T775L Series 2000 Electronic
Stand-Alone Staging Controller
INSTALLATION INSTRUCTIONS
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next
generation of commercial and agricultural controls
capable of remote sensing of temperature and providing
switched and/or proportional outputs to various types of
loads. A built-in time clock is standard.
The T775L model can be used to stage multiple relays
from two independent heat or cool setpoints. The number
of stages for each setpoint can be freely chosen, limited
only by the number of relays available.
The T775L can be configured with up to two T775S
Expansion Modules for a maximum of up to 12 stages.
IMPORTANT
The T775L is an operating control, not a limit or
safety control. If used in applications requiring
safety or limit controls, a separate safety or limit
control device is required.
Table 1. T775L Controller Configuration.
Controller ModelDescriptionOutput Reset
a
T775L2007
a
The T775L model can be used to stage multiple relays from two independent heat or cool setpoints. The number of stages for each setpoint can
be freely chosen, limited by the number of relays available (up to 12 stages using two T775S expansion modules).
In addition to the two staged loops, up to two additional relays can be available for independent on-off control.
b
The maximum number of non-sequenced relays is two (2) with each having its own setpoint and its own throttling range. These relays are available if not being used by the staged relay loops.
c
The T775L includes a digital input for use with the disable or setback option.
Stage Sequencer
with Reset
Yes
SPDT Relay
Outputs
b
4
Digital
Input
c
1
Number of
Sensor
Sensors
Inputs
Included
21 YesYesNEMA 1
Stage
Control
Addable
T775S Enclosure
E4436
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
Temperature Sensors
a
The controller accepts 1,097 Ohms PTC at 77°F (25°C):
• 50021579-001 – Standard sensor (included with all
models except NEMA 4X models)
• T775-SENS-STRAP – Strap-on sensor with wiring box
• T775-SENS-WR – Water resistant with 5 foot leads
(included with NEMA 4X models)
• T775-SENS-WT – Watertight with 6 foot lead
• T775-SENS-OAT – Outdoor air temperature sensor
• C7031B2008 – 6 inch duct mount with wiring box
• C7031D2003 – 5 inch immersion sensor with wiring
box (use immersion well; P/N 50001774-001)
Below are the changes to the T775L model star ting with
Series 3 (March 2009). Series 3 can be identified by the
sideways 3 after the part number on the device label.
1. MIN ON added.
2. SYNC added.
3. Differential and throttling range increased to 300°F.
4. Setpoint, Enable, and DHW options added to the DI
options.
Controller Dimensions
TOP
1 (25.5)
7/8 (22.5)
2 15/16 (74)
LEFTRIGHT
4 1/16 (103.4)
1/64 (3.8)
8 5/32
(207.1)
4 1/16 (103.4)
2 11/16 (68.1)
7/8 (22.5)
7 23/32
(196)
7/8 (22.5)
1 (25.5)
Fig. 1. T775L Dimensions in inches (mm).
62-0257—132
4 13/32 (112.1)
3 31/32 (101)
FRONT VIEW
BOTTOM
1/2 (12.4)
2 13/16 (71.8)
7/8 (22.5)
M24378
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
BEFORE INSTALLATION
Review the “Specifications” on page 37 before
installing the controller.
When Installing This Product
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
INSTALLATION AND SETUP
The following installation procedures are typically
performed in the order listed:
1. Mounting – see “Mounting” below.
2. Wiring – see “Wiring” on this page.
3. Checkout – see page 8.
4. Interface and Programming overview – see page 9.
5. Setup – see page 11.
6. Programming the Controller with no Reset – see
page 22
or
Programming the Controller with Reset – page 25.
7. Scheduling (optional) – see page 31.
Additional topics are:
• Temperature sensor calibration begins on page 8.
• Interface overview begins on page 9.
• Summary menu begins on page 36.
• Troubleshooting begins on page 36.
Mount the controller on any convenient interior location
using the four mounting holes provided on the back of the
enclosure using #6 or #8 screws (screws are not provided
and must be obtained separately). Use controller
dimensions in Fig. 1 on page 2 as a guide.
The controller may be mounted in any orientation.
However, mounting in the orientation shown in Fig. 1
permits proper viewing of the LCD display and use of the
keypad.
Temperature Sensor(s) Mounting
and Location
Temperature sensors may be located up to 1,000 feet
(304 m) from the T775L controller. See Table 3 on page 8
for calibration guidelines.
The sensors may be mounted on a wall or panel for
sensing space temperature, strapped to a pipe or inserted
in an immersion well (see Fig. 2) for hot or cold water
sensing, or taped to a standard cap or bulb holder for duct
air sensing. To prevent moisture or condensation entering
the sensor through the lead wire holes, mount the sensor
with the lead wires exiting the bottom of the sensor.
NOTES:
1.The included sensor is not designed for very
wet applications. For immersion applications,
an immersion well is used.
2.Heat conductive compound must be used in
immersion wells.
3.See “Temperature Sensors” on page 2 for this
type of installation.
SENSOR
PLACED
IN WELL
USE HEAT
CONDUCTIVE
COMPOUND
MOUNTING
This section describes the mounting procedures for the
controller and temperature sensor(s).
Controller Mounting
IMPORTANT
Avoid mounting in areas where acid fumes or
other deteriorating vapors can attack the metal
parts of the controller circuit board, or in areas
where escaping gas or other explosive vapors
are present.
IMPORTANT
The controller must be mounted in a position that
allows clearance for wiring, servicing, and
removal.
Use a screwdriver to pry out only the knockouts that you
will use.
If mounting on DIN rail, be sure to remove the knockouts
before mounting. See “Controller Wiring” on page 5 and
Fig. 7 on page 6 for recommended knockout usage and
locations. If you do not use an opened knockout be sure
to cover it.
1/2 NPT
Fig. 2. Sensor inserted in immersion well.
NOTE: Multiple sensors may be parallel-series wired
to sense average temperatures in large
spaces. See Fig. 3 on page 4.
IMMERSION
WELL
M24379
WIRING
All wiring must comply with applicable electrical codes
and ordinances, or as specified on installation wiring
diagrams. Controller wiring is terminated to the screw
terminal blocks located inside the device.
The remainder of this section describes the temperature
sensor wiring and the T775L controller wiring.
Wiring Connections Access
To access the wiring connections, remove the two screws
on the left side of the enclosure and gently swing open the
top. Be careful to not stress the ribbon cables that connect
the keypad and LCD display to the controller circuit board.
362-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
CAUTION
TO T775 CONNECTIONS (SENSOR A) OR (SENSOR B).
SENSORS
M24380
Temperature Sensor Wiring
Electrical Shock Hazard.
Can short equipment circuitry.
Make sure that metal tube of sensor does not
short against T terminals in wall-mounted case.
IMPORTANT
Poor wiring practices can cause erratic readings
from the sensor. Avoid the following to ensure
proper operation:
•Do not route the temperature sensor wiring with
building power wiring.
•Do not locate the temperature sensor wiring
next to control contactors.
•Do not locate the temperature sensor wiring
near electrical motors.
•Do not locate the temperature sensor wiring
near welding equipment.
•Make sure good mechanical connections are
made to both the sensor and the controller.
•Do not mount the sensor with the lead wire end
pointing up in an area where condensation
can occur.
If any of the above conditions cannot be avoided,
use shielded cable.
NOTE: Each temperature sensor must be wired to a
single T775 controller. However, a benefit of
the T775 controller’s accuracy is that there is
no more than a 2°F differential between any
two T775 controllers.
Reset Temperature Control
If you are implementing two-sensor reset control, Sensor
A must always be the controlled temperature and Sensor
B must always be the controlling temperature.
For example, in a reset control based on outside
temperature, Sensor A must be the inside sensor and
Sensor B must be the outside sensor.
Multiple Parallel Sensors
Multiple sensors can be parallel-series wired to sense
average temperatures in large spaces. To maintain control
accuracy, the number of sensors to be parallel-series
wired must be of the n
See Fig. 3.
2
power (for example, 4, 9, 16, etc.).
Fig. 3. Parallel-series wiring of sensors.
Temperature Sensor Wire Type and Size
Temperature sensors use standard AWG 18/2 unshielded
wire. For cable runs greater than 25 feet or where
electrical interference may be a problem, shielded cable is
recommended. See Fig. 4.
Refer to “Temperature Sensor Calibration” on page 8 for
wire size selection where cable runs are longer than 25
feet.
T
T
T
T
1
SENSORS A AND B USE THE TWO TT CONNECTIONS AND
ARE POLARITY INSENSITIVE.
Fig. 4. Sensor Wiring — Showing shielded cable connection to Sensor A.
62-0257—134
SENSOR A
1
SENSOR B
SHIELDED
CABLE
SHIELDED
CABLE
NOTE: SHIELDED CABLE MUST BE
CONNECTED TO AN EARTH
GROUND.
HOWEVER, DO NOT GROUND
SHIELDED CABLE AT SENSOR END.
NOTE: TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION FROM
SHIELDED CABLE AS CLOSE AS
POSSIBLE TO SENSOR BODY.
SENSOR
M24381
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
WARNING
CAUTION
CAUTION
CAUTION
C
+
W
1
2
M24296
NO HIGH VOLTAGE. CLASS 2 WIRING ONLY.
EARTH GROUND TERMINAL MUST BE CONNECTED
TO CONDUIT CLAMP LOCALLY.
1
2
Controller Wiring
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring,
or making wiring connections, to prevent electrical
shock or equipment damage.
Do not use 24 Vac power to power any external
loads if 120 Vac or 240 Vac is used to power
the T775L.
A separate earth ground is required.
Equipment damage can result if the earth ground
is not connected. See Fig. 5 and Table 2 on
page 6.
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Ensure that you are properly grounded before
handling the unit.
See Fig. 7 on page 6 for locating the appropriate power
input, remote sensors input, low voltage, contact closure,
and load output terminals.
Access to the terminals can be gained through standard
conduit knockouts (A through E in Fig. 7 on page 6)
located around the perimeter of the enclosure:
• Knockouts A and B should be used only for sensor and
low-voltage wiring.
• Knockouts C, D, and E can be used to gain access to
the load relay output terminals and 120/240 Vac power
wiring.
Controller Wiring Method
Wire the sensors and outputs, then wire the power
connection.
Each terminal can accommodate the following gauges of
wire:
• Single wire – from 14 AWG to 22 AWG solid or
stranded
• Multiple wires – up to two 22 AWG stranded
For 24, 120, or 240 Vac power connections:
Single wire – from 14 to 18 AWG solid or stranded
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire
in the required terminal location and tighten the
screw.
3. If two or more wires are being inser ted into one terminal location, twist the wires together a minimum
of three turns before inserting them to ensure
proper electrical contact.
4. Cut the twisted end of the wires to 3/16 in. (5 mm)
before inserting them into the terminal and tightening the screw.
5. Pull on each wire in all terminals to check for good
mechanical connection.
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
1/2 (13)
IMPORTANT
IMPORTANT
Fig. 5. Earth Ground.
