T775A/B/M Series 2000 Electronic
Stand-Alone Controllers
INSTALLATION INSTRUCTIONS
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next
generation of commercial and agricultural controls
capable of remote sensing of temperature and providing
switched and/or proportional outputs to various types of
loads.
Five models have analog (modulating) outputs for
actuator and motor control, and NEMA-4 weatherproof
enclosures are available for wet environments.
IMPORTANT
Each T775A/B/M controller is an operating
control, not a limit or safety control. If used in
applications requiring safety or limit controls, a
separate safety or limit control device is
required.
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
BEFORE INSTALLATION
Review the “Specifications” on page 35 before installing
the controller.
When Installing This Product
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
INSTALLATION AND SETUP
The following installation procedures are typically
performed in the order listed:
1. Mounting — See “Mounting” below.
2. Wiring — See “Wiring” on this page.
3. Checkout — See page 10.
4. Programming — See page 13.
5. Scheduling (optional) — See page 30.
Additional topics are:
• Temperature sensor calibration begins on page 10.
• Interface overview begins on page 11.
• Setup (for advanced options) begins on page 17.
• Summary menu begins on page 34.
• Troubleshooting begins on page 34.
MOUNTING
This section describes the mounting procedures for the
controller and temperature sensor(s).
Controller Mounting
IMPORTANT
Avoid mounting in areas where acid fumes or
other deteriorating vapors can attack the metal
parts of the controller circuit board, or in areas
where escaping gas or other explosive vapors
are present.
IMPORTANT
The controller must be mounted in a position that
allows clearance for wiring, servicing, and
removal.
Use a screwdriver to pry out only the knockouts that you
will use.
If mounting on DIN rail, be sure to remove the knockouts
before mounting. See “Controller Wiring” on page 5 and
Fig. 7 on page 6 for recommended knockout usage and
locations. If you do not use an opened knockout be sure
to cover it.
Mount the controller on any convenient interior location
using the four mounting holes provided on the back of the
enclosure using #6 or #8 screws (screws are not provided
and must be obtained separately). Use controller
dimensions in Fig. 1 on page 2 as a guide.
The controller may be mounted in any orientation.
However, mounting in the orientation shown in Fig. 1
permits proper viewing of the LCD display and use of the
keypad.
NEMA 4 Enclosure Mounting
For models with NEMA 4 enclosures, ensure that
waterproof wire/conduit fittings are used at the knockouts
for all wiring attachments. Refer to Fig. 7 on page 6 for
knockout locations.
IMPORTANT
For NEMA 4 enclosures, be sure to cover and
seal all unused open knockouts.
Temperature Sensor(s) Mounting and
Location
Temperature sensors may be located up to 1,000 feet
(304 m) from the T775A/B/M controller. Refer to Table 3
on page 10 for calibration guidelines.
The sensors may be mounted on a wall or panel for
sensing space temperature, strapped to a pipe or inserted
in an immersion well (see Fig. 2) for hot or cold water
sensing, or taped to a standard cap or bulb holder for duct
air sensing. To prevent moisture or condensation entering
the sensor through the lead wire holes, mount the sensor
with the lead wires exiting the bottom of the sensor.
NOTES:
1.The included sensor is not designed for very
wet applications. For immersion applications,
an immersion well is used.
2.Heat conductive compound must be used in
immersion wells.
3.Refer to “Temperature Sensors” on page 2 for
this type of installation.
1/2 NPT
USE HEAT
CONDUCTIVE
COMPOUND
IMMERSION
WELL
M24470
SENSOR
PLACED
IN WELL
Fig. 2. Sensor Inserted in Immersion Well.
NOTE: Multiple sensors may be parallel-series wired to
sense average temperatures in large spaces.
Refer to Fig. 3 on page 4.
WIRING
All wiring must comply with applicable electrical codes
and ordinances, or as specified on installation wiring
diagrams. Controller wiring is terminated to the screw
terminal blocks located inside the device.
The remainder of this section describes the temperature
sensor wiring and the T775A/B/M controller wiring.
362-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Wiring Connections Access
To access the wiring connections, remove the two screws
on the left side of the enclosure and gently swing open the
top. Be careful to not stress the ribbon cables that
connect the keypad and LCD display to the controller
circuit board.
Temperature Sensor Wiring
CAUTION
Electrical Shock Hazard.
Can short equipment circuitry.
Make sure that metal tube of sensor does not
short against T terminals in wall-mounted case.
IMPORTANT
Poor wiring practices can cause erratic readings
from the sensor. Avoid the following to ensure
proper operation:
• Do not route the temperature sensor wiring with
building power wiring.
• Do not locate the temperature sensor wiring next
to control contactors.
• Do not locate the temperature sensor wiring near
electrical motors.
• Do not locate the temperature sensor wiring near
welding equipment.
• Make sure good mechanical connections are
made to both the sensor and the controller.
• Do not mount the sensor with the lead wire end
pointing up in an area where condensation can
occur.
If any of the above conditions cannot be
avoided, use shielded cable.
NOTE: Each T775 controller must be wired to its own
sensor(s). However, a benefit of the T775
controller’s accuracy is that there is no more
than a 2° F (-7° C) differential between any two
T775 controllers.
Multiple Parallel Sensors
Multiple sensors can be parallel-series wired to sense
average temperatures in large spaces. To maintain
control accuracy, the number of sensors to be parallelseries wired must be of the n
16, etc.) (See Fig. 3).
SENSORS
TO T775 CONNECTIONS (SENSOR A) OR (SENSOR B).
2
power (for example, 4, 9,
M24471
Fig. 3. Parallel-Series Wiring of Sensors.
Temperature Sensor Wire Type and Size
Temperature sensors use standard AWG 18/2 unshielded
wire. For cable runs greater than 25 feet or where
electrical interference may be a problem, shielded cable
is recommended (See Fig. 4).
Refer to “Temperature Sensor Calibration” on page 10 for
wire size selection where cable runs are longer than 25
feet.
T
T
T
T
SENSOR A AND SENSOR B TERMINAL WIRING IS POLARITY INSENSITIVE.
1
SENSOR A
1
SENSOR B
SHIELDED
CABLE
Fig. 4. Sensor Wiring — Showing Shielded Cable Connection to Sensor A.
62-0254—054
SHIELDED
CABLE
NOTE: SHIELDED CABLE MUST BE
CONNECTED TO AN EARTH
GROUND.
HOWEVER, DO NOT GROUND
SHIELDED CABLE AT SENSOR END.
NOTE: TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION FROM
SHIELDED CABLE AS CLOSE AS
POSSIBLE TO SENSOR BODY.
SENSOR
M24472
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Controller Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring,
or making wiring connections, to prevent electrical
shock or equipment damage.
CAUTION
Do not use 24 Vac power to power any external
loads if 120 Vac or 240 Vac is used to power
the T775A/B/M controller.
CAUTION
A separate earth ground is required.
Equipment damage can result if the earth ground
is not connected. See Fig. 5 and Table 2 on page
6.
CAUTION
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Ensure that you are properly grounded before
handling the unit.
1
See Fig. 7 on page 6 for locating the appropriate power
input, remote sensors input, low voltage, contact closure,
and load output terminals.
Access to the terminals can be gained through standard
conduit knockouts (A through E in Fig. 7 on page 6)
located around the perimeter of the enclosure:
• Knockouts A and B should be used only for sensor and
low-voltage wiring.
• Knockouts C, D, and E can be used to gain access to
the load relay output terminals and 120/240 Vac power
wiring.
Controller Wiring Method
Wire the sensors and outputs, then wire the power
connection.
Each terminal can accommodate the following gauges of
wire:
• Single wire – from 14 AWG to 22 AWG solid or
stranded
• Multiple wires – up to two 22 AWG stranded
For 24, 120, or 240 Vac power connections:
• Single wire – from 14 to 18 AWG solid or stranded
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire
in the required terminal location and tighten the
screw.
3. If two or more wires are being inserted into one
terminal location, twist the wires together a
minimum of three turns before inserting them to
ensure proper electrical contact.
4. Cut the twisted end of the wires to 3/16 in. (5 mm)
before inserting them into the terminal and
tightening the screw.
5. Pull on each wire in all terminals to check for good
mechanical connection.
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
1/2 (13)
C
W
NO HIGH VOLTAGE. CLASS 2 WIRING ONLY.
1
EARTH GROUND TERMINAL MUST BE CONNECTED
2
TO CONDUIT CLAMP LOCALLY.
+
2
Fig. 5. Earth Ground.
IMPORTANT
Poor wiring practices can cause erratic readings
from the sensor. To ensure proper operation,
ensure that good mechanical connections are
made to both the sensor and the controller.
IMPORTANT
When wiring the input power, only one source of
power can be applied to the T775A/B/M
controller (24 Vac or 120 Vac or 240 Vac).
M24296
2. TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING SCREW.
THEN PULL ON EACH WIRE IN ALL
TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M24473
Fig. 6. Attaching Two or More Wires at Terminal
562-0254—05
Blocks.
