Honeywell T775U User Manual

62-0255-07
T775U Series 2000 Electronic Stand-Alone Controller
INSTALLATION INSTRUCTIONS
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote sensing of temperature, humidity, pressure, etc. and providing switched and proportional outputs to various types of loads. A built-in time clock is standard.
The T775U controller allows a wide range of sensors to be configured. Humidity, pressure, temperature, or any 0-5 Vdc, 0-10 Vdc, or 4-20 mA input is supported.
A Reset function is available where the Sensor B temperature (e.g. outside temperature) is used to provide reset control for Sensor A (e.g. humidity). For example, as the outside temperature gets colder, the setpoint can automatically be adjusted to prevent condensation.
IMPORTANT
The T775U is an operating control, not a limit or safety control. If used in applications requiring safety or limit controls, a separate safety or limit
Table 1. T775U Controller Configurations.
Controller
a
Model
T775U2006
T775U2016 N/A Yes 2 2
a
The T775U includes a digital input for use with the disable or setback option.
b
The modulating (analog) outputs may be 4-20 mA, 0-10 Vdc, 2-10 Vdc, or Series 90 selectable.
c
For the H775C1004, H775D1003, and H775E1002 model replacement, the T775U only partially replaces the function of these devices. Check application for suitability.
d
For the sensor inputs, Sensor A can be 0-10Vdc, 4-20mA, or a standard temperature input. Sensor B is a standard temperature sensor input only. Sensor B is used only for reset on the T775U2001.
e
The T775U2016 can control Sensor A (universal) and Sensor B (temperature) independently, like other standard T775 controllers.
Description Replaces
H775A1006 H775A1022
Universal: Humidity, Pressure, Temperature, etc.
H775A1048 H775A1063
H775B1005 H775C1004 H775D1003 H775E1002
Output
Reset
Yes 2 2
c
c
c
control device is required.
SPDT Relay
Outputs
Analog
(Mod)
Outputs
b
Sensor
Sensors
Inputs
Included Enclosure
d
2
e
2
Nbr of
None NEMA 1
None NEMA 1
E4436
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
Temperature Sensorsa (Sensor A or B)
The controller accepts 1,097 Ohms PTC at 77°F (25°C):
• 50021579-001 – Standard sensor (included with all models except NEMA 4X models)
• T775-SENS-WR – Water resistant with 5 foot leads (included with NEMA 4X models)
• T775-SENS-WT – Watertight with 6 foot lead
• T775-SENS-OAT – Outdoor air temperature sensor
• C7031D2003 – 5 inch immersion sensor with wiring box (use immersion well; P/N 50001774-001)
• C7031J2009 – 12 foot duct averaging sensor with wiring box
• C7046D1008 – 8 inch duct probe with mounting flange
• C7100D1001 – 12 inch fast response, duct averaging sensor with flange
• C7130B1009 – Room mount sensor
Differential Pressure Sensors
(Sensor A only)
P7640A and PWT pressure transducer models with selectable pressure ranges can be used.
The controller accepts pressure sensors with a signal output of 0-10 Vdc or 4-20 mA for any output range within the following ranges (the minimum and maximum for the sensor output range can be adjusted within the following limits):
• -500 to 500 PSI
• -30.0 to 30.0 inches w.c.
• -3,000 to 3,000 Pa
• -3,000 to 3,000 kPa
Humidity Sensors (Sensor A only)
The controller accepts 0-10 Vdc or 4-20 mA input with a range of 0-100%.
H7625, H7635, and H7655 models (available in 2, 3, and 5% RH accuracy) can be used.
CO2 Sensors
The controller accepts a 0-10 Vdc or 4-20 mA input from C7232 and C7632 CO units.
sensors and is settable in PPM
2
Universal Sensors (Sensor A only)
The controller accepts 0-5 Vdc, 0-10 Vdc or 4-20 mA input for temperature, pressure, humidity CO be programmed in units of °F, °C, %, Pa, kPa, PSI, In W.C., PPM, or may be unitless (none).
The PPM range is 0 to 9990.
Choosing none for units, results in no units being displayed on the home screen. If no unit is specified the range is -9999 to +9999.
Actuators
For more information on compatible actuators or other Honeywell products, such as dampers and valves, go to www.customer.honeywell.com select Product Selection Tool under Products.
• Spring return models: ML6425, ML7425, MS4105, MS4110, MS4120, MS7505, MS7510, MS7520, MS8105, MS8110, MS8120
• Non-spring return models: ML4161, ML6174, ML7161, MN6105, MN1010, MN7505, ML7164, MN8810
, etc. They may
2
. From the home page
Accessories
• 107324A – Bulb Holder, duct insertion
• 107408 – Heat Conductive Compound, 4 ounce
• 50001774-001 – Immersion Well, stainless steel 304, 1/2 in. threading
Product Changes
Below are the changes to T775U models starting with Series 3 (March 2009). Series 3 can be identified by the sideways 3 after the part number on the device label.
1. Setpoint and Enable options added to the DI options.
2. 0-5 Vdc sensor inputs are now available (for both models).
3. MIN ON time added.
4. HIDE option added to MOD1 and MOD2 (to hide
them on the home screen).
5. PPM and None added to sensors’ unit of measure.
6. With the new T775U2016 model, all outputs can be
controlled to Sensor A or Sensor B. The T775U2006 model controls only to Sensor A.
a
See form 62-0265 – Temperature Sensors for the T775
Series 2000 Stand-alone Controller
62-0255—07 2
Controller Dimensions
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
1 (25.5)
7/8 (22.5)
2 15/16 (74)
LEFT RIGHT
4 1/16 (103.4)
1/64 (3.8)
8 5/32 (207.1)
4 1/16 (103.4)
2 11/16 (68.1)
7/8 (22.5)
7 23/32
(196)
7/8 (22.5)
Fig. 1. T775U Dimensions in inches (mm).
BEFORE INSTALLATION
Review the “Specifications” on page 37 before installing the controller.
When Installing This Product
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard­ous condition.
2. Check ratings given in instructions and on the prod­uct to ensure the product is suitable for your appli­cation.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
INSTALLATION AND SETUP
The following installation procedures are typically performed in the order listed:
1. Mounting — see “Mounting” below.
2. Wiring — see “Wiring” on this page.
3. Checkout — see page 10.
Interface and Programming overview – see page 11.
4.
5. Setup – see page 13.
TOP
4 13/32 (112.1)
3 31/32 (101)
FRONT VIEW
1 (25.5)
BOTTOM
Programming the Controller with no Reset – see page 25
6.
or Programming the Controller with Reset – page 28.
7. Scheduling (optional)— see page 33.
Additional topics are:
• Sensor calibration begins on page 10.
• Interface overview begins on page 11.
• Summary menu begins on page 37.
• Troubleshooting begins on page 37.
1/2 (12.4)
MOUNTING
This section describes the mounting procedures for the controller and temperature sensor(s).
Controller Mounting
IMPORTANT
Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller circuit board, or in areas where escaping gas or other explosive vapors are present.
IMPORTANT
The controller must be mounted in a position that allows clearance for wiring, servicing, and removal.
2 13/16 (71.8)
7/8 (22.5)
M24546
3 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
CAUTION
Use a screwdriver to pry out only the knockouts that you will use.
If mounting on DIN rail, be sure to remove the knockouts before mounting. See “Controller Wiring” on page 7 and Fig. 12 on page 9 for recommended knockout usage and locations. If you do not use an opened knockout be sure to cover it.
Mount the controller on any convenient interior location using the four mounting holes provided on the back of the enclosure using #6 or #8 screws (screws are not provided and must be obtained separately). Use controller dimensions in Fig. 1 on page 3 as a guide.
The controller may be mounted in any orientation. However, mounting in the orientation shown in Fig. 1 on page 3 permits proper viewing of the LCD display and use of the keypad.
Humidity, Pressure, and Universal Sensor(s) Mounting and Location
These sensors may be mounted on a wall or panel. Follow the installation instructions specific to the sensor you are installing.
Temperature Sensor(s) Mounting and Location
Temperature sensors may be located up to 1,000 feet (304 m) from the T775U controller. See Table 4 on page 11 for calibration guidelines.
The sensors may be mounted on a wall or panel for sensing space temperature, strapped to a pipe or inserted in an immersion well (see Fig. 2) for hot or cold water sensing, or taped to a standard cap or bulb holder for duct air sensing. To prevent moisture or condensation entering the sensor through the lead wire holes, mount the sensor with the lead wires exiting the bottom of the sensor.
NOTES:
1. The included sensor is not designed for very
wet applications. For immersion applications, an immersion well is used.
2. Heat conductive compound must be used in
immersion wells.
3. See “Temperature Sensors (Sensor A or B)”
on page 2 for this type of installation.
SENSOR
PLACED IN WELL
USE HEAT
CONDUCTIVE
COMPOUND
WIRING
All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Controller wiring is terminated to the screw terminal blocks located inside the device.
The remainder of this section describes the sensor wiring and the T775U controller wiring.
Wiring Connections Access
To access the wiring connections, remove the two screws on the left side of the enclosure and gently swing open the top. Be careful to not stress the ribbon cables that connect the keypad and LCD display to the controller circuit board.
Temperature Sensor Wiring
Electrical Shock Hazard. Can short equipment circuitry.
Make sure that metal tube of sensor does not short against T terminals in wall-mounted case.
IMPORTANT
Poor wiring practices can cause erratic readings from the sensor. Avoid the following to ensure proper operation:
• Do not route the temperature sensor wiring with building power wiring.
• Do not locate the temperature sensor wiring next to control contactors.
• Do not locate the temperature sensor wiring near electrical motors.
• Do not locate the temperature sensor wiring near welding equipment.
• Make sure good mechanical connections are made to both the sensor and the controller.
• Do not mount the sensor with the lead wire end pointing up in an area where condensation can occur.
If any of the above conditions cannot be avoided, use shielded cable.
NOTE: Each T775 controller must be wired to its own
sensor(s). However, a benefit of the T775 controller’s accuracy is that there is no more than a 2°F differential between any two T775 controllers.
1/2 NPT
Fig. 2. Sensor inserted in immersion well.
NOTE: Multiple sensors may be parallel-series wired to
sense average temperatures in large spaces. See Fig. 3 on page 5.
62-0255—07 4
IMMERSION WELL
M24379
Reset Temperature Control
If you are implementing two-sensor reset control, Sensor A must always be the controlled temperature and Sensor B must always be the controlling temperature.
For example, in a reset control based on outside temperature, Sensor A must be the inside sensor and Sensor B must be the outside sensor.
Multiple Parallel Temperature Sensors
Multiple sensors can be parallel-series wired to sense average temperatures in large spaces. To maintain control accuracy, the number of sensors to be parallel­series wired must be of the n 16, etc.). See Fig. 3.
2
power (for example, 4, 9,
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SENSORS
TO T775 CONNECTIONS (SENSOR A) OR (SENSOR B).
M24548
Fig. 3. Parallel-series wiring of sensors.
T T
T T
Temperature Sensor Wire Type and Size
Temperature sensors use standard AWG 18/2 unshielded wire. For cable runs greater than 25 feet or where electrical interference may be a problem, shielded cable is recommended. See Fig. 4.
Refer to “Temperature Sensor Calibration” on page 10 for wire size selection where cable runs are longer than 25 feet.
SHIELDED CABLE
SENSOR A
1
SENSOR B
2
NOTE: SHIELDED CABLE MUST BE CONNECTED TO A SEPARATE EARTH GROUND. HOWEVER, DO NOT GROUND SHIELDED CABLE AT SENSOR END.
SHIELDED CABLE
SENSOR
NOTE: TO MINIMIZE NOISE PICKUP, MAKE SENSOR CONNECTION FROM SHIELDED CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY.
SENSORS A AND B ARE POLARITY INSENSITIVE WHEN USING A 1097 OHM PTC TEMPERATURE SENSOR.
1
SENSOR B IS USED ONLY IN RESET APPLICATIONS ON THE T775U20006.
2
Fig. 4. Sensor Wiring — 2-wire shielded cable connection from Sensor A to temperature sensor.
Humidity, Pressure, and Universal Sensor Wiring
Sensors with a 0-5 Vdc, 0-10Vdc or 4-20mA input to the T775U must be wired to the Sensor A terminal. Sensor B is used only as a temperature input.
Sensors use standard AWG 18 unshielded wire. For cable runs greater than 25 feet, shielded cable is recommended.
The sensors in Fig. 5 – 8 beginning on page 6 are examples and illustrate voltage and current wiring for 3­wire and 2-wire sensors to the Sensor A terminal. For terminal wiring details, see Fig. 11 and Table 2 on page 8. Other sensors are supported. See sensor descriptions on page 2.
NOTES:
1. Other transmitters can be wired in the same
manner. For example, the 0-10Vdc wiring shown in Fig. 5 on page 6 with the H76XX sensor can also be done with the P7640 or any other transmitter.
2. The T775U V terminal outputs 18 Vdc.
5 62-0255—07
M24549A
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SHIELDED CABLE
C S
SENSOR A
V
1
T
SENSOR B
T
1
THE T775U WILL ONLY ACCEPT 0-10 VDC AND 4-20 MA SENSORS. IF REPLACING AN H775 CONTROLLER THAT USES A C7600B OR OTHER 2-10 VDC SENSOR, THE SENSOR MUST BE REPLACED. REPLACE THE C7600B2008 SENSOR (2-10VDC OUTPUT) WITH THE H7655A1001 (0-10 VDC OUTPUT) SENSOR. THE H7655A1001 SENSOR USES THE SAME ENCLOSURE STYLING AND WIRING AS THE C7600B.
Fig. 5. Sensor Wiring — 3-wire shielded cable connection from Sensor A to 0-10 Vdc sensor
(H76xx humidity sensor shown).
C
3
S
SENSOR A
V T
SENSOR B
T
NOTES:
1. SHIELDED CABLE MUST BE CONNECTED TO A SEPARATE EARTH GROUND. HOWEVER, DO NOT GROUND SHIELDED CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP, MAKE SENSOR CONNECTION FROM SHIELDED CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY.
CSV
EXAMPLE OF
VO
GND
VIN
H76XX HUMIDITY SENSOR; 0-10 VDC CONNECTION
SHIELDED CABLE
2
V
PWR
OUT
1
S
COM
M24550
SHIELDED CABLE
C S
SENSOR A
V T
SENSOR B
T
Fig. 7. Sensor Wiring — 2-wire shielded cable
connection from Sensor A to a 0-10 Vdc sensor
using separate transformer.
EXAMPLE OF P7640A 4-20 MA SENSOR CONNECTION
PWR ZEROCOMOUT
NOTES:
1. SHIELDED CABLE MUST BE CONNECTED TO A SEPARATE EARTH GROUND. HOWEVER, DO NOT GROUND SHIELDED CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP, MAKE SENSOR CONNECTION FROM SHIELDED CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY.
EXAMPLE OF
P7640A
PRESSURE
SENSOR; 0-10 VDC
CONNECTION
L1
(HOT)
L2
24 VAC
PWR
S
OUT
C
COM
M24551
1
SHIELDED CABLE MUST BE CONNECTED TO A SEPARATE EARTH GROUND. DO NOT GROUND SHIELDED CABLE AT SENSOR END.
TO MINIMIZE NOISE PICKUP, MAKE SENSOR CONNECTION FROM SHIELDED
2
CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY.
THE T775 HAS AN INTEGRAL LOAD OF 500 OHMS WHICH RESULTS IN A
3
10V DROP AT 20MA. TO USE 4-20MA LOOP POWERED WIRING, THE SENSOR MUST BE CAPABLE OF OPERATION WITH 8V OR LESS ACROSS ITS TERMINAL.
Fig. 6. Sensor Wiring — 2-wire shielded cable
connection from 4-20 mA sensor to
T775 controller (loop powered wiring).
M24890C
62-0255—07 6
12-30 VDC
SHIELDED CABLE
C S V T T
Fig. 8. Sensor Wiring — 2-wire 4-20mA sensor input
to T775 controller using a separate (Vdc only)
S
SENSOR A
SENSOR B
transformer.
POWER SUPPLY
+ –
C
NOTES:
1. SHIELDED CABLE MUST BE CONNECTED TO A SEPARATE EARTH GROUND. HOWEVER, DO NOT GROUND SHIELDED CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP, MAKE SENSOR CONNECTION FROM SHIELDED CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY.
M24889A
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
WARNING
CAUTION
CAUTION
CAUTION
Controller Wiring
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.
Do not use 24 Vac power to power any external loads if 120 Vac or 240 Vac is used to power the T775U.
A separate earth ground is required.
Equipment damage can result if the earth ground is not connected. See Fig. 9 and Table 2 on page 8.
Equipment Damage Hazard. Electrostatic discharge can short equipment circuitry.
Ensure that you are properly grounded before handling the unit.
1
See Fig. 11 on page 8 for locating the appropriate power input, remote sensors input, low voltage, contact closure, and load output terminals.
Access to the terminals can be gained through standard conduit knockouts (A through E in Fig. 11 on page 8) located around the perimeter of the enclosure:
• Knockouts A and B should be used only for sensor and low-voltage wiring.
• Knockouts C, D, and E can be used to gain access to the load relay output terminals and 120/240 Vac power wiring.
Controller Wiring Method
Wire the sensors and outputs, then wire the power connection.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 14 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
For 24, 120, or 240 Vac power connections:
Single wire – from 14 to 18 AWG solid or stranded
Using Fig. 10 on page 7 as a guide, prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire
in the required terminal location and tighten the screw.
3. If two or more wires are being inserted into one ter­minal location, twist the wires together a minimum of three turns before inserting them to ensure proper electrical contact.
4. Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tighten­ing the screw.
5. Pull on each wire in all terminals to check for good mechanical connection.
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
1/2 (13)
C
W
NO HIGH VOLTAGE. CLASS 2 WIRING ONLY.
1
EARTH GROUND TERMINAL MUST BE CONNECTED
2
TO CONDUIT CLAMP LOCALLY.
+
2
Fig. 9. Earth Ground.
IMPORTANT
Poor wiring practices can cause erratic readings from the sensor. To ensure proper operation, ensure that good mechanical connections are made to both the sensor and the controller.
IMPORTANT
When wiring the input power, only one source of power can be applied to the T775U (24 Vac or 120 Vac or 240 Vac).
M24296
2. TWIST WIRES
TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M24552
Fig. 10. Attaching two or more wires at terminal
7 62-0255—07
blocks.
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
Controller Wiring Details
The wiring connection terminals are shown in Fig. 11 and are described in Table 2. See Fig. 12 – Fig. 18 beginning on page 9 for typical T775U wiring applications.
Fig. 11. T775U Terminal and Feature Locations.
KNOCKOUT A
C
MOD 1
2
MOD 2
DIGITAL
INPUT
KNOCKOUT B
POWER
3
24 VAC
OUTPUT RELAY 1
KNOCKOUT C
NO
C
NC
KNOCKOUT E
T
S
+
T
V T T
NO
C
NC
B
R
+
W B
R
+
W
+
C
+
120
COM
240
SENSOR A
1
SENSOR B
POWER 120/240 VAC
OUTPUT RELAY 2
KNOCKOUT D
1
WHEN USED FOR TEMPERATURE OR 4-20mA SENSING, SENSORS A AND B USE THE TWO TT CONNECTIONS AND ARE POLARITY INSENSITIVE.
2
FOR MOD 1 AND MOD 2 CURRENT (mA) OR VOLTAGE (VDC) OUTPUT, USE SIGNAL (+) & COMMON (-). FOR MOD 1 AND MOD 2 SERIES 90 OUTPUT, USE W, R, & B.
3
A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER SOURCE (24, 120, OR 240 VAC)
M24553A
Table 2. Description of Wiring Terminal Connections.
Connection
Ter mi nal
Label Description Connection Terminal Label Description
Sensors Outputs
C – common S – signal V – voltage
a
Sensor A
S and V 4-20mA input; see Fig. 7 on
T T
Sensor B T T Temperature Sensor; polarity
0-10 Vdc input: Universal
sensor for humidity, pressure,
temperature, etc.
Mod 1
Mod 2
+ - (Vdc or mA) W R B (Series 90)
page 6 24 Vac Power
Temperature Sensor; polarity
insensitive
insensitive
24V + + 24 Vac Hot
Common - 24 Vac Common
Ground
120 or 240 Vac Power
Modulating Output
b
Earth Ground
Input 120 Vac 120 120 Vac Power
DI + - Digital Input (dry contact) Common COM Common
Outputs 240 Vac 240 240 Vac Power
Relay 1 NO / COM /
Relay 2
a
For applications that do not use Reset, only Sensor A is available for use.
b
For Series 90 connections, you must insert a 340 Ohm resistor across terminals R and W. See Fig. 17 on page 10. The resistor is included with the controller.
c
A separate earth ground is required for all installations regardless of the power source (24, 120, or 240 Vac).
62-0255—07 8
NC 120-240 Vac Relay Output
c
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
WIRING APPLICATION EXAMPLES
Fig. 12 – 18 illustrate typical controller wiring for various applications.
NOTE: The electronic Series 90 output provided with
modulating T775 models can not drive electro­mechanical slidewire devices like older Series 3 modulating meters (prior to Series 6), V9055s, and S984s.
NOTE: For a wiring example of three Series 90 Modutrol
Motors, refer to the T775A/B/M Series 2000 Electronic Stand-alone Controllers Installation Instructions (form 62-0254).
C
T
1
S
+
T
V
L1
(HOT)
L2
LOAD 1
LOAD 2
24 VAC
NO
COM
C
+
NO
C
NC
NO
C
NC
C
T
S
+
T
1
V
C
+
NO COM
Fig. 14. Wiring for Two-stage Control with 120 or 240
NO
C
NC
FOR SPECIFIC SENSOR WIRING (TEMPERATURE, HUMIDITY,
1
PRESSURE, ETC), REFER TO THE SENSOR WIRING SECTIONS BEGINNING ON PAGE 4.
FOR 240 VAC LOAD, CON NECT TO 240 TERMINAL .
2
NO
C
NC
Vac (120 Vac Input and 120 Vac Load).
120V COM
2
120
240
COM
NO
LOAD 2
COM
LOAD 1
M24555A
COM
NO
FOR SPECIFIC SENSOR WIRING (TEMPERATURE, HUMIDITY,
1
PRESSURE, ETC), REFER TO THE SENSOR WIRING SECTIONS BEGINNING ON PAGE 4.
Fig. 12. Wiring for Two-stage Control – 24 Vac Input
HONEYWELL MODUTROL MOTOR WITH 4-20 mA MODULATING INPUT
T1 T2
POWER
OUTPUT
1
MODULATING OUTPUT TERMINAL (MOD 1)
USE SEPARATE TRANSFORMER FOR T775 WHEN USING 24 VAC.
1
Fig. 13. Wiring for mod motor or direct coupled
actuator with 4 to 20 mA control input.
+
and 24 Vac Load.
B
R
+
W B
R
+
W
M24554A
M24557A
INPUT
– +
M24559
DIGITAL
Fig. 15. Wiring for Digital Input (dry contact).
HONEYWELL MODUTROL MOTOR WITH VOLTAGE CONTROL INPUT
+
T1 T2 C R
1
POWER OUTPUT
MODULATING OUTPUT TERMINAL (MOD 1)
Fig. 16. Wiring for mod motor or direct coupled
9 62-0255—07
F
B
R
+
W B
R
+
W
1
USE SEPARATE TRANSFORMER FOR T775 WHEN USING 24 VAC.
actuator with 0-10 Vdc control input.
M24558A
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
WARNING
HONEYWELL ELECTRONIC SERIES 90 MODUTROL MOTOR
T1 T2 B WR
POWER
OUTPUT
2
MODULATING OUTPUT TERMINAL (MOD 1)
1
TO VERIFY OUTPUT, TEST OPEN CIRCUIT VOLTAGE BETWEEN THE MOD 1 TERMINALS W AND R.
- MINIMUM (DRIVE CLOSED) SIGNAL LESS THAN 0.17 VDC
- MAXIMUM (DRIVE OPEN) SIGNAL IS GREATER THAN 1.7 VDC
2
USE SEPARATE TRANSFORMER FOR T775 WHEN USING 24 VAC.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
3
1
B R
W
W
3
+
B R
+
M24560A
Fig. 17. Wiring for Series 90 Modutrol Motor Control.
HONEYWELL
ELECTRONIC SERIES 90
MODUTROL MOTOR
T1 T2 B WR
1
POWER
OUTPUT
MODULATING OUTPUT TERMINAL (MOD 1)
1
USE SEPAR AT E TRANSFORM ER FOR T775 WHEN USIN G 24 VAC.
A 250 OHM RES ISTOR PROVIDES 40% AUTH ORITY WHEN
2
USING A 150 OH M MINIMUM POSIT ION POTENTIOME TER.
3
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
Fig. 18. Wiring for Changeover Relay and
Minimum Position Potentiometer used with
MINIMUM POSITION
POTENTIOMETER
(Q209)
W R B
B
R
+
W B
R
+
W
SPDT CHAN GEOVER
2
3
Series 90 Modutrol Motors.
(H205 OR H705)
M24561A
CHECKOUT
Inspect all wiring connections at the controller terminals, and verify compliance with the installation wiring diagrams.
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring or making wiring connections, to prevent electrical shock or equipment damage.
If any wiring changes are required, first be sure to remove power from the controller before starting work. Pay particular attention to verifying the power connection (24, 120, or 240 Vac).
After the controller is mounted and wired, apply power.
Power Loss
The date and time settings are retained for 24 hours after a power outage. After a power loss of more than 24 hours, the date and time settings may need to be reentered. All other settings are stored permanently.
Humidity, Pressure, and Universal Sensor Calibration
A calibration parameter is available using Setup mode. The calibration range is +/- 10% of the Min Value to Max Value range setup for the sensor. See examples in Table 3.
Table 3. Calibration Range Examples.
Units
Min.
Value
Example
Max.
Valu e
Example
Min-Max
Range Result
Calibration
Range
PSI 100 400 300 ± 30 PSI
Inches W.C.
Pa or kPa
-20.0 20.0 40 ± 4 in. W.C.
-2,000 3000 5000 ± 500 Pa/kPa
% 10 100 90 ± 9%
The calibration value is set in section “1.2.2.3. CALIBRATE (Sensor A or B)” on page 16.
Temperature Sensor Calibration
As wire length increases, resistance increases and thus the temperature reading increases. If necessary, calibrate the sensor input by reducing the value by the amount shown in the Table 4 on page 11. For example, a wire run with 18 gauge wire of 1,000 feet, requires a calibration offset of -6.0°F.
IMPORTANT
If the calibration value in the table exceeds the controller’s calibration limits of +/-10°F (+/-6°C), you must use a heavier gauge wire.
For example, with a wire run of 1,000 feet you must use 20 AWG wire or heavier in order to cal­ibrate for wire loss within the limits of the control­ler.
See “1.2.2.3. CALIBRATE (Sensor A or B)” on page 16 for the instructions to enter the calibration value.
NOTE: The resistance output on the temperature
sensors change at the rate of 2.2 Ohms per °F (3.85 Ohms per °C).
62-0255—07 10
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
Table 4. Temperature Sensor Calibration for
Resistance Loss due to Wire Length.
AWG
Rating mΩ/ft
Temperature Offset in
200 ft 500 ft 1,000 ft
°F (Feet)
a
14 2.5 0.46 1.14 2.28
16 4.0 0.72 1.82 3.64
18 6.4 1.16 2.90 5.82
20 10.2 1.86 4.64 9.28
22 16.1 2.92 7.32 14.64
AWG
Rating mΩ/m
Temperature Offset in
°C (Meter)
100 m 200 m 300 m
a
14 8.3 0.44 0.86 1.30
16 13.2 0.68 1.38 2.06
18 21.0 1.10 2.18 3.28
20 33.5 1.74 3.48 5.22
22 52.8 2.74 5.48 8.22
a
This is the distance from the controller to the sensor (already accounts for round trip distance).
Fig. 19 shows how sensor resistance varies with temperature for a sensor having a positive temperature coefficient (PTC) of 2.1 Ohms per degree F (3.85 Ohms per degree C).
RESISTANCE (OHMS)
1489
1403
1317
1231
1145
1059
973
887
801
-40 -20 -10-30
1
20 40 60 80 100 120 140 160 180 200 220
0-20-40
POSITIVE TEMPERATURE COEFFICIENT (PTC) OF 2.1 OHMS PER °F
1097 ± 0.08 OHMS AT 77°F (25°C)
1
0 10 20 30 40 50 60 70 80 90 100
TEMPERATURE (DEGREES)
250
110
120
M24304
Fig. 19. Sensor Resistance vs. Temperature.
INTERFACE OVERVIEW
The T775U controller uses an LCD panel and 6-button keypad to provide status information and permit user input of the programming, setup, and scheduling parameters.
The following figure describes the display areas of the LCD and the keypad.
RELA
HOME
YS 1 2
MENU AREA
ON
SENSORS
SENSOR A
78
SENSOR B
84
o
F
o
F
DATA AREA
MOD1 40% MOD2 60% DI ON
home menu
LOCK ICON
6 BUTTON KEYPAD
M24563
Fig. 20. LCD Display - Home Screen And Keypad.
Menu Area – On the home screen, the LCD displays the
configured relays and whether they are active. In Program, Setup or Schedule mode, the LCD displays the current menu selection and its order within the menu hierarchy.
Data Area – On the home screen, the LCD displays the sensors and outputs status. In Setup or Program mode, the LCD displays menu choices, parameter selections, and data values.
Lock Icon – The icon indicates the MENU button is locked and prevents access to the Setup and Program menus.
NOTE: Pressing and holding the HOME and MENU but-
tons simultaneously for five seconds locks/ unlocks the MENU button.
6-Button Keypad – The keypad is used to access the menus and enter values (see “Using the LCD Panel Interface”).
Using the LCD Panel Interface
The 6-button keypad is used to move through the menus and enter or change parameter values.
°F
Home Button
°C
Pressing the HOME button at any time exits the current Programming or Setup display screen and returns to the home screen as shown in Fig. 20 and Fig. 21.
Menu Button
• Pressing the MENU button always displays the Program menu. If you are in Setup mode, you exit setup and return to the Program menu.
• Pressing and holding the MENU button for five seconds leaves the current screen and displays the Setup menu.
Left and Right Arrow Buttons (W and X)
Use these buttons to move backward (W) and forward (X) through the Program and Setup menus.
11 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
Up and Down Arrow Buttons (S and T)
Use these buttons to move your selection up and down through a menu or list.
• When the desired item is highlighted, you press the X
arrow button to display that item’s content.
• When a value is displayed (e.g. 70°F), the up and down arrows increase and decrease the value.
NOTE: Once you select an item from a list or enter a
value, pressing the W or X or HOME button accepts your selection or value and stores it in the controller’s memory.
Program, Schedule, and Summary Menus
To access these menus from the home screen, press the MENU button. See Fig. 22.
Home Screen
In the normal run state, the LCD home screen displays the current sensed temperatures, the modulating outputs status, the active status of the output relays, and error and status codes.
When using Reset, the Heat/Cool setpoint(s) display on the home screen for the Mod and Relay outputs; see Fig. 21.
Active relays are indicated by the small black square () just below the relay number. Fig. 21 shows the home screen with relay 2 energized.
Pressing the W and X buttons from the home screen cycles through each modulating output that is paired with the sensor it controls and the active output relays.
HOME RELAYS 1 2 ON
SENSORS SENSOR A
78
SENSOR B 84
MOD1 40% MOD2 60%
DI ON
Fig. 21. LCD Display - Home Screen Displaying
Sensors, Mod Outputs, and Active Relays.
NOTES:
1. The modulating output home screen and the
2. In Reset mode, the home screen displays the
IMPORTANT
After four minutes of inactivity (no buttons pressed), the LCD display reverts to the home screen display.
HOME RELAYS 1 2 ON
MOD 1 40% COOL
o
F
SETPOINT
74
o
F
SENSOR A 62
MOD1 40% MOD2 60%
DI ON
relay home screen do not dynamically update the active relay status, sensor values, and modulating output percentages. The informa­tion is a snapshot taken when you press the W or X button to display the screen.
effective setpoint.
o
F
o
F
HOME RELAYS 1 2 ON
REL 2 ON
HEAT SETPOINT
60
SENSOR A 62
RT 12345 HRS
MOD1 40% MOD2 60%
DI ON
Accessing the Menus
Menus are used for programming, scheduling, viewing the summary settings, and setup of advanced options.
62-0255—07 12
Depending on whether scheduling is enabled or not, the LCD displays one of two menus as shown in Fig. 22. Scheduling is enabled from the Setup menu’s Output settings (see “1.3.3.1. USE SCHED” on page 21).
Setup Menu
To access the Setup menu, press and hold the MENU
o
F
button for five seconds. See Fig. 23.
o
F
M24564
Using the Menus
When you are working with the menus, use the:
• Left arrow button (W) to scroll backward through the
• Right arrow button (X) to select the highlighted menu
• Up and Down arrow buttons (S and T) to scroll up
OR
MENU DISPLAY WHEN
SCHEDULING IS NOT SET
MENU
PROGRAM
EXIT
HOME RELAYS 1 2 ON
SENSORS SENSOR A
78
SENSOR B
84
MOD1 40% MOD2 60%
DI ON
menu
home
MENU DISPLAY WHEN
SCHEDULING IS SET
PROGRAM
SCHEDULE
o
F
SUMMARY EXIT
o
F
MENU
Fig. 22. Menus.
HOME RELAYS 1 2 ON
SENSORS SENSOR A
78
SENSOR B
84
MOD1 40% MOD2 60%
DI ON
menu
home
o
F
o
F
SECONDS
FIVE
SETUP
SENSORS
OUTPUTS EXIT
M24566
Fig. 23. Setup Menu.
menus
item and display its content
and down through a list of items or to increase or decrease the value of a displayed parameter
M24565
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
NOTES:
1. If you press the HOME button or there is no keypad activity for four minutes, you exit Program mode and return to the home screen.
2. If you press the MENU button, you exit and return to the menu.
PROGRAMMING OVERVIEW
The controller must be programmed before being placed into service.
IMPORTANT
During programming, the controller is live at all times. For example, the contacts may open and close when adjusting the setpoint.
The Programming process uses a hierarchical menu structure that is easy to use. You press the W and X arrow buttons to move forward and backward through the menus.
NOTES:
1. The T775U controller interface is intuitive. You may find that you do not need the follow­ing procedure instructions to program the controller. You may want to use this proce­dure simply as a reference to locate the par­ticular option or parameter of interest.
2. The menus can display only those relays that are defined in Setup (see “1.3.2. NBR OF RELAYS” on page 21). For example, if you configure only one relay, then only one relay displays on the appropriate menus.
3. If you press the HOME button or there is no keypad activity for four minutes, you exit Pro­gram mode and return to the home screen.
4. If you press the MENU button, you exit Program mode and return to the menu.
Setpoint and Differential
The following describes the relationship between setpoint and differential for heating and cooling. These settings are programmed for each output relay.
In heating mode, reverse acting mode, and humidify mode, the differential falls below the setpoint. The relay
de-energizes when the temperature rises to the setpoint. As the temperature drops to the setpoint minus the differential, the relay energizes.
In cooling mode, direct acting mode, and dehumidify mode, the differential falls above the setpoint. The relay
de-energizes when the temperature falls to the setpoint. As the temperature rises to the setpoint plus the differential, the relay energizes.
IMPORTANT
1. This action sets the maximum setpoint value of all outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is irre- versible. If you perform the action inadvertently and this setpoint adversely affects the control of your system, you must replace the controller.
Programming the T775U Controller
To program the controller, perform the setup configuration (see “1. Setup”) and then select one of the following procedures depending on whether the Reset function is to be used:
• Program the Outputs for No Reset — see “2. Programming Outputs (MOD and Relay) with No Reset” on page 25.
• Program the Outputs for Reset — see “3. Programming Outputs (MOD and Relay) with Reset” on page 28.
When programming is complete, you may continue with “4. Scheduling” on page 33.
1. SETUP
Setup provides the ability to change the factory default settings for the temperature sensors and outputs, to enable/disable reset control, and to enable/disable scheduling.
NOTE:
1. The T775U controller interface is intuitive. You may find that you do not need the follow­ing setup instructions for the sensors and out­puts. You may want to use this procedure simply as a reference to locate the particular option or parameter of interest.
2. If you press the HOME button or there is no keypad activity for four minutes, you exit Setup mode and return to the home screen.
3. If you press the MENU button, you exit Setup mode and return to the menu.
Once in Setup mode, you use the —
• Left arrow button (W) to scroll backward through the
Setup menus
• Right arrow button (X) to select the highlighted menu
item and display its content
• Up and Down arrow buttons (S and T) to scroll up
and down through a list of items or to increase or decrease the value of a displayed setup parameter
Setpoint High Limit
You can set an irreversible setpoint high limit maximum value for any single displayed setpoint value.
Adjust the setpoint (at any output) to the desired maximum setpoint. Then, simultaneously press the HOME, W, and X buttons and continue to press all three buttons for five seconds to set the setpoint high limit maximum to this value.
NOTE: You must press all three buttons at exactly the
same time for this action to occur.
13 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
Setup Procedure
The Setup process uses a hierarchical menu structure that is easy to use. You press the W and X arrow buttons to move forward and backward through the menus.
NOTE: The menus can display only those relays that
are defined in Setup (see “1.3.2. NBR OF RELAYS” on page 21). For example, if you con­figure only two relays, then only two relays dis­play on the appropriate menus.
SETUP
SENSORS
Fig. 24. Setup - Sensors Menu.
SETUP SENSORS
# SENSORS
Fig. 25. Setup - Sensors - Number of Sensors.
SETUP
SENSORS
# SENSORS
SENSOR A SENSOR B EXIT
SETUP
SENSORS
# SENSORS
ENTER
NUMBER OF
SENSORS
M24586
2
M24587
To change the controller’s sensors and output setup parameters, perform the following procedures in the order listed:
1. Enter Setup mode — see “1.1. Entering Setup Mode”
2. Setup Sensors — see “1.2. Setting up the Sensors”
3. Setup Outputs — see “1.3. Setting up the Outputs”
on page 17
4. Exit Setup Mode — see “1.4. Exiting Setup” on page 24
1.1. Entering Setup Mode
To enter Setup mode, press and hold the MENU button for five seconds to display the Setup menu. See Fig. 23 on page 12.
1.2. Setting up the Sensors
1. From the Setup menu, use the S and T buttons to
highlight SENSORS.
2. Press the X button to display the Sensors menu.
1.2.1. Number of SENSORS
The value entered here determines the number of sensors displayed on the home screen.
NOTE: For applications that do not use Reset, only one
sensor (Sensor A) is available for use.
1.
From the Sensors menu, highlight # SENSORS then
X
press the
2. Use the S and T buttons to enter the number of sensors (1 or 2).
3. Press the X button to accept the value and display the SENSOR A selection.
button to display the number of sensors.
Default: 2
SENSOR A
TYPE = 0-5V, 0-10V,
OR 4-20MA
SETUP SENSORS SENSOR A
TYPE
UNITS MIN VAL MAX VAL CALIBRATE LABEL EXIT
M24588A
1.2.2. SENSOR A
If you are implementing two-sensor reset control, Sensor A must always be the controlled temperature and Sensor B must always be the controlling temperature. For example, in a reset control based on outside temperature, Sensor A must be the inside sensor and Sensor B must be the outside sensor.
The menu selections change depending on whether the sensor type is 1097Ω PTC (temperature) or 0-10V / 4­20MA.
SETUP SENSORS
SENSOR A
SENSOR A
TYPE = PT1000
SETUP SENSORS SENSOR A
TYPE
UNITS CALIBRATE LABEL EXIT
Fig. 26. Setup - Sensors - Sensor A Menu.
62-0255—07 14
1. From the Sensors menu, highlight SENSOR A.
2. Press the X button to display the Sensor A selec-
tions.
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
A
SETUP SENSORS SENSOR A
TYPE
SENSORS SENSOR A
PT 1000
0-5V 0-10V 4-20MA
TYPE FOR SENSOR A
SETUP
TYPE
SELECT
Fig. 27. Setup - Sensors - Sensor A - Type.
SETUP SENSORS SENSOR A
UNITS
SENSORS SENSOR A
DEG F
DEG C
UNITS FOR SENSOR A
SETUP
UNITS
SELECT
Fig. 28. Setup - Sensors - Sensor A - Units.
1.2.2.1. TYPE (Sensor A only)
1. From the Sensor A selections, use the S and T
buttons to highlight TYPE.
2. Press the X button to display the type values.
3. Use the S and T buttons to highlight the desired
value PT1000 (1097Ω PTC), 0-5V, 0-10V, or 4­20MA.
Default: PT1000
NOTE: The default label PT1000 refers to a 1097Ω PTC
temperature sensor.
M24589
4. Press the X button to accept the units and return to
the Sensor A selections.
5. For PT1000 (1097Ω PTC) temperature sensors, go
to “1.2.2.2.1. UNITS (Sensor A or B; PT1000 [1097W PTC)]”. For 0-5V, 0-10V, and 4-20MA sensors, go to “1.2.2.2.2. UNITS (Sensor A only; 0-5V, 0-10V, or 4­20mA)”
1.2.2.2.1. UNITS (Sensor A or B; PT1000
[1097Ω PTC)]
If Sensor A is configured for °F or °C units, then the units selection does not appear for Sensor B, since Sensor B uses the units specified for Sensor A.
1. From the Sensor A selections, use the S and T
buttons to highlight UNITS.
2. Press the X button to display the temperature units.
3. Use the S and T buttons to highlight F or C.
Default: F (Fahrenheit)
M24590
4. Press the X button to accept the units and return to
the Sensor A selections.
Continue with “1.2.2.3. CALIBRATE (Sensor A or B)”.
SETUP SENSORS SENSOR A
UNITS
SENSORS SENSOR A
DEG F
DEG C PSI IN WC % RH PA KPA PPM NONE
UNITS FOR
SENSOR A
SETUP
UNITS
SELECT
Fig. 29. Setup - Sensors - Sensor A - Units.
1.2.2.2.2. UNITS (Sensor A only; 0-5V, 0-10V, or
4-20mA)
1. From the Sensor A selections, use the S and T
buttons to highlight UNITS.
2. Press the X button to display the units list.
3. Use the S and T buttons to scroll through the list
and highlight the desired unit of measure. You may need to scroll up or down to view all units.
Default: F (Fahrenheit)
M24591A
4. Press the X button to accept the units and return to
the Sensor A selections.
15 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
ENTER
MINIMUM
VALUE FOR
SENSOR A
SETUP SENSORS SENSOR A
MIN VAL
0.0
F
o
M24592A
ENTER
MAXIMUM
VALUE FOR
SENSOR A
SETUP
SENSORS
SENSOR A
MAX VAL
0.0
F
o
SETUP
SENSORS SENSOR A
MIN VAL
OR
MAX VAL
Fig. 30. Setup - Sensors - Sensor A - 0-5V, 0-10V, OR
4-20MA - MIN and MAX Value (showing °F).
SETUP SENSORS SENSOR A
CALIBRATE
SETUP
SENSORS
SENSOR A
CALIBRATE
0.0
ENTER
VALUE TO
CALIBRATE
SENSOR A
o
F
M24594
Fig. 31. Setup - Sensors - Sensor A - Calibrate.
1.2.2.2.3. MIN or MAX VALUE
0-5V, 0-10V or 4-20mA) The minimum and maximum values display only for Sensor A when its type is
1. From the Sensor A selections, use the S and T
buttons to highlight MIN VAL or MAX VAL.
2. Press the X button to display the units.
3. Use the S and T buttons to increase/decrease the
desired value.
Sensor Ranges:
°F -60.0 to 270.0 °C -51.0 to 132.0 PSI -500 to 500 IN WC -30.0 to 30.0 % 0.0 to 100.0 PA -3000 to 3000 KPA -3000 to 3000 PPM 0 to 9990 NONE -9999 to 9999
4. Press the X button to accept the units and return to
the Sensor A selections.
0-5V,
(Sensor A only;
0-10V or 4-20MA.
1.2.2.3. CALIBRATE (Sensor A or B)
Ensure that the wire size calibration value is within the limits for the sensor.
• For temperature sensors, see “Temperature Sensor Calibration” on page 10.
• For other sensors, see “Humidity, Pressure, and Universal Sensor Calibration” on page 10.
1. From the Sensor A selections, use the S and T
buttons to highlight CALIBRATE.
2. Press the X button to display the calibration value.
3. Use the S and T buttons to increase/decrease the
desired calibration value.
Default: 0.0 Sensor Range Temperature: +/-10°F (+/-6°C) Other Sensor Range: +/-10% of the Min to Max
values specified previously. See Table 3 on page 10 for examples.
4. Press the X button to accept the value and return to
the Sensor A selections.
SETUP SENSORS SENSOR A
LABEL
SETUP
SENSORS
SENSOR A
LABEL
SENSOR A BOILER A OUTDOOR A DUCT A DISCHRG A CHILLER A ROOM A
SELECT LABEL FOR SENSOR A
Fig. 32. Setup - Sensors - Sensor A - Label.
62-0255—07 16
1.2.2.4. LABEL (Sensor A or B input)
For a sensor already labeled, the display positions to and highlights that label.
1. From the Sensor A selections, use the S and T
buttons to highlight LABEL.
2. Press the X button to display the label list.
3. Use the S and T buttons to scroll through the list
and highlight the desired label. You may need to scroll up or down to view all possi­ble labels.
M24595
4. Use the X button to accept the highlighted label
and exit the list.
NOTE: The label names in list order are: Sensor, Boiler,
Outdoor, Duct, Dischrg, Chiller, Room, Supply, Return, and Animals.
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
A
SETUP SENSORS SENSOR A
UNITS CALIBRATE LABEL
EXIT
Fig. 33. Setup - Sensors - Sensor A - Exit.
SETUP SENSORS
SETUP
SENSORS
# SENSORS SENSOR A
SENSOR B
EXIT
Fig. 34. Setup - Sensors - Sensor B Menu.
1.2.2.5. Exit Sensor A Setup
Press the W button to exit Sensor A selections and return to the Sensors menu. or Use the S and T buttons to highlight EXIT and press the X button.
Continue with “1.2.3. SENSOR B (Temperature only)”
M24596
1.2.3. SENSOR B (Temperature only)
For two-sensor reset control, Sensor B must always be the controlling temperature. For example, in a reset control based on outside temperature, Sensor B must be the outside sensor.
NOTE: Sensor B is available only for reset on the
T775U2006, but can be controlled just like Sen­sor A on the T775U2016.
1. From the Sensors menu, use the T button to high-
M24597
light SENSOR B.
2. Press the X button to display the Sensor B menu.
3. Repeat the selections described in “1.2.2. SENSOR
A” through “1.2.2.4. LABEL (Sensor A or B input)” beginning on page 14, but perform only those steps applicable to Sensor B.
4. Press the W button to exit SENSOR B and return to
the Sensors menu. or Use the S and T buttons to highlight EXIT and press the X button.
5. Press the W button to exit the Sensors menu and
return to the Setup menu.
Continue with “1.3. Setting up the Outputs”.
SETUP
OUTPUTS
MOD 1
Fig. 35. Setup - Outputs Menu.
SETUP
OUTPUTS
MOD 1
TYPE
MIN OUT % INTEGRAL DERIVATIV SCHEDULE RESET HIDE EXIT
1.3. Setting up the Outputs
1. From the Setup menu, use the Sand T buttons to
highlight OUTPUTS.
2. Press the X button to display the Outputs menu.
NOTE: The menus (e.g. the Outputs menu shown here)
can display only those relays that are defined in Setup (see page 21). For example, if you config­ure only two relays, then only two relays display on the appropriate menus.
M24599
The following procedures set up each modulating output and relay output.
17 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP
OUTPUTS
MOD 1
SETUP
OUTPUTS
MOD 1
TYPE
MIN OUT % INTEGRAL DERIVATIV SCHEDULE RESET EXIT
M24599
Fig. 36. Setup - Outputs - Modulating Output Menu.
SETUP OUTPUTS MOD 1
TYPE
SETUP
OUTPUTS
MOD 1
TYPE
4 - 20 mA
0-10 V 2-10 V SERIES 90
SELECT
TYPE FOR
MOD 1
M24600
Fig. 37. Setup - Outputs - Mod Out - Type.
SETUP OUTPUTS MOD 1
MIN OUT %
Fig. 38. Setup - Outputs - Mod Out - Minimum Output
Percentage.
SETUP
OUTPUTS
MOD 1
MIN OUT %
0
ENTER
MINIMUM
PERCENT FOR
MOD 1
%
M24601
1.3.1. Setting up the Modulating Outputs
1. From the Output menu, use the S and T buttons to
highlight the desired modulating output (MOD 1 or MOD 2).
2. Press the X button to display the selected MOD
menu.
Use the remaining procedures, beginning with “1.3.1.1. TYPE (of output signal)”, to set up each modulating output. If you have two modulating outputs, repeat these procedures for each modulating output.
1.3.1.1. TYPE (of output signal)
1. From the Mod menu, use the S and T buttons to
highlight TYPE.
2. Press the X button to display the Type selections.
3. Use the Sand T buttons to highlight the desired
output type.
Default: 4-20 mA
4. Press the X button to accept the selected type and
return to the Mod menu.
1.3.1.2. MIN OUT %
The minimum output % prevents the output from dropping below the value entered. This value can be useful to maintain minimum damper position.
Using the time clock or digital input to disable the output forces the output to 0%.
1. From the Mod menu, use the S and T buttons to
highlight MIN OUT %.
2. Press the X button to display the Min Out %.
3. Use the S and T buttons to increase/decrease the
desired value from 0% to 100% in 1% increments.
Default: 0% Range: 0 to 100%
4. Press the X button to accept the percentage and
return to the Mod menu.
SETUP OUTPUTS MOD 1
INTEGRAL
Fig. 39. Setup - Outputs - Mod Out - Integral.
62-0255—07 18
SETUP OUTPUTS
MOD 1 INTEGRAL
400
ENTER INTEGRAL TIME FOR
MOD 1
SEC
1.3.1.3. INTEGRAL
1. From the Mod menu, use the S and T buttons to
highlight INTEGRAL.
2. Press the X button to display the Integral seconds.
3. Use the S and T buttons to increase/decrease the
value from 0 to 3,600 in 10 second increments.
Default: 400 seconds Range: 0 to 3,600 seconds
4. Press the X button to accept the seconds and
return to the Mod menu.
M24602
See the Notes on page 19 for Integral timing information.
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
NOTES: (Integral Timing)
1. The Integral time is factory set for 400 seconds. This is a good middle range and should satisfy many applications. The integral time can be increased for applications where sensed response is slow, and can be decreased for applications where sensed response is fast (e.g. discharge air control).
2. As a starting point, an optimal integral time for discharge air typically ranges from 12 to 200 seconds. An optimal integral time for room control typically ranges from 60 to 2,500 seconds. The purpose of integral action is to reduce or eliminate
the offset from setpoint during steady state control that is often seen in proportional only control.
3. Keep in mind that control is most sensitive to throttling range. Adjust the throttling range first before any adjustment to integral time. Adjust throttling range to be as wide as possible to start since this will provide the most stable control. Remember that the integral will eliminate the steady state error so you do not need to have a small throttling range to have accurate control. (Integral action allows for controlling to a setpoint even with a wide throttling range).
SETUP OUTPUTS MOD 1
DERIVATIV
SETUP
OUTPUTS
MOD 1
DERIVATIV
0
ENTER
DERIVATIVE
TIME FOR
MOD 1
SEC
Fig. 40. Setup - Outputs - Mod Out - Derivative.
SETUP OUTPUTS MOD 1
SCHEDULE
OUTPUTS
SCHEDULE
YES
NO
SCHEDULE
OUTPUTS
SETUP
MOD 1
USE
FOR
Fig. 41. Setup - Outputs - Mod Out - Schedule.
1.3.1.4. DERIVATIVE
The Derivative default value is factory set to zero (no derivative control). It is strongly recommended that the derivative remain at zero (0) unless you have a very good reason to adjust it. Derivative control is not needed in the vast majority of HVAC applications.
1. From the Mod menu, use the S and T buttons to
highlight DERIVATIV.
2. Press the X button to display the Derivative sec-
onds.
M24603
3. Use the S and T buttons to increase/decrease the
value.
Default: 0 (zero) Range: 0 to 3,600 seconds
4. Press the X button to accept the seconds and
return to the Mod menu.
1.3.1.5. SCHEDULE
The Schedule option displays only if the USE SCHED parameter is set to Yes (see page 21).
1. From the Mod menu, use the S and T buttons to
highlight SCHEDULE.
2. Use the S and T buttons to highlight YES or NO.
Default: YES
3. Press the X button to accept the selection and
return to the Mod menu.
Each output can be set up to follow or ignore the built in
M24604
scheduler. To disable the scheduler for all outputs, see “1.3.3.1. USE SCHED” on page 21.
19 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP OUTPUTS MOD 1
RESET
SETUP
OUTPUTS
MOD 1 RESET
YES-BOILER YES-OTHER
NO
USE
RESET
FOR
MOD1
Fig. 42. Setup - Outputs - Mod Out - Reset.
SETUP OUTPUTS MOD 1
HIDE
SETUP
OUTPUTS
MOD 1
HIDE
YES
NO
HIDE MOD 1 ON HOME SCREEN
Fig. 43. Setup - Outputs - Mod 1/2- Hide.
1.3.1.6. RESET
This selection enables the controller’s Reset function, and allows each output to be individually programmed for Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the first modulating output (MOD1) must be set for Reset here.
The RESET choice is offered for all outputs in setup
M24605
mode, and you can set any or all of them for Reset=YES or Reset=NO. The default is Reset=NO.
For the remaining outputs, if Reset=YES, then these outputs use the reset curve programmed for the first output.
1. From the Mod menu, use the S and T buttons to
highlight RESET.
2. Use the S and T buttons to highlight the desired
value.
Default: NO
3. Press the X button to accept the selection and
return to the Mod menu.
1.3.1.7. Hide
The Hide option is used to prevent the MOD 1 and MOD 2 outputs from displaying on the Home screen.
1. From the Mod menu, use the S and T buttons to
highlight HIDE.
2. Use the S and T buttons to highlight YES or NO.
Default: YES
3. Press the X button to accept the selection and
return to the MOD menu.
NOTE: The MOD1 and MOD2 outputs are still active
M28656
even when hidden from the Home screen.
SETUP
OUTPUTS
MOD 1
TYPE MIN OUT % INTEGRAL DERIVATIV SCHEDULE
EXIT
1.3.1.7. Exit Modulating Outputs Setup
Press the W button (or highlight EXIT and press the X button) to exit the Mod menu and return to the Outputs menu.
To configure the second modulating output, go to “1.3.1. Setting up the Modulating Outputs” on page 18.
When you finish setting up the two modulating outputs, continue with “1.3.2. NBR OF RELAYS”.
M24606
Fig. 44. Setup - Outputs - Mod Out - Exit.
62-0255—07 20
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
A
SETUP OUTPUTS OPTIONS
USE SCHED
SETUP OUTPUTS OPTIONS
USE SCHED
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24609
SETUP OUTPUTS
# RELAYS
SETUP OUTPUTS # RELAYS
2
ENTER
NUMBER OF
RELAYS
Fig. 45. Setup - Outputs - Number of Relays.
SETUP
OUTPUTS
OPTIONS
Fig. 46. Setup - Outputs - Options Menu.
Fig. 47. Setup - Outputs - Options - Schedule.
SETUP OUTPUTS OPTIONS
USE SCHED
MIN OFF MIN ON DI OPTS SHOW RT EXIT
1.3.2. NBR OF RELAYS
1. From the Outputs menu, use the Sand T buttons
to highlight # RELAYS.
2. Press the X button to display the number of relays.
3. Use the S and T buttons to display the number
from 1 to 2.
4. Press the X button to accept the value and display
the Outputs menu.
The number of relay outputs entered here determines how many relays display on the home screen.
M24607
1.3.3. OPTIONS
1. From the Outputs menu, use the Sand T buttons
to highlight OPTIONS.
2. Press the X button to display the Options menu.
M24608
1.3.3.1. USE SCHED
1.
Press the X button to display the schedule selections.
2. Use the Sand T buttons to highlight YES or NO.
Default: NO
3. Press the X button to accept the value and display
the MIN OFF option.
Selecting NO disables scheduling for all outputs.
Selecting YES enables scheduling for all outputs. When YES is selected, all individual outputs default to follow the schedule. However, each individual output can be removed from scheduling as desired.
With Scheduling enabled, when you return to Program mode, the new option for Scheduling displays. You can press the HOME button and then the MENU button to view the Schedule options in the menu.
See “1.3.1.5. SCHEDULE” on page 19.
21 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
M24610A
SETUP
OUTPUTS OPTIONS
ENTER MINIMUM OFF TIME
FOR RELAYS
SETUP OUTPUTS OPTIONS
MIN OFF
0
SEC
OR
MIN ON
SETUP
OUTPUTS
OPTIONS
MIN ON
0
SEC
MIN OFF
ENTER
MINIMUM
ON TIME
FOR RELAYS
1.3.3.2. MIN OFF or MIN ON
This is the minimum number of seconds of “off time” or “on time” for all relays.
1. Press the X button to display the Min Off/On value.
2. Use the S and T buttons to increase/decrease the
3. Press the X button to accept the seconds and
Fig. 48. Setup - Outputs - Options - Min Off/On Time.
NOTES:
desired number of seconds from 0 to 990 seconds in 10 second increments.
Default: 0 (zero) Range: 0 to 990 seconds
display the DI OPTIONS.
1. The minimum off time applies to all relay outputs.
2. When minimum off time is active, relays waiting to be energized display a flashing square underneath the relay number on the home screen.
3. If the minimum off time is not equal to zero (0), the minimum off time activates at power­up. To manually override, press the W button at any time.
SETUP OUTPUTS OPTIONS
DI OPTS
SETUP
OUTPUTS
OPTIONS
DI OPTS
DISABLE
SETPOINT SETBACK ENABLE IGNORE
SELECT DI
OPTIONS
FOR
OUTPUTS
M24611A
Fig. 49. Setup - Outputs - Options - DI Options.
1.3.3.3. DI OPTIONS (digital input options)
The DI Option you select applies to all outputs. This option overrides any Setpoint/Setback values entered in the Schedule.
1. Press the X button to display the DI Option selec-
tions.
2. Use the S and T buttons to highlight DISABLE,
SETBACK, or IGNORE.
Default: DISABLE
3. Press the X button to accept the value and display
the SHOW RT option.
When the digital input (DI) closes, all outputs follow the DI option value (Disable, Setback, or Ignore):
DISABLE disables the outputs; relays return to de­energized state and Mod outputs return to 0% output.
SETPOINT forces the control to the setpoint temperature.
SETBACK enables a setback temperature value to be programmed for each output. — To program the Setback temperature with Reset,
see Fig. 73 on page 31.
— To program the Setback temperature without
Reset, see Fig. 60 on page 26.
ENABLE energizes all relays to 100%. Use this option carefully.
IGNORE causes the digital input to have no effect on the Relay or Mod outputs.
62-0255—07 22
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP OUTPUTS OPTIONS
SHOW RT
YES
NO
SETUP
OUTPUTS
OPTIONS
SHOW RT
USE
RUNTIME
FOR
RELAYS
M24612
Fig. 50. Setup - Outputs - Options - Show Runtime.
SETUP
OUTPUTS
OPTIONS
USE SCHED MIN OFF DI OPTION SHOW RT
EXIT
M24613
Fig. 51. Setup - Outputs - Options - Exit.
SETUP
OUTPUTS
RELAY 1
SETUP
OUTPUTS
RELAY 1
SCHEDULE
RESET RESET RT EXIT
1.3.3.4. SHOW RT (show run time hours)
1. Press the X button to display the Show RT values.
2. Use the S and T buttons to select YES or NO.
Default: YES
3. Press the X button to accept the value and return to
the Options menu.
Selecting YES shows the RT (run time) hours for each relay on the home screen displays.
NOTE: Run times can be reset to zero for each individ-
ual relay. You must do this for each relay that you want to reset to zero. See “1.3.4.3. RESET RT (run time)” on page 24.
1.3.3.5. Exit Options Setup
Press the W button to exit the Options set up and return to the Outputs menu. or Use the S and T buttons to highlight EXIT and press the X button.
Continue with “1.3.4. Setting up the Relays”.
1.3.4. Setting up the Relays
1. From the Outputs menu, use the S and T buttons
to highlight the desired relay (1 or 2).
2. Press the X button to display the selected Relay
menu.
Continue with the remainder of this section to setup the relay outputs.
M24614
Fig. 52. Setup - Outputs - Relay Menu.
SETUP OUTPUTS RELAY 1
SCHEDULE
Fig. 53. Setup - Outputs - Relay - Schedule.
OUTPUTS
RELAY 1
SCHEDULE
YES
NO
SCHEDULE
OUTPUTS
SETUP
USE
FOR
1.3.4.1. SCHEDULE
This selection displays only if “Use Sched = YES” is selected during the Output Options setup (see page 21). When selected, individual outputs default to follow the schedule.
1. Press the X button to display the Schedule values.
2. Use the S and T buttons to select YES or NO.
Default: YES
3. Press the X button to accept the value and return to
the Relay menu.
An individual output can be selected to be controlled or
M24615
not controlled by the schedule.
If NO is selected, the Setback selection does not appear in the Program menu for this output.
23 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP OUTPUTS RELAY 1
RESET
YES
NO
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
Fig. 54. Setup - Outputs - Relay - Reset.
SETUP OUTPUTS RELAY 1
RESET RT
YES
NO
SETUP
OUTPUTS
RELAY 1
RESET RT
RESET
RUN TIME
FOR
RELAY 1
M24617
Fig. 55. Setup - Outputs - Relay - Reset Runtime.
1.3.4.2. RESET
IMPORTANT
For relays to use the Reset function of the con­troller, both modulating outputs (MOD 1 and MOD 2) must be set for Reset.
Relays that have Reset set to YES use the reset curve configured for MOD 1.
1. Press the X button to display the Reset values.
M24616
2. Use the S and T buttons to select YES or NO.
Default: NO
3. Press the X button to accept the value and return to
the Relay menu.
• If you select YES, then all other outputs display this Setup option and will use the reset curve programmed for the first output.
• If you select NO, then No Reset is configured for that output and all other subsequent outputs.
1.3.4.3. RESET RT (run time)
This selection displays only if “Show RT = YES” is selected during Output Options setup (see page 23).
1. Press the X button to display the Reset RT values.
2. Use the S and T buttons to select YES or NO.
Default: NO
3. Press the X button to accept the value and return to
the Relay menu.
Selecting YES immediately resets the output run time hours to zero for this output. When you subsequently return to this screen, the RESET RT defaults to NO.
NOTE: Run times can be reset to zero for each individ-
ual relay. You must do this for each relay that you want to reset to zero.
SETUP
OUTPUTS
RELAY 1
RESET SCHEDULE RESET RT
EXIT
1.3.4.4. EXIT Relay Setup
Press the W button to exit the selected relay set up and return to the Outputs menu.
To setup the next relay output go to “1.3.4. Setting up the Relays” on page 23.
When you finish setting up the relay outputs, continue with “1.4. Exiting Setup”.
M24618
Fig. 56. Setup - Outputs - Relay - Exit.
1.4. Exiting Setup
Press the HOME button to exit Setup mode and return to the home screen display. or Use the S and T buttons to highlight EXIT from the menu and press the X button.
This completes the Setup procedure.
62-0255—07 24
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
2. PROGRAMMING OUTPUTS (MOD AND RELAY) WITH NO
RESET
The T775U can be programmed for Reset or No Reset. From the factory, the T775U is programmed for No Reset. This section describes the steps necessary to program the controller for No Reset.
MENU
MENU PROGRAM
Fig. 57. Program Menu.
PROGRAM
MOD 1
Fig. 58. Program Menu - No Reset.
PROGRAM
MOD 1
MOD 2 RELAY 1 RELAY 2 EXIT
MENU
PROGRAM
MOD 1
SETPOINT
SETBACK SENSOR THROT RNG ACTION EXIT
M24567
M24580A
NOTE: For applications where Reset is not used, only
one sensor (Sensor A) is available for use.
2.1. Entering Program Mode
Press the MENU button, then select PROGRAM and press the X button to view the Program menu.
2.1.1. Program Menu for Outputs with
No Reset
From the Program menu, select MOD 1, MOD 2, RELAY 1, or RELAY 2 to view the parameters. This section illustrates the screens for selecting MOD 1, but other than as noted below, the programming is the same for each output.
NOTE: For Relays, DIFFRNTL replaces THROT RNG.
NOTE: The Setback parameter displays only if schedul-
ing is enabled (see Fig. 47 on page 21) or the DI Option is set to Setback. (see Fig. 49 on page 22).
Continue with “2.1.2. SETPOINT”.
PROGRAM MOD 1
SETPOINT
Fig. 59. Program - Setpoint.
MENU
PROGRAM
MOD 1
SETPOINT
70
ENTER
SETPOINT
FOR
MOD 1
2.1.2. SETPOINT
1. From the menu, use the S and T buttons to high-
light SETPOINT.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
o
F
M24581
desired setpoint temperature.
Default: 70°F (21°C) Range: -40°F to 248°F (-40°C to 120°C)
4. Press the X button to accept the setpoint tempera-
ture and display the next option.
25 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
PROGRAM MOD 1
SETBACK
Fig. 60. Program - Setback.
PROGRAM MOD 1
SENSOR
Fig. 61. Program - Sensor.
MENU
PROGRAM
MOD 1
SETBACK
ENTER
SETBACK SETPOINT FOR MOD 1
MENU
PROGRAM
MOD 1
SENSOR
SENSOR A
SENSOR B
SELECT
SENSOR
FOR
MOD 1
60
2.1.3. SETBACK
The Setback temperature option displays only if scheduling is enabled (see Fig. 47 on page 21) or the DI Option is set to Setback. (see Fig. 49 on page 22).
This is the desired setpoint temperature that you want to
o
F
use during setback mode for this output. For example, if your setpoint is 70°F and you want the temperature to drop 10°F during setback mode, enter 60°F as the set­point for this output.
M24584
1. From the menu, use the S and T buttons to high-
light SETBACK.
2. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 60°F (16°C) Range: -40°F to 248°F (-40°C to 120°C)
3. Press the X button to accept the value and display
the menu.
2.1.3. SENSOR
This sub-menu choice is only available on the T775U2016 model.
1. From the menu, use the S and T buttons to high-
light SENSOR A or SENSOR B.
2. Press the X button to accept the sensor selection
and display the next option.
M28660
PROGRAM MOD1
THROT RNG
MENU
PROGRAM
MOD 1
THROT RNG
20
ENTER THROTLLING RANGE FOR
MOD 1
2.1.5. THROTTLING RANGE or DIFFERENTIAL
Throttling Range displays for Modulating outputs. Differential is used for the Relay outputs.
o
F
M24582
Fig. 62. Program - Throttling Range or Differential.
The Throttling Range brackets the setpoint setting, e.g., if the setpoint is 72°F and the throttling range is 10°F, then the effective throttling temperature range is 67°F to 77°F.
In heating mode, the Differential is below the setpoint. The relay de-energizes when the temperature rises to the setpoint. As the temperature drops to the setpoint minus the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint. The relay de-energizes when the temperature falls to the setpoint. As the temperature rises to the setpoint plus the Differential, the relay energizes.
62-0255—07 26
1. From the menu, use the S and T buttons to high-
light THROT RNG or DIFFERNTL.
2. Press the X button to display the throttling range
value.
3. Use the S and T buttons to increase/decrease the
desired value.
Default: 20°F (-6.6°C) Range: 1°F to 150°F (1°C to 66°C)
4. Press the X button to accept the value and display
the next option.
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
PROGRAM MOD 1
ACTION
Fig. 63. Program - Action.
MENU
PROGRAM
MOD 1
ACTION
HEAT
COOL REV ACT DIR ACT HUMID DEHUMID
SELECT
ACTION
MOD 1
FOR
2.1.6. ACTION
1. From the menu, use the S and T buttons to high-
light ACTION.
Default: HEAT
2. Press the X button to display the action selections.
3. Use the S and T buttons to select the desired
value.
4. Press the X button to accept the highlighted selec-
tion and display the next option.
M24583
2.2. Program Next Output (Modulating
Output or Relay)
For the next output, select the desired MOD or Relay from the Program menu (see Fig. 57 on page 25).
Go to “2.1.2. SETPOINT” on page 25 to continue programming.
When you finish programming the outputs, continue with “1.3. Exit Programming without Reset”.
1.3. Exit Programming without Reset
Press the HOME button to leave programming mode and return to the home screen.
This completes the programming procedure for controllers that do not use Reset.
27 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
CAUTION
3. PROGRAMMING OUTPUTS (MOD AND RELAY) WITH
RESET
The T775U can be programmed for Reset or No Reset for each output. From the factory, the T775U is programmed for No Reset. This section describes the steps necessary to program the controller for Reset.
To use the Reset feature, the first output (MOD 1) must be set to Reset=YES in Setup mode (see “3.1. Setting Up the Controller for Reset”).
SETUP OUTPUTS MOD 1
RESET
Fig. 64. Reset Setup.
Determining and Setting the Reset Values
NOTE: When using the Reset feature, Sensor A must
be sensing the controlled temperature (e.g. Boiler), Sensor B must be sensing the resetting temperature (e.g. outdoor temp).
To program an output for Reset, refer to the values as shown in the examples below. Choose your own appropriate values for Sensor A maximum and minimum and Sensor B maximum and minimum.
Reset Example: (see Fig. 65)
• Sensor A is the boiler sensor and Sensor B is the outdoor sensor.
• Maximum boiler temperature desired is 210°F when the outdoor temperature is 20°F.
• Minimum boiler temperature desired is 160°F when the outdoor temperature is 70°F.
• With the above settings example, when the outdoor temperature is 50°F, the effective setpoint is 180°F.
Setback (optional) Example: (see Fig. 65)
• Setback of -10°F is used to drop the temperature at night by 10°F.
SETUP
OUTPUTS
MOD 1
RESET
YES-BOILER
YES-OTHER NO
USE RESET
FOR
MOD 1
M24568
NOTE: Even if the MOD outputs are not used, both
MOD 1 and MOD 2 must be set to Reset in order to configure Reset for the relay(s).
The reset curve established when programming the first output (MOD 1) is then used for all subsequent outputs that are configured for Reset, and each of those outputs will be offset from this curve.
For all outputs that will follow a reset curve, be sure to configure for Reset=YES in the setup mode. Choose Reset YES or NO for all other outputs you wish to reset, then press the HOME button to record your selection.
NOTE: The first output, Mod 1, must be set for Reset to
enable the controller’s Reset function.
3.1. Setting Up the Controller for Reset
1. Press and hold the MENU button for five seconds to
enter Setup mode.
2. Then choose:
OUTPUTS X
MOD1 X
RESET X
then select YES-BOILER or YES-OTHER (Fig. 64).
You can now press the HOME button to exit Setup mode and continue with “Determining and Setting the Reset Val ues ”.
• With the above settings example, when the outdoor temperature is 50°F, the effective setback setpoint is 170°F (180°F setpoint minus the 10°F setback).
NOTE: A single reset curve is programmed for the
MOD 1 output and is used by all outputs setup with RESET=YES.
If using the time clock or DI to go to setback, the T775P will shift the reset curve up or down and cause the controlled setpoint to exceed either the entered reset max. temp or min. temp (dropping below reset minimum is most common, since setback is normally below setpoint). If this is not desired, either do not use setback, or adjust the min. and max. values entered so that critical setpoints are not exceeded in the setback mode.
When Reset is programmed, the home screen displays the calculated Heat/Cool setpoint(s) for the Mod and Relay outputs based on the reset curve. See Fig. 21 on page 12.
62-0255—07 28
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
(BOILER MAX)
(BOILER MIN)
SP MAX A1
S E N S O R
A
SP MIN A2
220
210
200
190
180
170
160
150
140
°F
10
20
RESET B1
(OUTSD MIN)
SETBACK
OFFSET
-10°F
30 40 50 60
SENSOR B
70
RESET B2
(OUTSD MAX)
°F80
M24570
Fig. 65. Reset Curve for MOD 1 with Setback Offset.
PROGRAM MOD 1
MOD 1 RESET:
YES-OTHER AND
DI OPTION = SETBACK
MENU
PROGRAM
MOD 1
SP MAX A1
RESET B1 SP MIN A2 RESET B2 THROT RNG ACTION SETBACK EXIT
MOD 1 RESET:
YES-BOILER AND
DI OPTION = SETBACK
MENU
PROGRAM
MOD 1
OR
BOILR MAX
OUTSD MIN BOILR MIN OUTSD MAX THROT RNG ACTION SETBACK EXIT
M24571
Fig. 66. Setpoint Values for Reset and Setback.
NOTE: For MOD 2 and the Relays, a setpoint offset is
used. See “3.3.1. SETPOINT OFFSET (MOD 2 only)” on page 32.
The remainder of this section beginning with “3.2. Program Menus for Outputs with Reset” on page 29 describes the individual parameters for configuring outputs with Reset.
For your reference, the following Reset programming procedure uses the values in Fig. 65 above.
3.2. Program Menus for Outputs with
Reset
Press the MENU button, select PROGRAM, then highlight MOD 1 and press the X button to view the parameters.
The Reset curve settings (Fig. 67 through Fig. 70) are programmed for the first output (MOD 1) and these settings apply to all outputs that are configured for Reset. See Fig. 65 for the reset curve values used in the following section.
NOTE: The Setback parameter displays only if schedul-
ing is enabled (see Fig. 47 on page 21) or the DI Option is set to Setback (see Fig. 49 on page 22).
PROGRAM MOD 1
SP MAX A1
Fig. 67. Program - Sensor A Max. Setpoint.
PROGRAM MOD 1
RESET B1
SENSOR B VALUE
Fig. 68. Program -Sensor B Max. Setpoint.
MENU
PROGRAM
MOD 1
SP MAX A1
210
ENTER
MAXIMUM
SETPOINT FOR
SENSOR A
MENU
PROGRAM
MOD 1
RESET B1
20
ENTER
FOR MAXIMUM
SETPOINT
3.2.1. SP MAX A1 or BOILER MAX
(Setpoint maximum for Sensor A)
1. From the menu, use the S and T buttons to high-
light BOILER MAX or SP MAX A1.
2. Press the X button to display the maximum setpoint
o
F
M24572
o
F
M24573
value.
3. Use the S and T buttons to increase/decrease the
desired maximum setpoint temperature.
Default: 180°F (82°C) Range: -40°F to 248°F (-40°C to 120°C)
4. Press the X button to accept the setpoint tempera-
ture and display the next option.
3.2.2. RESET B1 or OUTSD MIN
(Sensor B value when at SP MAX A1 Setpoint)
1. From the menu, use the S and T buttons to high-
light RESET B1 or OUTSD MIN.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 10°F (-12°C) Range: -40°F to 248°F (-40°C to 120°C)
4. Press the X button to accept the value and display
the next option.
29 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
PROGRAM MOD 1
SP MIN A2
MENU
PROGRAM
MOD 1
SP MIN A2
160
ENTER
MINIMUM
SETPOINT FOR
SENSOR A
o
F
Fig. 69. Program - Sensor A Min. Setpoint.
PROGRAM MOD 1
RESET B2
Fig. 70. Program - Sensor B Min. Setpoint.
PROGRAM MOD 1
THROT RNG
MENU
PROGRAM
MOD 1
RESET B2
70
ENTER
SENSOR B VALUE
FOR MINIMUM
SETPOINT
MENU
PROGRAM
MOD 1
THROT RNG
20
ENTER
THROTTLING
RANGE FOR
FOR MOD 1
o
F
o
F
Fig. 71. Program - Throttling Range or Differential.
3.2.3. SP MIN A2 or BOILER MIN
(Setpoint minimum for Sensor A)
1. From the menu, use the S and T buttons to high-
light BOILER MIN or SP MIN A2.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired minimum setpoint temperature.
Default: 140°F (60°C) Range: -40°F to 248°F (-40°C to 120°C)
4. Press the X button to accept the setpoint tempera-
M24574
ture and display the next option.
3.2.4. RESET B2 or OUTSD MAX
(Sensor B value when at MIN A2 Setpoint)
1. From the menu, use the S and T buttons to high-
light RESET B2.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 60°F (16°C) Range: -40°F to 248°F (-40°C to 120°C)
4. Press the X button to accept the value and display
M24575
the next option.
3.2.5. THROTTLING RANGE or
DIFFERENTIAL
Throttling Range displays for Modulating outputs. Differential is used for the Relay outputs.
1. From the menu, use the S and T buttons to high-
light THROT RNG or DIFFERNTL.
2. Press the X button to display the throttling range
value.
3. Use the S and T buttons to increase/decrease the
desired value.
M24577
Default: 20°F (-6.6°C) Range: 1°F to 150°F (1°C to 66°C)
4. Press the X button to accept the value and display
the next option.
The Throttling Range brackets the setpoint setting, e.g., if the setpoint is 72°F and the throttling range is 10°F, then the effective throttling temperature range is 67°F to 77°F.
In heating mode, the Differential is below the setpoint. The relay de-energizes when the temperature rises to the setpoint. As the temperature drops to the setpoint minus the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint. The relay de-energizes when the temperature falls to the setpoint. As the temperature rises to the setpoint plus the Differential, the relay energizes.
62-0255—07 30
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
PROGRAM RELAY 1
ACTION
MENU
PROGRAM
RELAY 1 ACTION
HEAT
COOL REV ACT DIR ACT HUMID DEHUMID
SELECT ACTION
RELAY 1
FOR
Fig. 72. Program - Action Selection.
PROGRAM RELAY 1
SETBACK
MENU
PROGRAM
RELAY 1
SETBACK
-10
ENTER
SETBACK
SETPOINT
FOR RELAY 1
Fig. 73. Program - Setback (Offset).
3.2.6. ACTION
For the MOD 1 output (and for outputs with RESET=NO), the ACTION selection displays.
For all other outputs with RESET=YES, the ACTION selection does not display; continue with “3.2.7. SETBACK OFFSET (if configured)” on page 31.
1. From the menu, use the S and T buttons to high-
light ACTION.
Default: HEAT
M24578
2. Press the X button to display the action selections.
3. Use the S and T buttons to select the desired
value.
4. Press the X button to accept the highlighted selec-
tion and display the next option.
3.2.7. SETBACK OFFSET (if configured)
The Setback temperature option displays only if scheduling is enabled (see Fig. 47 on page 21) or the DI Option is set to Setback. (see Fig. 49 on page 22).
This value is the number of degrees plus (+) or minus (-)
o
F
that you want the temperature to be offset from the setpoint.
For example, If you want the temperature to be 10°F less than the setpoint during setback mode, enter -10°F. In
M24579
normal operations for heating, the offset will be negative. For cooling, the offset will be a positive value.
1. From the menu, use the S and T buttons to high-
light SETBACK.
2. Use the S and T buttons to increase/decrease the
desired setpoint temperature. Default: 0°F Range: -150°F to 150°F (-101°C to 66°C)
3. Press the X button to accept the value and display
the menu.
This completes the programming of the MOD 1 output.
To program the second Modulating output and the two relays, continue with “3.3. Second Modulating Output and Relays”.
31 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
MENU
PROGRAM
MOD 2
OFFSET
PROGRAM MOD 2
MENU
PROGRAM
MOD 2
OFFSET
THROT RNG ACTION SETBACK EXIT
-10
ENTER
SETPOINT
OFFSET
FOR
MOD 2
Fig. 74. Program - Setpoint Offset (MOD 2 only).
SP MAX A1
(BOILER MAX)
(BOILER MIN)
Fig. 75. Reset Curve with Offset for MOD 2.
S E N S O R
A
SP MIN A2
220
210
200
190
180
170
160
150
140
°F
MOD 2
SETPOINT
OFFSET
10
20
RESET B1
(OUTSD MIN)
MOD 1 SETPOINT
-10°F
30 40 50 60
SENSOR B
70
RESET B2
(OUTSD MAX)
o
M24547
F
M24569
3.3. Second Modulating Output and
Relays
For the second Modulating Output and the two Relays (if they are configured for Reset), the Offset parameter displays on the Program menu as shown in Fig. 74.
3.3.1. SETPOINT OFFSET (MOD 2 only)
This value is the number of degrees plus (+) or minus (-) that you want the temperature to be offset from the MOD 1 setpoint. See Fig. 75. For example, If you want the MOD 2 setpoint to be 10°F less than the MOD 1 setpoint, enter -10°F.
1. From the menu, use the S and T buttons to
highlight OFFSET.
2. Press the X button to display the value.
3. Use the S and T buttons to increase/decrease the
desired temperature. OFFSET Default: 0°F OFFSET Range: -150°F to 150°F (-101°C to 66°C)
4. Press the X button to accept the value and display
the next option.
3.3.2. Second Modulating Output and
Relays Programming
To complete the programming of MOD 2 or a Relay, perform the procedures in “3.2.5. THROTTLING RANGE or DIFFERENTIAL” through “3.2.7. SETBACK OFFSET (if configured)” beginning on page 30.
°F80
3.4. Exit Programming with Reset
When you finish programming the Modulating outputs and the Relays, press the HOME button to leave programming mode and return to the home screen.
This completes the programming procedure for controllers that use Reset.
62-0255—07 32
4. SCHEDULING
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
Scheduling provides the ability to set daily temperature settings for up to two events per day. Typically, these are the daytime (setpoint) and the nighttime (setback) settings.
IMPORTANT
To enable Scheduling, you must first enter Setup mode (press and hold the MENU button for 5 seconds), select OUTPUTS, select OPTIONS, select USE SCHED, and then select YES. (see “1.3.3.1. USE SCHED” on page 21).
IMPORTANT
To properly account for Daylight Saving time, be sure to set the Date before setting the Time. See “4.2.2. SET DATE” on page 34.
NOTE: The T775U controller interface is intuitive. You
may find that you do not need the following scheduling instructions. You may want to use this procedure simply as a reference to locate the particular option or parameter of interest.
NOTE: Each output is independently configurable to
follow the schedule or not. For modulating outputs, see “1.3.1.5. SCHEDULE” on page 19. For relay outputs, see “1.3.4.1. SCHEDULE” on page 23.
NOTES:
MENU
SCHEDULE
MENU
SCHEDULE
OPTIONS
MON-FRI SAT-SUN MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY SUNDAY EXIT
M24620
Fig. 76. Schedule - Menu.
1. If you press the HOME button or there is no keypad activity for four minutes, you exit Scheduling mode and return to the home screen.
2. If you press the MENU button, you exit Scheduling mode and return to the menu.
To create or change a schedule, you use the —
• Left arrow button(W) to scroll backward through the
Setup menus
• Right arrow button (X) to select the highlighted menu
item and display its content
• Up and Down arrow buttons (S and T) to scroll up
and down through a list of items or to increase or decrease the value of a displayed setup parameter
Creating a Schedule
To create a schedule, perform the following in the order listed:
1. Enable Scheduling in Setup mode - see “1.3.3.1.
USE SCHED” on page 21
2. Enter Schedule mode — see “4.1. Entering Sched­ule Mode”
3. Set the Schedule Options — see “4.2. OPTIONS”
4. Set Individual Schedules — begin with “4.3. Setting
Individual Schedules” on page 35
5. Exit Schedule Mode — see “4.4. Exiting Scheduling Mode” on page 36
4.1. Entering Schedule Mode
Press the MENU button, then select SCHEDULE and press the X button to view the Schedule menu.
MENU
SCHEDULE
OPTIONS
MENU
SCHEDULE
OPTIONS
SET TIME
SET DATE DAYLIGHT EXIT
M24621
4.2. OPTIONS
1. From the Schedule menu, use the S and T buttons
to highlight OPTIONS.
2. Press the X button to display the Options menu.
Fig. 77. Schedule - Options Menu.
33 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
MAIN SCHEDULE OPTIONS
SET TIME
SET
SYSTEM
TIME
MAIN
SCHEDULE
OPTIONS SET TIME
08:12 AM
M24622
4.2.1. SET TIME
Setting the system time is required to enable the controller to follow daylight saving time.
IMPORTANT
1. From the Options menu, use the S and T buttons
2. Press the X button to display the current system
3. Use the X button to cycle between the hour,
Fig. 78. Schedule - Options - System Time.
4. Use the S and T buttons to increase/decrease the
5. Press the W button to accept the Time and return to
Set the Date before setting the Time. See “4.2.2. SET DATE”.
to highlight SET TIME.
time setting.
minute, and AM/PM values.
desired value for the hour, minute, and AM/PM.
the Options menu.
MAIN SCHEDULE OPTIONS
SET DATE
MAIN
SCHEDULE
OPTIONS
SET DATE
01/01/2007
SET
SYSTEM
DATE
M24623
Fig. 79. Schedule - Options - System Date.
MAIN SCHEDULE OPTIONS
DAYLIGHT
SCHEDULE
OPTIONS
DAYLIGHT
YES
NO
DAYLIGHT
MAIN
USE
SAVING
TIME
M24624
Fig. 80. Schedule - Options - Daylight Saving Time.
4.2.2. SET DATE
Setting the system date is required to enable the controller to follow daylight saving time.
IMPORTANT
To properly account for Daylight Saving time, be sure to set the Date before setting the Time.
1. From the Options menu, use the S and T buttons to highlight SET DATE.
2. Press the X button to display the current system date setting.
3. Use the X button to cycle between the month, day, and year values.
4. Use the S and T buttons to increase/decrease the desired value for the month, day, and year.
5. Press the W button to accept the Date and return to the Options menu.
4.2.3. DAYLIGHT (daylight saving time)
1. From the Options menu, use the S and T buttons
to highlight DAYLIGHT.
2. Press the X button to display the current system setting for daylight saving time.
3. Use the S and T buttons to select YES or NO.
Default: YES
4. Press the X button to accept the value and return to the Options menu.
5. From the Options menu, use the Use the S and T buttons to highlight EXIT.
6. Press the X button to return to the Schedule menu.
62-0255—07 34
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
MENU
SCHEDULE
MON-FRI
MENU
SCHEDULE
MON-FRI
E1 SETPT
E1 TIME E2 SETPT E2 TIME EXIT
M24625
Fig. 81. Schedule Event Menu (Showing MON-FRI).
4.3. Setting Individual Schedules
As shown in the Schedule menu (Fig. 76 on page 33), schedules can be set for the following time periods:
• Monday through Friday
• Saturday and Sunday
• Individual days of the week
1. From the Schedule menu, use the S and T buttons to highlight the desired time period.
2. Press the X button to display the Schedule menu for the selected time period.
For each selected time period, the schedule event (E1 and E2) parameters are exactly the same as shown in Fig. 81.
SCHEDULING EXAMPLE
Setting the schedule is independent of the temperature settings for the relay outputs. Table 5 illustrates a weekly schedule for daytime (setpoint) and night time (setback) use and shows the factory default settings.
Table 5. Mon-Fri Schedule Defaults
DAY EVENT SETPT ACTION TIME
Mon-Fri Event 1 (E1) Setpoint
Mon-Fri Event 2 (E2) Setback
Sat-Sun Not used; remains in Setback from the
a
Setpoint time span is 6:00 AM until 5:59 PM because setback starts at 6:00 PM.
b
Setback time span is 6:00PM until 5:59 AM because setpoint starts at 6:00 AM.
To set a schedule, continue with “4.3.1. E1 SETPT (setpoint for event 1)”.
The following figures show the MON-FRI menu, but the menu selections are the same for any time period.
Mon-Fri E2 settings
6:00 AM
6:00 PM
a
b
MAIN SCHEDULE MON-FRI
E1 SETPT
MENU
SCHEDULE
MON-FRI
E1 SETPT
SETPOINT
SETBACK NOT USED
SELECT
SETPOINT
FOR
EVENT 1
4.3.1. E1 SETPT (setpoint for event 1)
1. From the selected time period menu, use the S and
T buttons to highlight E1 SETPT.
2. Press the X button to display the setpoint options.
3. Use the S and T buttons to highlight the desired
option.
4. Press the X button to accept the value and return to the selected time period menu.
M24626
Fig. 82. Schedule - Event 1 Setpoint.
35 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
MAIN SCHEDULE MON-FRI
E1 TIME
Fig. 83. Schedule - Event 1 Time.
MAIN
SCHEDULE
MON-FRI
E1 TIME
6:00 AM
SET TIME FOR
EVENT 1
4.3.2. E1 TIME (time for event 1)
1. From the selected time period menu, use the S and
T buttons to highlight E1 TIME.
2. Press the X button to display the current time set-
ting for event 1.
3. Use the X button to cycle between the hour,
minute, and AM/PM values.
4. Use the S and T buttons to increase/decrease the
desired value for the hour, minute, and AM/PM.
5. Press the W button to accept the time and return to
M24627
the selected time period menu.
4.3.3. E2 SETPOINT
Creating the setpoint for event 2 is accomplished the same way as the first event. See “4.3.1. E1 SETPT (setpoint for event 1)” on page 35 above.
(setpoint for event 2)
4.3.4. E2 TIME (time for event 2)
Creating the time for event 2 is accomplished the same way as the first event. See “4.3.2. E1 TIME (time for event
1)” above.
4.3.5. EXIT (exit from selected time period settings)
After entering the time for event 2, use the W button to exit the schedule time period and return to the Schedule menu to select a different time period.
When you finish scheduling the time periods, continue with “4.4. Exiting Scheduling Mode”.
4.4. Exiting Scheduling Mode
MENU
PROGRAM SCHEDULE SUMMARY
EXIT
Fig. 84. Scheduling Mode Exit.
62-0255—07 36
Press the HOME button to exit the Schedule menu and return to the home screen display. or Press the W button to return to the menu, then use the S and T buttons to highlight EXIT from the menu and press the X button.
This completes the Scheduling procedure.
M24628
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
MENU SUMMARY
MENU
SUMMARY
MONDAY
RELAY 1-2 E1: 06:00AM (72) E2: 06:00PM (65)
M24629
SUMMARY MENU
The Summary menu provides the ability to view the schedule (E1 and E2 times) for each relay for each day of the week.
NOTE: Scheduling must be enabled for the Summary
menu to display. Enabling the schedule is determined in the Setup process for the Output Options (see page 21).
Fig. 85. Summary Example - Monday Settings.
For each relay, the Summary display indicates the time and temperature (in parenthesis) for each of the two scheduled events E1 and E2.
1. Press the MENU button to view the menu.
2. Use the S and T buttons to highlight SUMMARY.
3. Press the X button to display the Summary
settings.
4. Use the X button to scroll forward through each day
of the week (Monday, Tuesday, Wednesday, Thursday, Friday, Saturday, and Sunday).
5. While viewing a specific day, use the S and T
buttons to cycle through the individual relay schedules for that day.
When finished, press the HOME button to return to the home display screen.
If programmed for Reset control, the Summary setpoints display as “RES” instead of a temperature value. For example, the display would show:
MONDAY STAGES E1: 06:00AM (RES) - indicating Reset E2: 06:00PM (05) - setback/offset degrees
TROUBLESHOOTING
Power Loss
The date and time settings are retained for 24 hours after a power outage. After a power loss of more than 24 hours, the date and time settings may need to be reentered. All other settings are stored permanently.
Errors and Diagnostics
The controller provides an error message and diagnostic status as described below.
Error Message
There is a two-character error code that displays in response to controller software problems:
EE
EEPROM Failure— The values read back from
the EEPROM are not the same as written into the EEPROM. This error cannot be field repaired. Replace the device.
Diagnostic Messages
There are two diagnostic messages that can display in response to sensor problems. The diagnostic codes that can flash on the display are:
– –
Sensor Open or Shorted — Two dashes display
when a sensor (typically temperature) is open or shorted. An open circuit is considered anything greater than 1570 ohms (greater than 300F), shorted anything less than 770 ohms (less than -73F). Which­ever stages are operating with this sensor cease to control (meaning relays go to OFF and proportional outputs go to zero percent).
This message can also mean that the sensor is pro­grammed, but not physically connected.
-60°F or 270°F (-51°C or 132°C) Blinking
Temperature Out of Range — The temperature
display blinks when the sensed temperature range is outside of the display range, below -60°F (-51°C) or above 270°F (132°C). The displayed value remains at that displayed limit and control continues. Controller continues to function unless an open or shorted state is detected.
Blinking relay status
Relay Minimum Off Time is Active — On the home
screen, each relay’s indicator () blinks while the relay’s minimum off time is active.
SPECIFICATIONS
Power: 24, 120, or 240 Vac; 50/60 Hz
A separate earth ground is required for any power
source.
Power Consumption:
• 8 VA maximum at 60 Hz
• 10 VA maximum at 50 Hz
Operating & Storage Temperature Ambient Rating:
• -40°F to 125°F (-40°C to 52°C) @ 50 Hz
• -40°F to 140°F (-40°C to 60°C) @ 60 Hz
Relative Humidity: 5% to 95% non-condensing
Relay Contact Output Ratings (N.O. and N.C.):
• 1/2 hp; 9.8 AFL, 58.8 ALR @ 120 Vac
• 1/2 hp; 4.9 AFL, 29.4 ALR @ 240 Vac
• 125 VA pilot duty @ 120/240 Vac
• 10A @ 24 Vac (resistive)
Modulating Outputs:
• 0-10 Vdc; drive a minimum of 2,000 Ohms
• 2-10 Vdc; drive a minimum of 2,000 Ohms
• 4-20 mA; drive a maximum of 600 Ohms
• Electronic Series 90
• Floating
37 62-0255—07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
DoC
Emissions Compliance
EN 55022: 2006 CISPR 22: 2006 VCCI V-3/2006.04 ICES-003, Issue 4: 2004 FCC PART 15 SUBPART B Class B Limit
Immunity Compliance
EN 61000-6-1: 2001 covering
EN 61000-4-2: 1995 + A1: 1998 + A2: 2001 EN 61000-4-3: 2002 EN 61000-4-4: 2004 EN 61000-4-5: 1995 + A1: 2001 EN 61000-4-6: 1996 + A1: 2001 EN 61000-4-8: 1993 + A1: 2001 EN 61000-4-11 2nd Ed.: 2004
Safety Compliance
UL 60730-1 for US and Canada
FCC Compliance Statement:
This equipment has been tested and found to comply with limits for a Class B digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide
reasonable protection against harmful interference in residential installations. This equipment generates, uses, and can radiate radio frequency energy, and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television equipment reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: — Reorient or relocate the receiving antenna — Move the equipment away from the receiver — Plug the equipment into an outlet on a circuit different
from that to which the receiver is connected
— Consult the dealer or an experienced radio/television
technician for additional suggestions
You are cautioned that any change or modifications to the equipment not expressly approve by the party responsible for compliance could void Your authority to operate such equipment.
This device complies with Part 15 of the FCC Rules. Operation is subjected to the following two conditions 1) this device may not cause harmful interference and 2) this device must accept any interference received, including interference that may cause undesired operation.
62-0255—07 38
T775U SERIES 2000 CONTROLLER
39 62-0255–07
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2009 Honeywell International In c. 62-0255—07 E.K. Rev. 10-09 Printed in U.S.A.
Loading...