Poor wiring practices can cause erratic readings
from the sensor. To ensure proper operation,
ensure that good mechanical connections are
made to both the sensor and the controller.
When wiring the input power, only one source of
power can be applied to the T775L (24, 120, or
240 Vac).
2. TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING SCREW.
THEN PULL ON EACH WIRE IN ALL
TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M24382
Fig. 6. Attaching two or more wires at terminal blocks.
562-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
Controller Wiring Details
The wiring connection terminals are shown in Fig. 7 and
are described in Table 2 on page 6.
See Fig. 8 – Fig. 12 beginning on page 7 for typical T775L
wiring applications.
KNOCKOUT A
T
T
T
T
T775 BUS
DIGITAL INPUT
KNOCKOUT B
POWER
2
24 VAC
OUTPUT
RELAY 4
OUTPUT
RELAY 1
KNOCKOUT C
1
SENSORS A AND B USE THE TWO TT CONNECTIONS AND ARE
POLARITY INSENSITIVE.
2
A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER
SOURCE (24, 120, OR 240 VAC).
–
+
–
+
C
+
C
KNOCKOUT E
NC
C
NO
NO
C
NC
NC
C
NO
NO
NC
Fig. 7. T775L Terminal and Feature Locations.
120
COM
240
SENSOR A
1
SENSOR B
OUTPUT
RELAY 3
POWER
120/240 VAC
OUTPUT
RELAY 2
KNOCKOUT D
M24383
Table 2. Description of Wiring Terminal Connections.
Connection
Terminal
LabelDescription
Sensors
Sensor A
Sensor B
T T
Temperature Sensor; polarity
insensitive
Outputs
Relay 1
Relay 2
Relay 3
NO
COMNC120-240 Vac Relay Output
Relay 4
Input
DI + -Digital Input (dry contact)
Interconnect
T775 BUS
+
Terminal Connection to/from
-
T775S
24 Vac Power
24V + +24 Vac Hot
Common -24 Vac Common
Ground
Earth Ground
a
120 or 240 Vac Power
120 Vac120120 Vac Power
CommonCOMCommon
240 Vac240240 Vac Power
a
A separate earth ground is required for all installations regardless
of the power source (24, 120, or 240 Vac).
NOTE: Relays 5–8 are assigned to the first T775S
Expansion Module, if connected. Relays 9–12
are assigned to the second T775S, if connected.
WIRING APPLICATION
EXAMPLES
Fig. 8 – 12 beginning on page 6 illustrate typical controller
wiring for various applications.
NOTE: The electronic Series 90 output provided with
modulating T775 models can not drive electro-mechanical slidewire devices like older
Series 3 modulating meters (prior to Series
6), V9055s, and S984s.
62-0257—136
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
L1
(HOT)
L2
24 VAC
COM
NO
COM
NO
M24384A
LOAD 2
LOAD 1
SENSOR A
C
NO
NC
C
NO
NC
T
T
C
+
L1
(HOT)
L2
24 VAC
M24385A
SENSOR A
C
NO
NC
C
NO
NC
C
NC
NO
C
NC
NO
T
T
COM
LOAD
4
NO
LOAD
3
LOAD
2
LOAD
1
C
+
COM
NO
COM
NO
COM
NO
SENSOR A
T
T
Fig. 8. Wiring for Two-stage Control – 24 Vac Input
and 24 Vac Load.
Fig. 9. Wiring for Four-stage Control – 24 Vac Input
and 24 Vac Load.
1
120V
COM
120
240
COM
NO
LOAD 2
COM
NO
COM
C
+
NO
C
NC
NO
C
NC
LOAD 1
FOR 240 VAC LOAD, CON NECT TO 240 TERMINAL .
1
Fig. 10. Wiring for Two-stage Control with 120 or 240
Vac (120 Vac Input and 120 Vac Load shown).
SENSOR B
T
T
T
T
C
+
C
LOAD 4
NC
NO
C
NO
C
NC
LOAD 1
NC
COM
C
NO
NO
NO
NC
FOR 240 VAC LOAD, CON NECT TO 240 TERMINAL .
1
Fig. 11. Wiring for Four-stage Control with 120 or 240
Vac (120 Vac Input and 120 Vac Load shown).
120V
COM
120
240
COM
SENSOR A
1
LOAD
3
LOAD
2
M24386A
M24387A
762-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
WARNING
M24391
DIGITAL
INPUT
+
–
M24304
TEMPERATURE (DEGREES)
RESISTANCE (OHMS)
1403
1317
1231
1145
1059
973
20 40 60 80 100 120 140 160 180 200 220
0 10 20 30 40 50 60 70 80 90 100
°F
°C
0-20-40
120
110
250
-40-20 -10-30
1489
887
801
1097 ± 0.08 OHMS
AT 77°F (25°C)
POSITIVE TEMPERATURE COEFFICIENT (PTC) OF 2.1 OHMS PER °F
1
1
See “1.1.1.2. CALIBRATE (the sensor)” on page 13 for
the instructions to enter the calibration value.
See Table 3 and Fig. 13 on page 8 for temperature
resistance information.
Table 3. Temperature Sensor Calibration for Resis-
tance Loss due to Wire Length.
AWG
Fig. 12. Wiring for Digital Input (dry contact).
RatingmΩ/ft
142.50.461.142.28
CHECKOUT
Inspect all wiring connections at the controller terminals,
and verify compliance with the installation wiring
diagrams.
164.00.721.823.64
186.41.162.905.82
2010.21.864.649.28
2216.12.927.3214.64
Temperature Offset in
°F (Foot)
a
200 ft500 ft1,000 ft
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring
or making wiring connections, to prevent electrical
shock or equipment damage.
If any wiring changes are required, first be sure to remove
power from the controller before starting work. Pay
particular attention to verifying the power connection (24,
120, or 240 Vac).
After the controller is mounted and wired, apply power.
Power Loss
The date and time settings are retained for 24 hours after
a power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.
Temperature Sensor Calibration
As wire length increases, resistance increases and thus
the temperature reading increases. If necessary, calibrate
the sensor input by reducing the value by the amount
shown in the Table 3. For example, a wire run with 18
gauge wire of 1,000 feet, requires a calibration offset of
-6.0°F.
IMPORTANT
If the calibration value in the table exceeds the
controller’s calibration limits of +/-10°F (+/-6°C),
you must use a heavier gauge wire.
For example, with a wire run of 1,000 feet you
must use 20 AWG wire or heavier in order to
calibrate for wire loss within the limits of the
controller.
62-0257—138
AWG
RatingmΩ/m
Temperature Offset in
°C (Meter)
100 m200 m300 m
a
148.30.440.861.30
1613.20.681.382.06
1821.01.102.183.28
2033.51.743.485.22
2252.82.745.488.22
a
This is the distance from the controller to the sensor
(already accounts for round trip distance).
Fig. 13 shows how sensor resistance varies with
temperature for a sensor having a positive temperature
coefficient (PTC) of 2.1 Ohms per degree F (3.85 Ohms
per degree C).
Fig. 13. Sensor Resistance vs. Temperature.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
DI ON
HOME
1
23456789101112
SENSORS
SENSOR A
78
SENSOR B
84
o
o
F
F
DI ON
HOME
o
F
o
F
L1 1-4ON
HEAT
SETPOINT
60
SENSOR A
78
RT 1436 HRS
123456789101112
DI ON
HOME
o
F
o
F
REL 9 OFF
HEAT
SETPOINT
60
SENSOR A
78
RT 684 HRS
123456789101112
M24398
INTERFACE OVERVIEW
The T775L controller uses an LCD panel and 6-button
keypad to provide status information and permit user input
of the programming, setup, and scheduling parameters.
The following figure describes the display areas of the
LCD and the keypad.
HOME
1 2 3 4 5 6 7 8 9 10 11 12
SENSORS
SENSOR A
78
SENSOR B
84
DI ON
home menu
Fig. 14. LCD Display - Home Screen And Keypad.
Menu Area – On the home screen, the LCD displays the
configured relays and whether they are active. In
Program, Setup, or Schedule mode, the LCD displays the
current menu selection and its order within the menu
hierarchy.
Data Area – On the home screen, the LCD displays the
sensors and outputs status. In Setup or Program mode,
the LCD displays menu choices, parameter selections,
and data values.
Lock Icon – The icon indicates the MENU button is
locked and prevents access to the Setup and Program
menus.
NOTE: Pressing and holding the HOME and MENU
buttons simultaneously for five seconds
locks/unlocks the MENU button.
6-Button Keypad – The keypad is used to access the
menus and enter values (see “Using the LCD Panel
Interface”).
Using the LCD Panel Interface
The 6-button keypad is used to move through the menus
and enter or change parameter values.
Home Button
Pressing the HOME button at any time exits the current
Programming or Setup display screen and returns to the
home screen as shown in Fig. 14 and Fig. 15.
Menu Button
• Pressing the MENU button always displays the
Program menu. If you are in Setup mode, you exit
setup and return to the Program menu.
o
F
o
F
MENU AREA
DATA AREA
LOCK ICON
6 BUTTON KEYPAD
M24397
• Pressing and holding the MENU button for five
seconds leaves the current screen and displays
the Setup menu.
Left and Right Arrow Buttons ( and )
Use these buttons to move backward () and forward ()
through the Program and Setup menus.
Up and Down Arrow Buttons ( and )
Use these buttons to move your selection up and down
through a menu or list.
• When the desired item is highlighted, you press the
arrow button to display that item’s content.
• When a value is displayed (e.g. 70°F), the up and
down arrows increase and decrease the value.
NOTE: Once you select an item from a list or enter a
value, pressing the or or HOME button
accepts your selection or value and stores it
in the controller’s memory.
Home Screen
In the normal run state, the LCD home screen displays
the current sensed temperatures, the active status of the
output loops and relays, and error and status codes.
When using Reset, the Heat/Cool setpoint(s) display on
the home screen for the Loop and Relay outputs; see Fig.
15.
Active relays are indicated by the small black square ()
just below the relay number. Fig. 15 shows the home
screen with relays 1, 2, and 4–6 energized.
Pressing the and buttons from the home screen
cycles through the sensors, loops, and additional relay(s).
Fig. 15. LCD Display - Home Screen Displaying
Sensors, Loops, and additional Relay(s).
NOTES:
1.The loop home screen and the relay home
screen do not dynamically update the active
relay status and sensor values. The information is a snapshot taken when you press the
or button to display the screen.
2.In Reset mode, the home screen displays the
effective setpoint.
IMPORTANT
After four minutes of inactivity (no buttons
pressed), the LCD display reverts to the home
screen display.
962-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
Accessing the Menus
Menus are used for setup, programming, scheduling, and
viewing the summary settings.
Program, Schedule, and Summary
Menus
To access these menus from the home screen, press the
MENU button. See Fig. 16.
HOME
123456789101112
SENSORS
SENSOR A
78
SENSOR B
84
DI ON
menu
home
MENU DISPLAY WHEN
SCHEDULING IS SET
PROGRAM
SCHEDULE
o
F
SUMMARY
EXIT
o
F
MENU
Fig. 16. Menus.
Depending on whether scheduling is enabled or not, the
LCD displays one of two menus as shown in Fig. 16.
Scheduling is enabled from the Setup menu’s Output
settings (see “1.3.3.1. USE SCHED” on page 15).
Setup Menu
To access the Setup menu, press and hold the MENU
button for five seconds. See Fig. 17.
HOME
1 2 3 4 5 6 7 8 9 10 11 12
SENSORS
SENSOR A
78
SENSOR B
84
DI ON
home
menu
o
F
o
F
FIVE
SECONDS
Fig. 17. Setup Menu.
Using the Menus
When you are working with the menus, use the:
• Left arrow button () to scroll backward through the
menus
• Right arrow button () to select the highlighted menu
item and display its content
OR
SENSORS
OUTPUTS
EXIT
MENU DISPLAY WHEN
SCHEDULING IS NOT SET
MENU
PROGRAM
EXIT
M24399
SETUP
M24400A
• Up and Down arrow buttons ( and ) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed parameter
NOTES:
1. If you press the HOME button or there is no keypad
activity for four minutes, you exit Program mode and
return to the home screen.
2. If you press the MENU button, you exit and return to
the menu.
PROGRAMMING OVERVIEW
The controller must be programmed before being placed
into service.
IMPORTANT
During programming, the controller is live at all
times. For example, the contacts may open and
close when adjusting the setpoint.
The programming process uses a hierarchical menu
structure that is easy to use. You press the
buttons to move forward and backward through the menus.
NOTES:
1. The T775L controller interface is intuitive. You may
want to use this procedure simply as a reference to
locate the particular option or parameter of interest.
2. The menus can display only those relays that are
defined in Setup (see “1.3.1. Number of RELAYS” on
page 14). For example, if you configure only one
relay, then only one relay displays on the appropriate
menus.
3. If you press the HOME button or there is no keypad
activity for four minutes, you exit Program mode and
return to the home screen.
4. If you press the MENU button, you exit Program
mode and return to the menu.
Control Loops
The T775L provides the capability to have up to two PID
control loops, which allow multiple stages to be assigned
to a single setpoint in each loop.
Setpoint and Differential
The following describes the relationship between setpoint
and differential for heating and cooling. These settings are
programmed for each output relay.
Heating Mode Setpoint and Differential
In heating mode, the differential is below the setpoint. The
relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the differential, the relay energizes.
Cooling Mode Setpoint and Differential
In cooling mode, the differential is above the setpoint. The
relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
differential, the relay energizes.
and arrow
62-0257—1310
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
M24297A
THROTTLING RANGE
STAGE 2 ON
STAGE 3 ON
STAGE 1 ON
-25%
STAGES
HYST.
75%
205°F185°F
0%
200°F
25%
195°F
STAGE 4 ON
50%
190°F
STAGE 1
STAGE 2
STAGE 3
STAGE 4
STAGE ENERGIZESSTAGE DE-ENERGIZES
Setpoint High Limit
You can set an irreversible setpoint high limit maximum
value for any single displayed setpoint value.
Adjust the setpoint (at any output) to the desired
maximum setpoint. Then, simultaneously press the
HOME,, and buttons and continue to press all three
buttons for five seconds to set the setpoint high limit
maximum to this value.
NOTE: You must press all three buttons at exactly
the same time for this action to occur.
IMPORTANT
1. This action sets the maximum setpoint value of
all outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is irre-versible. If you perform the action inadvertently
and this setpoint adversely affects the control of
your system, you must replace the controller.
Staged Operation
Staging occurs as illustrated in Fig. 18 for a Heat setpoint
of 200°F and a throttling range of 20°F when the Integral
value is zero (0). When the Integral is not zero, then the
actual temperatures at which stages energize and deenergize will vary from this example; see “1.3.4.2.
INTEGRAL” on page 18.
NOTE: A non-zero integral causes the control to
move toward the setpoint value.
Fig. 18. Staging Behavior
(when effective Setpoint = 200°F).
Programming the T775L Controller
In addition to the two staged loops, up to two additional
relays can be available for independent on-off control.
Examples of Loop and Relay configurations are:
• Number of relays = 8. Loop 1 uses relays 1-3, and
• Number of relays = 11. Loop 1 uses relays 1-5, and
• Number of relays = 12. Loop 1 uses relays 1-4, and
Loop 2 uses relays 4-6. The remaining two relays (7
and 8) are available for use.
Loop 2 uses relays 6-10. The remaining relay (11) is
available for use.
Loop 2 uses relays 5-8. Relays 9 and 10 are available
for use, but in this case, relays 11 and 12 are not
usable.
• Number of relays = 8. Loop 1 uses relays 1-6, and
Loop 2 uses relays 7-8. There are no additional relays
available for use.
IMPORTANT
If you change the number of relays, the controller
resets the number of relays per loop to zero (0)
for all loops. You must use Setup mode to reconfigure all loops and additional relays. See
page 11.
To program the controller, perform the setup configuration
(see “1. Setup”) and then select one of the following
procedures depending on whether the Reset function is to
be used:
• Program the Outputs for No Reset — see
“2. Programming Output (Loops and Additional Relays)
with No Reset” on page 22.
• Program the Outputs for Reset — see “” on page 25.
When programming is complete, you may continue with
“4. Scheduling” on page 31.
1. SETUP
Setup provides the ability to change the factory default
settings for the temperature sensors and outputs, to
enable/disable reset control, and to enable/disable
scheduling.
IMPORTANT
If you change the number of relays, the controller
resets the number of relays per loop to zero (0)
for all loops. You must use Setup mode to reconfigure all loops and additional relays.
NOTE: The T775L controller interface is intuitive.
You may want to use this procedure simply
as a reference to locate the particular option
or parameter of interest.
NOTES:
1.If you press the HOME button or there is no
keypad activity for four minutes, you exit
Setup mode and return to the home screen.
2.If you press the MENU button, you exit Setup
mode and go to the Program menu.
Once in Setup mode, you use the —
• Left arrow button() to scroll backward through the
Setup menus
• Right arrow button () to select the highlighted menu
item and display its content
• Up and Down arrow buttons ( and ) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed setup parameter
Setup Procedure
The Setup process uses a hierarchical menu structure
that is easy to use. You press the and arrow buttons
to move forward and backward through the menus.
NOTE: The menus can display only those relays that
are defined in Setup (see “1.3.1. Number of
RELAYS” on page 14). For example, if you
configure only two relays, then only two
relays display on the appropriate menus.
1162-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
SENSORS
SENSOR A
SETUP
SENSORS
SENSOR A
UNITS
CALIBRATE
LABEL
EXIT
M24430
To change the controller’s sensors and output setup
parameters, perform the following procedures in the order
listed:
1. Enter Setup mode — see “Entering Setup Mode”.
2. Setup Sensors — see “1. Setting up the Sensors”.
3. Setup Outputs — see “1.3. Setting up the Outputs”
on page 14.
4. Exit Setup Mode — see “1.4. Exiting Setup” on
page 22.
SETUP
SENSORS
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
M24428
Fig. 19. Setup - Sensors Menu.
SETUP
SENSORS
# SENSORS
SETUP
SENSORS
# SENSORS
2
ENTER
NUMBER OF
SENSORS
Fig. 20. Setup - Sensors - Number of Sensors.
M24429
Entering Setup Mode
To enter Setup mode, press and hold the MENU button for
five seconds to display the Setup menu. See Fig. 17 on
page 10.
1. Setting up the Sensors
1. From the Setup menu, use the and buttons to
highlight SENSORS.
2. Press the button to display the Sensors menu.
1.1. Number of SENSORS
The value entered here determines the number of
sensors displayed on the home screen.
1. From the Sensors menu, highlight # SENSORS
then press the button to display the number of
sensors.
2. Use the and buttons to enter the number of
sensors (1 or 2).
Default: 2
3. Press the button to accept the value and display
the SENSOR A selection.
Fig. 21. Setup - Sensors - Sensor A Menu.
62-0257—1312
1.1.1. SENSOR A
If you are implementing two-sensor reset control, Sensor
A must always be the controlled temperature and Sensor
B must always be the controlling temperature. For
example, in a reset control based on outside temperature,
Sensor A must be the inside sensor and Sensor B must
be the outside sensor.
1. From the Sensors menu, highlight SENSOR A.
2. Press the button to display the Sensor A selec-
tions.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
SENSORS
SENSOR A
UNITS
SENSORS
SENSOR A
DEG F
DEG C
UNITS FOR
SENSOR A
SETUP
UNITS
SELECT
Fig. 22. Setup - Sensors - Sensor A - Units.
SETUP
SENSORS
SENSOR A
CALIBRATE
SETUP
SENSORS
SENSOR A
CALIBRATE
0.0
ENTER
VAL UE TO
CALIBRATE
SENSOR A
o
F
Fig. 23. Setup - Sensors - Sensor A - Calibrate.
SETUP
SENSORS
SENSOR A
LABEL
SETUP
SENSORS
SENSOR A
LABEL
SENSOR A
BOILER A
OUTDOOR A
DUCT A
DISCHRG A
CHILLER A
ROOM A
SELECT
LABEL FOR
SENSOR A
Fig. 24. Setup - Sensors - Sensor A - Label.
1.1.1.1. UNITS (°F or °C)
IMPORTANT
This is a global change and affects the unit
values for all temperature parameters on all
displays.
This UNITS screen displays only for Sensor A.
1. From the Sensor A selections, use the and
buttons to highlight UNITS.
2. Press the button to display the temperature units.
M24431
3. Use the and buttons to highlight DEG F or
DEG C.
Default: F (Fahrenheit)
4. Press the button to accept the units and return to
the Sensor A selections.
1.1.1.2. CALIBRATE (the sensor)
Ensure that the wire size calibration value is within the
limits. See “Temperature Sensor Calibration” on page 8.
1. From the Sensor A selections, use the and
buttons to highlight CALIBRATE.
2. Press the button to display the calibration degree
value.
3. Use the and buttons to increase/decrease the
desired calibration degrees.
Default: 0
M24432
Range: +/-10°F (+/-6°C)
4. Press the button to accept the value and return to
the Sensor A selections.
1.1.1.3. LABEL (the sensor input)
For a sensor already labeled, the display positions to and
highlights that label.
1. From the Sensor A selections, use the and
buttons to highlight LABEL.
2. Press the button to display the label list.
3. Use the and buttons to scroll through list and
highlight the desired label.
You may need to scroll up or down to view all possible labels.
M24433
4. Use the button to accept the highlighted label
and exit the list.
NOTE: The label names in list order are: Sensor,
Boiler, Outdoor, Duct, Dischrg, Chiller, Room,
Supply, Return, and Animals.
SETUP
SENSORS
SENSOR A
UNITS
CALIBRATE
LABEL
EXIT
Fig. 25. Setup - Sensors - Sensor A - Exit.
1.1.1.4. Exit Sensor A Setup
Press the button to exit Sensor A selections and return
to the Sensors menu.
- or Use the and buttons to highlight EXIT and press the
button.
M24434
1362-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
For two-sensor reset control, Sensor B must always be
the controlling temperature. For example, in a reset
control based on outside temperature, Sensor B must be
the outside sensor.
1. From the Sensors menu, use the button to high-
light SENSOR B.
2. Press the button to display the Sensor B menu.
3. Repeat the selections described in “1.1.1. SENSOR
A” through “1.1.1.4. Exit Sensor A Setup” beginning
M24435
on page 12.
Continue with “1.3. Setting up the Outputs”.
1.3. Setting up the Outputs
1. From the Setup menu, use the and buttons to
highlight OUTPUTS.
2. Press the button to display the Outputs menu
3. Continue with “1.3.1. Number of RELAYS”.
M24436
1.3.1. Number of RELAYS
1. From the Outputs menu, use the and buttons
to highlight # RELAYS.
2. Press the button to display the number of relays.
3. Use the and buttons to select the number of
relays depending on setup. (See note below.)
4. Press the button to accept the value and display
the Outputs menu.
IMPORTANT
If you change the number of relays, the controller
M24437
resets the number of relays per loop to zero (0)
for all loops. You must use Setup mode to reconfigure all loops and additional relays.
NOTE: Up to two T775S Expansion Modules can be
connected to a T775L, making the following
outputs available:
T775L: 4 relay outputs
T775L with one T775S module: 8 relay outputs
T775L with two T775S modules: 12 relay outputs
62-0257—1314
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
OPTIONS
SETUP
OUTPUTS
OPTIONS
USE SCHED
MIN OFF
MIN ON
DI OPTS
SHOW RT
SYNC
EXIT
M24520A
SETUP
OUTPUTS
# LOOPS
SETUP
OUTPUTS
# LOOPS
2
ENTER
NUMBER OF
LOOPS
Fig. 29. Setup - Sensors - Number of Sensors.
Fig. 30. Setup - Outputs - Options Menu.
SETUP
OUTPUTS
OPTIONS
USE SCHED
Fig. 31. Setup - Outputs - Options - Schedule.
SETUP
OUTPUTS
OPTIONS
USE SCHED
YES
NO
SCHEDULE
OUTPUTS
USE
FOR
1.3.2. Number of LOOPS
The value entered here determines the number of loops
displayed on the home screen.
1. From the Outputs menu, highlight # LOOPS then
press the button to display the number of loops.
2. Use the and buttons to enter the number of
loops (1 or 2).
Default: 1
3. Press the button to accept the value and display
M24438
the Outputs menu.
1.3.3. OPTIONS
1. From the Outputs menu, use the and buttons
to highlight OPTIONS.
2. Press the button to display the Options menu.
1.3.3.1. USE SCHED
1. Press the button to display the schedule selec-
tions.
2. Use the and buttons to highlight YES or NO.
Default: NO
3. Press the button to accept the value and display
the MIN OFF option.
Selecting NO disables scheduling for all outputs.
Selecting YES enables scheduling for the setpoint.
However, each individual output can be removed from
M24440
scheduling as desired.
With Scheduling enabled, when you return to Program
mode, the new option for Scheduling displays. You can
press the HOME button and then the MENU button to
view the Schedule options in the menu.
1562-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
OPTIONS
ENTER
MINIMUM
OFF TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN OFF
0
SEC
M24522A
OR
MIN ON
ENTER
MINIMUM
ON TIME
FOR RELAYS
SETUP
OUTPUTS
OPTIONS
MIN ON
0
SEC
MIN OFF
1.3.3.2. MIN OFF or MIN ON
This is the minimum number of seconds of “off time” or
“on time” for all relays that are not configured in a loop.
1. Press the button to display the Min Off /On value.
2. Use the and buttons to increase/decrease the
desired number of seconds from 0 to 990 seconds
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the button to accept the seconds and
display the DI OPTS menu.
NOTES:
Fig. 32. Setup - Outputs - Min On/Off Options.
1. The minimum OFF or ON time applies to all
relays that are not configured in a loop.
2. When minimum OFF or ON time is active, relays
waiting to be energized display a flashing square
underneath the relay number on the home
screen.
3. If the minimum off time is not equal to zero (0),
the minimum off time activates at power-up.
4. To manually override, press the button.
SETUP
OUTPUTS
OPTIONS
DI OPTS
Fig. 33. Setup - Outputs - Options - DI Options.
SETUP
OUTPUTS
OPTIONS
DI OPTS
DISABLE
SETPOINT
SETBACK
ENABLE
DHW
IGNORE
SELECT DI
OPTION
FOR
RELAYS
1.3.3.3. DI OPTIONS (digital input options)
The DI Option that you select applies to all outputs. This
option overrides any Setpoint/Setback values entered in
the Schedule.
1. Press the button to display the DI Option
selections.
2. Use the and buttons to highlight DISABLE,
SETBACK, or IGNORE.
Default: DISABLE
3. Press the button to accept the value and display
M24442A
the SHOW RT menu.
When the digital input (DI) closes, all outputs follow the DI
option value (Disable, Setpoint, Setback, Enable, DHW, or
Ignore):
• DISABLE disables the outputs; relays return to deenergized state.
• SETPOINT forces the control to the setpoint
temperature.
• SETBACK enables a setback temperature value to be
programmed for each output and forces the control to
the setback temperature.
— To program the Setback temperature without
Reset, see Fig. 58 on page 24.
— To program the Setback temperature with Reset,
see Fig. 69 on page 28.
• ENABLE energizes all relays to 100%. Use this option
carefully.
• DHW: if a reset curve is being used, then the
controlled setpoint becomes the maximum setpoint
(either SP MAX A1 or BOILR MAX). If a reset curve is
not being used, then DI closure for DHW has no effect.
• IGNORE causes the digital input to have no effect on
the Relay outputs.
62-0257—1316
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
OPTIONS
SETUP
OUTPUTS
OPTIONS
USE SCHED
MIN OFF
MIN ON
DI OPTS
SHOW RT
SYNC
EXIT
M24520A
SETUP
OUTPUTS
OPTIONS
SHOW RT
YES
NO
SETUP
OUTPUTS
OPTIONS
SHOW RT
SHOW
RUN TIME
FOR
RELAYS
M24443
Fig. 34. Setup - Outputs - Options - Show Runtime.
SETUP
OUTPUTS
OPTIONS
SYNC
NO
YES
SETUP
OUTPUTS
OPTIONS
SYNC
ALL
SETPTS
CHANGE
M28657
Fig. 35. Setup - Outputs - Sync.
1.3.3.4. SHOW RT (show run time hours)
1. Press the button to display the Show RT values.
2. Use the and buttons to select YES or NO.
Default: YES
3. Press the button to accept the value and return to
the Options menu.
A limited feature in the T775L, selecting YES shows the
run time hours only of independent relays if they are
among the first four relays. Runtime of relays in a loop
cannot be shown.
NOTE: Run times can be reset to zero for each of the
first four independent relays. You must do
this for each relay that you want to reset to
zero. See “1.3.5.3. RESET RT (Run Time)” on
page 21.
1.3.3.5. SYNC (synchronize setpoint changes)
1. Press the button to display the Sync values.
2. Use the and buttons to select YES or NO.
Default: NO
3. Press the button to accept the value and return to
the Options menu.
Selecting YES causes all setpoints for all loops and
relays to sync to any change to loop
For example, assume the LOOP1 setpoint is 110°F,
LOOP2 is 115°F, and RELAY9 is 120°F. With SYNC=YES,
when the LOOP1 setpoint is adjusted to 112°F (increase
2°F), then LOOP2 and all other relay setpoints increase
by 2°F. Thus the LOOP2 setpoint is now 117°F and the
RELAY9 setpoint is 122°F.
Fig. 36. Setup - Outputs - Options - Exit.
SETUP
OUTPUTS
LOOP 1
SETUP
OUTPUTS
LOOP 1
# RELAYS
INTEGRAL
DERIVATIV
ON DELAY
OFF DELAY
SCHEDULE
RESET
EXIT
1.3.3.6. Exit Options Setup
Press the button (or highlight EXIT and press the
button) to exit and return to the Outputs menu.
Continue with “1.3.4. Setting up the Loops”
Fig. 37. Setup - Outputs - Loop 1 Menu.
1.3.4. Setting up the Loops
1. From the Outputs menu, use the and buttons
to highlight the desired loop (1 or 2 depending on
configuration).
2. Press the button to display the selected loop
menu.
Continue with the remainder of this section to
M24445
setup the loops.
1762-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
ENTER
NUMBER OF
RELAYS FOR
LOOP 1
SETUP
OUTPUTS
LOOP 1
# RELAYS
3
SETUP
OUTPUTS
LOOP 1
# RELAYS
M24446
1.3.4.1. Number of RELAYS
1. From the Loop 1 menu, use the and buttons to
highlight # RELAYS.
2. Press the button to display the number of relays.
3. Use the and buttons to select the number of
relays depending on setup. (SeeSee “1.3.1. Number of RELAYS” on page 14.)
4. Press the button to accept the value and display
the Loop 1 menu.
Fig. 38. Setup - Outputs - Loop 1 - Number of Relays.
SETUP
OUTPUTS
LOOP 1
INTEGRAL
Fig. 39. Setup - Outputs - Loop 1 - Integral.
NOTES:
1. The Integral time is factory set for 400 seconds. This
is a good middle range and should satisfy many
applications. The integral time can be increased for
applications where sensed response is slow, and can
be decreased for applications where sensed
response is fast (e.g. discharge air control).
2. As a starting point, an optimal integral time for
discharge air typically ranges from 12 to 200
seconds. An optimal integral time for room control
typically ranges from 60 to 2,500 seconds. The
purpose of integral action is to reduce or eliminate
the offset from setpoint during steady state control
that is often seen in proportional only control.
SETUP
OUTPUTS
LOOP 1
DERIVATIV
Fig. 40. Setup - Outputs - Loop 1 - Derivative.
DERIVATIVE
SETUP
OUTPUTS
LOOP 1
INTEGRAL
400
ENTER
INTEGRAL
TIME
FOR
LOOP 1
SETUP
OUTPUTS
LOOP 1
DERIVATIV
0
ENTER
TIME
FOR
LOOP 1
SEC
SEC
1.3.4.2. INTEGRAL
1. From the Loop 1 menu, use the and buttons to
highlight INTEGRAL.
2. Press the button to display the integral value.
3. Use the and buttons to change the integral
time from 0 to 3,600 seconds in increments of 10
seconds.
Default: 400 seconds
Range: 0 to 3,600 seconds
4. Press the button to accept the value and display
M24447
the Loop 1 menu.
3. Keep in mind that control is most sensitive to
throttling range. Adjust the throttling range first before
any adjustment to integral time. Adjust throttling
range to be as wide as possible to start since this will
provide the most stable control. Remember that the
integral will eliminate the steady state error so you do
not need to have a small throttling range to have
accurate control. (Integral action allows for controlling
to a setpoint even with a wide throttling range).
1.3.4.3. DERIVATIVE
The Derivative default value is factory set to zero (no
derivative control). It is strongly recommended that the
derivative remain at zero (0) unless you have a very good
reason to adjust it. Derivative control is not needed in the
vast majority of HVAC applications.
1. From the Loop 1 menu, use the and buttons to
highlight DERIVATIVE, then press the button to
display the derivative seconds.
2. Use the and buttons to increase/decrease the
value.
M24448
Default: 0 (zero)
Range: 0 to 3,600 seconds
3. Press the button to accept the value and display
the Loop 1 menu.
62-0257—1318
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
LOOP 1
ON DELAY
SETUP
OUTPUTS
LOOP 1
ON DELAY
0
ENTER
TIME FOR
INTERSTAGE
ON DELAY
SEC
Fig. 41. Setup - Outputs - Loop 1 - On Delay.
SETUP
OUTPUTS
LOOP 1
OFF DELAY
SETUP
OUTPUTS
LOOP 1
OFF DELAY
0
ENTER
TIME FOR
INTERSTAGE
OFF DELAY
SEC
Fig. 42. Setup - Outputs - Loop 1 - Off Delay.
SETUP
OUTPUTS
LOOP 1
SCHEDULE
OUTPUTS
SCHEDULE
YES
NO
SCHEDULE
SETUP
LOOP 1
USE
FOR
LOOP 1
Fig. 43. Setup - Outputs - Loop 1 - Schedule.
1.3.4.4. ON DELAY
This is the minimum time delay between consecutive ON
stages. This applies to all stages including the 1st stage.
1. From the Loop 1 menu, use the and buttons to
highlight ON DELAY, then press the button to display the interstage on delay.
2. Use the and buttons to change the on delay
time.
Default: 0 (zero) seconds
Range: 0 to 3,600 seconds in 10 second
M24449
increments
There is a built-in minimum delay of 1 second
between stages upon energizing.
3. Press the button to accept the value and display
the Loop 1 menu.
1.3.4.5. OFF DELAY
This is the minimum time delay between consecutive OFF
stages.
1. From the Loop 1 menu, use the and buttons to
highlight OFF DELAY, then press the button to
display the interstage off delay.
2. Use the and buttons to change the off delay
time.
Default: 0 (zero) seconds
Range: 0 to 3,600 seconds in 10 second
increments
M24450
There is a built-in minimum delay of 1 second
between stages upon energizing.
3. Press the button to accept the value and display
the Loop 1 menu.
1.3.4.6. SCHEDULE
The Schedule option displays only if the USE SCHED
parameter is set to Yes (see Fig. 31 on page 15).
1. From the Loop 1 menu, use the and buttons to
highlight SCHEDULE.
2. Press the button to display the value.
3. Use the and buttons to select YES or NO.
Default: YES
4. Press the button to accept the value and display
the Loop 1 menu.
An individual output can be selected to be controlled or
M24451
not controlled by the schedule. If NO is selected, the
Setback selection does not appear in the Program menu
for this output.
1962-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
LOOP 1
RESET
SETUP
OUTPUTS
LOOP 1
RESET
YES-BOILER
YES-OTHER
NO
USE
RESET
FOR
LOOP 1
Fig. 44. Setup - Outputs - Loop 1 - Reset.
SETUP
OUTPUTS
LOOP 1
SETUP
OUTPUTS
LOOP 1
# RELAYS
INTEGRAL
DERIVATIVE
ON DELAY
OFF DELAY
SCHEDULE
RESET
EXIT
1.3.4.7. RESET (Loop Reset)
This selection enables the controller’s Reset function, and
allows each output to be individually programmed for
Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the
first loop must be set for Reset.
The RESET choice is offered for all outputs in setup
mode, and you can set any or all of them for Reset=YES
or Reset=NO. The default is Reset=NO.
M24452
For the remaining outputs, if Reset=YES, then these
outputs use the reset curve programmed for the first
output.
1. From the Loop 1 menu, use the and buttons to
highlight RESET.
2. Press the button to display the value.
Default: NO
3. Use the and buttons to select the value.
4. Press the button to accept the value and display
the Loop 1 menu.
• If you select YES, then the second loop (and any
additional relays) display this Setup option.
• If you select NO, then No Reset is configured.
1.3.4.8. Exit Loop Setup
Use the and buttons to highlight EXIT and press the
button.
If you have additional relay outputs, continue with “1.3.5.
Setting up the Relays”. Otherwise, go to “1.4. Exiting
Setup” on page 22
Fig. 45. Setup - Outputs - Loop 1 - Exit.
SETUP
OUTPUTS
RELAY 9
Fig. 46. Setup - Outputs - Relay Menu.
62-0257—1320
SETUP
OUTPUTS
RELAY 9
SCHEDULE
RESET
RESET RT
EXIT
M24453
1.3.5. Setting up the Relays
1. From the Outputs menu, use the and buttons
to highlight the desired relay.
2. Press the button to display the selected relay
menu.
NOTE: There can be up to two additional relays.
For example: If there are 12 total relays, and
Loop 1 uses relays 1–4, and Loop 2 uses
relays 5–8, the two available additional relays
M24454
will be 9 and 10. (In this example, relays 11
and 12 are not usable since there can be only
two additional relays.)
Continue with the remainder of this section to setup the
relay outputs.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
RELAY 9
SCHEDULE
SETUP
OUTPUTS
RELAY 9
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24455
SETUP
OUTPUTS
RELAY 9
RESET
USE
RESET
FOR
RELAY 9
YES
NO
SETUP
OUTPUTS
RELAY 9
RESET
M24456
Fig. 47. Setup - Outputs - Relay - Schedule.
Fig. 48. Setup - Outputs - Relay - Reset.
1.3.5.1. SCHEDULE
This selection displays only if “Use Sched = YES” is
selected during the Output Options setup (see page 15).
When selected, individual outputs default to follow the
schedule.
1. Press the button to display the Schedule values.
2. Use the and buttons to select YES or NO.
Default: YES
3. Press the button to accept the value and return to
the Relay menu.
NOTE: If USE SCHED = YES, then the default is YES.
See “1.3.3.1. USE SCHED” on page 15.
An individual output can be selected to be controlled or
not controlled by the schedule.
If NO is selected, the Setback selection does not appear
in the Program menu for this output.
1.3.5.2. RESET (Relay Reset)
This selection enables or disables reset for the selected
relay.
IMPORTANT
To use the Reset function of the controller, the
first Loop must be set for Reset.
1. Press the button to display the Reset values.
2. Use the and buttons to select YES or NO.
Default: NO
3. Press the button to accept the value and return to
the Relay menu.
• If you select YES, then the second relay (if available)
displays this Setup option and uses the reset curve
programmed for the first output Loop.
• If you select NO, then No Reset is configured for the
remaining relay output.
SETUP
OUTPUTS
RELAY 9
RESET RT
Fig. 49. Setup - Outputs - Relay - Reset Runtime.
YES
NO
SETUP
OUTPUTS
RELAY 9
RESET RT
RESET
RUN TIME
FOR
RELAY 9
1.3.5.3. RESET RT (Run Time)
This selection displays only if “Show RT = YES” is
selected during Output Options setup (see page 17).
1. Press the button to display the Reset RT values.
2. Use the and buttons to select YES or NO.
Default: NO
3. Press the button to accept the value and return to
the Relay menu.
Selecting YES immediately resets the output run time
hours to zero for this output. When you subsequently
return to this screen, the RESET RT defaults to NO.
M24457
NOTE: Run times can be reset to zero for each of the
first four independent relays. You must do
this for each relay that you want to reset to
zero.
2162-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
RELAY 9
RESET
SCHEDULE
RESET RT
EXIT
M24458
SETUP
APP TYPE
SENSORS
OUTPUTS
EXIT
M24459
MENU
PROGRAM
MENU
PROGRAM
LOOP 1
LOOP 2
RELAY 9
RELAY 10
EXIT
M24401
1.3.5.4. Exit Relay Setup
Press the button to exit the selected relay set up and
return to the Outputs menu.
To setup the next additional relay output go to “1.3.5.
Setting up the Relays” on page 20.
If you are finished setting up the additional relay outputs,
continue with “1.4. Exiting Setup”.
Fig. 50. Setup - Outputs - Relay - Exit.
1.4. Exiting Setup
Press the HOME button to exit Setup mode and return to
the home screen display. Or, use the and buttons to
highlight EXIT from the menu and press the button.
This completes the Setup procedure. Continue with one of
the following sections depending on whether reset is
used:
• See “2. Programming Output (Loops and Additional
Relays) with No Reset” on page 22.
• See “3. Programming Output (Loops and Additional
Relays) with Reset” on page 25.
Fig. 51. Setup Exit.
2. PROGRAMMING OUTPUT
(LOOPS AND ADDITIONAL
RELAYS) WITH NO RESET
The T775L can be programmed for Reset or No Reset.
From the factory, the T775L is programmed for No Reset.
This section describes the steps necessary to program
the controller for No Reset. Continue with “2.1. Entering
Program Mode”.
62-0257—1322
Fig. 52. Program Menu.
If you are employing Reset, go to “3. Programming Output
(Loops and Additional Relays) with Reset” on page 25.
2.1. Entering Program Mode
Press the MENU button, then select PROGRAM and
press the button to view the Program menu.
PROGRAM
LOOP 1
LOOPS MENU
MENU
PROGRAM
LOOP 1
SETPOINT
THROT RNG
SENSOR
HEAT/COOL
SETBACK
EXIT
ADDITIONAL RELAYS
MENU
MENU
PROGRAM
RELAY 9
SETPOINT
DIFFRNTL
SENSOR
HEAT/COOL
SETBACK
EXIT
M24421
PROGRAM
RELAY 9
Fig. 53. Program Menus - No Reset.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
2.2. Program Menu for Outputs with No
Reset
From the Program menu, highlight the Loop or Relay
desired and press the button to view the parameters.
Fig. 53 shows both the Loop and Relay menus.
NOTE: The Setback parameter displays only if
scheduling is enabled (see Fig. 31 on
page 15) or the DI Option is set to Setback.
(see Fig. 33 on page 16).
Continue with “2.2.1. SETPOINT”.
PROGRAM
LOOP 1
SETPOINT
Fig. 54. Program - Setpoint.
PROGRAM
LOOP 1
THROT RNG
Fig. 55. Program - Throttling Range or Differential.
MENU
PROGRAM
LOOP 1
SETPOINT
o
70
ENTER
SETPOINT
FOR
LOOP 1
MENU
PROGRAM
LOOP 1
THROT RNG
o
20
ENTER
THROTTLING
RANGE FOR
LOOP 1
2.2.1. SETPOINT
1. From the menu, use the and buttons to high-
light SETPOINT.
2. Press the button to display the setpoint value.
3. Use the and buttons to increase/decrease the
desired setpoint temperature.
F
M24422
Default: 70°F (21°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the button to accept the setpoint tempera-
ture and display the next option.
2.2.2. THROTTLING RANGE or
DIFFERENTIAL
Throttling Range is used for Loops, and Differential
displays for the Relay outputs.
1. From the menu, use the and buttons to high-
F
M24423
light THROT RNG or DIFFRNTL.
2. Press the button to display the throttling range
value.
3. Use the and buttons to increase/decrease the
desired value.
Default: 20°F (-6.6°C)
Range: 1°F to 300°F (1°C to 149°C)
4. Press the button to accept the value and display
the next option.
The number of degrees selected for the throttling range is
divided between the number of stages. See page 11 for
staged operation.
In heating mode, the Differential is below the setpoint. The
relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint. The
relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
Differential, the relay energizes.
2362-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
PROGRAM
LOOP 1
SENSOR
SENSOR A
SENSOR B
Fig. 56. Program - Sensor.
PROGRAM
LOOP 1
HEAT/COOL
HEAT
COOL
Fig. 57. Program - Heat/Cool.
PROGRAM
LOOP 1
SETBACK
Fig. 58. Program - Setback.
MENU
PROGRAM
LOOP 1
SENSOR
SELECT
SENSOR
FOR
LOOP 1
MENU
PROGRAM
LOOP 1
HEAT/COOL
SELECT
HEAT/COOL
FOR
LOOP 1
MENU
PROGRAM
LOOP 1
SETBACK
60
ENTER
SETBACK
SETPOINT
FOR
LOOP 1
2.2.3. SENSOR
1. From the menu, use the and buttons to high-
light SENSOR.
2. Press the button to display the sensor selections.
3. Use the and buttons to select Sensor A or B.
4. Press the button to accept the highlighted sensor
and display the next option.
M24424
2.2.4. HEAT/COOL
1. From the menu, use the and buttons to high-
light HEAT/COOL.
Default: HEAT
2. Press the button to display the heat and cool
selections.
3. Use the and buttons to select Heat or Cool.
4. Press the button to accept the highlighted selec-
tion and display the next option.
M24425
2.2.5. SETBACK
The Setback temperature option displays only if
scheduling is enabled (see Fig. 31 on page 15) or the DI
Option is set to Setback. (see Fig. 33 on page 16).
This is the desired setpoint temperature that you want to
o
F
M24426
use during setback mode for this output. For example, if
your setpoint is 70°F and you want the temperature to
drop 10°F during setback mode, enter 60°F as the setpoint for this output.
1. From the menu, use the and buttons to high-
light SETBACK.
2. Use the and buttons to increase/decrease the
desired setpoint temperature.
Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)
3. Press the button to accept the value and display
the menu.
2.3. Program Next Output (Loop or Relay)
For the next output (loop or relay), select the desired loop
or relay from the Program menu (see Fig. 52 on page 22).
Go to “2.2.1. SETPOINT” on page 23 to continue
programming.
When you finish programming the outputs, continue with
“2.4. Exit Programming without Reset”.
2.4. Exit Programming without Reset
Press the HOME button to leave programming mode and
return to the home screen.
This completes the programming procedure for controllers that do not use Reset.
62-0257—1324
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
LOOP 1
RESET
SETUP
OUTPUTS
LOOP 1
RESET
USE
RESET
FOR
LOOP 1
YES-BOILER
YES-OTHER
NO
M24402
3. PROGRAMMING OUTPUT
(LOOPS AND ADDITIONAL
RELAYS) WITH RESET
The T775L can be programmed for Reset or No Reset for
each output. From the factory, the T775L is programmed
for No Reset. This section describes the steps necessar y
to program the controller for Reset.
Fig. 59. Reset Setup.
Determining and Setting the Reset
Val ues
NOTE: When using the Reset feature, Sensor A must
be sensing the controlled temperature (e.g.
Boiler), Sensor B must be sensing the resetting temperature (e.g. outdoor temp).
To program an output (loop or relay) for Reset, refer to the
values as shown in the examples below and in Fig. 60.
Choose your own appropriate values for Sensor A
maximum and minimum and Sensor B maximum and
minimum.
Reset Example: (see Fig. 60)
• Sensor A is the boiler sensor and Sensor B is the
outdoor sensor.
• Maximum boiler temperature desired is 210°F when
the outdoor temperature is 20°F.
• Minimum boiler temperature desired is 160°F when the
outdoor temperature is 70°F.
• With the above settings example, when the outdoor
temperature is 50°F, the effective setpoint is 180°F.
To use the Reset feature, Loop 1 must be set to
Reset=YES in Setup mode (see “3.1. Setting Up the
Controller for Reset”). The reset curve established when
programming Loop 1 is then used for the second Loop
and the additional relays.
The reset curve established when programming the first
Loop is then used for all subsequent Loops and any
additional relays that are configured for Reset, and each
of those outputs will be offset from this curve.
For all outputs that will follow a reset curve, be sure to
configure for Reset=YES in the setup mode. Choose
Reset YES or NO for all other outputs you wish to reset,
then press the HOME button to record your selection.
3.1. Setting Up the Controller for Reset
1. Press and hold MENU for five seconds to enter
Setup mode.
2. Then choose:
OUTPUTS
LOOP 1
RESET
then select YES-BOILER or YES-OTHER (Fig. 59).
You can now press the HOME button to exit Setup mode
and continue with “Determining and Setting the Reset
Val ues ”.
Setback (optional) Example:
• Setback of -10°F is used to drop the temperature at
night by 10°F.
• With the above settings example, when the outdoor
temperature is 50°F, the effective setback setpoint is
170°F (180°F setpoint minus the 10°F setback).
NOTE: A single reset curve is programmed for the
first output and is used by all outputs and
loops setup with RESET=YES.
NOTE: For subsequent outputs (Loop 2 and Relay),
a setpoint offset is used if that output is also
being Reset. See “3.4.1. SETPOINT OFFSET
(Loop 2 only)” on page 29.
When Reset is programmed, the home screen (Fig. 15 on
page 9) displays the calculated Heat/Cool setpoint(s) for
the Loop and Relay outputs based on the reset curve.
(see Fig. 60)
2562-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SENSOR B
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
200
140
10
SETBACK
OFFSET
-10°F
190
20
30 40 50 60
70
°F80
150
160
170
210
220
180
°F
RESET
B1
(OUTSD MIN)
RESET
B2
(OUTSD MAX)
S
E
N
S
O
R
A
M24404
MENU
PROGRAM
MENU
PROGRAM
LOOP 1
LOOP 2
RELAY 9
RELAY 10
EXIT
M24401
Fig. 60. Reset Curve for Loop 1 with Setback Offset.
Fig. 61. Program Menu.
The remainder of this section beginning with “3.2.
Entering Program Mode” describes the individual
parameters for configuring outputs with Reset.
For your reference, the following Reset programming
procedure uses the values in Fig. 60.
3.2. Entering Program Mode
Press the MENU button, then select PROGRAM and
press the button to view the Program menu.
OUTSD MIN
BOILR MIN
OUTSD MAX
THROT RNG
HEAT/COOL
SETBACK
EXIT
MENU
LOOP 1
M24405
3.3. Program Menus for Loops with
Reset
Press the MENU button, select PROGRAM, then select
Loop 1 and press the button to view the parameters.
Fig. 62 shows both of the Loop 1 menus. Your menu is the
one chosen in Fig. 59 on page 25
The Reset settings “3.3.1. SP MAX A1 or BOILER MAX
(Setpoint maximum for Sensor A)” through “3.3.4. RESET
B2 or OUTSD MAX (Sensor B value when at MIN A2
Setpoint)” are programmed for the first loop and these
settings apply to all outputs that are configured for Reset.
See Fig. 60 on page 26 for the reset curve values used in
the following section.
NOTE: The Setback parameter displays only if
scheduling is enabled (see Fig. 31 on
page 15) or the DI Option is set to Setback.
(see Fig. 33 on page 16).
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
ENTER
SENSOR B
VALUE FOR
MAXIMUM
SETPOINT
PROGRAM
LOOP 1
RESET B1
MENU
PROGRAM
LOOP 1
RESET B1
10
F
o
M24407
PROGRAM
LOOP 1
SP MAX A1
SETPOINT FOR
Fig. 63. Program - Sensor A Max. Setpoint.
Fig. 64. Program - Sensor B Max. Setpoint.
PROGRAM
LOOP 1
SP MIN A2
Fig. 65. Program - Sensor A Min. Setpoint.
MENU
PROGRAM
LOOP 1
SP MAX A1
180
ENTER
MAXIMUM
SENSOR A
MENU
PROGRAM
LOOP 1
SP MIN A2
140
ENTER
MINIMUM
SETPOINT
FOR
SENSOR A
3.3.1. SP MAX A1 or BOILER MAX
(Setpoint maximum for Sensor A)
1. From the menu, use the and buttons to high-
light SP MAX A1.
2. Press the button to display the maximum setpoint
o
F
M24406
value.
3. Use the and buttons to increase/decrease the
desired maximum setpoint temperature.
Default: 180°F (82°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the button to accept the setpoint tempera-
ture and display the next option.
3.3.2. RESET B1 or OUTSD MIN (Sensor B
value when at SP MAX A1 Setpoint)
1. From the menu, use the and buttons to high-
light RESET B1 or OUTSD MIN.
2. Press the button to display the setpoint value.
3. Use the and buttons to increase/decrease the
desired setpoint temperature.
Default: 10°F (-12°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the button to accept the value and display
the next option.
3.3.3. SP MIN A2 or BOILER MIN (Setpoint
minimum for Sensor A)
1. From the menu, use the and buttons to high-
light SP MIN A2.
2. Press the button to display the setpoint value.
o
F
M24408
3. Use the and buttons to increase/decrease the
desired minimum setpoint temperature.
Default: 140°F (60°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the button to accept the setpoint tempera-
ture and display the next option.
Fig. 66. Program - Sensor B Min. Setpoint.
PROGRAM
LOOP 1
RESET B2
MENU
PROGRAM
LOOP 1
RESET B2
o
F
60
ENTER
SENSOR B
VALUE FOR
MINIMUM
SETPOINT
3.3.4. RESET B2 or OUTSD MAX (Sensor B
value when at MIN A2 Setpoint)
1. From the menu, use the and buttons to high-
light RESET B2.
2. Press the button to display the setpoint value.
3. Use the and buttons to increase/decrease the
desired setpoint temperature.
Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)
4. Press the button to accept the value and display
M24409
the next option.
2762-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
PROGRAM
LOOP 1
THROT RNG
MENU
PROGRAM
LOOP 1
THROT RNG
20
ENTER
THROTTLING
RANGE
FOR
LOOP 1
Fig. 67. Program - Throttling Range.
PROGRAM
LOOP 1
HEAT/COOL
PROGRAM
LOOP 1
HEAT/COOL
HEAT
COOL
SELECT
HEAT/COOL
LOOP 1
MENU
FOR
o
F
3.3.5. THROTTLING RANGE
The number of degrees selected for the throttling range is
divided between the number of stages. See page 11 for
Staged Operation.
1. From the menu, use the and buttons to high-
light THROT RNG.
2. Press the button to display the throttling range
value.
3. Use the and buttons to increase/decrease the
desired value.
M24411
Default: 20°F (-6.6°C)
Range: 1°F to 300°F (1°C to 149°C)
4. Press the button to accept the value and display
the next option.
3.3.6. HEAT/COOL
1. From the menu, use the and buttons to high-
light HEAT/COOL.
Default: HEAT
2. Press the button to display the heat and cool
selections.
3. Use the and buttons to select Heat or Cool.
4. Press the button to accept the highlighted selec-
tion and display the next option.
M24412
Fig. 68. Program - Heat/Cool Selection.
PROGRAM
LOOP 1
SETBACK
Fig. 69. Program - Setback (Offset).
MENU
PROGRAM
LOOP 1
SETBACK
-10
ENTER
SETBACK
OFFSET
FOR
LOOP 1
3.3.7. SETBACK OFFSET (if configured)
The Setback temperature option displays only if
Scheduling is enabled (see Fig. 31 on page 15) or the DI
Option is set to Setback (see Fig. 33 on page 16).
This value is the number of degrees plus (+) or minus (-)
o
F
that you want the temperature to be offset from the
setpoint.
For example, If you want the temperature to be 10°F less
than the setpoint during setback mode, enter -10°F. In
normal operations for heating, the offset will be negative.
M24413
For cooling, the offset will be a positive value.
1. From the menu, use the and buttons to high-
light SETBACK.
2. Use the and buttons to increase/decrease the
desired setpoint temperature.
Default: 0°F
Range: -150°F to 150°F (-101°C to 66°C)
3. Press the button to accept the value and display
the menu.
This completes the programming of Loop 1. To program Loop 2, continue with “3.4. Loop 2”.
62-0257—1328
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SENSOR B
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
200
140
10
LOOP 2
SETPOINT
OFFSET
-10°F
190
20
30 40 50 60
70
°F80
150
160
170
210
220
180
°F
RESET B1
(OUTSD MIN)
RESET B2
(OUTSD MAX)
S
E
N
S
O
R
A
M24403
LOOP 1
SETPOINT
MENU
PROGRAM
LOOP 2
OFFSET
PROGRAM
LOOP 2
MENU
PROGRAM
LOOP 2
OFFSET
THROT RNG
HEAT/COOL
SETBACK
EXIT
-10
ENTER
SETPOINT
OFFSET
FOR
LOOP 2
Fig. 70. Program - Setpoint Offset (Loop 2 only).
Fig. 71. Reset Curve with Offset for Loop 2.
o
M24410
3.4. Loop 2
For the second loop (if it is configured for Reset), the
Offset parameter displays on the Program menu as
shown in Fig. 70.
F
3.4.1. SETPOINT OFFSET (Loop 2 only)
This value is the number of degrees plus (+) or minus (-)
that you want the temperature to be offset from the Loop 1
setpoint. See Fig. 71. For example, If you want the Loop 2
setpoint to be 10°F less than the Loop 1 setpoint, enter
-10°F.
1. From the menu, use the and buttons to
highlight OFFSET.
2. Press the button to display the value.
3. Use the and buttons to increase/decrease the
desired temperature.
OFFSET Default: 0°F
OFFSET Range: -150°F to 150°F (-101°C to
66°C)
4. Press the button to accept the value and display
the next option.
3.4.2. Loop 2 Programming
To complete the programming of Loop 2, perform the
procedures in “3.3.5. THROTTLING RANGE” through
“3.3.7. SETBACK OFFSET (if configured)” beginning on
page 28.
3.4.3. Exit Loop Programming with
Reset
When you finish programming the loop(s), press the
HOME button to leave programming mode and return to
the home screen.
If you have additional relays configured, continue with
“3.5. Program Menus for the Additional Relays with Reset”
on page 29.
If there are no additional relays, continue with “3.7. Exit
Programming with Reset” on page 31.
PROGRAM
RELAY 9
Fig. 72. Program Menus for Relays.
MENU
PROGRAM
RELAY 9
OFFSETDIFFRNTL
DIFFERENTIAL
SENSOR
HEAT/COOL
SETBACK
EXIT
3.5. Program Menus for the Additional
Relays with Reset
Press the MENU button, select PROGRAM, then select
an available relay to view the parameters. Fig. 72 shows
the example for relay 9. If Relays are not set for Reset in
Setup mode, simply enter the setpoint desired.
Up to two additional two relays can be available for
independent on-off control. Examples of Loop and Relay
configurations are:
M24414
2962-0257—13
• Number of relays = 8. Loop 1 uses relays 1-3,
and Loop 2 uses relays 3-6. The remaining two
relays (7 and 8) are available for use.
• Number of relays = 11. Loop 1 uses relays 1-5,
and Loop 2 uses relays 6-10. The remaining
relay (11) is available for use.
• Number of relays = 12. Loop 1 uses relays 1-4,
and Loop 2 uses relays 5-8. Relays 9 and 10
are available for use, but in this case, relays 11
and 12 are not usable.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
PROGRAM
RELAY 9
OFFSET
MENU
PROGRAM
RELAY 9
OFFSET
-10
ENTER
OFFSET
FOR
RELAY 9
Fig. 73. Program - Setpoint Offset.
PROGRAM
RELAY 9
DIFFRNTL
MENU
PROGRAM
RELAY 9
DIFFRNTL
20
ENTER
DIFFERENTIAL
FOR
RELAY 9
Fig. 74. Program - Differential.
3.5.1. SETPOINT OFFSET
This value is the number of degrees plus (+) or minus (-)
that you want the additional relay to be offset from the
setpoint curve created for Loop 1. For example, If you
want the temperature to be 10°F less than the Loop 1
o
F
setpoint, enter -10°F.
1. From the menu, use the and buttons to high-
light OFFSET.
2. Press the button to display the value.
3. Use the and buttons to increase/decrease the
M24415
desired setpoint temperature.
OFFSET Default: 0°F
OFFSET Range: -150°F to 150°F (-101°C to
66°C)
4. Press the button to accept the stepping and dis-
play the next option.
3.5.2. DIFFERENTIAL
Differential is used for the additional Relay outputs.
1. From the menu, use the and buttons to high-
light DIFFRNTL.
2. Press the button to display the differential value.
3. Use the and buttons to increase/decrease the
o
F
M24416
desired value.
Default: 20°F (-6.6°C)
Range: 1°F to 300°F (1°C to 149°C)
4. Press the button to accept the value and display
the next option.
In heating mode, the Differential is below the setpoint. The
relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint. The
relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
Differential, the relay energizes.
MENU
PROGRAM
RELAY 9
SENSOR
PROGRAM
RELAY 9
SENSOR
SENSOR A
SENSOR B
SELECT
SENSOR
FOR
RELAY 9
M24417
Fig. 75. Program - Sensor.
62-0257—1330
3.5.3. SENSOR
1. From the menu, use the and buttons to high-
light SENSOR.
2. Press the button to display the sensor selections.
3. Use the and buttons to select Sensor A or B.
4. Press the button to accept the highlighted sensor
and display the next option.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
PROGRAM
RELAY 9
HEAT/COOL
MENU
PROGRAM
RELAY 9
HEAT/COOL
HEAT
COOL
SELECT
HEAT/COOL
RELAY 9
FOR
Fig. 76. Program - Heat/Cool Selection.
PROGRAM
RELAY 9
SETBACK
MENU
PROGRAM
RELAY 9
SETBACK
-10
ENTER
SETBACK
OFFSET
FOR
RELAY 9
Fig. 77. Program - Setback (Offset).
3.5.4. HEAT/COOL
1. From the menu, use the and buttons to high-
light HEAT/COOL.
Default: HEAT
2. Press the button to display the heat and cool
selections.
3. Use the and buttons to select Heat or Cool.
4. Press the button to accept the highlighted selec-
tion and display the next option.
M24418
3.5.5. SETBACK OFFSET
The Setback temperature option displays only if
scheduling is enabled (see Fig. 31 on page 15) or the DI
Option is set to Setback. (see Fig. 33 on page 16).
This value is the number of degrees plus (+) or minus (-)
that you want the temperature to be offset from this relay’s
o
F
setpoint.
For example, If you want the temperature to be 10°F less
than the relay’s setpoint during setback mode, enter -10°F.
In normal operations for heating, the offset will be negative. For cooling, the offset will be a positive value.
M24419
1. From the menu, use the and buttons to high-
light SETBACK.
2. Use the and buttons to increase/decrease the
desired setpoint temperature.
Default: 0°F
Range: -150°F to 150°F (-101°C to 66°C)
3. Press the button to accept the value and display
the menu.
4. SCHEDULING
Scheduling provides the ability to set daily temperature
settings for up to two events per day. Typically, these are
the daytime (setpoint) and the nighttime (setback)
settings.
IMPORTANT
To enable Scheduling, you must first enter Setup
mode (press and hold the MENU button for 5
seconds), select OUTPUTS, select OPTIONS,
select USE SCHED, and then select YES. (see
“1.3.3.1. USE SCHED” on page 15).
3.6. Program Next Relay
If you have a second relay output, select that relay from
the Program menu, and go to “3.5. Program Menus for the
Additional Relays with Reset” on page 29.
When you finish programming the relay outputs, continue
with “3.7. Exit Programming with Reset”.
3.7. Exit Programming with Reset
Press the HOME button to leave programming mode and
return to the home screen. This completes the
programming procedure for the additional relays that use
Reset.
IMPORTANT
To properly account for Daylight Saving time, be
sure to set the Date before setting the Time.
See “4.2.2. SET DATE” on page 33.
NOTE: The T775L controller interface is intuitive.
You may want to use this procedure simply
as a reference to locate the particular option
or parameter of interest.
NOTE: Each loop and additional relay output can be
independently scheduled or not. For loops,
see “1.3.4.6. SCHEDULE” on page 19. For
relay outputs, see “1.3.5.1. SCHEDULE” on
page 21.
3162-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
NOTES:
1.If you press the HOME button or there is no
keypad activity for four minutes, you exit
Schedule mode and return to the home
screen.
2.If you press the MENU button, you exit
Schedule mode and return to the menu.
To create or change a schedule, you use the —
• Left arrow button () to scroll backward through the
Schedule menus
• Right arrow button () to select the highlighted menu
item and display its content
• Up and Down arrow buttons ( and ) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed schedule parameter
To create a schedule, perform the following in the order
listed:
1. Enable Scheduling in Setup mode —
see “1.3.3.1. USE SCHED” on page 15
2. Enter Schedule mode —
see “4.1. Entering Schedule Mode”
3. Set the Schedule Options —
see “4.2. OPTIONS”
4. Set Individual Schedules —
begin with “4.3. Setting Individual Schedules” on
page 33
5. Exit Schedule Mode —
see “4.4. Exiting Scheduling Mode” on page 35
4.1. Entering Schedule Mode
Press the MENU button, then select SCHEDULE and
press the button to view the Schedule menu.
4.2. OPTIONS
1. From the Schedule menu, use the and buttons
to highlight OPTIONS.
2. Press the button to display the Options menu.
Fig. 79. Schedule - Options Menu.
MAIN
SCHEDULE
OPTIONS
SET TIME
MAIN
SCHEDULE
OPTIONS
SET TIME
08:12 AM
SET
SYSTEM
TIME
Fig. 80. Schedule - Options - System Time.
62-0257—1332
M24461
4.2.1. SET TIME
Setting the system time is required to enable the
controller to follow daylight saving time.
IMPORTANT
Set the Date before setting the Time. See “4.2.2.
SET DATE”.
1. From the Options menu, use the and buttons
to highlight SET TIME.
2. Press the button to display the current system
M24462
time setting.
3. Use the button to cycle between the hour, minute,
and AM/PM values.
4. Use the and buttons to increase/decrease the
desired value for the hour, minute, and AM/PM.
5. Press the button to accept the Time and return to
the Options menu.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
MAIN
SCHEDULE
OPTIONS
SET DATE
MAIN
SCHEDULE
OPTIONS
SET DATE
01/01/2007
SET
SYSTEM
DATE
M24463
Fig. 81. Schedule - Options - System Date.
MAIN
SCHEDULE
OPTIONS
DAYLIGHT
SCHEDULE
DAYLIGHT
YES
NO
DAYLIGHT
MAIN
OPTIONS
USE
SAVING
TIME
M24464
Fig. 82. Schedule - Options - Daylight Saving Time .
MENU
SCHEDULE
MON-FRI
MENU
SCHEDULE
MON-FRI
E1 SETPT
E1 TIME
E2 SETPT
E2 TIME
EXIT
M24465
Fig. 83. Schedule Event Menu (Showing MON-FRI).
4.2.2. SET DATE
Setting the system date is required to enable the
controller to follow daylight saving time.
IMPORTANT
To properly account for Daylight Saving time, be
sure to set the Date before setting the Time.
1. From the Options menu, use the and buttons
to highlight SET DATE.
2. Press the button to display the current system
date setting.
3. Use the button to cycle between the month, day,
and year values.
4. Use the and buttons to increase/decrease the
desired value for the month, day, and year.
5. Press the button to accept the Date and return to
the Options menu.
4.2.3. DAYLIGHT (daylight saving time)
1. From the Options menu, use the and buttons
to highlight DAYLIGHT.
2. Press the button to display the current system
setting for daylight saving time.
3. Use the and buttons to select YES or NO.
Default: YES
4. Press the button to accept the value and return to
the Options menu.
5. From the Options menu, use the Use the and
buttons to highlight EXIT.
6. Press the button to return to the Schedule menu.
4.3. Setting Individual Schedules
As shown in the Schedule menu (Fig. 78 on page 32),
schedules can be set for the following time periods:
— Monday through Friday
— Saturday and Sunday
— Individual days of the week
1. From the Schedule menu, use the and buttons
to highlight the desired time period.
2. Press the button to display the Schedule menu
for the selected time period.
For each selected time period, the schedule event (E1
and E2) parameters are exactly the same as shown in
Fig. 83.
3362-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SCHEDULING EXAMPLE
Setting the schedule is independent of the temperature
settings for the relay outputs. Table 4 illustrates a weekly
schedule for daytime (setpoint) and night time (setback)
use and shows the factory default settings.
The remainder of this section shows the MON-FRI menu,
but the menu selections are the same for any time period.
Table 4. Mon-Fri Schedule Defaults
DAYEVENTSETPT ACTIONTIME
Mon-Fri Event 1 (E1)Setpoint
Mon-Fri Event 2 (E2)Setback
Sat-SunNot used; remains in Setback from the
a
Setpoint time span is 6:00 AM until 5:59 PM because
setback starts at 6:00 PM.
b
Setback time span is 6:00PM until 5:59 AM because
setpoint starts at 6:00 AM.
To set a schedule, continue with “4.3.1. E1 SETPT
(setpoint for event 1)”.
MAIN
SCHEDULE
MON-FRI
E1 SETPT
Mon-Fri E2 settings
MENU
SCHEDULE
MON-FRI
E1 SETPT
SETPOINT
SETBACK
NOT USED
SELECT
SETPOINT
EVENT 1
FOR
Fig. 84. Schedule - Event 1 Setpoint.
6:00 AM
6:00 PM
M24466
a
b
4.3.1. E1 SETPT (setpoint for event 1)
1. From the selected time period menu, use the and
buttons to highlight E1 SETPT.
2. Press the button to display the setpoint options.
3. Use the and buttons to highlight the desired
option.
4. Press the button to accept the value and return to
the selected time period menu.
Continue with “4.3.2. E1 TIME (time for event 1)” on
page 34.
MAIN
SCHEDULE
MON-FRI
E1 TIME
MAIN
SCHEDULE
MON-FRI
E1 TIME
6:00 AM
SET
TIME
FOR
EVENT 1
M24467
Fig. 85. Schedule - Event 1 Time.
62-0257—1334
4.3.2. E1 TIME (time for event 1)
1. From the selected time period menu, use the and
buttons to highlight E1 TIME.
2. Press the button to display the current time set-
ting for event 1.
3. Use the button to cycle between the hour, minute,
and AM/PM values.
4. Use the and buttons to increase/decrease the
desired value for the hour, minute, and AM/PM.
5. Press the button to accept the time and return to
the selected time period menu.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
4.3.3. E2 SETPOINT (setpoint for event 2)
Creating the setpoint for event 2 is accomplished the
same way as the first event. See “4.3.1. E1 SETPT
(setpoint for event 1)” on page 34.
4.3.4. E2 TIME (time for event 2)
Creating the time for event 2 is accomplished the same
way as the first event. See “4.3.2. E1 TIME (time for event
1)”.
4.3.5. EXIT (exit from selected time period
settings)
After entering the time for event 2, use the but ton to exit
the schedule time period and return to the Schedule
menu (Fig. 78 on page 32) to select a different time
period.
When you finish scheduling the time periods, continue
with “4.4. Exiting Scheduling Mode”.
4.4. Exiting Scheduling Mode
Press the HOME button to exit the Schedule menu and
return to the home screen display.
This completes the Scheduling procedure.
3562-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
MENU
SUMMARY
MENU
SUMMARY
MONDAY
RELAY 1-2
E1: 06:00AM (72)
E2: 06:00PM (65)
M24468
SUMMARY MENU
The Summary menu provides the ability to view the
schedule (E1 and E2 times) for each relay for each day of
the week.
NOTE: Scheduling must be enabled for the Sum-
mary menu to display. Enabling scheduling is
determined in the Setup process for the Output Options (see “1.3.3. OPTIONS” on
page 15).
Fig. 86. Summary Example - Monday Settings.
For each relay, the Summary display indicates the time
and temperature (in parenthesis) for each of the two
scheduled events E1 and E2.
1. Press the MENU button to view the menu.
2. Use the and buttons to highlight SUMMARY.
3. Press the button to display the Summary
settings.
4. Use the button to scroll forward through each day
of the week (Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday, and Sunday).
5. While viewing a specific day, use the and
buttons to cycle through the individual relay
schedules for that day.
When finished, press the HOME button to return to the
home display screen.
If programmed for Reset control, the Summary setpoints
display as “RES” instead of a temperature value. For
example, the display would show:
The date and time settings are retained for 24 hours after
a power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.
Errors and Diagnostics
The controller provides an error message and diagnostic
status as described below.
Error Message
There is a two-character error code that displays in
response to controller software problems:
EE
EEPROM Failure— The values read back from
the EEPROM are not the same as written into the
EEPROM. This error cannot be field repaired. Replace
the device.
Diagnostic Messages
There are two diagnostic messages that can display in
response to sensor problems. The diagnostic codes that
can flash on the display are:
– –
Sensor Open or Shorted— Two dashes display
when a sensor (typically temperature) is open or
shorted. An open circuit is considered anything
greater than 1570 ohms (greater than 300F), shorted
anything less than 770 ohms (less than -73F). Whichever stages are operating with this sensor cease to
control (meaning relays go to OFF and propor tional
outputs go to zero percent).
This message can also mean that the sensor is programmed, but not physically connected (open).
-60°F or 270°F (-51°C or 132°C) Blinking
Temperature Out of Range— The temperature
display blinks when the sensed temperature range is
outside of the display range, below -60°F (-51°C) or
above 270°F (132°C). The displayed value remains at
that displayed limit and control continues. Controller
continues to function unless an open or shorted state
is detected.
Blinking relay status
Relay Minimum Off Time is Active — On the home
screen, each relay’s indicator () blinks while the
relay’s minimum off time is active.
62-0257—1336
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SPECIFICATIONS
Power: 24, 120, or 240 Vac; 50/60 Hz;
A separate earth ground is required for any power
source.
Power Consumption:
• 8 VA maximum at 60 Hz
• 10 VA maximum at 50 Hz
Operating & Storage Temperature Ambient Rating:
• -40° F to 125° F (-40° C to 52° C) @ 50 Hz
• -40° F to 140° F (-40° C to 60° C) @ 60 Hz
Relative Humidity: 5% to 95% non-condensing
Relay Contact Output Ratings (N.O. and N.C.):
• 1/2 hp; 9.8 AFL, 58.8 ALR @ 120 Vac
• 1/2 hp; 4.9 AFL, 29.4 ALR @ 240 Vac
• 125 VA pilot duty @ 120/240 Vac
• 10A @ 24 Vac (resistive)
DoC
Emissions Compliance
EN 55022: 2006
CISPR 22: 2006
VCCI V-3/2006.04
ICES-003, Issue 4: 2004
FCC PART 15 SUBPART B Class B Limit
Immunity Compliance
EN 61000-6-1: 2001 covering
EN 61000-4-2: 1995 + A1: 1998 + A2: 2001
EN 61000-4-3: 2002
EN 61000-4-4: 2004
EN 61000-4-5: 1995 + A1: 2001
EN 61000-4-6: 1996 + A1: 2001
EN 61000-4-8: 1993 + A1: 2001
EN 61000-4-11 2nd Ed.: 2004
Safety Compliance
UL 60730-1 for US and Canada
FCC Compliance Statement:
This equipment has been tested and found to comply with
limits for a Class B digital device, pursuant to Part 15 of
the FCC rules. These limits are designed to provide
reasonable protection against harmful interference in
residential installations. This equipment generates, uses,
and can radiate radio frequency energy, and if not
installed and used in accordance with the instructions,
may cause harmful interference to radio communications.
However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does
cause interference to radio or television equipment
reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following
measures:
— Reorient or relocate the receiving antenna
— Move the equipment away from the receiver
— Plug the equipment into an outlet on a circuit different
from that to which the receiver is connected
— Consult the dealer or an experienced radio/television
technician for additional suggestions
You are cautioned that any change or modifications to the
equipment not expressly approve by the party responsible
for compliance could void Your authority to operate such
equipment.
This device complies with Part 15 of the FCC Rules.
Operation is subjected to the following two conditions 1)
this device may not cause harmful interference and 2) this
device must accept any interference received, including
interference that may cause undesired operation.
3762-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
62-0257—1338
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
3962-0257—13
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
By using this Honeywell literature, you agree that Honeywell will have no liability for any
damages arising out of your use or modification to, the literature. You will defend and indemnify
Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages,
including attorneys’ fees, arising out of, or resulting from, any modification to the literature by
you.