Honeywell T7560A, T7560B, T7560C Installation Instructions

T7560A,B,C Digital Wall Module

INSTALLATION INSTRUCTIONS

CAUTION: This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the Installation Instructions, may cause interference with radio communication. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case, users at their own expense will be required to take whatever measures may be required to correct the interference. Any unauthorized modification of this equipment may result in the revocation of the owner’s authority to continue its operation.

BEFORE INSTALLATION

All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital Wall Module (DWM) wiring can be sized from 16 to 22 AWG (1.5 to 0.34 mm2), depending on the application. The maximum length of wire from a device to a wall module is 164 ft (50 m). Twisted pair wire is recommended for wire runs longer than 100 ft (30.5 m).

CAUTION

EMI Noise Introduction.

Risk of erratic system operation.

Keep wiring at least one ft (305 mm) away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels. During installations, try to avoid areas of high EMI noise. Run wall module wiring separately from 50 Vac or greater power wiring.

Table 1. Types of DWM.

 

Sensor1

Setpoint

Bypass

Fan

 

 

 

 

Override

T7560A

Tmp

wheel

button

button

T7560B

Tmp/Hum

wheel

button

button

T7560C

Tmp/Hum

-

-

-

1 Tmp = Temperature sensor; Hum = Humidity sensor

Table 2. Controller SW requirements for powering via terminal 5 and new LCD signaling.

Fan Coil Unit

Hydronic

Chilled Ceiling

W7752

W7762

W7763

1.00.04

1.00.03

1.00.03

NOTE: A software module (ModAL module GNRSC02A) is available to adapt the wall module to the respective Excel 20, 50, 80, 100, 500, 600 controller, making any further configuring obsolete. Contact your local Honeywell distributor for further details.

DWM DISASSEMBLY

The T7560A,B,C comes packed with a subbase that mounts separately for ease of installation. The cover is fixed by a latch on the underside of the unit. Remove the cover as shown in Fig. 1 (T7560A,B) or Fig. 2 (T7560C):

1.Insert the tip of an awl or a similar narrow, pointed object into the small hole in the latch (T7560A,B) or simply depress the latch by hand (T7560C).

2.Pry off the cover.

Fig. 1. DWM disassembly (T7560A,B)

Fig. 2. DWM disassembly (T7560C)

® U.S. Registered Trademark

 

EN1B-0146GE51 R0303

Copyright © 2003 Honeywell Inc. All Rights Reserved

95-7620-4

T7560A,B,C DIGITAL WALL MODULES

INSTALLATION

Mount the wall module on an inside wall approximately 54 in. (1.3 m) from the floor (or as specified on the installation drawings) to allow exposure to the average zone temperature. Do not mount the wall module on an outside wall, on a wall containing water pipes or near air ducts. Avoid locations that are exposed to discharge air from registers or radiation from lights, appliances, or the sun.

The DWM is furnished with a terminal block; all field wiring connections are made to these eight terminals.

The DWM has to be mounted in vertical position with the LCD display to the top.

Mount the subbase directly on a wall (see Fig. 3) using the type of screws appropriate for the wall material.

Fig. 3. Mounting of DWM (T7560A,B shown)

See Fig. 6 for T7560A,B,C mounting dimensions.

Wiring

Wire the terminal blocks as follows:

1.Strip 3/16 in. (5 mm) of insulation from the conductor.

2.Insert the wire in the required terminal location and tighten the screw to complete the termination.

IMPORTANT

Deviation from this rule can result in improper electrical contact. See Fig. 4.

3. Verify DWM is wired according to Fig. 4.

NOTE: For specific wiring requirements, see the following Power section.

Power

The DWM can be powered either via the 5 V LED input (terminal 5) or via the 24 Vac/dc input (terminal 8).

IMPORTANT

The DWM can be powered only via terminal 5 with those controllers listed in Table 2, and if a

SW version listed in Table 2 or higher is installed. If the DWM is powered via terminal 5, the Excel 10 controller must be configured for LCD_DISPLAY (LED output continuously ON).

NOTE: The 24 Vac power supply is needed only with the T7560B DWM (for the humidity sensor).

Alternatively, a DC voltage source with 5...12 V can be connected to terminal 5 (see IMPORTANT note above).

Alternatively, a DC voltage source with 18...30 V (e.g. 22 Vdc from W7750 CVAHU) can be connected to terminal 8.

Input ratings

 

Terminal 5:

Imax 3 mA

min. 5 Vdc

max. 12 Vdc

Imax 5 mA

or LED output of any Excel 10 controller

Terminal 8:

24 Vac from controller; I < 5 mA

or

18...30 Vdc; I < 5 mA

Controllers with the following output ratings can be connected to terminal 5

(ratings are met by all Excel 10 controllers):

5 V with 389 ohms

4.3 V with 100 ohms

14.3 V with 1.5k ohms

Use up to 16 AWG (1.5 mm2) with a minimum of 18 AWG (1.0 mm2) wire for connecting 24 Vac power to terminal 8.

CAUTION

Low Voltage Equipment. Risk of equipment damage.

The 24 Vac power source for the DWM must be a Class II Power Source. To conform to Class II restrictions, transformers must not be larger than 100 VA. A transformer that is CE certified and meets the Low Voltage Device (LVD) requirements must be used in Europe for all installations of this product.

The DWM power usage is < 0.5 VA at 24 Vac. The DWM does not require a dedicated transformer. The DWM can get power from any convenient location in the 24 Vac power circuit.

The 24 Vac power can come from the 24 Vac power terminals on the nearest controller or directly from a 24 Vac transformer, whichever is closer.

95-7620-4

2

EN1B-0146GE51 R0303

 

Honeywell T7560A, T7560B, T7560C Installation Instructions

T7560A,B,C DIGITAL WALL MODULES

Terminals

<![if ! IE]>

<![endif]>00000081c

2

1

1 = Common

2 = Temperature sensor

3 = Setpoint (T7560C: Do not connect!)

4 = Bypass/fan* (T7560C: Do not connect!)

5 = LED input (T7560C: Do not connect!)

6 = Bypass** (T7560C: Do not connect!)

7 = Humidity output

8 = 24 Vac / 22 Vdc input

*With Excel 10 Controllers: W7750 (CVAHU), W7752 (FCU), and XL12

**With Excel 10 Controllers: W7751 (VAV), W7762 (HYD), and W7763 (CHC)

For W7753 (UV) and W7761 (RIO), see NOTE below.

Fig. 4. Wiring of DWM

NOTE: If connected to W7753 (UV) Controller, both terminals 4 and 6 must be connected.

W7761 Remote I/O Controller supports only terminals 2 (temperature), 7 (humidity), and

1 (common), as well as terminal 8 as voltage supply.

Wiring with terminal 8 is not necessary if: An FCU or CHC controller with software is connected (see table 2).

An Excel 500 with 6V/8V/10V signaling from the controller is used.

The T7560A is then powered by terminal 5.

When all wiring is complete, attach the cover of the DWM as is shown in Fig. 5.

NOTE: Make sure that the latch on the underside of the DWM engages properly.

Fig. 5. Mounting cover of T7560A,B DWM.

Fig. 6. DWM dimensions in inches (mm)

3

95-7620-4

 

EN1B-0146GE51 R0303