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Controller Wiring Details
The wiring connection terminals are shown in Fig. 7 and
are described in Table 2.
See Fig. 8 – Fig. 20 beginning on page 6 for typical
T775A/B/M wiring applications.
KNOCKOUT A
–
+
–
+
+
NC
C
NO
NO
C
NC
KNOCKOUT E
T
T
T
T
NC
C
NO
NO
C
NC
MOD 1
MOD 2
DIGITAL
INPUT
KNOCKOUT B
POWER
3
24 VAC
OUTPUT
RELAY 4
OUTPUT
RELAY 1
KNOCKOUT C
1
SENSORS A AND B USE THE TWO TT CONNECTIONS AND ARE
POLARITY INSENSITIVE.
2
FOR MOD 1 AND MOD 2 CURRENT (mA) OR VOLTAGE (VDC) OUTPUT,
USE SIGNAL (+) & COMMON (-).
FOR MOD 1 AND MOD 2 SERIES 90 OUTPUT, USE W, R, & B.
A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER
3
SOURCE (24, 120, OR 240 VAC).
B
R
W
2
B
R
W
–
+
C
120
COM
240
SENSOR A
1
SENSOR B
OUTPUT
RELAY 3
POWER
120/240 VAC
OUTPUT
RELAY 2
KNOCKOUT D
M24474
Table 2. Description of Wiring
Terminal Connections. (Continued)
ConnectionTerminal LabelDescription
Input
DI + -Digital Input (dry
contact)
24 Vac Power
24V + +24 Vac Hot
Common C24 Vac Common
Ground
Earth Ground
b
120 or 240 Vac Power
120 Vac120120 Vac Power
CommonCOMCommon
240 Vac240240 Vac Power
a
For Series 90 connections, you must insert a 340 Ohm
resistor across terminals R and W. Refer to Fig. 17 on
page 8. The resistor is included with the controller.
b
A separate earth ground is required for all installations
regardless of the power source (24, 120, or 240 Vac).
Refer to Fig. 5 on page 5.
WIRING APPLICATIONS
(EXAMPLES)
Fig. 8 – 20 illustrate typical controller wiring for various
applications.
SENSOR A
T
T
Fig. 7. T775A/B/M Terminal and Feature Locations.
NOTE: Refer to Table 1 on page 1 for the specific
configuration of sensors and outputs supported
by the model you are installing.
NOTE: For NEMA 4 enclosures, use waterproof fittings
for wiring/conduit connections at knockouts.
Table 2. Description of Wiring
Terminal Connections.
ConnectionTerminal LabelDescription
Sensors
Sensor AT TTemperature Sensor;
Sensor B
polarity insensitive
Outputs
Relay 1
Relay 2
Relay 3
Relay 4
Mod 1+ - (Vdc or mA)
Mod 2
62-0254—056
NO
COM
NC
W R B (Series 90)
120-240 Vac Relay
Output
a
Modulating Output
L1
(HOT)
L2
Fig. 8. Wiring for Two-Stage Control – 24 Vac Input
24 VAC
LOAD 1
LOAD 2
C
+
NO
COM
NO
C
NC
and 24 Vac Load.
NO
NC
COM
C
NO
M24475A
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
A
SENSOR A
T
T
L1
(HOT)
L2
Fig. 9. Wiring for Four-Stage Control – 24 Vac Input
24 VAC
LOAD
COM
4
NO
LOAD
NO
1
COM
COM
LOAD
NO
2
COM
LOAD
NO
3
and 24 Vac Load.
C
+
NC
C
NO
NO
NC
NC
C
NO
C
NO
C
NC
SENSOR A
T
T
T
T
C
+
C
LOAD 4
NC
NO
C
NO
C
NC
LOAD 1
120
COM
NC
COM
C
NO
NO
NO
NO
COM
NC
M24476
FOR 240 VAC LOAD, CON NECT TO 240 TERMINAL .
1
Fig. 11. Wiring for Four-Stage Control with 120 or 240
Vac (120 Vac Input and 120 Vac Load Shown).
120V
COM
1
240
SENSOR A
LOAD
3
LOAD
2
M24478A
120/240 VAC LINE
C
NO
COM
+
NO
C
NC
NO
C
NC
120V
COM
1
POWER SUPPLY
120
240
COM
NO
LOAD 2
COM
L1 ( HOT )
L2
LOAD 1
FOR 240 VAC LOAD, CON NECT TO 240 TERMINAL .
1
Fig. 10. Wiring for Two-Stage Control with 120 or 240
Vac (120 Vac Input and 120 Vac Load Shown).
M24477A
1
NO
C
NC
BARCODE
CLOSE RELAY TO DRIVE DEVICE OPEN. RELAY 1 SHOWN.
1
(RELAYS 1 AND 3 ARE USED FOR OPEN).
CLOSE RELAY TO DRIVE DEVICE CLOSED. RELAY 2 SHOWN.
2
(RELAYS 2 AND 4 ARE USED FOR CLOSE).
THE RELAYS MUST BE WIRED IN PAIRS WITH RELAYS 1 AND 2
BEING THE FIRST PAIR, AND RELAYS 3 AND 4 BEING THE SECOND PAIR.
Fig. 12. Wiring for Floating Output (Relay 1 and Relay
NO
C
NC
2 Pair Shown).
COM
2
NO
COM
NO
DEVICE
OPEN
COM
CLOSE
M24479
762-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
ML7984 ACTUATOR
T1 T2 B WR
C
POWER
OUTPUT
1
MODULATING OUTPUT
TERMINAL (MOD 1)
Fig. 13. Wiring for ML7984 Valve Actuator
(Using 4 to 20 mA Signal).
DIGITAL
INPUT
+
B
–
R
+
W
B
–
R
+
W
–
M24482
Fig. 14. Wiring for Digital Input (Dry Contact).
HONEYWELL MODUTROL MOTOR WITH
4-20 mA MODULATING INPUT
T1 T2
–
+
POWER
OUTPUT
1
MODULATING OUTPUT
TERMINAL (MOD 1)
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
1
Fig. 15. Wiring for Mod Motor or Direct Coupled
Actuator with 4 to 20 mA Control Input.
HONEYWELL MODUTROL MOTOR WITH
VOLTAGE CONTROL INPUT
T1 T2 C R
F
B
–
R
+
W
B
–
R
+
W
HONEYWELL ELECTRONIC
SERIES 90 MODUTROL MOTOR
1
B
R
–
W
B
R
W
3
+
–
+
M27228
T1 T2 BWR
POWER
OUTPUT
2
MODULATING
OUTPUT
TERMINAL
(MOD 1)
1
TO VERIFY OUTPUT, TEST OPEN CIRCUIT VOLTAGE BETWEEN
THE MOD 1 TERMINALS W AND R.
- MINIMUM (DRIVE CLOSED) SIGNAL LESS THAN 0.17 VDC
- MAXIMUM (DRIVE OPEN) SIGNAL IS GREATER THAN 1.7 VDC
2
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
3
Fig. 17. Wiring for Series 90 Modutrol Motor Control.
MINIMUM POSITION
POTENTIOMETER
(Q209)
W R B
B
–
R
+
W
B
3
–
R
+
W
M24481
HONEYWELL
ELECTRONIC SERIES 90
MODUTROL MOTOR
T1 T2 B WR
1
POWER
OUTPUT
MODULATING OUTPUT
TERMINAL (MOD 1)
1
USE SEPAR ATE TR ANSFORMER FOR T 775R WHEN USING 24 VAC.
A 250 OHM RES ISTOR PROVIDES 40% AUTH ORITY WHEN
2
USING A 150 OH M MINIMUM POSIT ION POTENTIOME TER.
3
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
Fig. 18. Wiring for Changeover Relay and
Minimum Position Potentiometer Used
with Series 90 Modutrol Motors.
SPDT CHAN GEOVER
(H205 OR H70 5)
2
M24484
M24485
1
POWER
OUTPUT
MODULATING OUTPUT
TERMINAL (MOD 1)
1
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
Fig. 16. Wiring for Mod Motor or Direct Coupled
Actuator with 0 to 10 Vdc Control Input.
B
–
R
+
W
B
–
R
+
W
M24483
62-0254—058
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
M9184 OR M9185
MODUTROL MOTOR
R
TR
W
TR
B
–
R
3
+
W
B
–
R
+
W
MODULATING OUTPUT
TERMINAL (MOD 1)
1
POWER SUPP LY. PROVIDE DISC ONNECT MEANS AN D OVERLOAD PROTECTION A S REQUIRED.
USE A 1300 OH M RESISTOR FOR TWO MOTO RS, 910 OHM RESISTOR FOR TH REE MOTORS.
2
THE 407EAU R ESISTOR KIT, WHICH IS SH IPPED WITH THE M9184 A ND M9185 MOTORS,
INCLUDES BOTH RESISTORS.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
3
2
B
M9184 OR M9185
MODUTROL MOTOR
R
TR
W
TR
B
M9184 OR M9185
MODUTROL MOTOR
R
TR
W
TR
B
Fig. 19. Wiring for Three Series 90 Modutrol Motors.
(HOT)
1
L1
L2
M24486
L1 (HOT)L2
MINIMUM
6
3
B
9
–
R
+
W
B
–
R
+
W
–
+
8
POWER
24 VAC
C
+
MODULATING OUTPUT TERMINAL (MOD 1)
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
UP TO SIX SIMILAR MOTORS CAN BE CONNECTED IN UNISON.
USE RESISTOR BETWEEN R AND B ON THE MOD 1 TERMINAL: 1300 OHMS FOR TWO MOTORS; 910 OHMS FOR THREE MOTORS (4074EAU KIT).
3
IF COMMON TRANSFORMER IS USED, ALL MOTORS MUST BE IN PHASE. CONNECT THE SAME TRANSFORMER LEAD TO T1 ON EACH MOTOR,
4
CONNECT THE OTHER TRANSFORMER LEAD TO T2 ON EACH MOTOR.
USE TEMPERATURE CONTROLLER SUCH AS H205 OR H705, OR T675A FOR CHANGEOVER CONTROL.
5
AUTHORITY OF MINIMUM POSITION POTENTIOMETER, IF USED, INCREASES WITH THE NUMBER OF MOTORS IN PARALLEL. WITH ONE MOTOR,
6
50% STROKE; WITH TWO MOTORS, 100% STROKE; WITH THREE MOTORS, 100% STROKE WITH 1/3 OF FULL POTENTIOMETER ROTATION.
7
REVERSING THE B AND W TERMINALS ON ONE OR MORE MOTORS WILL NOT AFFECT CONTROL PERFORMANCE ON THE OTHER MOTORS.
THE SYSTEM CAN BE CONFIGURED TO HAVE SOME MOTORS BE REVERSE ACTING AND OTHER MOTORS BE DIRECT ACTING.
USE SEPARATE TRANSFORMER FOR T775 WHEN POWERING FROM 24 VAC.
8
THE SYSTEM IS SHOWN CONNECTED FOR COOLING. FOR HEATING, REVERSE THE W AND B LEADS OF THE MODULATING OUTPUT ON THE
9
T775 CONTROLLER.
Fig. 20. Wiring for Unison Control of M9184 or M9185 Modutrol IV Motor Using One Minimum Position
Potentiometer for All Motors.
POSITION
POTENTIOMETER
(Q209/S963)
W
R
B
CHANGEOVER
5
CONTROLLER
1
W
2
R
3
B
M9184 OR M9185
MODUTROL MOTOR
R
W
B
M9184 OR M9185
MODUTROL MOTOR
R
W
B
M9184 OR M9185
MODUTROL MOTOR
R
W
7
B
TR
TR
TR
TR
TR
TR
4
2
2
2
1
M24487
962-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
CHECKOUT
Inspect all wiring connections at the controller terminals,
and verify compliance with the installation wiring
diagrams.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring
or making wiring connections, to prevent electrical
shock or equipment damage.
If any wiring changes are required, first be sure to remove
power from the controller before starting work. Pay
particular attention to verifying the power connection (24,
120, or 240 Vac).
After the controller is installed and wired, apply power.
Power Loss
The date and time settings are retained for 24 hours after
a power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.
Temperature Sensor Calibration
As wire length increases, resistance increases and thus
the temperature reading increases. If necessary, calibrate
the sensor input by reducing the value by the amount
shown in the Table 3. For example, a wire run with 18
gauge wire of 1,000 feet, requires a calibration offset of
-6.0° F (-21° C).
IMPORTANT
If the calibration value in the table exceeds the
controller’s calibration limits of +/-10° F (+/-6° C),
you must use a heavier gauge wire.
For example, with a wire run of 1,000 feet you
must use 20 AWG wire or heavier in order to
calibrate for wire loss within the limits of the
controller.
See “2.2.2.2. CALIBRATE (the sensor)” on page 18 for
the instructions to enter the calibration value.
Table 3. Temperature Sensor Calibration for
Resistance Loss Due to Wire Length.
AWG
RatingmΩ/ft
Temperature Offset in
200 ft500 ft1,000 ft
°F (Foot)
a
142.50.461.142.28
164.00.721.823.64
186.41.162.905.82
2010.21.864.649.28
2216.12.927.3214.64
AWG
RatingmΩ/m
Temperature Offset in
°C (Meter)
100 m200 m300 m
a
148.30.440.861.30
1613.20.681.382.06
1821.01.102.183.28
2033.51.743.485.22
2252.82.745.488.22
a
This is the distance from the controller to the sensor
(already accounts for round trip distance).
Fig. 21 shows how sensor resistance varies with
temperature for a sensor having a positive temperature
coefficient (PTC) of 2.1 Ohms per degree F (3.85 Ohms
per degree C).
RESISTANCE (OHMS)
1489
1403
1317
1231
1145
1059
973
887
801
-40-20 -10-30
POSITIVE TEMPERATURE COEFFICIENT (PTC) OF 2.1 OHMS PER °F
1
20 40 60 80 100 120 140 160 180 200 220
0-20-40
1097 ± 0.08 OHMS
AT 77°F (25°C)
1
0 10 20 30 40 50 60 70 80 90 100
TEMPERATURE (DEGREES)
250
110
120
M24304
Fig. 21. Sensor Resistance vs. Temperature.
°F
°C
62-0254—0510
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
INTERFACE OVERVIEW
The T775A/B/M controllers use an LCD panel and
6-button keypad to provide status information and permit
user input of the programming, setup, and scheduling
parameters.
The following figure describes the display areas of the
LCD and the keypad.
HOME
RELAYS 1 2 3 4
ON
SENSORS
SENSOR A
78
SENSOR B
84
MOD1 40%
MOD2 60%
DI ON
home menu
Fig. 22. LCD Display - Home Screen And Keypad.
Menu Area – On the home screen, the LCD displays the
configured relays and whether they are active. In
Program, Setup or Schedule mode, the LCD displays the
current menu selection and its order within the menu
hierarchy.
Data Area – On the home screen, the LCD displays the
sensors and outputs status. In Setup or Program mode,
the LCD displays menu choices, parameter selections,
and data values.
Lock Icon – The icon indicates the MENU button is
locked and prevents access to the Setup and Program
menus.
NOTE: Pressing and holding the HOME and MENU
buttons simultaneously for five seconds locks/
unlocks the MENU button.
6-Button Keypad – The keypad is used to access the
menus and enter values (See “Using the LCD Panel
Interface”).
Using the LCD Panel Interface
The 6-button keypad is used to move through the menus
and enter or change parameter values.
Home Button
Pressing the HOME button at any time exits the current
Programming or Setup display screen and returns to the
home screen as shown in Fig. 22 and Fig. 23.
o
F
o
F
MENU AREA
DATA AREA
LOCK ICON
6 BUTTON KEYPAD
M24488
Menu Button
• Pressing the MENU button always displays the
Program menu. If you are in Setup mode, you exit
setup and return to the Program menu.
• Pressing and holding the MENU button for five
seconds leaves the current screen and displays
the Setup menu.
Left and Right Arrow Buttons (W and X)
Use these buttons to move backward (W) and forward (X)
through the Program and Setup menus.
Up and Down Arrow Buttons (S and T)
Use these buttons to move your selection up and down
through a menu or list.
• When the desired item is highlighted, you press the X
arrow button to display that item’s content.
• When a value is displayed (e.g. 70° F), the up and
down arrows increase and decrease the value.
NOTE: Once you select an item from a list or enter a
value, pressing the W or X or HOME button
accepts your selection or value and stores it in
the controller’s memory.
Home Screen
In the normal run state, the LCD home screen displays
the current sensed temperatures, the modulating outputs
status, the active status of the output relays, and error and
status codes.
Active relays are indicated by the small black square ()
just below the relay number. Fig. 23 shows the home
screen with relays 1, 2, and 4 energized.
Pressing the W and X buttons from the home screen
cycles through each modulating output that is paired with
the sensor it controls and the active output relays.
HOME
RELAYS 1 2 3 4
ON
SENSORS
SENSOR A
78
SENSOR B
84
MOD1 40%
MOD2 60%
DI ON
Fig. 23. LCD Display - Home Screen Displaying
Sensors, Active Relays, and Mod Outputs.
NOTE: The modulating output home screen and the
relay home screen do not dynamically update
the active relay status, sensor values, and
modulating output percentages. The information
is a snapshot taken when you press the W or X
button to display the screen.
IMPORTANT
After four minutes of inactivity (no buttons
pressed), the LCD display reverts to the home
screen display.
o
F
o
F
HOME
RELAYS 1 2 3 4
ON
MOD 1 40%
COOL
SETPOINT
74
SENSOR A
62
MOD1 40%
MOD2 60%
DI ON
o
F
o
F
HOME
RELAYS 1 2 3 4
ON
REL 1 ON
HEAT
SETPOINT
60
SENSOR A
62
RT 12345 HRS
MOD1 40%
MOD2 60%
DI ON
M24489
o
F
o
F
1162-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Accessing the Menus
Menus are used for programming, scheduling, viewing the
summary settings, and setup of advanced options.
Programming, Scheduling, and Summary Menus
To access these menus from the home screen, press the
MENU button (See Fig. 24).
MENU DISPLAY WHEN
o
F
o
F
SCHEDULING IS SET
MENU
PROGRAM
SCHEDULE
SUMMARY
EXIT
HOME
RELAYS 1 2 3 4
ON
SENSORS
SENSOR A
78
SENSOR B
84
MOD1 40%
MOD2 60%
DI ON
menu
home
Fig. 24. Menus.
Depending on whether scheduling is enabled or not, the
LCD displays one of two menus as shown in Fig. 24.
Scheduling is enabled from the Setup menu’s Output
settings (See “2.3.3.1. USE SCHED” on page 24).
Setup Menu
To access the Setup menu, press and hold the MENU
button for five seconds (Refer to Fig. 25).
SCHEDULING IS NOT SET
OR
MENU DISPLAY WHEN
MENU
PROGRAM
EXIT
M24490
HOME
RELAYS 1 2 3 4
ON
SENSORS
SENSOR A
78
SENSOR B
84
MOD1 40%
MOD2 60%
DI ON
menu
home
o
F
o
F
SECONDS
FIVE
SETUP
SENSORS
OUTPUTS
EXIT
M24491
Fig. 25. Setup Menu.
Using the Menus
When you are working with the menus, use the:
• Left arrow button (W) to scroll backward through the
menus
• Right arrow button (X) to select the highlighted menu
item and display its content
• Up and Down arrow buttons (S and T) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed parameter
NOTE: If you press the HOME button or there is no
keypad activity for four minutes, you exit
Program mode and return to the home screen.
If you press the MENU button, you exit and
return to the menu.
62-0254—0512
1. PROGRAMMING
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
The controller must be programmed before being placed
into service.
IMPORTANT
During programming, the controller is live at all
times. For example, the contacts may open and
close when adjusting the setpoint.
The Programming process uses a hierarchical menu
structure that is easy to use. You press the W and X
arrow buttons to move forward and backward through the
menus.
NOTES:
1.The controller interface is intuitive. You may
find that you do not need the following
procedure instructions to program the
controller. You may want to use this
procedure simply as a reference to locate the
particular option or parameter of interest.
2.The menus can display only those relays that
are defined in Setup (See “2.3.2. NBR OF
RELAYS” on page 24). For example, if you
configure only two relays, then only two
relays display on the appropriate menus.
3.If you press the HOME button or there is no
keypad activity for four minutes, you exit
Program mode and return to the home
screen.
4.If you press the MENU button, you exit
Program mode and return to the menu.
Setpoint and Differential
The following describes the relationship between setpoint
and differential for heating and cooling. These settings are
programmed for each output relay.
Heating Mode Setpoint and Differential
In heating mode, the differential is below the setpoint. The
relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the differential, the relay energizes.
Cooling Mode Setpoint and Differential
In cooling mode, the differential is above the setpoint. The
relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
differential, the relay energizes.
Setpoint High Limit
You can set a single irreversible setpoint high limit
maximum value, which is applied to all outputs.
Adjust the setpoint (at any output) to the desired
maximum setpoint. Then, simultaneously press the
home,W, and X buttons and continue to press all three
buttons for five seconds to set the setpoint high limit
maximum to this value.
NOTE: You must press all three buttons at exactly the
same time for this action to occur.
IMPORTANT
1. This action sets the maximum setpoint value of
all outputs to the setpoint high limit maximum.
2. Setting the high limit setpoint maximum is irreversible. If you perform the action
inadvertently gently and this setpoint adversely
affects the control of your system, you must
replace the controller.
1362-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Programming the T775A/B/M Controller
To program the controller, perform the following
procedures in the order listed:
1. Enter Program mode — see “1.1. Entering Program
Mode”
2. Program the Outputs — see “1.2. Program Menu for
Outputs” on page 14
MENU
PROGRAM
MENU
PROGRAM
MOD 1
MOD 2
RELAY 1
RELAY 2
RELAY 3
RELAY 4
EXIT
Fig. 26. Program Menu.
PROGRAM
RELAY 1
Fig. 27. Program Menu Outputs.
OR
RELAY 1
RELAY 2
RELAY 3
RELAY 4
EXIT
MENU
PROGRAM
RELAY 1
SETPOINT
DIFFRNTL
SENSOR
HEAT/COOL
SETBACK
EXIT
MENU
PROGRAM
When programming is complete, you may continue with
“3. Scheduling” on page 30 or, for advanced options,
continue with “2. Setup (Advanced Options)” on page 17.
1.1. Entering Program Mode
Press the MENU button, then select PROGRAM and
press the X button to view the Program menu.
Fig. 26 shows the Program menus for controllers with and
without Modulating Outputs.
NOTE: Modulating outputs are not available on the
T775A and T775B controller models.
M24492
1.2. Program Menu for Outputs
Press the MENU button, select PROGRAM, then select
RELAY 1 (or MOD 1) to view the parameters. Fig. 27
shows RELAY 1.
NOTE: For MOD 1 and 2, THROT RNG replaces
DIFFRNTL.
NOTE: The Setback parameter displays only if
scheduling is enabled (See Fig. 55 on page 24)
or the DI Option is set to Setback. (See Fig. 57
M24493
on page 25).
Continue with “1.2.1. SETPOINT”.
PROGRAM
RELAY 1
SETPOINT
MENU
PROGRAM
RELAY 1
SETPOINT
70
ENTER
SETPOINT
FOR
RELAY 1
o
F
1.2.1. SETPOINT
M24494
Fig. 28. Program - Setpoint.
62-0254—0514
1. From the menu, use the S and T buttons to
highlight SETPOINT.
2. Press the X button to display the setpoint value.
3. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 70° F (21° C)
Range: -40° to 248° F (-40° to 120° C)
4. Press the X button to accept the setpoint
temperature and display the next option.
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
PROGRAM
RELAY 1
DIFFRNTL
MENU
PROGRAM
RELAY 1
DIFFRNTL
20
ENTER
DIFFERENTIAL
FOR
RELAY 1
o
F
M24495
Fig. 29. Program - Differential or Throttling Range.
MENU
PROGRAM
RELAY 1
SENSOR
PROGRAM
RELAY 1
SENSOR
SENSOR A
SENSOR B
SELECT
SENSOR FOR
RELAY 1
M24496
Fig. 30. Program - Sensor.
1.2.2. DIFFERENTIAL or THROTTLING RANGE
Differential is used for Relay outputs and Throttling Range
is used for Modulating outputs.
1. From the menu, use the S and T buttons to
highlight THROT RNG or DIFFERNTL.
2. Press the X button to display the throttling range
value.
3. Use the S and T buttons to increase/decrease the
desired value.
Default: 20° F (-7° C)
Range: 1° to 150° F (1° to 66° C).
4. Press the X button to accept the value and display
the next option.
In heating mode, the Differential is below the setpoint.
The relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint.
The relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
Differential, the relay energizes.
The Throttling Range brackets the setpoint setting, e.g., if
the setpoint is 72°F (22° C) and the throttling range is
10° F (-12° C), then the effective throttling temperature
range is 67° to 77° F (19° to 25° C). This applies to both
modulating outputs and floating outputs.
1.2.3. SENSOR
1. From the menu, use the S and T buttons to
highlight SENSOR.
2. Press the X button to display the sensor selections.
3. Use the S and T buttons to select Sensor A or B.
4. Press the X button to accept the highlighted sensor
and display the next option.
PROGRAM
RELAY 1
HEAT/COOL
HEAT
COOL
Fig. 31. Program - Heat/Cool.
MENU
PROGRAM
RELAY 1
HEAT/COOL
SELECT
HEAT/COOL
FOR
RELAY 1
1.2.4. HEAT/COOL
1. From the menu, use the S and T buttons to
highlight HEAT/COOL.
Default: HEAT
2. Press the X button to display the heat and cool
selections.
3. Use the S and T buttons to select Heat or Cool.
4. Press the X button to accept the highlighted
selection and display the next option.
M24497
1562-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
PROGRAM
RELAY 1
SETBACK
Fig. 32. Program - Setback.
MENU
PROGRAM
RELAY 1
SETBACK
ENTER
SETBACK
SETPOINT
FOR RELAY 1
MENU
PROGRAM
MOD 1
MOD 2
RELAY 1
RELAY 2
RELAY 3
RELAY 4
EXIT
60
1.2.5. SETBACK
The Setback temperature option displays if scheduling is
enabled (See Fig. 55 on page 24) or the DI Option is set
to Setback. (See Fig. 57 on page 25).
This is the desired setpoint temperature that you want to
o
F
use during setback mode for this output. For example, if
your setpoint is 70° F (21° C) and you want the
temperature to drop 10° F during setback mode, enter
60° F (16° C) as the setpoint for this output.
M24498
1. From the menu, use the S and T buttons to
highlight SETBACK.
2. Use the S and T buttons to increase/decrease the
desired setpoint temperature.
Default: 60° F (16° C)
Range: -40° to 248° F (-40° to 120° C)
3. Press the X button to accept the value and display
the menu.
1.2.6. Program Next Output (Mod or Relay)
For the next output (Mod or Relay), select the desired
output from the Program menu (Refer to Fig. 26 on page
14).
Go to “1.2.1. SETPOINT” on page 14 to program the next
output.
When you finish programming the outputs, continue with
“1.2.7. Exiting Program Mode” on page 16.
1.2.7. Exiting Program Mode
Press the HOME button to leave programming mode and
return to the home screen.
This completes the programming procedure.
M24499
Fig. 33. Program - Exit.
62-0254—0516
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
2. SETUP (ADVANCED OPTIONS)
Setup provides the ability to change the factory default
settings for the temperature sensors and outputs, to
enable/disable reset control, and to enable/disable
scheduling.
NOTE: The controller interface is intuitive. You may find
that you do not need the following setup
instructions for the sensors and outputs. You
may want to use this procedure simply as a
reference to locate the particular option or
parameter of interest.
NOTES:
1.If you press the HOME button or there is no
keypad activity for four minutes, you exit
Setup mode and return to the home screen.
2.If you press the MENU button, you exit Setup
mode and return to the menu.
Setup Procedure
The Setup process uses a hierarchical menu structure
that is easy to use. You press the W and X arrow buttons
to move forward and backward through the menus.
NOTE: The menus can display only those relays that
are defined in Setup (see “2.3.2. NBR OF
RELAYS” on page 24). For example, if you
configure only two relays, then only two relays
display on the appropriate menus.
SETUP
SENSORS
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
Once in Setup mode, you use the —
• Left arrow button(W) to scroll backward through the
Setup menus
• Right arrow button (X) to select the highlighted menu
item and display its content
• Up and Down arrow buttons (S and T) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed setup parameter
To change the controller’s sensors and output setup
parameters, perform the following procedures in the order
listed:
1. Enter Setup mode — see “2.1. Entering Setup
Mode”
2. Setup Sensors — see “2.2. Setting up the Sensors”
3. Setup Outputs — see “2.3. Setting up the Outputs”
on page 21
4. Exit Setup Mode — see “2.4. EXIT Setup Mode” on
page 29
2.1. Entering Setup Mode
To enter Setup mode, press and hold the MENU button
for five seconds to display the Setup menu. Refer to Fig.
25 on page 12.
2.2. Setting up the Sensors
1. From the Setup menu, use the S and T buttons to
highlight SENSORS.
2. Press the X button to display the Sensors menu.
Fig. 34. Setup - Sensors Menu.
SETUP
SENSORS
# SENSORS
SETUP
SENSORS
# SENSORS
2
ENTER
NUMBER OF
SENSORS
Fig. 35. Setup - Sensors - Number of Sensors.
M24500
2.2.1. Number of SENSORS
The value entered here determines the number of
sensors displayed on the home screen.
1. From the Sensors menu, highlight # SENSORS
then press the X button to display the number of
sensors.
2. Use the S and T buttons to enter the number of
sensors (1 or 2).
M24501
Default: 2
3. Press the X button to accept the value and display
the SENSOR A selection.
1762-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
SENSORS
SENSOR A
SETUP
SENSORS
SENSOR A
UNITS
CALIBRATE
LABEL
EXIT
Fig. 36. Setup - Sensors - Sensor A Menu.
SETUP
SENSORS
SENSOR A
UNITS
SENSORS
SENSOR A
DEG F
DEG C
SELECT
UNITS FOR
SENSOR A
SETUP
UNITS
Fig. 37. Setup - Sensors - Sensor A - Units.
SETUP
SENSORS
SENSOR A
CALIBRATE
SETUP
SENSORS
SENSOR A
CALIBRATE
0.0
ENTER
VALUE TO
CALIBRATE
SENSOR A
o
F
Fig. 38. Setup - Sensors - Sensor A - Calibrate.
2.2.2. SENSOR A
1. From the Sensors menu, highlight SENSOR A.
2. Press the X button to display the Sensor A
selections.
M24502
2.2.2.1. UNITS (° F or ° C)
IMPORTANT
This is a global change and affects the unit
values for all temperature parameters on all
displays.
The UNITS screen displays only for Sensor A.
1. From the Sensor A selections, use the S and T
M24503
buttons to highlight UNITS.
2. Press the X button to display the temperature units.
3. Use the S and T buttons to highlight F or C.
Default: F (Fahrenheit)
4. Press the X button to accept the units and return to
the Sensor A selections.
2.2.2.2. CALIBRATE (the sensor)
Ensure that the wire size calibration value is within the
limits. See “Temperature Sensor Calibration” on page 10.
1. From the Sensor A selections, use the S and T
buttons to highlight CALIBRATE.
2. Press the X button to display the calibration degree
value.
3. Use the S and T buttons to increase/decrease the
desired calibration degrees.
M24504
Default: 0.0
Range: +/-10° F (+/-6° C)
4. Press the X button to accept the value and return to
the Sensor A selections.
SETUP
SENSORS
SENSOR A
LABEL
Fig. 39. Setup - Sensors - Sensor A - Label.
SETUP
SENSORS
SENSOR A
LABEL
SENSOR A
BOILER A
OUTDOOR A
DUCT A
DISCHRG A
CHILLER A
ROOM A
SELECT
LABEL FOR
SENSOR A
2.2.2.3. LABEL (the sensor input)
For a sensor already labeled, the display positions to and
highlights that label.
M24505
NOTE: The label names in list order are: Sensor, Boiler,
62-0254—0518
1. From the Sensor A selections, use the S and T
buttons to highlight LABEL.
2. Press the X button to display the label list.
3. Use the S and T buttons to scroll through list and
highlight the desired label.
You may need to scroll up or down to view all
possible labels.
4. Use the X button to accept the highlighted label
and exit the list.
Outdoor, Duct, Dischrg, Chiller, Room, Supply,
Return, and Animals.
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
SENSORS
SENSOR A
UNITS
CALIBRATE
LABEL
EXIT
Fig. 40. Setup - Sensors - Sensor A - Exit.
SETUP
SENSORS
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
Fig. 41. Setup - Sensors - Sensor B Menu.
SETUP
SENSORS
SENSOR B
CALIBRATE
LABEL
LIMIT
EXIT
2.2.2.4. Exit Sensor A Setup
Press the W button to exit Sensor A selections and return
to the Sensors menu.
or
Use the S and T buttons to highlight EXIT and press the
X button.
M24506
2.2.3. SENSOR B
For the T775M2030 and T775M2048 models only, which
have a High/Low modulating temperature limit, the LIMIT
item displays on the Sensor B menu.
1. From the Sensors menu, use the T button to
highlight SENSOR B.
2. Press the X button to display the Sensor B menu.
M24507
2.2.3.1. CALIBRATE
Setting the calibration value is accomplished the same
way as the Sensor A. See “2.2.2.2. CALIBRATE (the
sensor)” on page 18.
2.2.3.2. LABEL
Setting the label is accomplished the same way as the
Sensor A. See “2.2.2.3. LABEL (the sensor input)” on
page 18.
1962-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
For the T775M2030 and T775M2048 models only, the
LIMIT item displays on the Sensor B menu.
NOTE: The LIMIT option acts only on Modulating
Output 1.
1. From the Sensors menu, use the T button to
highlight SENSOR B.
2. Press the X button to display the Sensor B menu.
M24508
3. Use the S and T buttons to select the LIMIT item.
4. Use the X button to display the Limit selections.
5. Use the S and T buttons to select the desired limit,
(Disable, Hi Limit, or Low Limit).
Default: Disable
6. Press the X button to accept the value and return to
the Sensor B menu.
When you select Hi Limit or Low Limit, the Sensor B menu
changes and adds the Hi/Low Limit and Throttling Range
items.
If you are setting a Hi or Low Limit, continue with “2.2.4.1.
HI LIMIT or LOW LIMIT (Sensor B only)”.
If you selected Disable for the Limit value, continue with
“2.3. Setting up the Outputs” on page 21.
2.2.4.1. HI LIMIT or LOW LIMIT(Sensor B only)
Fig. 43 shows the Hi Limit (Heat mode), but the process is
the same for setting the Low Limit (Cool mode). For
proper operation, the high limit should be used only in the
Heat mode, and the low limit only in the Cool mode.
Sensor B can be assigned a high/low limit, so that as you
are controlling temperature at Sensor A, the control
adjusts its modulating output to prevent exceeding the
user-entered limit for Sensor B.
o
F
1. From the Sensor B menu, use the T button to
highlight HI LIMIT or LOW LIMIT.
2. Press the X button display the LIMIT value.
3. Use the S and T buttons to increase/decrease the
M24509
desired Limit value.
4. Press the X button to accept the value and return to
the Limit menu.
62-0254—0520
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
The throttling range for the modulating high or low limit
positions the setpoint at the end of the throttling range.
For example, with a high (Heat) limit at Sensor B of 200°
F and a throttling range of 10° F, the modulating output
controlling Sensor A begins to throttle back at 190° F
(88° C), and fully closes at 200° F (93° C). Conversely, the
throttling range for the low limit begins above the Cooling
setpoint in the same manner.
1. From the Limit menu, use the T button to highlight
o
F
M24510
THROT RNG.
2. Use the S and T buttons to increase/decrease the
desired value for the Throttling Range.
Default = 0
3. Press the X button to accept the value and return to
the Limit menu.
4. Press the W button to exit the Limit menu.
5. Press the W button to exit the Sensors menu and
return to the Setup menu.
2.3. Setting up the Outputs
1. From the Setup menu, use the Sand T buttons to
highlight OUTPUTS.
2. Press the X button to display the Outputs menu.
NOTE: The menus (e.g. the Outputs menu shown here)
can display only those relays that are defined in
Setup (see page 24). For example, if you
configure only two relays, then only two relays
M24511
display on the appropriate menus.
The following procedures set up each modulating output
and relay output.
1. From the Output menu, use the S and T buttons to
highlight the desired modulating output (MOD 1 or
MOD 2).
2. Press the X button to display the selected MOD
menu.
NOTE: Modulating outputs are not available on the
T775A and T775B controller models. If you are
M24512
setting up one of these controllers, skip to “2.3.2.
NBR OF RELAYS” on page 24.
Use the remaining procedures, beginning with “2.3.1.1.
TYPE (of output signal)”, to set up each modulating
output. If you have two modulating outputs, repeat these
procedures for each modulating output.
2162-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
OUTPUTS
MOD 1
TYPE
SETUP
OUTPUTS
MOD 1
TYPE
4 - 20 mA
0-10 V
2-10 V
SERIES 90
SELECT
TYPE FOR
MOD 1
2.3.1.1. TYPE (of output signal)
M24513
Fig. 47. Setup - Outputs - Mod Out - Type.
SETUP
OUTPUTS
MOD 1
MIN OUT %
Fig. 48. Setup - Outputs - Mod Out - Minimum Output
SETUP
OUTPUTS
MOD 1
INTEGRAL
Percentage.
SETUP
OUTPUTS
MOD 1
MIN OUT %
0
ENTER
MINIMUM
PERCENT FOR
MOD 1
SETUP
OUTPUTS
MOD 1
INTEGRAL
400
ENTER
INTEGRAL
TIME FOR
MOD 1
SEC
2.3.1.2. MIN OUT %
The minimum output % prevents the output from dropping
below the value entered. This value can be useful to
maintain minimum damper position.
Using the time clock or digital input to disable the output
%
forces the output to 0%.
M24514
2.3.1.3. INTEGRAL
M24515
Fig. 49. Setup - Outputs - Mod Out - Integral.
NOTES:
1.The Integral time is factory set for 400
seconds. This is a good middle range and
should satisfy many applications. The integral
time can be increased for applications where
sensed response is slow, and can be
decreased for applications where sensed
response is fast (e.g. discharge air control).
2.As a starting point, an optimal integral time for
discharge air typically ranges from 12 to 200
seconds. An optimal integral time for room
control typically ranges from 60 to 2,500
seconds. The purpose of integral action is to
reduce or eliminate the offset from setpoint
during steady state control that is often seen
in proportional only control.
62-0254—0522
1. From the Mod menu, use the S and T buttons to
highlight TYPE.
2. Press the X button to display the Type selections.
3. Use the Sand T buttons to highlight the desired
output type.
Default: 4-20 mA
4. Press the X button to accept the selected type and
return to the Mod menu.
1. From the Mod menu, use the S and T buttons to
highlight MIN OUT %.
2. Press the X button to display the Min Out %.
3. Use the S and T buttons to increase/decrease the
desired value from 0% to 100% in 1% increments.
Default: 0%
Range: 0 to 100%
4. Press the X button to accept the percentage and
return to the Mod menu.
1. From the Mod menu, use the S and T buttons to
highlight INTEGRAL.
2. Press the X button to display the Integral seconds.
3. Use the S and T buttons to increase/decrease the
value from 0 to 3,600 in 10 second increments.
Default: 400 seconds
Range: 0 to 3,600 seconds
4. Press the X button to accept the seconds and
return to the Mod menu.
3.Keep in mind that control is most sensitive to
throttling range. Adjust the throttling range
first before any adjustment to integral time.
Adjust throttling range to be as wide as
possible to start since this will provide the
most stable control. Remember that the
integral will eliminate the steady state error so
you do not need to have a small throttling
range to have accurate control. (Integral
action allows for controlling to a setpoint even
with a wide throttling range).
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
OUTPUTS
MOD 1
DERIVATIV
SETUP
OUTPUTS
MOD 1
DERIVATIV
0
ENTER
DERIVATIVE
TIME FOR
MOD 1
SEC
Fig. 50. Setup - Outputs - Mod Out - Derivative.
SETUP
OUTPUTS
MOD 1
SCHEDULE
OUTPUTS
SCHEDULE
YES
NO
SCHEDULE
OUTPUTS
SETUP
MOD 1
USE
FOR
Fig. 51. Setup - Outputs - Mod Out - Schedule.
2.3.1.4. DERIVATIVE
The Derivative default value is factory set to zero (no
derivative control). It is strongly recommended that the
derivative remain at zero (0) unless you have a very good
reason to adjust it. Derivative control is not needed in the
vast majority of HVAC applications.
1. From the Mod menu, use the S and T buttons to
highlight DERIVATIV.
2. Press the X button to display the Derivative
M24516
seconds.
3. Use the S and T buttons to increase/decrease the
value.
Default: 0 (zero)
Range: 0 to 3,600 seconds
4. Press the X button to accept the seconds and
return to the Mod menu.
2.3.1.5. SCHEDULE
The Schedule option displays only if the USE SCHED
parameter is set to Yes (See page 24).
1. From the Mod menu, use the S and T buttons to
highlight SCHEDULE.
2. Use the S and T buttons to highlight YES or NO.
Default: YES
3. Press the X button to accept the selection and
return to the Mod menu.
Each output can be set up to follow or ignore the built in
M24517
scheduler. To disable the scheduler for all outputs, see
“2.3.3.1. USE SCHED” on page 24.
SETUP
OUTPUTS
MOD 1
TYPE
MIN OUT %
INTEGRAL
DERIVATIV
SCHEDULE
EXIT
Fig. 52. Setup - Outputs - Mod Out - Exit.
2.3.1.6. EXIT
Press the W button (or highlight EXIT and press the X
button) to exit the Mod menu and return to the Outputs
menu.
If you have a second modulating output to configure, go to
“2.3.1. Setting up the Modulating Outputs” on page 21.
If you are finished setting up the modulating outputs,
continue with “2.3.2. NBR OF RELAYS”.
M24518
2362-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
OUTPUTS
# RELAYS
SETUP
OUTPUTS
# RELAYS
4
ENTER
NUMBER OF
RELAYS
Fig. 53. Setup - Outputs - Number of Relays.
SETUP
OUTPUTS
OPTIONS
Fig. 54. Setup - Outputs - Options Menu.
SETUP
OUTPUTS
OPTIONS
USE SCHED
MIN OFF
DI OPTS
SHOW RT
EXIT
2.3.2. NBR OF RELAYS
1. From the Outputs menu, use the Sand T buttons
2. Press the X button to display the number of relays.
3. Use the S and T buttons to display the number
4. Press the X button to accept the value and display
M24519
NOTES:
2.3.3. OPTIONS
1. From the Outputs menu, use the Sand T buttons
2. Press the X button to display the Options menu.
M24520
to highlight # RELAYS.
from 1 to 4 depending on the model. (See notes
below.)
the Outputs menu.
1.The T775A/B/M models have the following
outputs available:
T775A20191 relay output
T775B2016up to 2 relay outputs
T775B2024up to 4 relay outputs
T775B2032up to 2 relay outputs
T775B2040up to 4 relay outputs
T775M2006no relay outputs
T775M2014up to 4 relay outputs
2.The number of relay outputs entered here
determines how many relays display on the
home screen.
to highlight OPTIONS.
SETUP
OUTPUTS
OPTIONS
USE SCHED
OUTPUTS
OPTIONS
USE SCHED
YES
NO
SCHEDULE
OUTPUTS
SETUP
USE
FOR
Fig. 55. Setup - Outputs - Options - Schedule.
62-0254—0524
2.3.3.1. USE SCHED
1. Press the X button to display the schedule
selections.
2. Use the Sand T buttons to highlight YES or NO.
Default: NO
3. Press the X button to accept the value and display
the MIN OFF option.
Selecting NO disables scheduling for all outputs.
M24521
Selecting YES enables scheduling for all outputs. When
YES is selected, all individual outputs default to follow the
schedule. However, each individual output can be
removed from scheduling as desired.
With Scheduling enabled, when you return to Program
mode, the new option for Scheduling displays. You can
press the home key and then the menu key to view the
Schedule options in the menu.
See “2.3.1.5. SCHEDULE” on page 23.
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
OUTPUTS
OPTIONS
MIN OFF
SETUP
OUTPUTS
OPTIONS
MIN OFF
0
ENTER
MINIMUM
OFF TIME
FOR RELAYS
SEC
M24522
Fig. 56. Setup - Outputs - Options - Min Off Time.
SETUP
OUTPUTS
OPTIONS
DI OPTS
SETUP
OUTPUTS
OPTIONS
DI OPTS
DISABLE
SETBACK
IGNORE
SELECT DI
OPTIONS
OUTPUTS
FOR
M24523
Fig. 57. Setup - Outputs - Options - DI Options.
2.3.3.2. MIN OFF (minimum off time for all relays)
This is the minimum number of seconds of “off time” for
all relays.
1. Press the X button to display the Min Off value.
2. Use the S and T buttons to increase/decrease the
desired number of seconds from 0 to 990 seconds
in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the X button to accept the seconds and
display the DI OPTIONS.
NOTES:
1.The minimum off time applies to all relay
outputs.
2.When minimum off time is active, relays
waiting to be energized display a flashing
square underneath the relay number on the
home screen.
3.If the minimum off time is not equal to zero
(0), the minimum off time activates at powerup. To manually override, press the W button
at any time.
2.3.3.3. DI OPTIONS (digital input options)
The DI Option you select applies to all outputs. This
option overrides any Setpoint/Setback values entered in
the Schedule.
1. Press the X button to display the DI Option
selections.
2. Use the S and T buttons to highlight DISABLE,
SETBACK, or IGNORE.
Default: DISABLE
3. Press the X button to accept the value and display
the SHOW RT option.
When the digital input (DI) closes, all outputs follow the DI
option value (Disable, Setback, or Ignore):
• DISABLE disables the outputs; relays return to deenergized state and Mod outputs return to 0% output.
• SETBACK enables a setback temperature value to be
programmed for each output.
— To program the Setback temperature, see Fig. 32
on page 16.
• IGNORE causes the digital input to have no effect on
the Relay or Mod outputs.
SETUP
OUTPUTS
OPTIONS
SHOW RT
YES
NO
SETUP
OUTPUTS
OPTIONS
SHOW RT
USE
RUNTIME
FOR
RELAYS
M24524
Fig. 58. Setup - Outputs - Options - Show Runtime.
2.3.3.4. SHOW RT (show run time hours)
1. Press the X button to display the Show RT values.
2. Use the S and T buttons to select YES or NO.
Default: YES
3. Press the X button to accept the value and return to
the Options menu.
Selecting YES shows the RT (run time) hours for each
relay on the home screen displays.
NOTE: Run times can be reset to zero for each
individual relay. You must do this for each relay
that you want to reset to zero. See “2.3.4.3.
RESET RT (run time hours)” on page 28.
2562-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
OUTPUTS
OPTIONS
USE SCHED
MIN OFF
DI OPTION
SHOW RT
EXIT
Fig. 59. Setup - Outputs - Options - Exit.
SETUP
OUTPUTS
RELAY 1
SETUP
OUTPUTS
RELAY 1
TYPE
SCHEDULE
RESET
RESET RT
EXIT
Fig. 60. Setup - Outputs - Relay Menu.
SETUP
OUTPUTS
RELAY 1
TYPE
SETUP
OUTPUTS
RELAY 1
TYPE
STANDARD
FLOATING
SELECT
TYPE FOR
RELAY 1
Fig. 61. Setup - Outputs - Relay - Type.
2.3.3.5. Exit Options Setup
Press the W button (or highlight EXIT and press the X
button) to exit and return to the Outputs menu.
Continue with “2.3.4. Setting up the Relays”
M24525
2.3.4. Setting up the Relays
1. From the Outputs menu, use the S and T buttons
to highlight the desired relay (1-4 depending on
model).
2. Press the X button to display the selected relay
menu.
The TYPE selection shown in Fig. 60 displays only for
Relay 1 and Relay 3.
M24526
Continue with the remainder of section 3.4 to setup the
relay outputs.
2.3.4.1. TYPE (standard or floating)
The Floating option is only available on the T775B2016,
T775B2024, T775B2032, and T775B2040 models.
For these models, this selection displays only for Relay 1
and/or Relay 3.
1. Press the X button to display the Type values.
2. Use the S and T buttons to select STANDARD OR
FLOATING.
Default: STANDARD (not floating)
M24527
3. Press the X button to accept the value and return to
the Relay menu.
If you select FLOATING, the relays are paired (1-2 or 3-4)
and are setup together. Continue with “2.3.4.1.1. Floating
Relay Menu”.
If you select STANDARD, go to “2.3.4.2. SCHEDULE” on
page 28.
62-0254—0526
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
The Derivative option displays only on the T775B2016,
T775B2024, T775B2032, and T775B2040 models when
the Type option = Floating.
1. From the menu, use the S and T buttons to
highlight DERIVATIV.
2. Press the X button to display the actuator value.
3. Use the S and T buttons to increase/decrease the
desired number of seconds.
Default: 0 seconds
Range: 0 to 3,600 seconds)
4. Press the X button to accept the value and display
the SCHEDULE option.
Continue with “2.3.4.2. SCHEDULE” for the remaining
relay selections.
(modulating/floating relay only)
2.3.4.2. SCHEDULE
This selection displays only if “Use Sched = YES” is
selected during the Output Options setup (see page 24).
When selected, individual outputs default to follow the
schedule.
1. Press the X button to display the Schedule values.
2. Use the S and T buttons to select YES or NO.
Default: YES
3. Press the X button to accept the value and return to
the Relay menu.
An individual output can be selected to be controlled or
not controlled by the schedule.
If NO is selected, the Setback selection does not appear
in the Program menu for this output.
SETUP
OUTPUTS
RELAY 1
RESET RT
Fig. 67. Setup - Outputs - Relay - Reset Runtime.
YES
NO
SETUP
OUTPUTS
RELAY 1
RESET RT
RESET
RUN TIME
FOR
RELAY 1
2.3.4.3. RESET RT (run time hours)
This selection displays only if “Show RT = YES” is
selected during Output Options setup (see page 25).
M24533
Selecting YES immediately resets the output run time
hours to zero for this output. When you subsequently
return to this screen, the RESET RT defaults to NO.
NOTE: Run times can be reset to zero for each
62-0254—0528
1. From the Relay menu, press the X button to display
the Reset RT values.
2. Use the S and T buttons to select YES or NO.
Default: NO
3. Press the X button to accept the value and return to
the Relay menu.
individual relay. You must do this for each relay
that you want to reset to zero.
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SETUP
OUTPUTS
RELAY 1
RESET
SCHEDULE
RESET RT
EXIT
Fig. 68. Setup - Outputs - Relay - Exit.
2.4. EXIT Setup Mode
Press the W button to exit the selected relay set up and
return to the Outputs menu.
To setup the next relay output go to “2.3.4. Setting up the
Relays” on page 26.
If you are finished setting up the relay outputs, press the
HOME button to exit Setup mode and return to the home
screen display.
M24534
This completes the Setup procedure.
2962-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
3. SCHEDULING
Scheduling provides the ability to set daily temperature
settings for up to two events per day. Typically, these are
the daytime (setpoint) and the nighttime (setback)
settings.
IMPORTANT
To enable Scheduling, you must first enter Setup
mode (press and hold the MENU button for 5
seconds), select OUTPUTS, select OPTIONS,
select USE SCHED, and then select YES. (See
“2.3.3.1. USE SCHED” on page 24).
IMPORTANT
To properly account for Daylight Saving time, be
sure to set the Date before setting the Time.
See “3.2.2. SET DATE” on page 31.
NOTE: Each output is independently configurable to
follow the schedule or not. For modulating
outputs, See “2.3.1.5. SCHEDULE” on page 23.
For relay outputs, see “2.3.4.2. SCHEDULE” on
page 28.
NOTE: The controller interface is intuitive. You may find
that you do not need the following scheduling
instructions. You may want to use this procedure
simply as a reference to locate the particular
option or parameter of interest.
1. From the Options menu, use the S and T buttons
to highlight DAYLIGHT.
2. Press the X button to display the current system
setting for daylight saving time.
3. Use the S and T buttons to select YES or NO.
Default: YES
4. Press the X button to accept the value and return to
the Options menu.
5. From the Options menu, use the Use the S and T
buttons to highlight EXIT.
6. Press the X button to return to the Schedule menu.
3162-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
MENU
SCHEDULE
MON-FRI
MENU
SCHEDULE
MON-FRI
E1 SETPT
E1 TIME
E2 SETPT
E2 TIME
EXIT
M24541
Fig. 74. Schedule Event Menu (Showing MON-FRI).
3.3. Setting Individual Schedules
As shown in the Schedule menu (Fig. 69 on page 30),
schedules can be set for the following time periods:
• Monday through Friday
• Saturday and Sunday
• Individual days of the week
1. From the Schedule menu, use the S and T buttons
to highlight the desired time period.
2. Press the X button to display the Schedule menu
for the selected time period.
For each selected time period, the schedule event (E1
and E2) parameters are exactly the same as shown in
Fig. 74.
SCHEDULING EXAMPLE
Setting the schedule is independent of the temperature
settings for the relay outputs. The following illustrates a
weekly schedule for daytime (setpoint) and night time
(setback) use and shows the factory default settings:
Table 4. Mon-Fri Schedule Defaults
DAYEVENTSETPT ACTIONTIME
Mon-Fri Event 1 (E1) Setpoint
Mon-Fri Event 2 (E2) Setback
Sat-Sun Not used; remains in Setback from Mon-Fri
E2 settings
a
Setpoint time span is 6:00 AM until 5:59 PM because
setback starts at 6:00 PM.
b
Setback time span is 6:00PM until 5:59 AM because
setpoint starts at 6:00 AM.
To set a schedule, continue with “3.3.1. E1 SETPT
(setpoint for event 1)”.
The following figures show the MON-FRI menu, but the
menu selections are the same for any time period.
6:00 AM
6:00 PM
a
b
MAIN
SCHEDULE
MON-FRI
E1 SETPT
MENU
SCHEDULE
MON-FRI
E1 SETPT
SETPOINT
SETBACK
NOT USED
SELECT
SETPOINT
FOR
EVENT 1
Fig. 75. Schedule - Event 1 Setpoint.
62-0254—0532
3.3.1. E1 SETPT (setpoint for event 1)
1. From the selected time period menu, use the S and
T buttons to highlight E1 SETPT.
2. Press the X button to display the setpoint options.
3. Use the S and T buttons to highlight the desired
option.
4. Press the X button to accept the value and return to
the selected time period menu.
M24542
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
MAIN
SCHEDULE
MON-FRI
E1 TIME
Fig. 76. Schedule - Event 1 Time.
MAIN
SCHEDULE
MON-FRI
E1 TIME
6:00 AM
SET
TIME
FOR
EVENT 1
3.3.2. E1 TIME (time for event 1)
1. From the selected time period menu, use the S and
T buttons to highlight E1 TIME.
2. Press the X button to display the current time
setting for event 1.
3. Use the X button to cycle between the hour,
minute, and AM/PM values.
4. Use the S and T buttons to increase/decrease the
desired value for the hour, minute, and AM/PM.
M24543
5. Press the W button to accept the time and return to
the selected time period menu.
3.3.3. E2 SETPOINT (setpoint for event 2)
Creating the setpoint for event 2 is accomplished the
same way as the first event. See “3.3.1. E1 SETPT
(setpoint for event 1)” on page 32.
3.3.4. E2 TIME (time for event 2)
Creating the time for event 2 is accomplished the same
way as the first event. See “3.3.2. E1 TIME (time for event
1)” above.
3.3.5. EXIT (exit from selected time period settings)
After entering the time for event 2, use the W button to exit
the schedule time period and return to the Schedule menu
(Fig. 69 on page 30) to select a different time period.
When you finish scheduling the time periods, continue
with “3.4. Exiting Scheduling Mode”.
3.4. Exiting Scheduling Mode
Press the HOME button to exit the Schedule menu and
return to the home screen display.
This completes the Scheduling procedure.
3362-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SUMMARY MENU
The Summary menu provides the ability to view the
schedule (E1 and E2 times) for each relay for each day of
the week.
NOTE: Scheduling must be enabled for the Summary
menu to display. Enabling the schedule is
determined in the Setup process for the Output
Options (see page 24).
MENU
SUMMARY
Fig. 77. Summary Example - Monday Settings.
For each relay, the Summary display indicates the time
and temperature (in parenthesis) for each of the two
scheduled events E1 and E2.
1. Press the MENU button to view the menu.
2. Use the S and T buttons to highlight SUMMARY.
3. Press the X button to display the Summary
settings.
4. Use the X button to scroll forward through each day
of the week (Monday, Tuesday, Wednesday,
Thursday, Friday, Saturday, and Sunday).
5. While viewing a specific day, use the S and T
buttons to cycle through the individual relay
schedules for that day.
When finished, press the home key to return to the home
display screen.
MENU
SUMMARY
MONDAY
RELAY 1-2
E1: 06:00AM (72)
E2: 06:00PM (65)
M24545
TROUBLESHOOTING
Power Loss
The date and time settings are retained for 24 hours after
a power outage. After a power loss of more than 24 hours,
the date and time settings may need to be reentered. All
other settings are stored permanently.
Errors and Diagnostics
The controller provides an error message and diagnostic
status as described below.
Error Message
There is a two-character error code that displays in
response to controller software problems:
EE
EEPROM Failure — The values read back from
the EEPROM are not the same as written into the
EEPROM. This error cannot be field repaired. Replace
the device.
Diagnostic Messages
There are two diagnostic messages that can display in
response to sensor problems. The diagnostic codes that
can flash on the display are:
– –
Sensor Open or Shorted — Two dashes display
when a sensor (typically temperature) is open or
shorted. An open circuit is considered anything
greater than 1570 ohms (greater than 300F), shorted
anything less than 770 ohms (less than -73F).
Whichever stages are operating with this sensor
cease to control (meaning relays go to OFF and
proportional outputs go to zero percent).
This message can also mean that the sensor is
programmed, but not physically connected.
-60° or 270° F (-51° or 132° C) Blinking
Blinking relay status
62-0254—0534
Temperature Out of Range — The temperature
display blinks when the sensed temperature range is
outside of the display range, below -60° F (-51° C) or
above 270° F (132° C). The displayed value remains at
that displayed limit and control continues. Controller
continues to function unless an open or shorted state
is detected.
Relay Minimum Off Time is Active — On the home
screen, each relay’s indicator () blinks while the
relay’s minimum off time is active.
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
SPECIFICATIONS
Power: 24, 120, or 240 Vac; 50/60 Hz;
A separate earth ground is required for any power source.
Power Consumption:
• 8 VA maximum at 60 Hz
• 10 VA maximum at 50 Hz
Operating & Storage Temperature Ambient Rating:
• -40° to 125° F (-40° to 52° C) @ 50 Hz
• -40° to 140° F (-40° to 60° C) @ 60 Hz
Relative Humidity: 5% to 95% non-condensing
Relay Contact Output Ratings (N.O. and N.C.):
• 1/2 hp; 9.8 AFL, 58.8 ALR @ 120 Vac
• 1/2 hp; 4.9 AFL, 29.4 ALR @ 240 Vac
• 125 VA pilot duty @ 120/240 Vac
• 10A @ 24 Vac (resistive)
Modulating Outputs:
• 0-10 Vdc; drive a minimum of 2,000 Ohms
• 2-10 Vdc; drive a minimum of 2,000 Ohms
• 4-20 mA; drive a maximum of 600 Ohms
• Electronic Series 90
• Floating
DOC
Emissions Compliance
EN 55022: 2006
CISPR 22: 2006
VCCI V-3/2006.04
ICES-003, Issue 4: 2004
FCC PART 15 SUBPART B Class B Limit
Safety Compliance
UL 60730-1 and Part 2-9 for US and Canada
FCC Compliance Statement:
This equipment has been tested and found to comply with
limits for a Class B digital device, pursuant to Part 15 of
the FCC rules. These limits are designed to provide
reasonable protection against harmful interference in
residential installations. This equipment generates, uses,
and can radiate radio frequency energy, and if not
installed and used in accordance with the instructions,
may cause harmful interference to radio communications.
However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does
cause interference to radio or television equipment
reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following
measures:
— Reorient or relocate the receiving antenna
— Move the equipment away from the receiver
— Plug the equipment into an outlet on a circuit different
from that to which the receiver is connected
— Consult the dealer or an experienced radio/television
technician for additional suggestions
You are cautioned that any change or modifications to the
equipment not expressly approve by the party responsible
for compliance could void Your authority to operate such
equipment.
This device complies with Part 15 of the FCC Rules.
Operation is subjected to the following two conditions 1)
this device may not cause harmful interference and 2) this
device must accept any interference received, including
interference that may cause undesired operation.
Immunity Compliance
EN 61000-6-1: 2001 covering
EN 61000-4-2: 1995 + A1: 1998 + A2: 2001
EN 61000-4-3: 2002
EN 61000-4-4: 2004
EN 61000-4-5: 1995 + A1: 2001
EN 61000-4-6: 1996 + A1: 2001
EN 61000-4-8: 1993 + A1: 2001
EN 61000-4-11 2nd Ed.: 2004
3562-0254—05
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée