are 14 AWG (2.5 sq mm)
with a wire nut. Include a pigtail with this wire group
and attach the pigtail to the individual terminal block.
Wiring Modules Without a Removable Terminal Block
Attach the wires as follows:
1. Connect controller sensor leads to the sensor screw
terminals.
NOTE: T7770A1006 have a 20K ohm sensor,
T7770A3002 have a 10K ohm sensor. They
are for use in averaging for the T7350. They do
not have E-bus network terminals.
2. If the module has E-bus terminals, connect the
controller E-bus leads to these screw terminals.
USING AN EXCEL 20 WITH THIS WALL MODULE REQUIRES WIRING (AT
CONTROLLER) THE 1500 OHMBAG ASSEMBLY RESISTOR IN SERIES
WITH TERMINAL 7.
SETPT
FAN
SPEED
SWITCH
AI COM
SENSOR
—T7770E HAS A SINGLE-SPEED FAN
—T7770F HAS A THREE-SPEED FAN
—CHANGE AND VERIFY DIP SWITCH
POSITIONS FOR THESE EXCEL
CONTROLLERS (S4-2,4=ON;
1,3,5=OFF)
123456789
S4
1
2345
ON
Fig. 12. Wiring diagram for T7770E10XX, F10XX
Wall Modules wired to Excel 600/500/100/80/20.
1
FAN
BYPASS
LED
1 TERMINAL 5 IS USED ONLY WITH T7770E,F MODEL SENSORS.
SETPT
FAN
SPEED
SWITCH
GND
SENSOR
NOTE:
—T7770E HAS A SINGLE-SPEED FAN
—T7770F HAS A THREE-SPEED FAN
—VERIFY DIP SWITCH POSITIONS
E-BUS
E-BUS
(S4-1,3,5=ON; 2,4=OFF)
123456789
S4
1
2345
ON
Fig. 13. Wiring diagram for T7770E10XX, F10XX,
G10XX Wall Modules wired to Excel 10 W7753.
M11407
M11408
M11409
Fig. 9. Wiring diagram for T7770C10XX, D10XX
Wall Modules wired to Excel 10 W7753.
NOTE: VERIFY DIP
SWITCH POSITIONS
LED
BYPASS
GND
SENSOR
E-BUS
(S4-1,2,3,4=ON; 5=OFF)
E-BUS
123456789
S4
1
2345
ON
M11404
Fig. 10. Wiring diagram for T7770D10XX Wall Modules
USING AN EXCEL 20 WITH THIS WALL MODULE REQUIRES WIRING
(AT CONTROLLER) THE 1500 OHM BAG ASSEMBLY RESISTOR IN SERIES
WITH TERMINAL 7.
FAN
SPEED
SWITCH
AI COM
SENSOR
NOTES:
—T7770G HAS A THREE-SPEED FAN
—CHANGE AND VERIFY DIP SWITCH
POSITIONS FOR THESE EXCEL
CONTROLLERS (S4-2,4=ON;
1,3,5=OFF)
123456789
S4
1
2345
ON
Fig. 15. Wiring diagram for T7770G10XX Wall
Modules wired to Excel 600/500/100/80/20.
T7350 SUBBASE
T4T3
T3
T4
T7770A3002
THE T7771A3002 IS A 10K OHM SENSOR.
1
T4
11
T7770A3002
T3
M22408
M11411
1.
1/2
(13)
STRIP 1/2 IN.
(13 MM) FROM
WIRES TO BE
ATTACHED AT
ONE TERMINAL.
2.
TWIST WIRES
TOGETHER
WITH PLIERS
(A MINIMUM OF
THREE TURNS).
CONTROLLER OR
WALL MODULE
E-BUS CONNECTOR
TERMINALS
3.
CUT TWISTED END OF WIRES TO
3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING
SCREW. THEN PULL ON EACH WIRE
IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M11413
Fig. 17. Attaching two wires at wall module terminals.
When all wiring is complete, attach the cover of the
T7770A,B,C,D,E,F,G Wall Module by reversing step 3
of Fig. 1. Insert and tighten locking screw by reversing
step 1 on Fig. 1.
NOTE: The locking screw must be installed and tight for
a secure T7770 installation.
Fig. 16. Two T7770A3002 Wall Modules wired to a T7350
for temperature averaging.
Automation and Control SolutionsACS Control Products
Honeywell International Inc.Honeywell Limited-Honeywell LimitéeHoneywell AG
1985 Douglas Drive North35 Dynamic DriveBöblinger Straße 17
Golden Valley, MN 55422Scarborough, OntarioD-71101 Schönaich
M1V 4Z9Phone (49-7041) 637-01
Fax (49-7041) 637-493
95-7538—4 B.B. Rev. 7-04 www.honeywell.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.