T775 Series 2000 Electronic Stand-Alone
Controllers
APPLICATION GUIDE AND CROSS REFERENCE
63-7147—3
Page 2
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
IMPORTANT
The T775R is an operating control, not a limit or
safety control. If used in applications requiring safety
or limit controls, a separate safety or limit control
device is required.
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775 APPLICATION TIPS
Q Does the T775 save programmed values if the power is
lost?
A Yes. The T775 has an EEPROM that saves all values
entered and restores them once power is reapplied. The
date and time settings are retained for 24 hours after a
power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.
Q What is the time constant for the T775?
A The T775 standard sensor (50021579-001) has a time
constant of approximately 8 seconds. The T775 samples
sensor input every 100 milliseconds and updates the
control and display every 1 second.
Q Can sensors be shared by several T775s to simplify
installation or provide more stages?
A Each T775 must be wired to its own sensor(s), However, a
benefit of the T775 controller's high accuracy is that there
is no more than a 2° differential between any two T775
controllers.
COMPATIBLE COMPONENTS
Temperature Sensors
The controller accepts 1,097 Ohms PTC at 77° F (25° C):
• 50021579-001 – Standard sensor (included with all models
except T775U2006 and NEMA 4X models)
• T775-SENS-STRAP – Strap on sensor with wiring box
• T775-SENS-WR – Water resistant with 5 foot leads
(included with NEMA 4X models)
• T775-SENS-WT – Watertight with 6 foot lead
• T775-SENS-OAT – Outdoor air temperature sensor
• C7031B2005 – 6 inch duct mount with wiring box.
• C7031D2003 – 5 inch immersion sensor with wiring box
(use immersion well; P/N 50001774-001)
• C7046D1008 – 8 inch duct probe with mounting flange
• C7100D1001 – 12 inch fast response, duct averaging
sensor with flange
• C7130B1009 – Room mount sensor
Humidity Sensors (T775U only)
The controller accepts 0-10 Vdc or 4-20 mA input with a range
of 0-100%
H7625, H7635, and H7655 models (available in 2, 3, and 5%
RH accuracy) can be used.
1
Q Can a T775 be powered with dc voltage?
A No. The T775 controllers may be powered with 24 Vac,
120 Vac, or 240 Vac only, and a separate earth ground is
required.
Q Is a separate earth ground required?
A Yes. Each T775 controller must have its own earth ground,
regardless of the power source (24, 120, or 240 Vac). The
earth ground must be connected to the earth ground
terminal on the 24 Vac terminal block.
Q Can sensors be series-parallel wired to the T775 to provide
an average temperature?
A Yes. Sensors can be series-parallel wired to the T775. In
order to maintain control accuracy, the number of sensors
wired must be of the n
Q How do I know that my selection or value has been
entered?
A Once you have selected an item from a list or entered a
value using the ! and " buttons, pressing the # or $ or
HOME button accepts your selection or value and stores it
in the controller’s memory.
Q What are the T775 Series 2000 Controller specifications?
A Refer to the T775 Series 2000 Electronic Stand-Alone
Controllers - Specification Data (form 63-1318-01).
2
power (i.e. 4, 9, 16, etc.).
Low Differential Pressure Sensors (T775U
only)
P7640A pressure transducer models with selectable pressure
ranges can be used.
The controller accepts pressure sensors with a signal output
of 0-10 Vdc or 4-20 mA for any output range within the
following ranges (the minimum and maximum for the sensor
output range can be adjusted within the following limits):
-500 to 500 PSI
-30.0 to 30.0 inches w.c.
-3,000 to 3,000 Pa
-3,000 to 3,000 kPa
Universal Sensors (T775U only)
The controller accepts 0-10 Vdc or 4-20 mA input for
temperature, pressure, humidity, etc. C7232 and C7632 CO
sensors are also compatible but output is displayed in %
instead of ppm. (Refer to Table 2 on page 29 and the T775U
installation Instructions, form 62-0255-01.)
Actuators
For more information on compatible actuators or other
Honeywell products, such as dampers and valves, go to
www.customer.honeywell.com
Product Selection Tool under Products.
In Table 1, a check mark (!) indicates that the controller
model has this feature. A number indicates the quantity (e.g.,
the T775M2030 has 4 standard SPDT relay outputs), and
“n/a” indicates the feature is not applicable to that controller
model.
Table 1. T775 Controller Features by Model Number.
Feature
User Interface
2x4 inch LCD display with English language display !!!! !!!!!!!!!!!!!!n/a
Keypad lockout!!!!!!!!!!!!!!!!!!n/a
Applications
Standard heating/cooling!!!!!!!!!!!!!!!!!!!
Modulating!!!!!!!!!
Boiler/Chiller!!!!!!!!!!!!!!!!!!!
Reset!!!!!!!!!
Stage (Loop) control of up to 12 relays!!!
Temperature, humidity, pressure, or other
application requiring 0-10 Vdc or 4-20 mA input
Expansion module (4-relays per module; 2 modules
max.)
Power
24 or 120/240 Vac with separate earth ground!!!!!!!!!!!!!!!!!!!
Relay Outputs
SPDT!!!!!!!!!!!!!!!!!!!
Number of standard1242440424244422024
Number of floating
(each floating output eliminates 2 relays)
Runtime displayed on relays 1-4 (optional)!!!!!!!!!!!!!!!!!!n/a
Configurable minimum off time!!!!!!!!!!!!!!!!!!!
Expandable to 12 relays using T775S expansion
modules (4 relays per expansion module)
Warm weather shutdown!n/a
Modulating Outputs
Number of outputs0000002222200220220
Independently selectable for 0-10 Vdc, 2-10 Vdc,
4-20 mA, or Series 90
Modulating high/low limit control!!!!!n/a
Digital Output
Number of outputs0000000000010000000
High, low, and differential alarm!
T775A2009
T775B2016
T775B2024
T775B2032
T775B2040
0121200000002001000
T775M2006
T775M2014
T775M2022
T775M2030
T775L2007
!!!
!!!!!!!!!
T775M2048
T775R2001
T775P2003
T775R2019
T775R2027
T775R2035
T775R2043
T775U2006
T775S2008
!
!
63-7147—34
Page 5
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Table 1. T775 Controller Features by Model Number. (Continued)
T775M2006
T775M2014
T775M2022
T775M2030
T775A2009
T775B2016
T775B2024
T775B2032
T775B2040
T775L2007
T775M2048
T775R2001
T775R2019
T775R2027
T775R2035
T775R2043
T775P2003
T775U2006
T775S2008
Feature
Pump Output (configurable for last relay)
Number of outputs0000000000010000001
Prepurge/Postpurge!!
Pump Exercise!!
Sensor Inputs
Number of sensor inputs1222222222232222220
Number of sensors included111111111113222220n/a
1097 Ohms PTC at 77° F (25° C)!!!!!!!!!!!!!!!!!!n/a
0-10 Vdc or 4-20 mA input for temperature, humidity,
! n/a
pressure, etc.
Calibration capability ±10° F (±6° C) or
!!!!!!!!!!!!!!!!!!n/a
for T775U, ±10% of sensor range
1° sensed temperature accuracy!!!!!!!!!!!!!!!!!!n/a
Sensed temperature range from -60° to 270° F
!!!!!!!!!!!!!!!!!!n/a
(-51° to 132° C)
Digital Input
Number of inputs1111111111111111111
Setpoints
Maximum number of setpoints124244264641464224n/a
Range -40° to 248° F (-40° to 120° C)!!!!!!!!!!!!!!!!!!!
Maximum high setpoint option (irreversible)!!!!!!!!!!!!!!!!!!n/a
Integral and Derivative Options
Integral time selectable from 0 to 3,600 seconds! !!!!!!!!!!!!!!!!!n/a
Derivative time selectable from 0 to 3,600 seconds!!!!!!!!!!!!!!!!!!n/a
Stag ing
Standard staging!!!
First on, first off!!
Equalized runtime!!
On delay and Off delay between stages!!!
Time Clock Scheduler
DST option!!!!!!!!!!!!!!!!!!n/a
2 events per day!!!!!!!!!!!!!!!!!!n/a
Selectable for setback, disable, or ignore to control
!!!!!!!!!!!!!!!!!!n/a
all outputs
Enclosures
NEMA 1!!!!!!!!!!!!!! !
NEMA 4X!!!!
563-7147—3
Page 6
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775 OPERATIONS
Integral Action
“Droop” and equipment hunting can be minimized by
summing (integrating) the offset errors over time and adding
this correction to the output voltage.
A non-zero value for the integral time will allow the controlled
temperature to try and reach the setpoint value.
The integral time is factory set for 400 seconds and is similar
to the response time to the T775 Series 1000 models. This is
a good middle range and should satisfy many applications.
The integral time can be increased for applications where
sensed response is slow, and can be decreased for
applications where sensed response is fast (e.g. discharge air
control).
As a starting point, an optimal integral time for discharge air
typically ranges from 12 to 200 seconds. An optimal integral
time for room control typically ranges from 60 to 2,500
seconds. The purpose of integral action is to reduce or
eliminate the offset from setpoint during steady state control
that is often seen in proportional-only control.
Keep in mind that the controller is most sensitive to throttling
range. Adjust the throttling range first before making any
adjustment to integral time. Adjust throttling range to be as
wide as possible to start, because this will provide the most
stable control. Remember that the integral will eliminate the
steady state error so you do not need to have a small throttling
range to have accurate control. (Integral action allows for
controlling to setpoint even with a wide throttling range.)
Derivative Action
Proportional-integral-derivative (PID) control adds the
derivative function to PI control. The derivative function
opposes any change and is proportional to the rate of change.
The more quickly the control point (actual sensed
temperature) changes, the more corrective action the PID
system provides.
Differential vs. Throttling Range
Differential is used for relay outputs, and throttling range is
used for modulating outputs.
Setpoint and Differential
The following describes the relationship between setpoint and
differential for heating and cooling. These settings are
programmed for each output relay.
HEATING MODE SETPOINT AND DIFFERENTIAL
In heating mode, the differential is below the setpoint. The
relay de-energizes when the temperature rises to the setpoint.
As the temperature drops to the setpoint minus the
differential, the relay energizes.
COOLING MODE SETPOINT AND DIFFERENTIAL
In cooling mode, the differential is above the setpoint. The
relay de-energizes when the temperature falls to the setpoint.
As the temperature rises to the setpoint plus the differential,
the relay energizes.
Throttling Range
The throttling range brackets the setpoint setting, e.g., if the
setpoint is 72° F (22° C) and the throttling range is 10° F
(-12° C), then the effective throttling temperature range is
67° to 77° F (19° to 25° C) . This applies to both modulating
outputs and floating outputs.
Throttling Range for Modulating High or Low Limit
On models that support this feature, the throttling range for
the modulating high or low limit positions the setpoint at the
end of the throttling range. For example, with a high (Heat)
limit at sensor B of 200° F (93° C) and a throttling range of
10° F (-12° C), the modulating output controlling sensor A
begins to throttle back at 190° F (88° C), and fully closes at
200° F (93° C). Conversely, the throttling range for the low
limit begins above the Cooling setpoint in the same manner.
If the control point moves away from the setpoint, the
derivative function outputs a corrective action to bring the
control point back more quickly than through integral action
alone. If the control point moves toward the setpoint, the
derivative function reduces the corrective action to slow down
the approach to the setpoint, which reduces the possibility of
overshoot. The rate time setting determines the effect of the
derivative action. The rate time is the time interval by which
the derivative function advances the effect of the proportional
action. In T775 controllers, the derivative rate time can range
from 0 to 3,600 seconds. The higher the derivative setting, the
greater the effect.
For all T775 Series 2000 controllers, the derivative default
value is factory set to zero (no derivative control). It is strongly
recommended that the derivative remain at zero (0) unless
you have a very good reason to adjust it. Derivative control is
not needed in the vast majority of HVAC applications.
63-7147—36
Setpoint High Limit
You can set an irreversible setpoint high limit maximum value
for any single setpoint temperature value. This prevents the
user from setting any setpoint above the chosen high setpoint
limit, which is useful for meeting some local codes.
Adjust the setpoint (at any output) to the desired maximum
setpoint. Then, simultaneously press the HOME, #, and $
buttons, and continue to press all three buttons for five
seconds to set the setpoint high limit maximum to this value.
NOTE: You must press all three buttons at exactly the same
time for this action to occur.
IMPORTANT
1. This action sets the maximum setpoint value of all
outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is irreversible. If you perform the action inadvertently
and this setpoint adversely affects the control of your
system, you must replace the controller.
Page 7
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Reset Programming (T775L, T775P, T775R,
and T775U models only)
To program an output for reset, refer to the values as shown in
the example below and in Fig. 1. Choose your own
appropriate values for Sensor A maximum and minimum and
Sensor B maximum and minimum.
Reset Example:
• Sensor A is the boiler sensor and sensor B is the outdoor
sensor.
• Maximum boiler temperature desired is 210° F (99° C)
when the outdoor temperature is 20° F (-7° C).
• Minimum boiler temperature desired is 160° F (71° C)
when the outdoor temperature is 70° F (21° C).
With the above settings example, when the outdoor
temperature is 50° F (10° C), the effective setpoint is 180° F
(82° C).
Setpoint Offset
NOTE: The Setpoint Offset is used for subsequent outputs
only.
This value is the number of degrees plus (+) or minus (-) that
you want the temperature to be offset from the first output’s
setpoint. See Fig. 1. For example, If you want the second
output setpoint to be 10° F (-12° C) less than the first output
setpoint, enter -10° F (-23° C).
°F
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
Fig. 1. Reset Curve with Offset for Subsequent Outputs.
The reset curve established when programming the first
output (Fig. 1) is then used for all subsequent outputs that are
configured for Reset = YES, and each of those outputs will be
offset from this curve.
220
210
S
200
E
N
190
S
O
180
R
170
A
160
150
140
RELAY 2
SETPOINT
OFFSET
-10°F
10
20
RESET B1
(OUTSD MIN)
30 40 50 60
SENSOR B
RELAY 1
SETPOINT
70
RESET B2
(OUTSD MAX)
°F80
M24862
Choose Reset = NO for any outputs you do not wish to reset,
then press the HOME button to record your selection.
NOTES:
1.A single reset curve is programmed for the first
output and is used by all outputs setup for Reset.
2.For subsequent outputs, a setpoint offset is used
if that output is also being Reset.
When Reset is programmed, the home screen conveniently
displays the calculated Heat/Cool setpoint(s) for the outputs
based on the reset curve.
Setback (Optional) Description
The Setback temperature option is available only if scheduling
is enabled or the Digital Input Option is set to Setback.
This value is the number of degrees plus (+) or minus (-) that
you want the temperature to be setback (offset) from the
setpoint at a predetermined time.
For example, if you want the temperature to be 10° F (-12° C)
less than the setpoint during setback mode, enter -10° F
(-23° C). See Fig. 2
In normal operations for heating, the offset will be a negative
value; for cooling, the offset will be a positive value.
Setback (optional) Example:
• Setback of -10° F (-23° C) is used to drop the temperature
at night by 10° F (-12° C).
With the above settings example, when the outdoor
temperature is 50° F (10° C), the effective setback setpoint is
170° F (77° C) 180° F (82° C) setpoint minus the 10° F
(-12° C) setback).
°F
220
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
Fig. 2. Reset Curve for First Output with Setback Offset.
210
S
200
E
N
190
S
O
180
R
A
170
160
150
140
10
(OUTSD MIN)
20
RESET B1
SETBACK
OFFSET
-10°F
30 40 50 60
SENSOR B
(OUTSD MAX)
70
RESET B2
°F80
M24861
763-7147—3
Page 8
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775 APPLICATIONS
Water Source Heat Pump Loop Water
Controller – T775B
Application Description
Water is circulated in a loop to remove waste heat and to
provide cooling from a multiple heat pump system. In this
example, the T775B controls heating and cooling systems to
maintain the loop water temperature between preset upper
and lower limits. Alarms are sounded to annunciate
abnormally high or low water temperatures.
NOTE: T775R reset models can also be used in this
application.
Sensor Designation
This device application only requires one sensor. Sensor A is
mounted in a well, located in the main loop water line before
the water source heat pump take-offs.
Operation
In this example, if the loop water temperature drops to 55° F
(13° C), heat is added to the system by the boiler (Relay 1)
until it reaches the setpoint. If the temperature drops further,
Relay 2 sounds the low temperature alarm at 54° F (12° C).
If the loop water temperature rises to 95° F (35° C), Relay 3
brings on cooling. If the temperature rises to 96° F (36° C),
Relay 4 powers the high temperature alarm.
NOTE: If no alarms are present, Relay 2 and 4 may be used
as additional heating and cooling relays.
Programming Example
Relay 1: Enables boiler circuit
Program for:
—Heat
— Setpoint = 65° F (18° C)
— Differential = 10° F (-12° C)
Relay 2: Low temperature alarm circuit
Program for:
—Heat
— Setpoint = 55° F (13° C)
— Differential = 1° F (-17° C)
Relay 3: Enables cooling circuit (heat extraction)
Program for:
—Cool
— Setpoint = 85° F (29° C)
— Differential = 10° F (-12° C)
Relay 4: High temperature alarm circuit
Program for:
—Cool
— Setpoint = 95° F (35° C)
— Differential = 1° F (-17° C)
Setpoints may differ according to equipment manufacturers.
See their recommendations.
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
SENSOR A
(LOOP WATER)
T
T
T775B
2
L1
(HOT)
L2
HI TEMP
ALARM
ADD
HEAT
LO TEMP
ALARM
SUBTRACT
HEAT
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
1
2
24 VAC POWER TERMINAL BLOCK.
C
+
RELAY
4
NC
NO
RELAY
RELAY
3
NC
C
NO
C
NC
1
NO
C
NO
C
NC
RELAY
2
120
COM
1
120 VAC
240
M24863
63-7147—38
Fig. 3. T775B Wiring - Loop Water Controller.
Page 9
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Chiller – T775B
Application Description
As the water temperature in the sump rises, the T775B
sequentially cycles on the spray pump valve and two relays of
fans. If the water temperature in the sump drops below 40° F
(4° C), the T775B energizes a sump dump drain valve to
prevent system freeze up.
NOTE: T775R reset models can also be used in this
application.
Sensor Designation
This device application only requires one sensor. Sensor A is
sensing sump water temperature.
Operation
In this example, the sump water temperature rises above the
Cooling relay 1 setpoint plus differential 65° F (18° C) to bring
on the spray pump valve. If the temperature continues to rise,
Cooling relays 2; 70° F (21° C) and 3; 75° F (24° C) energize
the evaporation fans as needed.
If the sump water temperature drops below 40° F (4° C)
(setpoint minus differential), the sump water freeze up
protection is provided by energizing Heating relay 4.
Relay 4: Controlling dumping of sump at freeze condition
Program for:
— Heat
— Setpoint = 50° F (10° C)
— Differential = 10° F (-12° C)
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
SENSOR A
(SUMP WATER)
T
T
T775B
Programming Example
Relay 1: Controlling spray water pump and/or valve
Program for:
— Cool
— Setpoint = 60° F (16° C)
— Differential = 5° F (12° C)
Relay 2: Controlling fan # 1
Program for:
— Cool
— Setpoint = 65° F (18° C)
— Differential = 5° F (12° C)
Relay 3: Controlling fan # 2
Program for:
— Cool
— Setpoint = 70° F (21° C)
— Differential = 5° F (12° C)
L1
(HOT)
L2
2
C
+
SUMP
DUMP
VALV E
SPRAY
PUMP
VALV E
FAN
#1
FAN
#2
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE
1
TERMINAL BLOCK.
2
24 VAC POWER TERMINAL BLOCK.
RELAY
4
NC
NO
C
NO
NC
RELAY
1
C
RELAY
3
NC
C
NO
NO
C
NC
RELAY
2
Fig. 4. T775B Wiring - Chiller.
120
COM
1
120 VAC
240
M24864
963-7147—3
Page 10
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Chiller, Rotary Compressor – T775B
Application Description
The T775B is controlling the discharge water temperature of a
rotary compressor. The T775B provides an optional low
temperature or low pressure cut-out circuit.
NOTE: T775R reset models can also be used in this
application.
Sensor Designation
This device application only requires one sensor. Sensor A is
sensing discharge water and controls 1 or 2 compressors.
Operation
In this example, the cooling capacity of a Rotary Compressor
is controlled by a slide valve, which when moved towards
open or closed, allows more or less refrigerant into the
compressor. Open and Closed solenoid valves position this
slide valve. The T775B is configured such that two relays are
used to position a single slide valve in a floating mode by
controlling the respective solenoid valves. Capacity of rotary
compressors may also be controlled by variable speed drives,
not covered here.
Programming Example
Relay 1: Compressor #1 controlling the Close solenoid valve
Program for:
—Cool
— Setpoint = 52° F (11° C)
— Differential = 2° F (-17° C)
Relay 2: Compressor #1 controlling the Open solenoid valve
Program for:
—Cool
— Setpoint = 56° F (13° C)
— Differential = 2° F (-17° C)
Relay 3: Compressor #2 controlling the Close solenoid valve
Program for:
—Cool
— Setpoint = 56° F (13° C)
— Differential = 2° F (-17° C)
Relay 4: Compressor #2 controlling the Open solenoid valve
Program for:
—Cool
— Setpoint = 60° F (16° C)
— Differential = 2° F (-17° C)
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
(DISCHARGE WATER)
SENSOR A
T
T
T775B
2
C
+
RELAY
4
NC
C
NO
NO
C
NC
RELAY
1
COOL MODE COMPRESSOR #1
OPEN SOLENOID
ENERGIZED
NULL
CLOSE SOLENOID
ENERGIZED
COOL MODE COMPRESSOR #2
OPEN SOLENOID
ENERGIZED
NULL
CLOSE SOLENOID
ENERGIZED
RELAY
3
NC
C
NO
RELAY
NO
C
NC
2
(HOT)
L1
L2
COMPRESSOR
#2
OPEN
SOLENOID
COMPRESSOR
#1
CLOSE
SOLENOID
COMPRESSOR
#1
OPEN
SOLENOID
COMPRESSOR
#2
CLOSE
SOLENOID
1
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE
TERMINAL BLOCK.
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Cooling Tower Control – T775B2040
Application Description
The T775B2040 is controlling a cooling tower fan, based on
two sensor inputs, to control the low and high fan speeds and
provide cold weather shutdown.
NOTE: T775R2001 reset model can also be used in this
application.
Sensor Designation
This device application requires two sensors:
• Sensor A is sensing the sump temperature.
• Sensor B is sensing the outside air temperature.
Operation
As the sump temperature increases, the low fan speed is
energized by relay 1. On further increase in temperature, relay
2 closes, which energizes the high fan speed and shuts off the
low fan speed. Relay 3 provides cold weather shutdown of the
fan. Relay 3 is wired in series with the common wire of relays
1 and 2, so when relay 3 breaks at 55° F (13° C), power to the
fan is interrupted.
Programming Example
Optional: In Setup, label sensors A and B as desired.
Relay 1: Control to the fan low speed based on the sump
temperature.
Program for:
— Setpoint = 65° F (18° C)
— Differential =5° F (12° C)
— Cool
— Sensor A
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring
SENSO R B - OUTSID E AIR TEM PERATUR E
SENSO R A - SUMP TE MPERATURE
T
T
T
T775B2040
T
2
120
COM
240
NO
NC
1
120 VAC
COM
FAN
NO
COM
C
+
RELAY
4
NC
NO
C
NO
NC
RELAY
1
RELAY
3
NC
C
NO
C
NO
C
NC
RELAY
2
Relay 2: Control to the fan high speed based on the sump
temperature
Program for:
— Setpoint = 70° F (21° C)
— Differential = 5° F (12° C)
— Cool
— Sensor A
Relay 3: Control to the fan cutoff based on the outside air
temperature
Program for:
— Setpoint = 55° F (13° C)
— Differential = 1° F (12° C)
— Cool
— Sensor B
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
IMPORTANT
By programming the relay 3 setpoint at 55° F (13° C),
the T775 is wired to cutoff power to the cooling fan.
Once the outside air temperature rises above 55° F
(13° C), relays 1 and 2 control the fan speed based
on their setpoints for Sensor A Sump.
MOTOR COMMON
LOW SPEED WINDING
HIGH SPEED WINDING
1
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE
TERMINAL BLOCK.
2
24 VAC POWER TERMINAL BLOCK.
M25513
Fig. 6. T775B2040 Wiring for Cooling Tower Control.
Device Checkout
The T775B performance can be checked out to determine if
proper operation exists.
For example, when the outside air temperature is at 55° F
(13° C) or less, the fan should be off. Use the alternate Home
screens to verify that the fan is on or off, based on the outside
air temperature (sensor B).
NOTE: The alternate Home screens do not show live
updates of the sensor temperature. They show the
temperature only at the moment the button is
pressed.
1.From the Home screen, use the $ button to verify
the setpoint temperature for relay 3.
2.Then, press the HOME button to view the actual
outside air temperature (sensor B).
1163-7147—3
Page 12
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Time-based Control of Fan, Pump, etc. –
T775 (all models)
Application Description
In this example, the T775B is able to energize a fan, pump,
lights, economizer, or other device based on a daily time
schedule rather than based on temperature.
Operation
In this example, one relay will energize at 6:00 a.m. and deenergize at 6:00 p.m. daily to operate a fan, pump, or anything
at all.
Configuration Example
Place a 1,000 Ohm resistor at Sensor B (to simulate a
constant 32° F (0° C) temperature reading).
Wire the device to the normally open contacts on a relay.
Relay 1 is used in this example. See Fig. 7
Programming Example
Program in Setup for:
— Outputs
Options
Use Scheduler = YES
NOTE: Keep in mind that if the scheduler is energized, all
relays will follow the time schedule. If you do not
want some outputs to go into a setback mode,
choose Scheduler = NO for those outputs, or
program the setpoint and setback to the same
temperature.
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
1
T
T775B
T
T
SENSOR B
T
Program in Schedule for:
— Options
Set Date = current date
1
Set Time = current time
Set Daylight = YES or NO
— Mon-Fri
E1 Setpoint = Setpoint
E1 Time = 06:00 AM
E2 Setpoint = Setback
E2 Time = 6:00 PM
Relay 1: Control the device (fan, pump, etc.)
Program for:
— Setpoint = 0° F (-17° C)
— Differential = 1° F (-17° C)
— Sensor = Sensor B
— Setback =100° F (38° C)
— Action = Cool
Now the relay will close at 6:00 a.m. and open at 6:00 p.m.,
daily.
1
The Date must be set before the Time is set.
2
COM
3
120 VAC
240
M28021
L2
L1
(HOT)
C
+
RELAY
4
NC
C
FAN,
PUMP,
LIGHTS,
ECONOMIZER,
OR
OTHER DEVICE
INSERT 1000 OHM RESISTOR.
1
24 VAC POWER TERMINAL BLOCK.
2
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE
3
TERMINAL BLOCK.
NO
RELAY
NO
C
NC
1
RELAY
3
NC
C
NO
RELAY
NO
NC
120
C
2
Fig. 7. T775B Wiring for time-based fan, pump or other
device.
63-7147—312
Page 13
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Damper or Valve Modulation – T775M or
T775R
Application Description
In this example, a T775M is controlling an actuator, based on
temperature input, to modulate a damper or valve.
Sensor Designation
This device application requires one sensor.
• Sensor A is sensing outside temperature
NOTE: Sensor A or Sensor B can be used in this
application.
Programming Example
Program in Setup for:
— Modulating Output (MOD) 1:
Type = 2-10V (or whatever output signal is preferred)
Minimum Output % = 0% (range is 0-100%)
Modulating Output 1:Enable actuator circuit
Program for:
— Setpoint = 120° F (49° C)
— Throttling Range = 10° F (-12° C)
— Sensor = Sensor A
— Heat or Cool
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
Wiring
See Figures 8-9 for wiring connections for the T775M with
examples of an MS75xx actuator and an ML7425 valve
actuator.
MS75xx
SPRING RETURN
DIRECT COUPLED ACTUATOR (DCA)
WIRING
STRIP
1
2
3
4
5
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
MOD 1
B
R
W
L1
(HOT)
1
L2
C
–
+
S
V
T
T
Fig. 8. T775M Wiring - Damper Modulation
(2-10 Vdc shown).
ML7425
SPRING RETURN
ACTUATOR
1
L1
(HOT)
L2
VALV E
WIRING
STRIP
F
+
–
T2
T1
O1
O2
TS
MOD 1
B
–
R
+
W
SENSOR A
T775M
C
S
V
T
T
M24881A
SENSOR A
T775M
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Hot Water Reset – T775R
Application Description
The T775R is controlling the boiler water temperature with two
stages (relays), based on outside temperature using a reset
curve and an offset for relay 2.
Sensor Designation
This device application requires two sensors.
• Sensor A is sensing hot water discharge temperature of
the boiler.
• Sensor B is sensing outside air temperature
Operation
In this example, when the outside temperature reaches
70° F (21° C), the desired water temperature of the boiler is
160° F (71° C). Likewise, when the outside temperature drops
to 20° F (-7° C), the hot water temperature needs to be
210° F (99° C). See Fig. 10.
°F
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
220
210
S
200
E
N
190
S
O
180
R
170
A
160
150
140
10
(OUTSD MIN)
OFFSET -10°F
20
RESET B1
RELAY 2
SETPOINT
30 40 50 60
SENSOR B
Fig. 10. Hot Water Reset Curve.
RELAY 1
SETPOINT
70
RESET B2
(OUTSD MAX)
°F80
M24871
MENU
PROGRAM
RELAY 2
OFFSET
-10
ENTER
SETPOINT
OFFSET
FOR
RELAY 2
o
F
M24321
PROGRAM
RELAY 2
MENU
PROGRAM
RELAY 2
OFFSET
DIFFRNTL
HEAT/COOL
SETBACK
EXIT
Fig. 11. Program Mode - Relay 2 Offset.
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
IMPORTANT
By programming the boiler setpoint at 210° F (99° C)
the T775 has established 210° F (99° C) as the
highest operating point that will be allowed when the
outside temperature falls below 20° F (-7° C). As the
outside temperature increases above 20° F (-7° C),
the boiler will be reset downward per the reset ratio
until it reaches the minimum setpoint, 160° F.
Assuming an outside temperature of 20° F (-7° C), Fig. 12
describes the actions of relays 1 and 2 to control the boiler
temperature. As the boiler temperature falls below 210° F
(99° C), relay 1 activates (relay 1 Differential is 20° F (-7° C),
so relay closes at 190° F (88° C). If relay 1 cannot raise the
boiler temperature and the boiler temperature continues to fall
to 180° F °, relay 2 activates (relay 2 Differential is 20° F
(-7° C) 180° to 200° F (82° to 93° C) When the boiler is able to
reach 200° F (93° C), then relay 2 deactivates and relay 1
remains active until the temperature reaches 210° F (99° C).
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
—MOD 1
—# Relays = 2
— Relay 1
— Relay 2
Relay 1: Control to the discharge water temperature
Program for: (Refer to the reset curve in Fig. 10.)
— Boiler Max = 210° F (99° C)
— Outside Min = 20° F (-7° C)
— Boiler Min = 160° F (71° C)
— Outside Max = 70° F (21° C)
— Differential = 20° F (-7° C)
—Sensor A
—Heat
Relay 2: Control to the discharge water temperature
Program for:
— Setpoint Offset = -10° F (-12° C) (See Fig. 11)
—Sensor A
—Heat
63-7147—314
→ Reset = YES-BOILER
→ Reset = YES-BOILER
→ Reset = YES-BOILER
BOILER DISCHARGE
TEMPERATURE
RELAY 1 OFF
210°
RELAY 1
DIFFERENTIAL
RANGE
DIFFERENTIAL
RELAY 2
RANGE
200°
190°
180°
RELAY 2 OFF
RELAY 1 ON
RELAY 2 ON
M24877
Fig. 12. Relay Actions.
NOTE: The Hot Water Reset application continues on the
next page.
Page 15
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Hot Water Reset (continued)
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
(HOT WATER DISCHARGE)
L1
(HOT)
L2
SENSOR A
SENSOR B
(OUTSIDE AI R)
HOT
WATER
BOILER #1
HOT
WATER
BOILER #2
2
C
+
RELAY
4
NC
NO
C
NO
NC
RELAY
1
T
T
T
T775R
T
1
120
COM
120 VAC
240
RELAY
3
NC
C
NO
C
NO
C
NC
RELAY
2
Device Checkout
The T775 performance can be checked out to determine if
proper operation exists.
For example, when the outside air temperature is at 50° F
(10° C), the boiler setpoint temperature should be 180° F
(82° C). See Fig. 14. Use the alternate Home screens to
check that the effective setpoint is adjusting correctly based
on the outside air temperature (sensor B).
NOTE: The alternate Home screens do not show live
updates of the sensor temperature. They show the
temperature only at the moment the button is
pressed.
1.From the Home screen, use the $ button to verify
the setpoint temperature for each output.
2.Then, press the HOME button to view the actual
outside air temperature (sensor B).
BOILER SETPOINT
TEMPERATURE
210°
190°
180°
170°
160
Fig. 14. Boiler Discharge Temperature Setpoint vs.
Outside Temperature.
OUTSIDE AIR
TEMPERATURE
20°
30°200°
40°
50°
60°
70°
M24873
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE
1
TERMINAL BLOCK.
2
24 VAC POWER TERMINAL BLOCK.
Fig. 13. T775R WirIng - Hot Water Reset.
M24872
1563-7147—3
Page 16
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Chilled Water Reset – T775R
Application Description
The T775R is controlling the chiller water temperature, based
on outside temperature using a reset curve.
Multiple stages can also be controlled by using an offset from
the main setpoint for the subsequent relay outputs. When
enabling multiple stages for reset, each stage can have its
own programmable offset from relay 1 (stage 1).
Sensor Designation
This device application requires two sensors.
• Sensor A is sensing the water temperature of the chiller.
• Sensor B is sensing outside air temperature.
Operation
In this example, when the outside temperature reaches 90° F
(32° C), the desired water temperature of the chiller is
45° F (7° C). Likewise, when the outside temperature drops to
70° F (21° C), the chilled water temperature needs to be 60° F
(16° C).
°F
65
SP MAX A1
SENSOR A
(CHILLER)
60
55
50
Relay 1: Control to the chilled water temperature
Program for: (Refer to the reset curve in Fig. 15.)
— Setpoint Max A1 (Chiller) = 60° F (16° C)
— Reset B1 (Outside Min) = 70° F (21° C)
— Setpoint Min A2 (Chiller) = 45° F (7° C)
— Reset B2 (Outside Max) = 90° F (32° C)
— Differential = 10° F (-12° C)
—Cool
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
IMPORTANT
By programming the Chiller setpoint at 45° F (7° C)
the T775 has established 45° F (7° C) as the lowest
operating control point that will be allowed during
reset with the above conditions satisfied.
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
SENSOR B
(OUTSIDE AI R)
SENSOR A (CHILLED WATER)
T
T
T
T775R
T
SP MIN A2
45
40
6595
RESET B1
(OUTSD MIN)
70
758085
90
RESET B2
(OUTSD MAX)
SENSOR B (OUTSIDE AIR)
Fig. 15. Chiller Reset Curve.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
—MOD 1
—# Relays = 1
— Relay 1
→ Reset = YES-OTHER
→ Reset = YES-OTHER
°F
M24874
2
COM
1
120 VAC
240
M24875
L2
L1
(HOT)
C
+
RELAY
4
NC
C
NO
CHILLER
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE
1
TERMINAL BLOCK.
2
24 VAC POWER TERMINAL BLOCK.
NO
NC
RELAY
1
C
RELAY
3
NC
C
NO
NO
C
NC
RELAY
2
120
Fig. 16. T775R Wiring - Chilled Water Reset.
NOTE: The Chilled Water Reset application continues on
the next page.
63-7147—316
Page 17
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Chilled Water Reset (continued)
Device Checkout
The T775 performance can be checked out to determine if
proper operation exists.
For example, when the outside air temperature is at 80° F
(27° C), the chiller water temperature should be 52.5° F
(11° C). See Fig. 17. Use the alternate Home screens to
check that the effective setpoint is adjusting correctly based
on the outside air temperature (sensor B).
NOTE: The alternate Home screens do not show live
updates of the sensor temperature. They show the
temperature only at the moment the button is
pressed.
1.From the Home screen, use the $ button to verify
the setpoint temperature for each output.
2.Then, press the HOME button to view the actual
outside air temperature (sensor B).
CHILLED WATER
SETPOINT TEMPERATURE
60°
56.25°
52.5°
48.75°
45°
OUTSIDE AIR
TEMPERATURE
70°
75°
80°
85°
90°
M24876
Fig. 17. Chiller Setpoint vs. Outside Temperature.
1763-7147—3
Page 18
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Multi-Stage Boiler Control (No Reset) –
T775P
Application Description
The T775P is providing multistage boiler control based on the
boiler's discharge water temperature. The T775P uses the
fourth output relay to energize the primary pump.
Sensor Designation
This device application requires two sensors.
• Sensor A is sensing discharge water and is used to control
3 boiler stages.
• Sensor C is sensing the return water.
NOTE: Control can be to either sensor A or C.
Operation
In this example, as the heating load increases, additional
stages of heat will cycle ON as the boiler water temperature
decreases. The T775P will stage three boilers to provide
sufficient heating. (See Fig. 18.) The primary circulating pump
energizes whenever any stage is energized.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
— # Stages = 3 (T775 assigns pump to Relay 4)
— Options
Seconds = 0 to 3,600 (default is 0)
— Options
Temperature = 30 to 100° F (-1 to 38° C)
— STG4/Pump: (Relay 4 controls the pump output)
Enable = YES
Exercise = YES or NO
Prepurge = -300 to 300 seconds (default is 0)
Postpurge = 0 to 300 seconds (default is 0)
NOTES:
1.A positive Prepurge time causes the pump to
2.The Postpurge time causes the pump to run for
Return to the Setup menu, and select Alarms:
— High Alarm = YES
— High Limit = 220° F (93° C)
NOTE: This model has Equal Runtime options, which can be
Stages 1-3: Control to the discharge water temperature
Program for:
— Setpoint = 200° F (93° C)
— Throttling Range = 18° F (-8° C)
—Sensor A
—Heat
IMPORTANT
→ On Delay and Off Delay:
→ WWSD = YES or NO
energize before the first stage energizes.
A negative time causes the pump to energize
after the first stage energizes.
the set number of seconds after the last stage
de-energizes.
configured with the Lead Lag output option in Setup.
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
Refer to the staging diagram in Fig. 18 for individual stage
behavior.
STAGES
STAGE 3 ON
HYST.
STAGE 2 ON
STAGE 1 ON
STAGE 1
-33%
206°F200°F194°F188°F
1
STAGE ENERGIZESSTAGE DE-ENERGIZES
DISCHARGE WATER TEMPERATURE
1
STAGE 2
0%33%67%
THROTTLING RANGE (18°F)
STAGE 3
M24867
Fig. 18. Boiler Control Staging Behavior (when the
effective setpoint = 200° F).
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
SENSOR A (DISCHARGE WATER)
T
SENSOR C
(RETURN WATER)
ALARM
NC
NO
C
NC
C
RELAY
2
+
4
NC
NO
C
RELAY
(HOT)
L1
(HOT)
L2
L2
DIGITAL OUTPUT
C
NO
L1
PUMP
BOILER #1
BOILER #2
BOILER #3
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE
1
TERMINAL BLOCK.
2
24 VAC POWER TERMINAL BLOCK.
Fig. 19. T775P Wiring - Multi-Stage Boiler Control
(No Reset).
T
T775P
T
T
1
120
COM
120 VAC
240
M24866
RELAY
3
NC
C
NO
NO
C
NC
1
NO
C
NC
RELAY
2
63-7147—318
Page 19
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Multi-Stage Boiler Control (Reset) – T775P
Application Description
The T775P is providing multistage boiler control based on the
boiler's discharge water temperature. The T775P uses the
fourth output relay to energize the primary pump.
Any number of stages from 1 to 12 can be configured (T775P
and T775L models). The throttling range is divided equally
among the stages.
Sensor Designation
This device application requires three sensors.
• Sensor A is sensing discharge water and is used to control
3 boiler stages.
• Sensor B is sensing outside temperature and is used for
reset.
• Sensor C is sensing the return water temperature.
NOTE: Control can be to either sensor A or C.
Operation
In this 3-stage example, as the heating load increases,
additional stages of heat will cycle ON as the boiler water
temperature decreases. The T775P will stage three boilers to
provide sufficient heating. See Fig. 20 for staging behavior.
The primary circulating pump energizes whenever any stage
is energized.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
— # Stages = 3 (T775 assigns pump to Relay 4)
— Options
— Options
Seconds = 0 to 3,600 (default is 0)
— Options
Temperature = 30 to 100° F (-1 to 38° C)
— STG4/Pump: (Relay 4 controls the pump output)
Enable = YES
Exercise = YES or NO
Prepurge = -300 to 300 seconds (default is 0)
Postpurge = 0 to 300 seconds (default is 0)
Return to the Setup menu, and select Alarms:
— High Alarm = YES
— High Limit = 220° F (104° C)
Stages 1-3: Control to the discharge water temperature
Program for: (Refer to the reset curve in Fig. 21.)
— Boiler Max = 210° F (99° C)
— Outside Min = 20° F (-7° C)
— Boiler Min = 160° F (71° C)
— Outside Max = 70° F (21° C)
— Throttling Range = 18° F (-8° C)
— Sensor A
— Heat
— Setback = -10° F (-12° C) (Optional)
→ Reset = YES-BOILER
→ On Delay and Off Delay:
→ WWSD = YES or NO
1
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
STAGES
STAGE 3 ON
HYST.
STAGE 2 ON
STAGE 1 ON
STAGE 1
-33%0%33%67%
206°F200°F194°F188°F
1
STAGE ENERGIZESSTAGE DE-ENERGIZES
DISCHARGE WATER TEMPERATURE
1
STAGE 2
THROTTLING RANGE (18°F)
STAGE 3
M28043
Fig. 20. Boiler Control Staging Behavior (when effective
setpoint = 200° F).
°F
220
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
210
S
200
E
N
190
S
O
180
R
A
170
160
150
140
10
(OUTSD MIN)
20
RESET B1
SETBACK
OFFSET
-10°F
(OPTIONAL)
30 40 50 60
SENSOR B
70
RESET B2
(OUTSD MAX)
°F80
M24869
Fig. 21. Reset Curve with Optional Setback Offset.
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
See Fig. 22 on page 20.
NOTE: The Multi-Stage Boiler Control (Reset) application
continues on the next page.
1
See Notes in “Programming Example” on page 18 for an
explanation of Prepurge and Postpurge times
1963-7147—3
Page 20
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Multi-Stage Boiler Control (Reset)
(continued)
SENSOR B (OUTSIDE AIR)
SENSOR C
(RETURN WATER)
2
C
+
RELAY
L1
(HOT)
L2
L1
(HOT)
L2
1
2
PUMP
BOILER #1
BOILER #2
BOILER #3
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
24 VAC POWER TERMINAL BLOCK.
4
NC
C
NO
RELAY
NO
C
NC
1
Fig. 22. T775P Wiring - Multi-Stage Boiler Control
with Reset.
SENSOR A
(DISCHARGE WATER)
T
T
T
T775P
T
T
T
RELAY
3
NC
C
NO
NO
C
NC
RELAY
2
120
COM
1
120 VAC
240
M24868
Multi-Stage Chiller Control (No Reset) –
T775P
Application Description
The T775P is providing multistage cooling control based on
the chiller’s discharge water temperature. The T775P uses
the fourth output relay to energize the primary pump.
Any number of stages from 1 to 12 can be configured (T775P
and T775L models). The throttling range is divided equally
among the stages.
Sensor Designation
This device application requires three sensors.
• Sensor A is sensing chiller discharge water and is used to
control 3 chiller stages.
• Sensor B is sensing outside temperature and is used to
control relay 4, the pump output.
• Sensor C is sensing the chiller return water temperature.
NOTE: Control can be to either sensor A or C.
Operation
In this 3-stage example, as the cooling load increases,
additional stages of cooling will cycle ON as the chiller water
temperature increases. The T775P will stage three chillers to
provide sufficient cooling. See Fig. 23 for staging behavior.
The primary circulating pump energizes whenever any stage
is energized.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
— # Stages = 3 (T775 assigns pump to Relay 4)
— Options
Seconds = 0 to 3,600 (default is 0)
— STG4/Pump: (Relay 4 controls the pump output)
Enable = YES
Exercise = YES or NO
Prepurge = -300 to 300 seconds (default is 0)
Postpurge = 0 to 300 seconds (default is 0)
Return to the Setup menu, and select Alarms:
— Low Alarm = YES
— Low Limit = 54° F (12° C)
Stages 1-3: Control to the discharge water temperature
Program for:
— Setpoint = 72° F (22° C)
— Throttling Range = 12° F (-11° C)
—Sensor A
—Cool
IMPORTANT
1
See Notes in “Programming Example” on page 18 for an
explanation of Prepurge and Postpurge times.
STAGE 1 ON
Fig. 23. Chiller Control Staging Behavior (when the
→ On Delay and Off Delay:
1
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
STAGES
STAGE 3 ON
HYST.
STAGE 2 ON
STAGE 2
STAGE 1
-33%
68°F72°F76°F80°F
1
STAGE ENERGIZESSTAGE DE-ENERGIZES
CHILLER DISCHARGE WATER TEMPERATURE
1
0%33%67%
THROTTLING RANGE (12°F)
effective setpoint = 72° F).
STAGE 3
M28009
63-7147—320
Page 21
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
SENSOR B (OUTSIDE AIR)
SENSOR C
(CHILLER
RETURN WATER)
2
C
+
RELAY
L1
(HOT)
L2
L1
(HOT)
L2
1
2
PUMP
CHILLER 1
CHILLER 2
CHILLER 3
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
24 VAC POWER TERMINAL BLOCK.
4
NC
NO
RELAY
Fig. 24. T775P Wiring - Multi-Stage Chiller Control
(No Reset).
SENSOR A
(CHILL ER DISC HARGE WATER)
T
T
T
T
T
T
RELAY
NC
C
NO
C
NC
1
C
NO
T775P
3
NO
C
NC
RELAY
2
120
COM
1
120 VAC
240
M28008
4 Stage with Pump Output and Reset – T775P using a T775S Expansion Module
Application Description
The T775P is providing multistage boiler control based on the
boiler's discharge water temperature. Four stages and a
dedicated pump output are used in this example. The T775P
uses the eighth output relay to energize the primary pump.
NOTE: The pump output is always the last relay output. In
this application example, four relays are used for
staged boiler control. A T775S expansion module is
added to provide the additional relay for the pump.
However, the pump must be the last relay, so it is
configured as relay 8 on the T775S module.
Any number of stages from 1 to 12 can be configured (T775P
and T775L models). The throttling range is divided equally
among the stages.
Sensor Designation
This device application requires three sensors.
• Sensor A is sensing discharge water and controls 4 stages.
• Sensor B is sensing outside temperature and is used for
reset.
• Sensor C is sensing the return water temperature.
NOTE: Control can be to either sensor A or C.
Operation
As the heating load increases additional stages of heat will
cycle ON as the boiler water temperature decreases. In this
example, the T775P provides four stage control when the
effective setpoint is 200° F (93° C). (See Fig. 25.) The primary
circulating pump energizes whenever any stage is energized.
NOTE: The pump output must always be the last relay on
the controller or expansion module (relay 4, 8, or 12).
NOTE: For applications with 3 stages or less with a pump
output, an additional expansion module is not
needed.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
— # Stages = 4 (T775 assigns pump to Relay 8)
—Options
2163-7147—3
→ Reset = YES-BOILER
Page 22
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
— STG8/Pump: (Relay 8 controls the pump output)
Enable = YES
Exercise = YES or NO
Prepurge = -300 to 300 seconds (default is 0)
Postpurge = 0 to 300 seconds (default is 0)
Stages 1-4: Control to the discharge water temperature
Program for: (Refer to the reset curve in Fig. 26.)
— Boiler Max = 210° F (99° C)
— Outside Min = 20° F (-7° C)
— Boiler Min = 160° F (71° C)
— Outside Max = 70° F (21° C)
— Throttling Range= 20° F (-7° C)
—Sensor A
—Heat
1
See Notes in “Programming Example” on page 18 for an
explanation of Prepurge and Postpurge times.
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
1
IMPORTANT
By programming the boiler setpoint at 210° F
(-99° C) the T775 has established 210° F (-99° C) as
the highest operating point that will be allowed when
the temperature falls below 20° F (-7° C). As
temperature increases above 20° F (-7° C), the boiler
will be reset downward per the reset ratio until it
reaches the minimum setpoint of 160° F (-99° C), at
70° F (21° C) and above outdoor temperature.
STAGES
STAGE 4 ON
50%
STAGE 4
75%0%25%
M28010
STAGE 3 ON
STAGE 2 ON
STAGE 1 ON
HYST.
STAGE 2
STAGE 1
-25%
205°F185°F200°F195°F190°F
1
THROTTLING RANGE (20°F)
STAGE ENERGIZESSTAGE DE-ENERGIZES
DISCHARGE WATER TEMPERATURE
1
STAGE 3
Fig. 25. Staging Behavior (when the effective setpoint =
200° F (93° C))
°F
220
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
210
S
200
E
N
190
S
O
180
R
A
170
160
150
140
10
(OUTSD MIN)
20
RESET B1
30 40 50 60
SENSOR B
(OUTSD MAX)
70
RESET B2
°F80
M24878
Fig. 26. Reset Curve.
NOTE: The 4 Stage with Pump Output and Reset application
continues on the next page.
63-7147—322
Page 23
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
4 Stage with Pump Output and Reset
(continued)
T
T
T
T
T
T
NO
C
NC
1
(HOT)
L2
–
1
+
L1
STAGE
4
COM
NO
STAGE
STAGE
STAGE
NO
COM
1
2
3
3
C
+
RELAY
4
NC
C
NO
RELAY
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
SENSOR B
SENSOR A
SENSOR C
T
T
T775PT775S
–
1
+
3
C
NO
+
RELAY
8
NC
NO
PUMP
C
NO
RELAY
5
C
NC
L2
L1
(HOT)
RELAY
3
NC
C
NO
NO
C
NC
RELAY
2
COM
NO
120
COM
COM
NO
240
2
120 VAC
COM
RELAY
7
NC
C
NO
NO
C
NC
RELAY
6
120
COM
2
120 VAC
240
T775 BUS TERMINALS PROVIDE WIRING CONNECTIONS TO/FROM T775P/L AND T775S.
1
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
2
24 VAC POWER TERMINAL BLOCK.
3
Fig. 27. T775P Wiring - 4 Stage with Pump Output and Reset.
Device Checkout
The T775 performance can be checked out to determine if
proper operation exists.
For example, when the outside air temperature is at 50° F
(10° C), the boiler temperature should be 180° F (22° C). See
Fig. 28. Use the alternate Home screen to check that the
effective setpoint is adjusting correctly based on the outside
air temperature (sensor B).
NOTE: The alternate Home screen does not show live
updates of the sensor temperature. They show the
temperature only at the moment the button is
pressed.
1.From the Home screen, use the $ button to verify
the setpoint temperature for each output.
2.Then, press the HOME button to view the actual
outside air temperature (sensor B).
M24556
BOILER DISCHARGE
SETPOINT TEMPERATURE
210°
OUTSIDE AIR
TEMPERATURE
20°
30°200°
190°
180°
170°
160
40°
50°
60°
70°
M24880
Fig. 28. Boiler Discharge Temperature vs. Outside
Temperature.
2363-7147—3
Page 24
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
3 Stage Reciprocating Chiller – T775L
Application Description
The T775L is controlling the return water in a reciprocating
chiller with fast-dump freeze protection, low temperature
cutoff, and optional low pressure cutoff.
Sensor Designation
This device application requires two sensors.
• Sensor A is sensing return water and controlling three
stages of cooling.
• Sensor B is sensing discharge water and is controlling
relay 4 for freeze protection.
Operation
Return water is one indication of the cooling load in the water
loop. For example, the higher the return water temperature
the higher the apparent load and more stages of refrigeration
or cooling would be required. If a large load is quickly dropped
from the loop, or for some reason water flow through the
chiller is reduced, discharge water temperature may drop
rapidly to freezing conditions. In this example, Sensor B in the
discharge water will prevent damage to the system by fast-dumping all cooling stages upon close-to-freezing conditions.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
—# Relays = 3
— # Loops = 1
— Options
— Loop 1
— Loop 1
Loop 1: Chiller cooling
Program for:
— Setpoint = 62° F (17° C)
— Throttling Range = 12° F (-11° C)
—Sensor A
—Cool
Relay 4: Low temperature cutoff for freeze protection
Program for:
— Setpoint = 40° F (4° C)
— Differential = 4° F (-16° C)
—Sensor B
—Heat
→ DI Options = Disable
(acts as low pressure cutoff)
→ # Relays = 3
→ Reset = NO
SENSOR A
(RETURN WATER)
SENSOR B
(DISCHARGE
WATER)
DIGITAL INPUT
(LOW PRESSURE
CUTOFF)
L1 (HOT)
L2
COOL #1
COOL #2
COOL #3
12POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
24 VAC POWER TERMINAL BLOCK.
2
C
RELAY
4
NC
NO
C
RELAY
T
T
T
T775L
T
RELAY
3
NC
C
120
NO
NO
C
NC
1
NO
C
NC
RELAY
240
COM
2
Fig. 29. T775L Wiring - Reciprocating Chiller.
STAGES
STAGE 3 ON
STAGE 2 ON
STAGE 1 ON
HYST.
STAGE 2
STAGE 1
-33%
58°F62°F66°F70°F
1
STAGE ENERGIZESSTAGE DE-ENERGIZES
0%33%67%
THROTTLING RANGE (12°F)
STAGE 3
1
120 VAC
COM
M25514
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
63-7147—324
CHILLER DISCHARGE WATER TEMPERATURE
1
M13895
Fig. 30. Chiller Control Staging Behavior (when the
effective setpoint = 62° F (17° C)).
Page 25
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
4 Stage Heat and 6 Stage Cool – T775L
Application Description
The T775L is providing control for four boilers based on the
boiler's discharge water temperature and providing multistage
cooling control.
NOTE: The T775L (with up to two expansion modules) can
control any number of heating and cooling stages up
to a maximum of 12 stages.
Sensor Designation
This device application requires two sensors.
• Sensor A is sensing boiler discharge water temperature for
staged heating control.
• Sensor B is used for cooling control.
Operation
In this example, as the heating load increases, additional
stages of heat will cycle ON as the temperature decreases at
sensor A. The T775L will use four stages to provide sufficient
heating. The six cooling stages are controlled by sensor B.
NOTES:
1.The Interstage ON and OFF delay is an option for
both the heating and the cooling loops.
2.Because only 10 of the 12 relays are being used,
the remaining two relays can be used as
independent controls, each with its own setpoint
and throttling range.
Loop 2: Control to sensor B
Program for:
— Setpoint = 72° F (22° C)
— Throttling Range = 12° F (-11° C)
— Sensor B
— Cool
— Relays = 5-10
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
Wiring
All output relays should have a common power wiring source,
which may or may not be the same as the T775 power wiring.
See Fig. 31 on page 26.
NOTE: The 4 Stage Heat and 6 Stage Cool application
continues on the next page.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode. Select the Outputs menu, and then select:
— # Relays = 10 (4 heat and 6 cool)
— # Loops = 2
— Loop 1
— Loop 1
— Loop 2 → # Relays = 6
— Loop 2
NOTES:
1.The Integral setup parameter can be left at the
2.The On Delay and Off Delay setup parameters
Loop 1: Control to sensor A
Program for:
— Setpoint = 200° F (93° C)
— Throttling Range = 20° F (-7° C)
— Sensor A
— Heat
— Relays = 1-4
1
Reset can be used for the T775L. However, keep in mind
that only one reset curve can be programmed. This means
that you can offset from the curve, but you cannot create a
second reset curve. Normally reset curves can be used for
Heat or Cool, not both.
→ # Relays = 4
→ Reset = NO
1
→ Reset = NO
factory default setting or adjusted as needed for
each loop.
can be adjusted according to the application.
2563-7147—3
Page 26
63-7147—326
4 Stage Heat and 6 Stage Cool (continued)
SENSOR B
SENSOR A
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
L1
(HOT)
L2
L1
(HOT)
L2
24 VAC
HEAT
4
HEAT
1
HEAT
2
HEAT
3
COM
NO
NO
COM
T
T
T
T775LFIRST
T
–
1
+
–
1
+
5
C
C
+
RELAY
4
NC
NO
C
NO
NC
RELAY
1
NO
C
NC
RELAY
2
COM
NO
120
4
COM
COM
240
COM
NO
NO
COM
RELAY
3
NC
C
NO
C
+
RELAY
8
NC
C
NO
RELAY
NO
2
NO
C
NC
5
COOL 4
T
T
T775S
–
1
+
–
3
+
55
C
RELAY
7
NC
C
NO
COOL 3
NO
C
NC
RELAY
6
120
COM
240
NO
NO
COM
4
COOL
1
COOL
2
120 VAC
RELAY
NO
COM
+
12
NC
NO
C
RELAY
T
T
SECOND
T775S
4
120 VAC
RELAY
11
NC
C
NO
NO
C
NC
9
NO
C
NC
RELAY
10
120
COM
240
NO
COM
COOL
6
COOL 5
T775 BUS TERMINALS PROVIDE WIRING CONNECTIONS TO/FROM T775L AND T775S.
1
2
USE PIGTAIL CONNECTI ONS TO WIR E THE T7 75 BUS TERM INALS O N THE FIRST T 775S
SECOND T775S MUST HAVE A JUM PER INSTALLED AS SHOW N AT THE JUMPER TERMI NAL.
3
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
4
24 VAC POWER TERMINAL BLOCK.
5
Fig. 31. T775L Wiring - 4 Stage Heat and 6 Stage Cool using 2 Loops.
M27239
Page 27
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Pressure with a Variable Frequency Drive
(VFD) – T775U
Application Description
In this application the T775U is controlling duct pressure with
a fan controlled by an NXS or NXL Variable Frequency Drive.
A P7640 pressure sensor, located in the duct, is providing
sensor input to the T775U to control the fan speed. The VFD
is looking for a 4-20 mA PID control signal from the T775U
and will drive the fan with a signal directly proportional to this
T775U output.
For additional information about the NXS or NXL variable
frequency drives (VFD), refer to the VFD Reference Guide,
form 63-9469.
Sensor Designation
This device application requires one sensor.
• Sensor A is sensing pressure at the duct (reference is at
the room).
Operation
In this example, as the sensed pressure decreases, the fan
speed increases. Assume we have a 0-10 Vdc sensor output
for 0-5 inches water column. First, set up a Sensor type of
0-10 Vdc into the T775U sensor A settings, and a minimum
(0) and maximum (5) inches water column for the sensor
range.
Also set up a 4-20 mA PID modulating output loop (MOD 1) at
the T775U with a setpoint of 2.5 inches and a throttling range
of 2 inches, and a reverse acting action. At a sensed pressure
of 2.5 inches (in other word, at setpoint), MOD 1 will output
close to 50% or about 12 mA. At 1.5 inches water column, the
output will be 100% or about 20 mA, and at 3.5 inches water
column, the output will be 0% or about 4 mA. Keep in mind
these values are valid for proportional control and will differ in
a PID loop where integral (usually desired) and derivative
(less often required) are set to non-zero values.
Integral and derivative time may need to be adjusted, along
with the throttling range.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode, and then select:
— Sensors
Type = 0-10V
Units = IN WC
Minimum Value = 0.0
Maximum Value = 5.0
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
IMPORTANT
After programming the VFD, be sure to check the
following:
1. Verify that the VFD value P7.1.1.2 (AI2 mode) is set
to 2 (4-20 mA).
2. Verify that the jumper block X2 on the Expansion
board A is in Current Input Mode (a jumper is across
the A terminals, and a jumper is across the B
terminals).
3. Verify that the P7640A pressure sensor is set to:
Output = Voltage
Range = 0 to 5 inches w.c.
Mode = Unidirectional (default)
Volt = 10 Vdc
Wiring
See Fig. 32 for wiring connections for the T775U, the pressure
sensor, and the Variable Frequency Drive.
VFD BOARD A
54
SHIELDED CABLE
MOD 1
C
B
–
R
+
W
S
SENSOR A
V
T
T
Fig. 32. T775U Wiring - Pressure with a VFD (loop
powered wiring).
NOTES:
1. SHIELDED CABLE MUST BE
CONNECTED TO A SEPARATE
EARTH GROUND. HOWEVER,
DO NOT GROUND SHIELDED
CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION
FROM SHIELDED CABLE AS
CLOSE AS POSSIBLE TO
SENSOR BODY.
CSV
OUT
P7640A
COM
PRESSURE
SENSOR;
0-10 VDC
CONNECTION
M28006
POWER
2763-7147—3
Page 28
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Carbon Dioxide (CO2) Sensing – T775U
Application Description
In this application, the T775U is controlling an outside air
damper based on CO
CO
levels.
2
Sensor Designation
This device application requires one sensor.
• Sensor A is sensing CO
Operation
In this example, as the CO2 level increases a damper is
opened to allow fresh air to enter the facility.
Many CO
Because ppm units are not available on the T775, there are
sensors are used with a 0-2,000 ppm output range.
2
two choices.
• You could set up for percent (%), and enter 0 and 100 for
the minimum and maximum sensor inputs. Then use
Table 2 to convert the percent to ppm levels.
• Alternatively, you can set the units for Pa (Pascals, a unit of
pressure not normally used in the United States) and enter
0 for a minimum and 2,000 for a maximum. The controller
will simply convert the input signal (0-10 Vdc or 4-20 mA)
into the correct ppm value and display it on the screen.
Units will still show Pa, but this may be easier than
converting using the table.
Programming Example
Program in Setup:
Press and hold the MENU button for 5 seconds to enter
Setup mode, and then select:
—Sensors
Type = 0-10V
Units = %
Minimum Value = 0.0
Maximum Value = 100.0
sensing input, to maintain reasonable
2
in parts per million
2
→ Sensor A:
Table 2. CO
CO2 PPM
PPM to % conversion.
2
Percentage Display
00%
20010%
40020%
60030%
80040%
1,00050%
1,20060%
1,40070%
1,60080%
1,80090%
2,000100%
Alternatively you can choose Pascals (Pa) as the units and
enter the minimum and maximum PPM levels for the sensor
(0 to 2,000 for example). The controller will show the correct
CO
level but displays Pascals (Pa) instead of PPM.
2
Wiring
See Fig. 33 for wiring connections for the T775U and the CO2
sensor.
SHIELDED CABLE
–
+
SENSOR A
NOTES:
1. SHIELDED CABLE MUST BE
CONNECTED TO A SEPARATE
EARTH GROUND. HOWEVER,
DO NOT GROUND SHIELDED
CABLE AT SENSOR END.
2. TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION
FROM SHIELDED CABLE AS
CLOSE AS POSSIBLE TO
SENSOR BODY.
NOTE: Sensor A is a 0-10 Vdc CO
range of 0 to 2,000 PPM
sensor (C7232) with a
2
IMPORTANT
After the desired value is selected, be sure to press
the # or $ or HOME button in order to save that
value in the controller’s memory.
The T775U displays the sensor output as a percentage (%).
Use Table 2 to convert from % to PPM.
63-7147—328
–
+
+
ANALOG
OUT
–
M24882
24 V
C7232 CO2 SENSOR
(0-10 VDC CONNECTION)
RED
BLACK
1
L1 (HOT)
USE SEPARATE 24 V TRANFORMER TO POWER THE C7232 CO2 SENSOR.
1
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775 APPLICATION REPLACEMENT
EXAMPLES
This section describes how a T775 Series 2000 Electronic
Stand-Alone Controller is wired and programmed to replace
various older generation Honeywell devices.
T675A COMPRESSOR LOCKOUT
W973A
2
COOL 2
T775M2030 Replacement for W973A Logic
Panel
This replacement example illustrates how a T775M2030 is
configured to replace a two-stage Heat and two-stage Cool
W973A Logic Panel.
• Fig. 34 illustrates the wiring connections for the W973A
Logic Panel.
• Fig. 35 and Table 3 on page 31 illustrate the wiring and
configuration of the T775M2030 controller.
T675A HIGH LIMIT
1HEAT2
1COOL2
L1
(HOT)
HEAT 1
HEAT 2
1
L2
1
1
L1
(HOT)
L2
L1
(HOT)
L2
C7046
DISCHARGE
SENSOR
4
FAN RELAY
FAN START
RELAY
M954 MOTOR
COOL 1
W1
T1
B1
T2
R1
(HEATING)
(OPTIONAL) PLENUM
FAN CONTROL
4
MOD-HEATMOD-COOL
SENSORSTAT24VECONO
C +20NH
T
T7067 THERMOSTAT
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
W973A SHOWN. W973B HAS 3 HEAT AND 3 COOL STAGES.
2
USE MODULATING AND/OR OUTPUT RELAYS DEPENDING ON APPLICATION.
3
USE FAN START RELAY AND/OR PLENUM FAN CONTROL FOR AUTOMATIC FAN OPERATION IN
NOTE: The T775R Replacement for W964F Aquatrol Panel with Floating Actuator continues on the next page.
63-7147—332
Page 33
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775R Replacement for W964F Aquatrol
Panel with Floating Actuator (continued)
OPTIONAL
MOTOR
CONFIGURATION
MODULATING OUTPUT (MOD 1)
T1 T2BWR
POWER
3
OUTPUT
7
NO
COM
B
–
R
+
W
5
C
+
RELAY
4
NC
NO
C
RELAY
NOTE: Fig. 37 is for wiring purposes only. A thorough review
of the existing W964F application is required in order
to determine the capability of the T775 controller
replacement.
HONEYWELL ELECTRONIC SERIES 90
MODUTROL MOTOR
2
SENSOR A (STANDARD TE MPERATURE SENSO R)
–
C
S
+
V
4
T
T
NO
C
NC
1
1
SENSOR B (OUTDOOR SENSOR)
T
T
T775R
RELAY
3
NC
C
NO
NO
C
NC
RELAY
2
120
COM
240
NO
COM
6
120 VAC
7
MOTOR
OPEN
COM
CLOSE
8
120/240 VAC LINE
1
OTHER MOTORS SUCH AS 4-20 MA, 0-10 VDC, AND 2-10 VDC, MAY BE USED ON THE MOD 1 OUTPUT.
2
TO VERIFY OUTPUT, TEST OPEN CIRCUIT VOLTAGE BETWEEN THE MOD 1 TERMINALS W AND R.
- MINIMUM (DRIVE CLOSED) SIGNAL LESS THAN 0.17 VDC
- MAXIMUM (DRIVE OPEN) SIGNAL IS GREATER THAN 1.7 VDC
3
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
4
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
5
24 VAC POWER TERMINAL BLOCK.
6
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
7
RELAY 1 CLOSES TO DRIVE DEVICE OPEN.
RELAY 2 CLOSES TO DRIVE DEVICE CLOSED.
8
MOTOR CAN BE AN M944B, M644, M6184, ML6984, ML6420, ETC.
M28014
Fig. 37. T775R Wiring Connections for Replacing a W964F Aquatrol Panel.
NOTE: The T775R Replacement for W964F Aquatrol Panel with Floating Actuator continues on the next page.
3363-7147—3
Page 34
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775R Replacement for W964F Aquatrol
Panel with Floating Actuator (continued)
In this replacement application, the T775R provides the
following, as described in Table 4.
Table 4. T775R Replacement for W964F
Component/FunctionW964F AquatrolT775R Replacement
SensorsT7044A or T7043A
T7043B
Reset ratio and parallel shift n/aReset programming in the T775R provides the reset curve.
On/Off motor controlJumper terminals 1
and 2 on the W964F
Actuator motor speedn/aUse the Integral Time and Throttling Range to tune the T775R control.
Differentialn/aUse the Throttling Range to tune the T775R control.
Program setbackn/aThe T775R provides Setback and alternate setpoint programming parameters.
MotorM944BSeries 90, 4-20 mA, 0-10 Vdc, or 2-12 Vdc motor may be used.
Sensor A - Standard 1097 Ohm temperature sensor.
Sensor B - Standard 1097 Ohm temperature sensor.
See “Temperature Sensors” on page 3.
If the W964F provided On/Off motor control, then wire motor to a relay output
on the T775R to provide On/Off control.
63-7147—334
Page 35
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775L Replacement for S984 Step Controller
This replacement example illustrates how a T775L using a
T775S Expansion module is configured to replace a S984
Step Controller.
NOTE: This replacement section also applies to the S684
Step Controller.
SERIES 90
CONTROLLER
S400A
DELAY
TIMER
9
132
L1 (HOT)L2
1
R
R
WHITE
B
B
W
9
5
W
6
4
ORANGE
S984 STEP CONTROLLER
STAGE 1STAGE 2STAGE 3STAGE 4STAGE 5
NC
NO
NC
Fig. 38 illustrates the wiring connections for the S984 Step
Controller.
Fig. 39 and Table 5 on page 36 illustrate the wiring and
configuration of the T775L controller.
NO
NC
23
NO
NC
NO
NC
NO
1R1
6
L1
L2
3
4
W
4
R
B
P
7
N
ON-OFF
SWITCH
1
8
L1 (HOT)
L1 (HOT)
9
L2
1
L2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
SWITCHES SHOWN WITH DEVICE ENERGIZED.
2
REFER TO SPECIFICATIONS FOR NUMBER OF SWITCHES.
3
AUXILIARY POTENTIOMETER ON S984J ONLY. TERMINAL LABELED “AUX.”
4
THIS HOOKUP IS FOR A COOLING SYSTEM. FOR A HEATING SYSTEM, REVERSE W AND B.
5
6
WHEN SHIPPED, LEADS ARE JOINED WITH A WIRE NUT. TO DELAY STAGES ON, REMOVE WIRE NUT FROM ORANGE AND WHITE
LEADS AND CONNECT TO DELAY TIMER. TO DELAY STAGES OFF, REMOVE WIRE NUT
FROM BLUE AND WHITE LEADS AND CONNECT TO DELAY TIMER.
7
REMOVE JUMPER AND CONNECT ON-OFF SWITCH HERE IF S984 MUST RETURN TO START PPOSITION DURING OFF CYCLE.
CLIP OUT JUMPER (TERMINAL 6 TO L1) AND CONNECT SEPARATE POWER SOURCE HERE IF SEPARATION OF SWITCHING STAGES
NOTE: The T775L Replacement for S984 Step Controller continues on the next page.
3563-7147—3
M28015
Page 36
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775L Replacement for S984 Step Controller
(continued)
SENSOR A (C7100D1001)
SENSOR B (SPACE OR OUTDOOR TEMPERATURE)
T
T
T775LT775S
NO
C
NC
RELAY
2
COM
NO
120
3
COM
COM
240
NO
RELAY
3
NC
C
NO
(HEAT/COOL CHANGEOVER)
2
L1
(HOT)
L2
DIGITAL INPUT
T6031 OR T675A
24 VAC
COOL 2
HEAT
1
HEAT
2
COOL 1
COM
NO
NO
COM
T
T
1
–
+
–
+
4
C
+
RELAY
4
NC
C
NO
NO
C
NC
RELAY
1
T775 BUS TERMINALS PROVIDE WIRING CONNECTIONS TO/FROM T775L AND T775S.
1
SETUP T HE CONT ROL (T6 031 OR T765) SO THAT IT CLOSES O N A TEMPER ATURE FALL.
2
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
3
24 VAC POWER TERMINAL BLOCK.
4
NOTE: Fig. 39 is for wiring purposes only. A thorough review
of the existing S984 application is required in order to
determine the capability of the T775 controller
replacement.
1
–
+
4
C
NO
COM
+
RELAY
8
NC
C
NO
NO
C
NC
RELAY
5
RELAY
7
NC
C
NO
NO
C
NC
RELAY
6
120
COM
240
NO
COM
3
120 VAC
COOL 4
COOL 3
M28018
Fig. 39. T775L Wiring Connections for Replacing a S984 Step Controller.
In this replacement application, the T775L provides the following, as described in Table 5:
Table 5. T775L Replacement for S684 or S984.
Component/FunctionS684 or S984 T775L Replacement
SensorSeries 60, Series 90,
T915, T991, T921,
W902, etc. controller
Sensor A - Standard 1097 Ohm temperature sensor.
Sensor B - Standard 1097 Ohm temperature sensor; (required only if reset
control is used; i.e. a T991B or W902A controller was used.)
See “Temperature Sensors” on page 3.
NOTE: If you are implementing two-sensor reset control, Sensor A must
always be the controlled temperature and Sensor B must always
be the controlling temperature. For example, in a reset control
based on outside temperature, Sensor A must be the inside sensor
and Sensor B must be the outside sensor.
Delay TimerS400AUse the On Delay and Off Delay programmable parameters of the T775L.
Throttling Rangen/aSet the programmable Throttling Range parameter to match the application.
ResetT991B or W902A
Reset programming in the T775L provides the reset curve.
(if used)
Loads 1 - 5n/aProgram the 5 relays into a single loop.
Auxiliary Pot.S964J onlyThe T775L Controller with two T775S Expansion modules allows for up to
12 relay outputs.
63-7147—336
Page 37
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775L Replacement for W7100C Discharge
Air Controller
This replacement example illustrates how a T775L using a
T775S Expansion module is configured to replace a two-stage
Heat and four-stage Cool W7100C Discharge Air Controller.
L1 (HOT)
1
L2
L1 (HOT)
1
L2
M955 MOTOR
(ECONOMIZER)
W1
7
DISCHARGE
4
4
R1
B1
2
C7100
SENSOR
WR
WR
TR
TR
2K2
7 6
W
W
2K2
1K1
5
1K1
5
MINIMUM POSITION
POTENTIOMETER
2K1
400 OHM (4 COOLING STAGES)
8
2K1
200 OHM (2 HEATING STAGES)
T7047C1025 SPACE RESET SENSOR OR
C7031G1016 OUTDOOR RESET SENSOR
Q209A
R
W
BWR
312
H205 OUTDOOR
AIR CHANGEOVER
S963B1037 REMOTE
POTENTIOMETER
3
S963B1078 OR S963B1086
HEATING REMOTE
SETPOINT POTENTIOMETER
S963B1078 OR S963B1086
COOLING REMOTE
SETPOINT POTENTIOMETER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
USE ONLY WITH SPACE RESET SENSOR. CONNECT IN SERIES AS SHOWN.
3
WHEN RESET NOT USED, JUMPER TERMINALS 6 AND 7.
SET HEAT AND COOL DISCHARGE SETPOINTS USING REMOTE SETPOINT POTENTIOMETERS. TURN SETPOINT KNOB ON W7100
4
TO MINIMUM POSITION. USE OF THE S963B1086 WILL CHANGE SETPOINT RANGE TO 40 TO 140°F.
GROUND CASE OF REMOTE SETPOINT POTENTIOMETER TO PREVENT PROBLEMS DUE TO STATIC ELECTRICITY.
5
WHEN CHANGEOVER TERMINALS 9 AND 10 ARE USED ON HEAT/COOL MODELS, JUMPER TERMINALS 9 AND 10 TO CHANGE OVER TO
6
HEATING (LOCKS OUT COOLING WHEN JUMPERED).
WHEN ECONOMIZER IS NOT USED, JUMPER TERMINALS Y AND 9 WITH THE 510 OHM, 1/4 WATT, 5 PERCENT RESISTOR CONTAINED
7
IN THE 4074EFV BAG ASSEMBLY.
8
REMOVE FACTORY INSTALLED 400 OHM RESISTOR JUMPER AND RECONNECT FOR COOLING-ONLY MODE, 4-STAGE OPERATION
(CHANGE VALUE FOR OTHER NUMBER OF STAGES). FOR 2-STAGES IN HEATING MODE, USE 200 OHM, 1/8 WATT RESISTOR FOR
BEST OPERATION.
Fig. 40 illustrates the wiring connections for the W7100C
Discharge Air Controller.
Fig. 41 and Table 6 on page 39 illustrate the wiring and
configuration of the T775L controller.
NOTE: The T775L Replacement for W7100C Discharge Air Controller continues on the next page.
3763-7147—3
Page 38
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775L Replacement for W7100C Discharge
Air Controller (continued)
SENSOR A (C7100D1001)
SENSOR B (SPACE OR OUTDOOR TEMPERATURE)
T
T
T775LT775S
NO
C
NC
RELAY
2
COM
NO
3
120
COM
RELAY
3
NC
C
NO
(HEAT/COOL CHANGEOVER)
2
L1
(HOT)
L2
DIGITAL INPUT
T6031 OR T675A
24 VAC
COOL 2
HEAT
1
HEAT
2
COOL 1
Fig. 41. T775L Wiring Connections for Replacing a W7100C Discharge Air Controller.
COM
NO
NO
COM
T
T
1
–
+
–
+
4
C
+
RELAY
4
NC
C
NO
NO
C
NC
RELAY
1
T775 BUS TERMINALS PROVIDE WIRING CONNECTIONS TO/FROM T775L AND T775S.
1
SETUP T HE CONT ROL (T6 031 OR T765) SO THAT IT CLOSES O N A TEMPER ATURE FALL.
2
POWER WITH 24 VAC OR 120/240 VAC AT THE APPROPRIATE TERMINAL BLOCK.
3
24 VAC POWER TERMINAL BLOCK.
4
COM
NO
NOTE: Fig. 41 is for wiring purposes only. A thorough review
of the existing W7100C application is required in
order to determine the capability of the T775
controller replacement.
1
–
+
4
C
240
NO
COM
+
RELAY
8
NC
C
NO
NO
C
NC
RELAY
5
RELAY
7
NC
C
NO
NO
C
NC
RELAY
6
120
COM
240
NO
COM
3
120 VAC
COOL 4
COOL 3
M28018
NOTE: The T775L Replacement for W7100C Discharge Air Controller continues on the next page.
63-7147—338
Page 39
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
T775L Replacement for W7100C Discharge
In this replacement application, the T775L provides the
following, as described in Table 6:
Air Controller (continued)
Table 6. T775L Replacement for W7100C.
W7100C
Component/Function
SensorC7100
EconomizerM955, Q209A, and H705The T775L can not provide a direct economizer function. However, an
Heat/Cool switch
changeover
Setpoint and Reset• Setpoint and Reset dialReset programming in the T775L provides the reset curve.
Control BandControl Band dialSet the programmable Throttling Range parameter to match the
Satellite (if used)W7101A (if used)By adding up to two T775S Expansion modules, you have up to 12
Discharge Air ControllerT775L Replacement
Sensor A - C7100D1001
T7047C1025 and S963B1037
T675AConnect the Digital Input terminal to an outdoor temperature control,
• S963B1078 or S963B1086 Remote setpoint adjustment is not possible.
• S963B1037 and
T7047C1025
Sensor B - Standard 1097 Ohm temperature sensor; space or outdoor
See “Temperature Sensors” on page 3.
output relay can be used to enable a separate economizer module
(e.g., W7212) to provide economization.
e.g. T6031 or T675A).
Program the Digital Input for Setback using -40° F (-40° C) for the
T675A cooling setpoint to lock out the cooling system during cold
weather.
NOTES: 1. Reset can be used for Heating or Cooling, but not both.
2. Remote adjustment of the reset curve is not possible.
application.
relays available.
3963-7147—3
Page 40
63-7147—340
T775 CROSS REFERENCE
Table 7. Cross Reference.
Recommended
Temperature ° F
Old
ControlManufacturer
NOTE: For all T775 Series 2000 Controllers, the Setpoint Temperature Range is -40° to 248° F (-40° to 120° C).
A350A/BJohnsonT775A2009Johnson model: 1 SPDT temperature
A350A/B with
1 S350
A350A/B with
up to 3 S350s
A350A/B with
more than 3
S350s
A350PJohnsonT775M2006Johnson model: 1 mod temperature
A350P with
up to 2 S350s
A350P with
up to 4 S350s
A350R with
up to 3 S350s
A350S with
up to 4 S350s
A350P with
A350R
A350P with
A350R and
multiple
S350s
JohnsonT775B2032 Johnson model: Multiple SPDT temperature
JohnsonT775B2040Johnson model: Multiple SPDT temperature
JohnsonT775B2040 plus
JohnsonT775M2048Johnson model: 1 mod temperature with relays
JohnsonT775M2030Johnson model: 1 mod temperature with relays
JohnsonT775R2001 or
JohnsonT775R2001 or
JohnsonT775R2043Johnson model: 1 mod temperature with reset
JohnsonT775R2027 or
/ Humidity
Range (RH)
Switch
Action
Cap
Length
Honeywell
Electromechanical
Replacement
Johnson System 350
Table 7 lists the manufacturers in the following order:
• Johnson (System 350) — beginning on page 40
• Honeywell — beginning on page 41
• Johnson (Mechanical) — beginning on page 44
• White Rogers — beginning on page 47
• Barber Colman — beginning on page 48
• Ranco — beginning on page 49
• Tekmar — beginning on page 50
Recommended
Honeywell
Well #
(Order Sep.)
Honeywell
Electronic
Replacement
additional
T775Bs as
needed.
T775R2035
T775R2035
T775R2019
Honeywell
Well #
(Order Sep.)Comments
Johnson model: Multiple SPDT temperature
Johnson model: Mod temperature with reset and
SPDTs
Johnson model: Mod temperature with reset and
SPDTs
Johnson model: 1 mod temperature with reset and
SPDTs
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
can be configured with up to two T775S expansion modules for a maximum of 12 stages
2
if staging 4 relays and a pump output add one T775S2008 expansion module
3
if staging 9 relays and a pump output add two T775S2008 expansion modules
10k
Ω at 77°F1097Ω at 77°F 10kΩ at 77°F1097Ω at 77°F10kΩ at 77°F1097Ω at 77°F 1097Ω at 77°F10kΩ at 77°F1097Ω at 77°F 1097Ω at 77°F10kΩ at 77°F1097Ω at 77°F10kΩ at 77°F1097Ω at 77°F10kΩ at 77°F1097Ω at 77°F
!!
!!!! !!!!!! !
need external timer
(tekmar Timer 031)
!!
need external timer
(tekmar Timer 031)
!!
need external timer
(tekmar Timer 031)
!
need external timer
(tekmar Timer 031)
!
need external timer
(tekmar Timer 031)
!
!!!!!!!!!!
Page 51
NOTES
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
5163-7147—3
Page 52
T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée