T775L Series 2000 Electronic
Stand-Alone Staging Controller
INSTALLATION INSTRUCTIONS
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next
generation of commercial and agricultural controls
capable of remote sensing of temperature and providing
switched and/or proportional outputs to various types of
loads. A built-in time clock is standard.
The T775L model can be used to stage multiple relays
from two independent heat or cool setpoints. The number
of stages for each setpoint can be freely chosen, limited
only by the number of relays available.
The T775L can be configured with up to two T775S
Expansion Modules for a maximum of up to 12 stages.
IMPORTANT
The T775L is an operating control, not a limit or
safety control. If used in applications requiring
safety or limit controls, a separate safety or limit
control device is required.
Table 1. T775L Controller Configuration.
Controller ModelDescriptionOutput Reset
a
T775L2007
a
The T775L model can be used to stage multiple relays from two independent heat or cool setpoints. The number of stages for each setpoint can
be freely chosen, limited by the number of relays available (up to 12 stages using two T775S expansion modules).
In addition to the two staged loops, up to two additional relays can be available for independent on-off control.
b
The maximum number of non-sequenced relays is two (2) with each having its own setpoint and its own throttling range. These relays are available if not being used by the staged relay loops.
c
The T775L includes a digital input for use with the disable or setback option.
Stage Sequencer
with Reset
Yes
SPDT Relay
Outputs
b
4
Digital
Input
c
1
Number of
Sensor
Sensors
Inputs
Included
21 YesYesNEMA 1
Stage
Control
Addable
T775S Enclosure
E4436
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
Temperature Sensors
a
The controller accepts 1,097 Ohms PTC at 77°F (25°C):
• 50021579-001 – Standard sensor (included with all
models except NEMA 4X models)
• T775-SENS-STRAP – Strap-on sensor with wiring box
• T775-SENS-WR – Water resistant with 5 foot leads
(included with NEMA 4X models)
• T775-SENS-WT – Watertight with 6 foot lead
• T775-SENS-OAT – Outdoor air temperature sensor
• C7031B2008 – 6 inch duct mount with wiring box
• C7031D2003 – 5 inch immersion sensor with wiring
box (use immersion well; P/N 50001774-001)
Below are the changes to the T775L model star ting with
Series 3 (March 2009). Series 3 can be identified by the
sideways 3 after the part number on the device label.
1. MIN ON added.
2. SYNC added.
3. Differential and throttling range increased to 300°F.
4. Setpoint, Enable, and DHW options added to the DI
options.
Controller Dimensions
TOP
1 (25.5)
7/8 (22.5)
2 15/16 (74)
LEFTRIGHT
4 1/16 (103.4)
1/64 (3.8)
8 5/32
(207.1)
4 1/16 (103.4)
2 11/16 (68.1)
7/8 (22.5)
7 23/32
(196)
7/8 (22.5)
1 (25.5)
Fig. 1. T775L Dimensions in inches (mm).
62-0257—132
4 13/32 (112.1)
3 31/32 (101)
FRONT VIEW
BOTTOM
1/2 (12.4)
2 13/16 (71.8)
7/8 (22.5)
M24378
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
BEFORE INSTALLATION
Review the “Specifications” on page 37 before
installing the controller.
When Installing This Product
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
INSTALLATION AND SETUP
The following installation procedures are typically
performed in the order listed:
1. Mounting – see “Mounting” below.
2. Wiring – see “Wiring” on this page.
3. Checkout – see page 8.
4. Interface and Programming overview – see page 9.
5. Setup – see page 11.
6. Programming the Controller with no Reset – see
page 22
or
Programming the Controller with Reset – page 25.
7. Scheduling (optional) – see page 31.
Additional topics are:
• Temperature sensor calibration begins on page 8.
• Interface overview begins on page 9.
• Summary menu begins on page 36.
• Troubleshooting begins on page 36.
Mount the controller on any convenient interior location
using the four mounting holes provided on the back of the
enclosure using #6 or #8 screws (screws are not provided
and must be obtained separately). Use controller
dimensions in Fig. 1 on page 2 as a guide.
The controller may be mounted in any orientation.
However, mounting in the orientation shown in Fig. 1
permits proper viewing of the LCD display and use of the
keypad.
Temperature Sensor(s) Mounting
and Location
Temperature sensors may be located up to 1,000 feet
(304 m) from the T775L controller. See Table 3 on page 8
for calibration guidelines.
The sensors may be mounted on a wall or panel for
sensing space temperature, strapped to a pipe or inserted
in an immersion well (see Fig. 2) for hot or cold water
sensing, or taped to a standard cap or bulb holder for duct
air sensing. To prevent moisture or condensation entering
the sensor through the lead wire holes, mount the sensor
with the lead wires exiting the bottom of the sensor.
NOTES:
1.The included sensor is not designed for very
wet applications. For immersion applications,
an immersion well is used.
2.Heat conductive compound must be used in
immersion wells.
3.See “Temperature Sensors” on page 2 for this
type of installation.
SENSOR
PLACED
IN WELL
USE HEAT
CONDUCTIVE
COMPOUND
MOUNTING
This section describes the mounting procedures for the
controller and temperature sensor(s).
Controller Mounting
IMPORTANT
Avoid mounting in areas where acid fumes or
other deteriorating vapors can attack the metal
parts of the controller circuit board, or in areas
where escaping gas or other explosive vapors
are present.
IMPORTANT
The controller must be mounted in a position that
allows clearance for wiring, servicing, and
removal.
Use a screwdriver to pry out only the knockouts that you
will use.
If mounting on DIN rail, be sure to remove the knockouts
before mounting. See “Controller Wiring” on page 5 and
Fig. 7 on page 6 for recommended knockout usage and
locations. If you do not use an opened knockout be sure
to cover it.
1/2 NPT
Fig. 2. Sensor inserted in immersion well.
NOTE: Multiple sensors may be parallel-series wired
to sense average temperatures in large
spaces. See Fig. 3 on page 4.
IMMERSION
WELL
M24379
WIRING
All wiring must comply with applicable electrical codes
and ordinances, or as specified on installation wiring
diagrams. Controller wiring is terminated to the screw
terminal blocks located inside the device.
The remainder of this section describes the temperature
sensor wiring and the T775L controller wiring.
Wiring Connections Access
To access the wiring connections, remove the two screws
on the left side of the enclosure and gently swing open the
top. Be careful to not stress the ribbon cables that connect
the keypad and LCD display to the controller circuit board.
362-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
CAUTION
TO T775 CONNECTIONS (SENSOR A) OR (SENSOR B).
SENSORS
M24380
Temperature Sensor Wiring
Electrical Shock Hazard.
Can short equipment circuitry.
Make sure that metal tube of sensor does not
short against T terminals in wall-mounted case.
IMPORTANT
Poor wiring practices can cause erratic readings
from the sensor. Avoid the following to ensure
proper operation:
•Do not route the temperature sensor wiring with
building power wiring.
•Do not locate the temperature sensor wiring
next to control contactors.
•Do not locate the temperature sensor wiring
near electrical motors.
•Do not locate the temperature sensor wiring
near welding equipment.
•Make sure good mechanical connections are
made to both the sensor and the controller.
•Do not mount the sensor with the lead wire end
pointing up in an area where condensation
can occur.
If any of the above conditions cannot be avoided,
use shielded cable.
NOTE: Each temperature sensor must be wired to a
single T775 controller. However, a benefit of
the T775 controller’s accuracy is that there is
no more than a 2°F differential between any
two T775 controllers.
Reset Temperature Control
If you are implementing two-sensor reset control, Sensor
A must always be the controlled temperature and Sensor
B must always be the controlling temperature.
For example, in a reset control based on outside
temperature, Sensor A must be the inside sensor and
Sensor B must be the outside sensor.
Multiple Parallel Sensors
Multiple sensors can be parallel-series wired to sense
average temperatures in large spaces. To maintain control
accuracy, the number of sensors to be parallel-series
wired must be of the n
See Fig. 3.
2
power (for example, 4, 9, 16, etc.).
Fig. 3. Parallel-series wiring of sensors.
Temperature Sensor Wire Type and Size
Temperature sensors use standard AWG 18/2 unshielded
wire. For cable runs greater than 25 feet or where
electrical interference may be a problem, shielded cable is
recommended. See Fig. 4.
Refer to “Temperature Sensor Calibration” on page 8 for
wire size selection where cable runs are longer than 25
feet.
T
T
T
T
1
SENSORS A AND B USE THE TWO TT CONNECTIONS AND
ARE POLARITY INSENSITIVE.
Fig. 4. Sensor Wiring — Showing shielded cable connection to Sensor A.
62-0257—134
SENSOR A
1
SENSOR B
SHIELDED
CABLE
SHIELDED
CABLE
NOTE: SHIELDED CABLE MUST BE
CONNECTED TO AN EARTH
GROUND.
HOWEVER, DO NOT GROUND
SHIELDED CABLE AT SENSOR END.
NOTE: TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION FROM
SHIELDED CABLE AS CLOSE AS
POSSIBLE TO SENSOR BODY.
SENSOR
M24381
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
WARNING
CAUTION
CAUTION
CAUTION
C
+
W
1
2
M24296
NO HIGH VOLTAGE. CLASS 2 WIRING ONLY.
EARTH GROUND TERMINAL MUST BE CONNECTED
TO CONDUIT CLAMP LOCALLY.
1
2
Controller Wiring
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring,
or making wiring connections, to prevent electrical
shock or equipment damage.
Do not use 24 Vac power to power any external
loads if 120 Vac or 240 Vac is used to power
the T775L.
A separate earth ground is required.
Equipment damage can result if the earth ground
is not connected. See Fig. 5 and Table 2 on
page 6.
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Ensure that you are properly grounded before
handling the unit.
See Fig. 7 on page 6 for locating the appropriate power
input, remote sensors input, low voltage, contact closure,
and load output terminals.
Access to the terminals can be gained through standard
conduit knockouts (A through E in Fig. 7 on page 6)
located around the perimeter of the enclosure:
• Knockouts A and B should be used only for sensor and
low-voltage wiring.
• Knockouts C, D, and E can be used to gain access to
the load relay output terminals and 120/240 Vac power
wiring.
Controller Wiring Method
Wire the sensors and outputs, then wire the power
connection.
Each terminal can accommodate the following gauges of
wire:
• Single wire – from 14 AWG to 22 AWG solid or
stranded
• Multiple wires – up to two 22 AWG stranded
For 24, 120, or 240 Vac power connections:
Single wire – from 14 to 18 AWG solid or stranded
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire
in the required terminal location and tighten the
screw.
3. If two or more wires are being inser ted into one terminal location, twist the wires together a minimum
of three turns before inserting them to ensure
proper electrical contact.
4. Cut the twisted end of the wires to 3/16 in. (5 mm)
before inserting them into the terminal and tightening the screw.
5. Pull on each wire in all terminals to check for good
mechanical connection.
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
1/2 (13)
IMPORTANT
IMPORTANT
Fig. 5. Earth Ground.
Poor wiring practices can cause erratic readings
from the sensor. To ensure proper operation,
ensure that good mechanical connections are
made to both the sensor and the controller.
When wiring the input power, only one source of
power can be applied to the T775L (24, 120, or
240 Vac).
2. TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING SCREW.
THEN PULL ON EACH WIRE IN ALL
TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M24382
Fig. 6. Attaching two or more wires at terminal blocks.
562-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
Controller Wiring Details
The wiring connection terminals are shown in Fig. 7 and
are described in Table 2 on page 6.
See Fig. 8 – Fig. 12 beginning on page 7 for typical T775L
wiring applications.
KNOCKOUT A
T
T
T
T
T775 BUS
DIGITAL INPUT
KNOCKOUT B
POWER
2
24 VAC
OUTPUT
RELAY 4
OUTPUT
RELAY 1
KNOCKOUT C
1
SENSORS A AND B USE THE TWO TT CONNECTIONS AND ARE
POLARITY INSENSITIVE.
2
A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER
SOURCE (24, 120, OR 240 VAC).
–
+
–
+
C
+
C
KNOCKOUT E
NC
C
NO
NO
C
NC
NC
C
NO
NO
NC
Fig. 7. T775L Terminal and Feature Locations.
120
COM
240
SENSOR A
1
SENSOR B
OUTPUT
RELAY 3
POWER
120/240 VAC
OUTPUT
RELAY 2
KNOCKOUT D
M24383
Table 2. Description of Wiring Terminal Connections.
Connection
Terminal
LabelDescription
Sensors
Sensor A
Sensor B
T T
Temperature Sensor; polarity
insensitive
Outputs
Relay 1
Relay 2
Relay 3
NO
COMNC120-240 Vac Relay Output
Relay 4
Input
DI + -Digital Input (dry contact)
Interconnect
T775 BUS
+
Terminal Connection to/from
-
T775S
24 Vac Power
24V + +24 Vac Hot
Common -24 Vac Common
Ground
Earth Ground
a
120 or 240 Vac Power
120 Vac120120 Vac Power
CommonCOMCommon
240 Vac240240 Vac Power
a
A separate earth ground is required for all installations regardless
of the power source (24, 120, or 240 Vac).
NOTE: Relays 5–8 are assigned to the first T775S
Expansion Module, if connected. Relays 9–12
are assigned to the second T775S, if connected.
WIRING APPLICATION
EXAMPLES
Fig. 8 – 12 beginning on page 6 illustrate typical controller
wiring for various applications.
NOTE: The electronic Series 90 output provided with
modulating T775 models can not drive electro-mechanical slidewire devices like older
Series 3 modulating meters (prior to Series
6), V9055s, and S984s.
62-0257—136
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
L1
(HOT)
L2
24 VAC
COM
NO
COM
NO
M24384A
LOAD 2
LOAD 1
SENSOR A
C
NO
NC
C
NO
NC
T
T
C
+
L1
(HOT)
L2
24 VAC
M24385A
SENSOR A
C
NO
NC
C
NO
NC
C
NC
NO
C
NC
NO
T
T
COM
LOAD
4
NO
LOAD
3
LOAD
2
LOAD
1
C
+
COM
NO
COM
NO
COM
NO
SENSOR A
T
T
Fig. 8. Wiring for Two-stage Control – 24 Vac Input
and 24 Vac Load.
Fig. 9. Wiring for Four-stage Control – 24 Vac Input
and 24 Vac Load.
1
120V
COM
120
240
COM
NO
LOAD 2
COM
NO
COM
C
+
NO
C
NC
NO
C
NC
LOAD 1
FOR 240 VAC LOAD, CON NECT TO 240 TERMINAL .
1
Fig. 10. Wiring for Two-stage Control with 120 or 240
Vac (120 Vac Input and 120 Vac Load shown).
SENSOR B
T
T
T
T
C
+
C
LOAD 4
NC
NO
C
NO
C
NC
LOAD 1
NC
COM
C
NO
NO
NO
NC
FOR 240 VAC LOAD, CON NECT TO 240 TERMINAL .
1
Fig. 11. Wiring for Four-stage Control with 120 or 240
Vac (120 Vac Input and 120 Vac Load shown).
120V
COM
120
240
COM
SENSOR A
1
LOAD
3
LOAD
2
M24386A
M24387A
762-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
WARNING
M24391
DIGITAL
INPUT
+
–
M24304
TEMPERATURE (DEGREES)
RESISTANCE (OHMS)
1403
1317
1231
1145
1059
973
20 40 60 80 100 120 140 160 180 200 220
0 10 20 30 40 50 60 70 80 90 100
°F
°C
0-20-40
120
110
250
-40-20 -10-30
1489
887
801
1097 ± 0.08 OHMS
AT 77°F (25°C)
POSITIVE TEMPERATURE COEFFICIENT (PTC) OF 2.1 OHMS PER °F
1
1
See “1.1.1.2. CALIBRATE (the sensor)” on page 13 for
the instructions to enter the calibration value.
See Table 3 and Fig. 13 on page 8 for temperature
resistance information.
Table 3. Temperature Sensor Calibration for Resis-
tance Loss due to Wire Length.
AWG
Fig. 12. Wiring for Digital Input (dry contact).
RatingmΩ/ft
142.50.461.142.28
CHECKOUT
Inspect all wiring connections at the controller terminals,
and verify compliance with the installation wiring
diagrams.
164.00.721.823.64
186.41.162.905.82
2010.21.864.649.28
2216.12.927.3214.64
Temperature Offset in
°F (Foot)
a
200 ft500 ft1,000 ft
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring
or making wiring connections, to prevent electrical
shock or equipment damage.
If any wiring changes are required, first be sure to remove
power from the controller before starting work. Pay
particular attention to verifying the power connection (24,
120, or 240 Vac).
After the controller is mounted and wired, apply power.
Power Loss
The date and time settings are retained for 24 hours after
a power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.
Temperature Sensor Calibration
As wire length increases, resistance increases and thus
the temperature reading increases. If necessary, calibrate
the sensor input by reducing the value by the amount
shown in the Table 3. For example, a wire run with 18
gauge wire of 1,000 feet, requires a calibration offset of
-6.0°F.
IMPORTANT
If the calibration value in the table exceeds the
controller’s calibration limits of +/-10°F (+/-6°C),
you must use a heavier gauge wire.
For example, with a wire run of 1,000 feet you
must use 20 AWG wire or heavier in order to
calibrate for wire loss within the limits of the
controller.
62-0257—138
AWG
RatingmΩ/m
Temperature Offset in
°C (Meter)
100 m200 m300 m
a
148.30.440.861.30
1613.20.681.382.06
1821.01.102.183.28
2033.51.743.485.22
2252.82.745.488.22
a
This is the distance from the controller to the sensor
(already accounts for round trip distance).
Fig. 13 shows how sensor resistance varies with
temperature for a sensor having a positive temperature
coefficient (PTC) of 2.1 Ohms per degree F (3.85 Ohms
per degree C).
Fig. 13. Sensor Resistance vs. Temperature.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
DI ON
HOME
1
23456789101112
SENSORS
SENSOR A
78
SENSOR B
84
o
o
F
F
DI ON
HOME
o
F
o
F
L1 1-4ON
HEAT
SETPOINT
60
SENSOR A
78
RT 1436 HRS
123456789101112
DI ON
HOME
o
F
o
F
REL 9 OFF
HEAT
SETPOINT
60
SENSOR A
78
RT 684 HRS
123456789101112
M24398
INTERFACE OVERVIEW
The T775L controller uses an LCD panel and 6-button
keypad to provide status information and permit user input
of the programming, setup, and scheduling parameters.
The following figure describes the display areas of the
LCD and the keypad.
HOME
1 2 3 4 5 6 7 8 9 10 11 12
SENSORS
SENSOR A
78
SENSOR B
84
DI ON
home menu
Fig. 14. LCD Display - Home Screen And Keypad.
Menu Area – On the home screen, the LCD displays the
configured relays and whether they are active. In
Program, Setup, or Schedule mode, the LCD displays the
current menu selection and its order within the menu
hierarchy.
Data Area – On the home screen, the LCD displays the
sensors and outputs status. In Setup or Program mode,
the LCD displays menu choices, parameter selections,
and data values.
Lock Icon – The icon indicates the MENU button is
locked and prevents access to the Setup and Program
menus.
NOTE: Pressing and holding the HOME and MENU
buttons simultaneously for five seconds
locks/unlocks the MENU button.
6-Button Keypad – The keypad is used to access the
menus and enter values (see “Using the LCD Panel
Interface”).
Using the LCD Panel Interface
The 6-button keypad is used to move through the menus
and enter or change parameter values.
Home Button
Pressing the HOME button at any time exits the current
Programming or Setup display screen and returns to the
home screen as shown in Fig. 14 and Fig. 15.
Menu Button
• Pressing the MENU button always displays the
Program menu. If you are in Setup mode, you exit
setup and return to the Program menu.
o
F
o
F
MENU AREA
DATA AREA
LOCK ICON
6 BUTTON KEYPAD
M24397
• Pressing and holding the MENU button for five
seconds leaves the current screen and displays
the Setup menu.
Left and Right Arrow Buttons ( and )
Use these buttons to move backward () and forward ()
through the Program and Setup menus.
Up and Down Arrow Buttons ( and )
Use these buttons to move your selection up and down
through a menu or list.
• When the desired item is highlighted, you press the
arrow button to display that item’s content.
• When a value is displayed (e.g. 70°F), the up and
down arrows increase and decrease the value.
NOTE: Once you select an item from a list or enter a
value, pressing the or or HOME button
accepts your selection or value and stores it
in the controller’s memory.
Home Screen
In the normal run state, the LCD home screen displays
the current sensed temperatures, the active status of the
output loops and relays, and error and status codes.
When using Reset, the Heat/Cool setpoint(s) display on
the home screen for the Loop and Relay outputs; see Fig.
15.
Active relays are indicated by the small black square ()
just below the relay number. Fig. 15 shows the home
screen with relays 1, 2, and 4–6 energized.
Pressing the and buttons from the home screen
cycles through the sensors, loops, and additional relay(s).
Fig. 15. LCD Display - Home Screen Displaying
Sensors, Loops, and additional Relay(s).
NOTES:
1.The loop home screen and the relay home
screen do not dynamically update the active
relay status and sensor values. The information is a snapshot taken when you press the
or button to display the screen.
2.In Reset mode, the home screen displays the
effective setpoint.
IMPORTANT
After four minutes of inactivity (no buttons
pressed), the LCD display reverts to the home
screen display.
962-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
Accessing the Menus
Menus are used for setup, programming, scheduling, and
viewing the summary settings.
Program, Schedule, and Summary
Menus
To access these menus from the home screen, press the
MENU button. See Fig. 16.
HOME
123456789101112
SENSORS
SENSOR A
78
SENSOR B
84
DI ON
menu
home
MENU DISPLAY WHEN
SCHEDULING IS SET
PROGRAM
SCHEDULE
o
F
SUMMARY
EXIT
o
F
MENU
Fig. 16. Menus.
Depending on whether scheduling is enabled or not, the
LCD displays one of two menus as shown in Fig. 16.
Scheduling is enabled from the Setup menu’s Output
settings (see “1.3.3.1. USE SCHED” on page 15).
Setup Menu
To access the Setup menu, press and hold the MENU
button for five seconds. See Fig. 17.
HOME
1 2 3 4 5 6 7 8 9 10 11 12
SENSORS
SENSOR A
78
SENSOR B
84
DI ON
home
menu
o
F
o
F
FIVE
SECONDS
Fig. 17. Setup Menu.
Using the Menus
When you are working with the menus, use the:
• Left arrow button () to scroll backward through the
menus
• Right arrow button () to select the highlighted menu
item and display its content
OR
SENSORS
OUTPUTS
EXIT
MENU DISPLAY WHEN
SCHEDULING IS NOT SET
MENU
PROGRAM
EXIT
M24399
SETUP
M24400A
• Up and Down arrow buttons ( and ) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed parameter
NOTES:
1. If you press the HOME button or there is no keypad
activity for four minutes, you exit Program mode and
return to the home screen.
2. If you press the MENU button, you exit and return to
the menu.
PROGRAMMING OVERVIEW
The controller must be programmed before being placed
into service.
IMPORTANT
During programming, the controller is live at all
times. For example, the contacts may open and
close when adjusting the setpoint.
The programming process uses a hierarchical menu
structure that is easy to use. You press the
buttons to move forward and backward through the menus.
NOTES:
1. The T775L controller interface is intuitive. You may
want to use this procedure simply as a reference to
locate the particular option or parameter of interest.
2. The menus can display only those relays that are
defined in Setup (see “1.3.1. Number of RELAYS” on
page 14). For example, if you configure only one
relay, then only one relay displays on the appropriate
menus.
3. If you press the HOME button or there is no keypad
activity for four minutes, you exit Program mode and
return to the home screen.
4. If you press the MENU button, you exit Program
mode and return to the menu.
Control Loops
The T775L provides the capability to have up to two PID
control loops, which allow multiple stages to be assigned
to a single setpoint in each loop.
Setpoint and Differential
The following describes the relationship between setpoint
and differential for heating and cooling. These settings are
programmed for each output relay.
Heating Mode Setpoint and Differential
In heating mode, the differential is below the setpoint. The
relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the differential, the relay energizes.
Cooling Mode Setpoint and Differential
In cooling mode, the differential is above the setpoint. The
relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
differential, the relay energizes.
and arrow
62-0257—1310
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
M24297A
THROTTLING RANGE
STAGE 2 ON
STAGE 3 ON
STAGE 1 ON
-25%
STAGES
HYST.
75%
205°F185°F
0%
200°F
25%
195°F
STAGE 4 ON
50%
190°F
STAGE 1
STAGE 2
STAGE 3
STAGE 4
STAGE ENERGIZESSTAGE DE-ENERGIZES
Setpoint High Limit
You can set an irreversible setpoint high limit maximum
value for any single displayed setpoint value.
Adjust the setpoint (at any output) to the desired
maximum setpoint. Then, simultaneously press the
HOME,, and buttons and continue to press all three
buttons for five seconds to set the setpoint high limit
maximum to this value.
NOTE: You must press all three buttons at exactly
the same time for this action to occur.
IMPORTANT
1. This action sets the maximum setpoint value of
all outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is irre-versible. If you perform the action inadvertently
and this setpoint adversely affects the control of
your system, you must replace the controller.
Staged Operation
Staging occurs as illustrated in Fig. 18 for a Heat setpoint
of 200°F and a throttling range of 20°F when the Integral
value is zero (0). When the Integral is not zero, then the
actual temperatures at which stages energize and deenergize will vary from this example; see “1.3.4.2.
INTEGRAL” on page 18.
NOTE: A non-zero integral causes the control to
move toward the setpoint value.
Fig. 18. Staging Behavior
(when effective Setpoint = 200°F).
Programming the T775L Controller
In addition to the two staged loops, up to two additional
relays can be available for independent on-off control.
Examples of Loop and Relay configurations are:
• Number of relays = 8. Loop 1 uses relays 1-3, and
• Number of relays = 11. Loop 1 uses relays 1-5, and
• Number of relays = 12. Loop 1 uses relays 1-4, and
Loop 2 uses relays 4-6. The remaining two relays (7
and 8) are available for use.
Loop 2 uses relays 6-10. The remaining relay (11) is
available for use.
Loop 2 uses relays 5-8. Relays 9 and 10 are available
for use, but in this case, relays 11 and 12 are not
usable.
• Number of relays = 8. Loop 1 uses relays 1-6, and
Loop 2 uses relays 7-8. There are no additional relays
available for use.
IMPORTANT
If you change the number of relays, the controller
resets the number of relays per loop to zero (0)
for all loops. You must use Setup mode to reconfigure all loops and additional relays. See
page 11.
To program the controller, perform the setup configuration
(see “1. Setup”) and then select one of the following
procedures depending on whether the Reset function is to
be used:
• Program the Outputs for No Reset — see
“2. Programming Output (Loops and Additional Relays)
with No Reset” on page 22.
• Program the Outputs for Reset — see “” on page 25.
When programming is complete, you may continue with
“4. Scheduling” on page 31.
1. SETUP
Setup provides the ability to change the factory default
settings for the temperature sensors and outputs, to
enable/disable reset control, and to enable/disable
scheduling.
IMPORTANT
If you change the number of relays, the controller
resets the number of relays per loop to zero (0)
for all loops. You must use Setup mode to reconfigure all loops and additional relays.
NOTE: The T775L controller interface is intuitive.
You may want to use this procedure simply
as a reference to locate the particular option
or parameter of interest.
NOTES:
1.If you press the HOME button or there is no
keypad activity for four minutes, you exit
Setup mode and return to the home screen.
2.If you press the MENU button, you exit Setup
mode and go to the Program menu.
Once in Setup mode, you use the —
• Left arrow button() to scroll backward through the
Setup menus
• Right arrow button () to select the highlighted menu
item and display its content
• Up and Down arrow buttons ( and ) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed setup parameter
Setup Procedure
The Setup process uses a hierarchical menu structure
that is easy to use. You press the and arrow buttons
to move forward and backward through the menus.
NOTE: The menus can display only those relays that
are defined in Setup (see “1.3.1. Number of
RELAYS” on page 14). For example, if you
configure only two relays, then only two
relays display on the appropriate menus.
1162-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
SENSORS
SENSOR A
SETUP
SENSORS
SENSOR A
UNITS
CALIBRATE
LABEL
EXIT
M24430
To change the controller’s sensors and output setup
parameters, perform the following procedures in the order
listed:
1. Enter Setup mode — see “Entering Setup Mode”.
2. Setup Sensors — see “1. Setting up the Sensors”.
3. Setup Outputs — see “1.3. Setting up the Outputs”
on page 14.
4. Exit Setup Mode — see “1.4. Exiting Setup” on
page 22.
SETUP
SENSORS
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
M24428
Fig. 19. Setup - Sensors Menu.
SETUP
SENSORS
# SENSORS
SETUP
SENSORS
# SENSORS
2
ENTER
NUMBER OF
SENSORS
Fig. 20. Setup - Sensors - Number of Sensors.
M24429
Entering Setup Mode
To enter Setup mode, press and hold the MENU button for
five seconds to display the Setup menu. See Fig. 17 on
page 10.
1. Setting up the Sensors
1. From the Setup menu, use the and buttons to
highlight SENSORS.
2. Press the button to display the Sensors menu.
1.1. Number of SENSORS
The value entered here determines the number of
sensors displayed on the home screen.
1. From the Sensors menu, highlight # SENSORS
then press the button to display the number of
sensors.
2. Use the and buttons to enter the number of
sensors (1 or 2).
Default: 2
3. Press the button to accept the value and display
the SENSOR A selection.
Fig. 21. Setup - Sensors - Sensor A Menu.
62-0257—1312
1.1.1. SENSOR A
If you are implementing two-sensor reset control, Sensor
A must always be the controlled temperature and Sensor
B must always be the controlling temperature. For
example, in a reset control based on outside temperature,
Sensor A must be the inside sensor and Sensor B must
be the outside sensor.
1. From the Sensors menu, highlight SENSOR A.
2. Press the button to display the Sensor A selec-
tions.
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.