Honeywell T7350 User Manual

T7350
Commercial Programmable Thermostat
SYSTEM ENGINEERING
Contents
Device Description .............................................................................................. 2
Control Application .............................................................................................. 2
Network Control Provided ................................................................................... 3
Models .................................................................................................................................. 3
Abbreviations and Definitions .................................................................................................................................. 4
Network Configurations .................................................................................................................................. 9
Application Steps .................................................................................................................................. 10
Appendix A - Network Tools & Workstations ......................................................................................................................... 20
Appendix B - Network Alarm Reporting .................................................................................................................................. 21
Appendix C - Network Error Reporting ................................................................................................................................... 23
Products Covered ................................................................................................ 3
Applicable Literature ............................................................................................ 4
Performance Specifications ................................................................................. 5
Communications .................................................................................................. 7
L
ONMARK
Overview ............................................................................................................. 10
Step 1. Plan the System ...................................................................................... 11
Step 2. Determine Required Network Devices .................................................... 11
Step 3. Layout Communications and Power Wiring: .......................................... 11
L
ONWORKS
Cable Termination ............................................................................................... 12
Wiring Details ...................................................................................................... 12
Step 4. Prepare Wiring Diagrams ........................................................................ 12
General Considerations ....................................................................................... 15
Step 5. Order Equipment ..................................................................................... 17
Step 6. Configure T7350 ..................................................................................... 17
Step 7. Troubleshooting ....................................................................................... 18
®
Functional Profile .............................................................................. 8
®
Bus Layout ...................................................................................... 11
Appendix D - Network Access to Local Sensor Data ............................................................................................................. 25
Appendix E - Scheduling Network Devices ............................................................................................................................ 25
Appendix F - Network Master Clock ........................................................................................................................................ 25
Appendix G - Network Connections to Other LCBS Devices ................................................................................................ 26
Appendix H - T7350H Network Variable Summary ................................................................................................................. 34
® U.S. Registered Trademark © 2004 Honeywell International Inc. All Rights Reserved
63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

INTRODUCTION

Device Description

The T7350H is a LONMARK® certified thermostat that provides networking capability in a L
ONWORKS
transformer-coupled Free Topology Transceiver (FTT). See Fig. 1.
The T7350H communicates with many L including the following: — Other T7350H Communicating Commercial Thermostat
devices.
— T7300F/Q7300H Commercial Thermostat/Communicating
Subbase. — Excel 15 S7760A Command Display. — Excel 10 W7750A,B,C Constant Volume Air Handler Unit
(CVAHU) Controller. — Excel 15 W7760A, B, C Building & Plant Managers. — Excel 10 W7751B, D, F, H, J Variable Air Volume Terminal
Unit Controllers. — Excel 10 W7752D, E, F, G Fan Coil Unitcontrollers. — Excel 10 W7753A Unit Ventilator Controller. — Excel 10 W7762A,B Hydronic Controllers. — Excel 10 W7763C, D, E Chilled Ceiling Controllers.
NOTEBOOK PC
®
system using a
ONMARK
RS-232 SERIAL PORT
SLTA
®
devices
BUILDING MANAGER
1481216
EXCEL 15 W7760
30 31
17 23
37

Control Application

The T7350H programmable communicating Thermostat controls commercial single zone heating, ventilating and air conditioning (HVAC) equipment through staged and modulating outputs. The T7350H consists of a two piece assembly with a thermostat cover and subbase. The thermostat cover includes the keypad and display for 7-day programming. Calendar programming is available through a direct connect PDA (Configuration Tool) or network (L
ONSPEC™ with model T7350H) tool configuration. The
subbase includes equipment control, inputs and network connections. The subbase mounts on the wall and the thermostat cover mounts to the subbase. In addition, the T7350H model can communicate local sensor data, schedule information, master clock operations and accept configuration and override instructions to or from other devices/tools in a L
ONWORKS
application in a three-stage heat and two-stage cool heat pump system. For additional hookups, see Fig. 10 through 12.
44
S7760
®
network. Fig. 9 shows a typical T7350H
WALL MODULE
EXCEL 10
CVAHU
LonWorks BUS
T7350H
MODEM
Select
Back
MODEM
BUILDING MANAGER
1481216
RS-232 SERIAL PORT
SLTA
EXCEL 15 W7760
17 23
30 31
44
37
S7760
Select
Back
EXCEL 10
CVAHU
LonWorks BUS
Fig. 1. Typical T7350H LONWORKS® network diagram.
WALL MODULE
T7350H
M22490
63-4368 2
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

Network Control Provided

The T7350H communicates with other network devices, or nodes, for sharing data such as local inputs. Through the network, a Command Display (S7760) is used to view or modify T7350H operational modes including:
• Weekly Schedule.
• Holiday Schedule.
• Room Temperature SetPoints (Occupied, Unoccupied, Standby).
• Manual Occupancy Override.
• Temperature Setpoints.
• Update Time Clock.
Network connected Workstations and Configuration Tools are used to view and modify additional T7350 operational modes:
• Command Fan operating mode (On, Auto)
• Command Application mode (Auto, Off, Heating, Cooling)
By using network messaging, the T7350H may share the following local inputs with other T7350, T7300/Q7300, XL15 or XL10 network connected devices:
• Room Humidity and Temperature.
• Outdoor Air Temperature.
• Occupancy Sensor.
• Unoccupied Bypass User Input.
Network messaging also supports distribution of local user commands and operational states from a single T7350H. That is, network connected T7350H and XL10 devices can be configured to follow the local user commands and states from a single (master) T7350H. These local T7350 commands include the following:
• Application mode (Auto, Off, Heating, Cooling).
• Occupancy (Occupied, Unoccupied, Bypass, Standby).
• Bypass (unoccupied override).
• Setpoint.
• Time synchronization from a T7350H designated as network master clock.
• Master Time Scheduling of Occupied, Unoccupied and Standby states.

MODELS

Table 1. T7350 Communicating Thermostat Models.
Maximum
a
Stages
Model Applications
T7350H1009 Conventional
or Heat Pump
T7350H1017 Modulating
a
All models are down-selectable and can be configured to control fewer stages than the maximum allowed.
b
Heat pump applications for these models have a maximum of two heat stages and two cool stages.
c
One extra stage (of either heat or cool) can be configured using the auxiliary relay.
3 (2)b3 (4)
2 modulating, 2 relay
b
c
FeaturesHeat Cool
Humidity, Occupancy, Outdoor, Discharge Air Capability
Humidity, Occupancy, Outdoor, Discharge Air Capability, 4-20 mA output (2-10 Vdc with 500 ohm resistor)

Products Covered

This System Engineering manual describes how to apply the T7350H Communicating Thermostat and related accessories to typical applications. Devices include:
• T7350H Commercial Communicating Thermostat.
• Excel 15 W7760A or B Building Manager.
• Excel 15 W7760C Plant Manager.
• Excel 10 Controllers including: W7750, W7751, W7752, W7753, W7762.
Other products:
• Q7760A Serial LonTalk
• Q7740A,B FTT Repeaters.
• 209541B FTT Termination Module.
See Table 2 for additional products.
Table 2. Additional Products.
Part Number
R8242A Contactor, 24 Vac
AT72D, AT88A … 24vac
T7770A-D Wall Modules
T7771 Wall Module with
4074EYD Wallplate for
AK3798 Single pair network
AK3797 Single pair network
AK3799 Double pair
®
Adapter.
Product
Description Comments
coil, DPDT.
Transformers.
active display.
For covering an T7770 Wall Modules.
cable, U.L. Type CMR
cable plenum rated, U.L. Type CMP
network cable plenum rated, U.L. Typ e CMP
existing hole in
a wall
3 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

Applicable Literature

The following list of documents contains general information related to the T7350H Communicating Commercial Thermostats.
Table 3. Applicable Literature
Form No. Title
63-1299 T7350 Commercial Programmable
Thermostat Spec Data
62-0195 T7350 Commercial Programmable
Thermostat Installation Instructions
63-2605 T7350 Commercial Programmable
Thermostat Product Data
74-2976 Excel L
ONSPEC™ ZL7760A Specification
Data
74-2937 Excel LONSPEC™ ZL7760A User’s Guide
74-3123 Light Commercial Building Solution System
Communication Guide
74-2697 T7770A, B, C, D, E, F, G Wall Module
Specification Data
95-7538 T7770A, B, C, D, E, F, G Wall Module
Installation Instructions
63-2617 T7771 Wall Module Product Data
74-2972 S7760A Command Display Specification
Data.
74-2858 Q7740A,B FTT Repeater Specification
Data.
95-7555 Q7740A,B FTT Repeater Installation
Instructions.
®
74-2954 Q7760A SLTA-10 Serial LonTalk
Adapter
Specification Data.
®
95-7511 Q7760A SLTA-10 Serial LonTalk
Adapter
Installation Instructions.
95-7554 209541B Termination Module Installation
Instructions

ABBREVIATIONS AND DEFINITIONS

Application—A special use Building Control function.
Binding—The process of logically connecting network
variables in one node to network variable(s) in other node(s). Binding is performed by a network management Tool (such as
L
ONSPEC™) that writes the binding information into the
EEPROM memory of all the neuron’s involved. The binding information is saved in the network image of each neuron.
Building Manager—A LONMARK® certified device that can be used to monitor and control HVAC equipment and other miscellaneous loads in a distributed network.
Command Display—A device that can be used to monitor data and change parameters of network connected devices.
CVAHU—Excel 10 Constant Volume Air Handler Unit Controller.
Excel 10s—A family of application - specific HVAC controllers such as the Excel 10 CVAHU and Excel 10 VAV.
HVAC—Heating, Ventilating and Air Conditioning.
I/O—Input/Output.
LCBS—Light Commercial Building Solution. These systems
are configured with the L monitored with a Workstation such as LonStation
ONSPEC™ network tool and
®. Many
LCBS networks include the W7760B & C plant managers. Routers (including Q7751A) are not supported by the LCBS network configuration L
ONSPEC™-ZL7760A—A network connected tool which
L
ONSPEC™ tool.
configures, commissions, calibrates and monitors the Honeywell Light Commercial Building Solution Q7300, T7350H, Excel 10 and Excel 15 family of controllers.
L
ONSTATIO N—A low-cost, easy-to-use Light Commercial
Building Solution workstation that provides advanced building control capabilities for small to medium-size buildings.
ONWORKS
L
communicating with each other using the LonTalk
®
Network—A data network based on neurons
®
protocol.
Mandatory Mechanisms/Objects/Network Variables— Mandatory mechanisms and network variables that are implemented in all the Excel 10 devices.
NamedObjects—These objects are visible on the network as functional independent entities and are accessed by name. Typical examples of NamedObjects are Controllers, ControlLoops and LogicFunction blocks contained in devices such as the XL5a or XL15b.
Network Management Node—A L
ONWORKS
®
node that is responsible for configuring the network, installing the nodes, binding the network variables between nodes, and general network diagnostics.
63-4368 4
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Network Variables—A class of variables defined in Neuron C that allows communication over the L
ONWORKS
®
network to other nodes on the network. An output network variable in one node can be bound to a corresponding input network variable(s) in other node(s). Changing the value of the output network variable in one node causes the new value to be automatically communicated to the bound input network variable(s) in other node(s). When an input network variable is updated, a nv_update_occurs and the event is posted at the receiving node(s) so that the application program can take action based on the change. A network management node (for example XL15A or XL15C) that explicitly reads and/or writes the network variable can also poll network variables. Network variables can contain one data field (one or two bytes) or multiple data fields (a structure).
Neuron—Refers to the Echelon implements the L
ONWORKS
®
semiconductor device which
®
protocol on a network connected
device such as the T7350H Honeywell controller.
Node—A device implementing layers one through six of the LonTalk
®
protocol including a Neuron® Chip, transceiver,
memory, and support hardware.
Notebook PC—Portable personal computer.
PDA—Personal Digital Assistant. In the case of the T7350
product this is a hand held electronic device operating with the Palm OS. A Honeywell provided PDA application program is used to configure the T7350 thermostat using a direct RS232 connection. Before purchasing a PDA, check the latest Configuration software release note for a list of qualified PDA models. Network connected T7350H models can be configured without a PDA using L
ONSPEC™.
Programmable Controller—A controller that has a variable number of control loops of different types and is user programmed to execute an application. The user can select the number and type of control loops. The user also has the capability of generating new types of control loops. Some examples of Honeywell programmable controllers include the XL15A and XL15B.
Recovery Mode or Recovery Period—The time in unoccupied periods when the temperature control is adjusting the control setpoint so that the space temperature reaches the occupied setpoint when the schedule change occurs.
RIO—Excel 10 Remote Input/Output device.
RTC—Real Time Clock.
Schedule—The structure that defines the occupancy states
and the time of the changes between these states. In the case of the T7350, schedules are organized around a eight day weekly structure including an extra day for designated holidays. Holidays are scheduled by yearly calendar events.
SGPU—Significant Event Notification and Guaranteed Periodic Update.
SGPUC—Significant Event Notification and Guaranteed Periodic Update with Change Field.
SLTA—Serial LonTalk coupled LonTalk
®
Adapter. Adapts the transformer
®
messages to the RS-232 Serial Port.
SNVT—Standard Network Variable Type.
SCPT—Standard Configuration Parameter Type.
XL15A—W7760A Honeywell building level controller.
XL15B—W7760B Honeywell building level controller.
XL15C—W7760C Honeywell plant level controller.

Performance Specifications

IMPORTANT
The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit might not exactly match listed specifications. This product is tested and calibrated under closely controlled conditions; minor performance differences can be expected if those conditions are changed.
Models: See Table 4.
Dimensions: See Fig. 2.
Finish (color): Trident White.
Batteries: No batteries required.
Table 4. T7350 Thermostat Features.
a
b
Humidity, Occupancy, Outdoor, Discharge Air Capability
Features
Model Applications
T7350H1009 Conventional
or
Maximum Stages
b
3 (2)
3 (4)
Heat Pump
T7350H1017 Modulating
2 modulating, 2
c
Humidity, Occupancy,
relay
Outdoor, Discharge Air Capability, 4-20 mA output (2-10 Vdc with 500 ohm resistor)
a
All models are down-selectable and can be configured to control fewer stages than the maximum allowed.
b
Heat pump applications for these models have a maximum of two heat stages and two cool stages.
c
One extra stage (of either heat or cool) can be configured using the auxiliary relay.
5 63-4368
Auxiliary
Relay
Isolated Normally Open
ONWORKS®
L
Capability?Heat Cool
Yes
Yes
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Mounting Means:
Mounts on subbase. Subbase Mounts On:
Wall: Using two 5/8 in. long #6-32 screws (included). Outlet Box: Using sheet metal screws.
Throttling Range for Modulating Outputs:
Automatically adjusts based on heat/cool stages. Manually
adjustable with PDA.
Clock Accuracy (at 77°F [25°C]): ±1 min./month (30 days).
Minimum Stage Operation Time (fixed):
Minimum On
Heat: 1 minutes. Cool: 3 minutes.
Minimum Off (Cool and Heat Pump): 1 minute.
Electrical Ratings:
Power: 24 Vac, 50/60 Hz.; 20 to 30 Vac, 50/60 Hz. Input:
Temperature: 20K ohms. Humidity: 0-10 Vdc. Outdoor: 3000 PTC. Discharge Air: 20K ohms. Occupancy Sensor: Dry contact switching 30 Vdc at 1 mA.
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum. Inrush: 7.5A maximum.
Modulating Output: 4 to 20 mA with 510 ohm maximum
terminating resistance.
System Current Draw (without load):
5 VA maximum at 30 Vac, 50/60 Hz.
NOTE: Relays are N.O. Single-Pole, Single-Throw (SPST).
Outdoor Sensor Wiring: Requires 18 gauge wire.
Humidity Ratings: 5% to 90% RH, noncondensing.
Emergency Heat Indication:
Display indicates when Emergency Heat is activated (Em).
Temperature:
Ratings:
Operating Ambient: 30°F to 110°F (-1°C to 43°C).
Shipping: -30°F to +150°F (-34°C to +66°C). Display Accuracy: ±1°F (±1°C). Setpoint:
Range:
Heating: 40°F to 90°F (4°C to 32°C).
Cooling: 45°F to 99°F (7°C to 37°C). Deadband: 2°F (1°C). Default Settings: See Table 5.
Loss of Power: The thermostat maintains programmed times
and temperatures for the life of the product. Clock and day information is retained for a minimum of 48 hours.
NOTE: To achieve the 48-hour power-loss clock retention,
the T7350 must be powered for at least 5 minutes.
Communicating Model T7350H:
Connection Terminals for the L
ONWORKS
®
Bus.
Network jack for quick access by personal computer based
tools. Communications service-pin pushbutton to simplify startup. L
ONMARK
ONMARK
L L
ONMARK ONMARK
L Honeywell L
®
Controller.
Functional Profile: 8500_20 Space Comfort
®
SCC Object Type: 8504 Rooftop See Fig. 3.
®
Program Identifier: 80:00:0C:55:04:03:04:2E.
®
Application Interoperability: version 3.3
ONMARK
®
Plug-In file downloads:
http://plugin.ge51.honeywell.de/index.htm#
PDA System Requirements:
Palm OS: 3.5.x to 5.2.1 Dynamic Heap: 256K bytes. Free RAM Space: 1000K bytes. Serial Communications: RS232.
Approvals:
European Community Mark (CE) Listed. UL 873 Recognized, NEC Class 2. FCC Part 15 subpart J Class A. cUL.
Table 5. Default Setpoints.
Not
Control Occupied
Occupied Standby
Heating 70°F (21°C) 55°F (13°C) 67°F (19°C)
Cooling 75°F (24°C) 85°F (29°C) 78°F (26°C)
Accessories:
Duct Discharge Air Sensors: C7041B (6 or 12 in.),
C7041C (18 in.), C7041J (12 ft averaging),
C7770A (8 in. probe). Outdoor Air Sensors: C7089A, C7170A,
C7031G2014 (weatherproof). Temperature Sensors (Remote): C7772A, T7770A1006,
T7770B1046, T7770C1044, T7770D1000, T7771. Economizer Logic Modules: W6210, W6215, W7210, W7212,
W7215, W7459. Humidity Sensors: H7625A,B; H7635A,B,C, H7655B. PDA Units: Palm™ V, M125, and i705 handhelds;
TRGPro™ handheld; ZIRE™ 71 handheld;
TUNGSTEN™ T handheld. Others:
209541B FTT network termination module.
209651A Vertical Mounting Hardware Wallplate Adapter
(Trident white). 50000083-001 Thermostat Interface Module (TIM). 50000452-001 Troubleshooting Cable. AK3797 Single pair network cable plenum rated,
U.L. Type CMP. AK3798 Single pair network cable, U.L. Type CMR. AK3799 Double pair network cable plenum rated,
U.L. Type CMP. Q7740A FTT network 2-way repeater. Q7740B FTT network 4-way repeater. TG511, TG512 Universal Versaguard™ Thermostat
guards.
63-4368 6
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
2-3/16 (56)
2-1/32
(52)
2-1/32
(52)
1-9/16
(40)
4-1/16
(104)
M22432
4-1/2 (114)
SUBBASE
1-5/8
(42)
6-3/4 (171)
2-3/8 (60)
3-1/4 (83)
6-9/16 (166)
1-5/8
(42)
Fig. 2. Dimensions of thermostat and subbase in in. (mm).

Communications

The T7350H provides networking capability in a LONWORKS® system using a Free Topology Transceiver (FTT) transformer­coupled communications port running at 78 kilobits per second (kbs). The transformer-coupled communications interface offers a much higher degree of common-mode noise rejection while ensuring dc isolation. L
ONWORKS
networks are very flexible and convenient to install and maintain, but it is imperative that the network layout be carefully planned and accurate documentation created and maintained. This aids in compliance verification and future expansion of the network. It also minimizes unknown or inaccurate wire run lengths, node-to-node (device-to-device) distances, node counts, total wire length, inaccurate repeater/ router locations, and misplaced or missing terminations. L
ONWORKS
®
networks can be configured in a variety of ways; refer to the E-Bus FTT Network Wiring Guidelines, form 74­2865, for a complete description of network topology rules and maximum network wire length. If longer runs are required, add a Q7740A 2-way or Q7740B 4-way repeater to extend the L
ONWORKS
on LCBS L types for L
®
Bus length. Q7751A routers are not supported
ONSPEC™ configured systems. Approved cable
ONWORKS
®
Bus communications wiring are Level IV, 22 AWG (0.34 sq mm) plenum or non-plenum rated unshielded, twisted pair, solid or stranded conductor wire. Refer to Table 2 for a list of Honeywell network cable part numbers. Other Echelon® approved cable may also be used. Run communications wiring in a conduit, if needed, with non­switched 24 Vac or sensor wiring. The Free Topology Transceiver (FTT) communications L
ONWORKS
a polarity insensitive, free topology wiring scheme that, in turn, supports star, loop, and/or bus wiring.
®
FTT
®
Bus supports
7 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

LONMARK® Functional Profile

Hardware OutputHardware Output
nviRequest
nv1
SNVT_obj_request
nviTimeSet
nv3
SNVT_ time_stamp
nviFileReq
nv5
SNVT_file_req
nviFilePos
nv7
SNVT_file_pos
nc1 - nciDeviceName nc2 - nciApplVer
nviInUse
nv9
UNVT_inUse
nviPgm
nv10
UNVT_pgmIn
Node
Object
Mandatory Network
nvoStatus
nv2
SNVT_ obj_status
Variables
nvoFileStat
nv6
SNVT_file_status
Optional Network Variables
Configuration Properties
UCPTdevName UCPTapplVer
Manufacturer
(manf specific) (manf specific)
nv11
nv12
nv13
Defined Section
nv14
nv15
nv16
nv17
nv18
nroT7350Ver UNVT_version
nroPgmVer UNVT_pgmId
nvoPgm UNVT_pgmOut
nvoTime SNVT_time_stamp
nvoAlarmH UNVT_alarm
nvoAlarmStatus UNVT_alarmStatus
nvoAlarmLog UNVT_alarmLog
nvoError UNVT_error
nviSpaceTemp
nv1
SNVT_temp_p
nviSetpoint
nv2
SNVT_ temp_p
nviOccSchedule
nv5
SNVT_tod_event
nviOccManCmd
nv6
SNVT_occupancy
nviOccSensor
nv7
SNVT_occupancy
nviApplicMode
nv8
SNVT_hvacMode
nviOutdoorTemp
nv19
SNVT_Temp_p
nviSpaceRH
nv20
SNVT_lev_percent
nc1 - nciSndHrtBt nc4 - nciRevHrtBt nc2 - nciSetpoints nc6 - nciBypassTime nciConfig nciConfigPts nciDayLghtSav nciDaySchedule0 nciDaySchedule1 nciDaySchedule2 nciDaySchedule3 nciDaySchedule4 nciDaySchedule5 nciDaySchedule6 nciDaySchedule7 nciHolSched
SCC-Rooftop
Object Number 8504.
nvoSpaceTemp
Mandatory Network Variables
Optional Network Variables
nv26
SNVT_ temp_p
nvoUnitStatus
nv27
SNVT_hvac_status
nvoEffectSetpt
nv28
SNVT_temp_p
nvoEffectOccup
nv29
SNVT_occupancy
nvoHeatCool
nv30
SNVT_hvac_mode
nvoDischAirTemp
nv34
SNVT_temp_p
nvoTerminalLoad
nv37
SNVT_lev_percent
nvoSpaceRH
nv43
SNVT_lev_percent
nvoOutdoorTemp
nv45
SNVT_temp_p
Configuration Properties
SNVT_time_sec SNVT_time_sec SNVT_temp_setpt SNVT_time_min UCPTconfig UCPTconfigPts UCPTdaylightSav UCPTschedule0 UCPTschedule1 UCPTschedule2 UCPTschedule3 UCPTschedule4 UCPTschedule5 UCPTschedule6 UCPTschedule7 UCPTholSched
(mandatory)
(mandatory)
(manf specific) (manf specific) (manf specific) (manf specific) (manf specific) (manf specific) (manf specific) (manf specific) (manf specific) (manf specific) (manf specific) (manf specific)
(optional)
(optional)
Hardware Input
Fig. 3. T7350H LONMARK® Space Comfort Controller Rooftop Object (8504) with Node Object.
63-4368 8
nviBypass
nv30
SNVT_switch
nviFanAuto
nv31
SNVT_switch
nviManValue
nv32
UNVT_manValue
nviDlcShed
nv34
UNVT_dlcShed
Manufacturer
Defined Section
Hardware Input
nvoBypass
nv43
SNVT_switch
nvoOccSchedule
nv44
SNVT_tod_event
nvoOccSensor
nv45
SNVT_occupancy
nvoData1
nv46
UNVT_data1
nvoData2
nv47
UNVT_data2
M22431
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

NETWORK CONFIGURATIONS

The T7350H can be configured to perform a variety of activities in which data is sent to and/or received from other nodes on the L
ONWORKS
shared with other network devices includes: — Current year, month, day, hour, minute, second. — System mode (HEAT, COOL, AUTO, OFF, EM HEAT). — Current fan setting (ON, AUTO). — Space temperature. — Space relative humidity. — Discharge air temperature. — Outdoor air temperature. — Occupancy sensor status. — Terminal load. — Current setpoint. — Occupied/Unoccupied schedule commands. — Current occupancy status. — Occupancy schedule including current occupancy state,
next state and time in minutes until next scheduled
change of occupancy state. — Relay status (heat/cool stages and fan). — Alarm status. — Alarm log including the last five alarms. — Device Error status. — Bypass state (multiple XL10 devices follow the bypass
operation of a master device).
A network configuration tool is used to configure the T7350H Thermostats and other nodes with which the T7350H interacts. The following is a brief description of the configurable features that can be commanded over the network:
•Time Master:
When a T7350H is designated as the network time master, the current time of day and date is synchronized across the network every minute. The L Screen can be used to configure a T7350H as the Network Time Master. Whenever the time of day or date of the time master is changed, it automatically adjusts all the other network devices (T7350H, Q7300 & XL15A) bound to the time master. When a T7350H is controlled by a time master, the local day light saving schedule is disabled. The Day Light Saving option on all time master recipients should be disabled. This prevents erroneous time changes (local daylight savings switchover) during temporary network outages.
Source Destination
T7350H.nvoTime or XL15a.nvoTimeOut Q7300.nvoTime
®
network. Information that can be
ONSPEC™ T7350H General
T7350H.nviTimeSet or XL15a.nviTimeIn Q7300.nviTime
the user is not prevented from making local schedule changes at the recipient thermostat. Local schedule changes (at a recipient device) have no effect on the scheduling commands received from the master device. When a T7350H is designated as a master schedule device, it sends its schedule information (current state, next state, time until next change of state) to the appropriate T7350H(s) which, in turn, overrides any existing internal time schedule. The T7350H Thermostat can provide master scheduling information to multiple Excel 10 devices. One T7350H shares the schedule information (current state, next state, time until next change of state) with the designated Excel 10 devices.
Source Destination
T7350H.nvoOccSchedule or XL15a.nvoTodEventCmd[i] Q7300.nvoOccSchedulei
T7350H.nviOccSchedule or XL10.nviTodEvent XL15c.nviTodEventIn[i]
• System Mode Settings: System mode settings (HEAT, COOL, AUTO, OFF, EM HEAT) can be commanded by a remote T7350H or other compatible XL10 device. A one to many network binding can be used to command multiple devices from a single unit. In addition, a network connected Workstation can be used to change the System Mode.
Command Source Command Destination
T7350H.nvoHeatCool
T7350H.nviApplicMode
or Workstation
• Fan Settings: Fan settings (ON, AUTO) can be changed from a network connected Workstation.
Source Destination
Workstation
T7350H.nviFanAuto
or Network Tool
• Outdoor Air Temperature Sharing: If a valid outdoor air temperature value is received at the T7350H OAT network variable input, that value will be used in the T7350H. The local OAT sensor of the T7350H is ignored until the network sensor fails.
Source Destination
T7350H.nviOutdoorTemp or XL10.nvoOdTemp XL15c.nvoOdTemp
T7350H.nvoOutdoorTemp or XL10.nviOdTemp XL15c.nviOdTemp
• Time Schedule: The occupancy schedule used by a T7350H may reside locally in that device or remotely in another schedule device (T7350H, XL15a, XL15b or T7300/Q7300). Local schedules can be created and modified using the T7350H keypad, a direct connected PDA, a network connected configuration tool (L
ONSPEC™) or Command Display.
External schedules can also be modified using the keypad of the master schedule device, or with a network connected configuration tool or Workstation. When a T7350H receives scheduling information over the network,
• Discharge Air Temperature Sharing: The discharge air temperature value can be shared with other devices on the network. Note that the T7350H does not accept a network discharge air temperature input.
Source Destination
T7350H.nvoDischAirTemp XL15c.nviDATemp
• Space Temperature Sharing: If a valid space temperature value is received at the T7350H Space Temperature network variable input, that
9 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
value will be used in the T7350H as the primary controlled variable. The local space temperature sensor of the T7350H is ignored until the network sensor fails.
Source Destination
T7350H.nvoSpaceTemp or XL10.nvoSpaceTemp
• Space Humidity Sharing: If a valid humidity value is received at the T7350H Space Humidity network variable input, that value will be used in the T7350H as the humidity control variable. The local space humidity sensor of the T7350H is ignored until the network sensor fails.
Source Destination
T7350H.nvoSpaceRH T7350H.nviSpaceRH
• Current Setpoint Sharing: If a valid setpoint value is received at T7350H nviSetpoint, that value will be used by the T7350H as the center setpoint. The heat and cool setpoints are then calculated from this value and are used in the T7350H as the occupied setpoints. During unoccupied periods, nviSetpoint is ignored.
Source Destination
T7350H.nvoEffectSetpt or XL10.nvoEffectSetpt
T7350H.nviSpaceTemp
or XL15c.nviRARH
T7350H.nviSetpoint
• Occupancy Bypass: Any internal or external scheduled unoccupied state in the T7350H is overridden by a network occupancy bypass command. Bypass is a method to command unoccupied override over the network from another controller (typically a T7350H or XL10). The source controller manages the bypass timing.
Source Destination
T7350H.nvoBypass or XL10.nvoBypass XL15a.nvoBypass[i] XL15c.nvoBypass[i]
• Manual occupancy: Provides a method to command the occupancy state from a network workstation. Effective occupancy override works on a “last in wins” basis. That is, the last occupancy override command received from any source determines the override state. The workstation can command occupied, unoccupied, standby, bypass, or not active (null). There are several ways to return the device to normal schedule operation.
1. Power failure reset at the T7350H.
2. Workstation issues a “not active” (null) network com-
mand to T7350H.nviOccManCmd.
3. User activates “Temporary Occupied” button on the
local keyboard. This can be followed by a “Run Sched­ule” local command.
4. If manual occupancy is commanded to bypass and the
bypass timer times out.
T7350H.nviBypass
• Occupancy Sensor Sharing: If a valid value is received at the T7350H occupancy sensor network variable input, that value will be used in the T7350H as the occupancy sensor. The local T7350H occupancy sensor is ignored until the network sensor fails.
Source Destination
T7350H.nvoOccSensor or XL10.nvoSensorOcc NetworkSensor
NOTE: The occupancy or motion sensor is active whenever
The T7350H effective occupancy is determined in Table 6.
Occupied Open Standby
Occupied Closed Occupied
Standby NA Standby
Unoccupied NA Unoccupied
the device is scheduled “Occupied” and a remote or network occupancy sensor is configured.
Table 6. T7350H Effective Occupancy.
Schedule
Occupancy
Occupancy/Motion
Sensor Contact
T7350H.nviOccSensor
Effective
Occupancy
Source Destination
Workstation Command Display XL15b
T7350H.nviOccManCmd

APPLICATION STEPS

Overview

The application steps shown in Table 7 are guidelines for configuring the T7350H in a L explain the network role of the T7350H.
Table 7. Application Steps.
Step Description
1 Plan the system.
2 Determine required network devices.
3 Lay out communications and power wiring.
4 Prepare wiring diagrams.
5 Order equipment.
6 Configure T7350.
7 Troubleshooting.
ONWORKS
®
Bus network and
63-4368 10
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Refer to the Light Commercial Building Solution System Communication Guide form 71-3123 and the E-Bus Wiring Guidelines, form 74-2865 for a complete description of network topology rules. Prepare Wiring Diagrams, for wiring details. Plan to configure each controller. Refer to the Excel L
ONSPEC™ User Guide, form 74-2937, to configure the
T7350H, XL15 and XL10 Controllers.

Step 1. Plan the System

Plan the use of the T7350H Thermostat according to the job requirements. Determine the location and functionality of each device. Verify the sales estimate for the number of other controllers and devices required. Check the number and type of other required accessories. When planning the system layout, consider potential expansion possibilities for future growth. Planning is very important if HVAC systems and controllers are to be added in future projects.
NOTEBOOK PC
SHIELDED
RS-232 SERIAL PORT
INTERFACE CABLE
Q7760 SLTA
CABLE PART NO. 205979
LonWorks BUS PORT
T7350H

Step 2. Determine Required Network Devices

A maximum of 60 nodes can communicate on a single L
ONWORKS
comprises one node. If more than 60 nodes are needed, a Q7751A Router or Q7740 Repeater is necessary. A router or repeater allows up to 120 controller nodes per network, divided between two L that routers are not supported by the LCBS L system configuration tool. Refer to the Light Commercial Building Solution System Communication Guide form 71-3123 for LCBS details. Refer to the E-Bus Wiring Guidelines, form 74-2865, for a complete description of network topology rules and maximum wire lengths. A 209541B Termination Module may be required. Refer to the Excel 10 FTT Termination Module Installation Instructions form, 95-7554.
®
Bus segment. Each LONWORKS® Bus device
ONWORKS
®
Bus segments. Please note
ONSPEC

Step 3. Layout Communications and Power Wiring:

L
ONWORKS
The communications LONWORKS® Bus, is a 78-kilobit network that uses transformer isolation and differential Manchester encoding. The Free Topology Transceiver (FTT) LONWORKS® communications Bus supports a polarity insensitive, free topology wiring scheme, refer to the E-Bus Wiring Guidelines form, 74-2865, for a complete description of L network topology rules. Fig. 5 shows T7350H devices connected in a typical free topology L
®
Bus Layout
ONWORKS
ONWORKS
®
network.
®
M22492
Fig. 4. Connecting personal computer to LonWorks® bus.
NOTEBOOK PC
T7350H
RS-232
SLTA
MODEM
T7350H
MODEM
RS-232
SLTA
T7350H T7350H
LonWorks BUS
MODEM
T7350H T7350H
LonWorks BUS
RS-232
SLTA
T7350H
T7350H
LonWorks BUS
T7350H
T7770 WITH NO LonWorks BUS ACCESS
T7770
LonWorks BUS
I/O CONNECTIONS
JACK FOR OPERATOR TERMINAL
Fig. 5. Typical topology for T7350 devices in LONWORKS® network.
11 63-4368
M22493
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

Cable Termination

The FTT network segment requires termination for proper data transmission performance. Use a 209541B Termination Module to connect two of the three termination module wires to the L
ONWORKS
Wiring Guidelines form 74-2865 for details.
®
Bus terminals. Refer to LONWORKS® Bus
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
Singly Terminated Network Segment
In a singly terminated topology segment, only one termination is required and can be placed anywhere on the segment. Singly terminated segments use the yellow and brown wires. If the network topology requires a singly terminated termination module at a T7350H, connect the singly terminated module wiring on the appropriate terminals as shown in Fig. 6.
SUBBASE
BROWN
ORANGE
T5 T6 T7 T4
EB
YELLOW
T3
OSOS ASAS
M
MHC HPHSEB
X
PART NO. 209541B TERMINATION MODULE
W3/Y4 Y3 W2
AUX
RC
AUXRH
Y2
W1 GY1
M22494
Fig. 6. Singly terminated LonWorks® bus termination
module.
Doubly Terminated Daisy-Chain Network Segment
In a doubly terminated daisy-chained topology segment, two terminations are required, one at each end of the topology segment. Doubly terminated segments use the orange and brown wires. If the network topology requires a doubly terminated module at a T7350H (T7350H is the first or last device on the network cable) connect the termination module wiring on the appropriate terminals as shown in Fig. 7. For additional wiring information, refer to the E-Bus Wiring Guidelines, form 74-2865, and the Excel 10 FTT Termination Module Installation Instructions, form 95-7554.
SUBBASE
T5 T6 T7 T4
T3
OSOS ASAS
W3/Y4 Y3 W2
AUX
Y2
IMPORTANT
All wiring must agree with applicable codes, ordi­nances and regulations.
1. Loosen subbase terminal screws and connect system
wires.
NOTE: Maximum (and recommended) wire size is 18-
gauge. Do not use wire smaller than 22-gauge. Fol­low equipment manufacturer wiring instructions when available. Refer to the Wiring Diagram section for typical hookups. A letter code is located near each terminal for identification. Refer to the Specifi­cations section, Tables 8 and 9 for terminal designa­tions.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole in the wall.
4. Plug the hole with nonflammable insulation to prevent
drafts from affecting the thermostat.

Wiring Details

LONWORKS® network cable should be wired separately from the power and I/O wires when installing T7350H models. If this is not possible, use a minimum of 4 in. (102 mm) separation between split ferrite cores (Fair-Rite 0443164151, www.fair-rite.com) to ensure compliance with Class B limits (does not apply to Class A limits). See Fig. 8 to apply ferrite cores to L
ONWORKS
®
Bus input and output.

Step 4. Prepare Wiring Diagrams

Fig. 9 through 12 show T7350 terminal arrangements and provide detailed wiring diagrams. Reference these diagrams to prepare the site-specific job drawings.
1.
WIRES TO T7300H COMMUNICATING SUBBASE
RC
W1 GY1
AUXRH
M22495
®
bus termination
BROWN
YELLOW
EB
ORANGE
M
PART NO. 209541B TERMINATION MODULE
Fig. 7. Doubly terminated L
MHC HPHSEB
X
ONWORKS
modules.
63-4368 12
M22496
WIRES TO ALL INPUTS AND OUTPUTS
2.
WIRES TO T7300H COMMUNICATING SUBBASE
Fig. 8. Ferrite core wires from T7350H to L
inputs and outputs.
WIRES TO ALL INPUTS AND OUTPUTS
ONWORKS
®
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
DISCHARGE AIR SENSOR
OSOS ASAS
MHC HPHSEB
4
ECONOMIZER
X
3
HEAT RELAY 3
AUX
W3/Y4 Y3 W2
AUXRH
RC
HEAT RELAY 2
W1 G
Y1
HEAT RELAY 1
COMPRESSOR CONTACTOR 1
COMPRESSOR CONTACTOR 2
Y2
COMPRESSOR CONTACTOR 3
FAN RELAY
M22499
LONWORKS
BUS
LONWORKS
BUS
OUTDOOR
123456789
T3
AIR SENSOR
M
MOTION SENSOR
T7770 REMOTE SENSOR
SUBBASE
T5 T6 T7 T4
EB
®
®
L2
2
1
L1
(HOT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
2
3
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
HUMIDITY SENSOR
Fig. 9. Typical hookup of T7350H1009 in three-stage heat and three-stage cool conventional system with one
transformer.
LONWORKS
BUS
LONWORKS
BUS
2
1
OUTDOOR
T7770 REMOTE SENSOR
SUBBASE
T5 T6 T7 T4
EB
®
®
L2
L1
(HOT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
2
3
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
L2
L1
(HOT)
HUMIDITY SENSOR
AIR SENSOR
123456789
T3
M
MOTION SENSOR
AUXILIARY TRANSFORMER
DISCHARGE AIR SENSOR
OSOS ASAS
MHC HPHSEB
X
HEAT RELAY 3
AUX
W3/Y4 Y3 W2
AUXRH
RC
3
4
ECONOMIZER
HEAT RELAY 2
W1 G
Y1
HEAT RELAY 1
COMPRESSOR CONTACTOR 1
COMPRESSOR CONTACTOR 2
Y2
COMPRESSOR CONTACTOR 3
FAN RELAY
M22497
Fig. 10. Typical hookup of T7350H1009 with auxiliary transformer.
13 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
LONWORKS
BUS
LONWORKS
BUS
1
OUTDOOR
123456789
T3
AIR SENSOR
M
MOTION SENSOR
DISCHARGE AIR SENSOR
OSOS AS AXAS
MHC HPHSEB
RCX
2
MODULATING
HEAT
(4-20 mA)
+
AC
AH
W1 G
AUXRH
HEAT RELAY 1
3
ECONOMIZER
T7770 REMOTE SENSOR
SUBBASE
T5 T6 T7 T4
EB
®
®
L2
L1
(HOT)
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
2
3
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
HUMIDITY SENSOR
MODULATING
+
R
X
AUX
Y1
FAN RELAY
COMPRESSOR CONTACTOR 1
(4-20 mA)
COOL
R
X
COOLING
TRANSFORMER
L2
L1
(HOT)
M22498
1
Fig. 11. Typical hookup of T7350H1017 for system with two independent heat stages (one modulating), two independent
cool stages (one modulating), and two transformers.
OUTDOOR
T7770 REMOTE SENSOR
SUBBASE
T5 T6 T7 T4
HS
®
LONWORKS
BUS
®
ONWORKS
L
BUS
L2
1
L1
(HOT)
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
2
3
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
L2
L1
(HOT)
HUMIDITY SENSOR
AIR SENSOR
123456789
T3
M
MOTION SENSOR
AUXILIARY TRANSFORMER
DISCHARGE AIR SENSOR
OSOS AS MXAS
MHC HP
RCX
2
ECONOMIZER
MODULATING
(4-20 mA)
+
MC
MH
W1 G
AUXRH
HEAT RELAY 1
3
R
HEAT
X
Y1
COMPRESSOR CONTACTOR 1
FAN RELAY
MODULATING
(4-20 mA)
+
AUX
COOL
R
X
L2
1
L1
COOLING
TRANSFORMER
(HOT)
M22491
Fig. 12. Typical hookup of T7350H1017 for system with two independent heat stages (one modulating), two independent
cool stages (one modulating), and three transformers.
63-4368 14

General Considerations

Table 8 lists wiring types, sizes and distances for the T7350 and Excel 10 products. The T7350 terminal strip accepts 18 through 22 AWG (0.82 to 0.34 sq. mm) wire.
Table 8. Field Wiring Reference.
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Wire Function
Digital Outputs: W Y G AUX X
Modulating Outputs: MX MH MC
Remote Humidity Sensor: HS HC HP
Discharge Air Temperature Sensor: AS
Outdoor Air Temperature Sensor: OS
Motion Sensor: M
Wall Module connections: T3-T7
Power Wiring to: X RH RC
ONWORKS
L
®
Bus
(Non-Plenum).
LONWORKS® Bus (Plenum Rated).
Recommended Wire
Size (Minimum)
18 AWG (0.82 sq mm) five wire cable bundle.
Specification or
Requirement
Standard thermostat wire.
Honeywell Part
Number Distance (Maximum)
AK3726 1000 feet.
18 AWG (0.82 sq mm) 1 pair per output. AK3757C, AK3744C,
AK3741A, AK3702x
18 to 22 AWG (0.82 to 0.34 sq mm)
18 to 22 AWG (0.82 to 0.34 sq mm)
3 wires. AK3746C, AK3724,
AK3703x
1 pair. AK4606ABE,
AK4628AWH, AK3702x, AK3741A, AK3744C, AK3757C
18 AWG (0.82 sq mm) 1 pair. AK3757C, AK3744C,
AK3741A, AK3702x
18 to 22 AWG (0.82 to 0.34 sq mm)
1 pair. AK4606ABE,
AK4628AWH, AK3702x, AK3741A, AK3744C, AK3757C
18 to 22 AWG (0.82 to 0.34 sq mm)
Twisted pair wire is recommended for wire runs longer than 100 ft. The number of pairs depends on the model
AK4606ABE, AK4628AWH, AK3702x, AK3741A, AK3744C, AK3757C,
AK3726 and functions selected.
18 to 14 (0.82 to 2.0 sq mm) use heavier wire for
1
AWG
NEC Class II, 140°F (60°C) rating.
AK3702x, AK3741A,
AK3744C, AK3757C,
AK3712x, AK3754
longer runs.
22 AWG (0.34 sq mm)
Nema Level IV U.L. Type CMR
AK3798 (1 pair) Refer to E-bus Wiring
Twisted pair stranded conductor, nonshielded.
22 AWG (0.34 sq mm)
Nema Level IV U.L. Type CMP
AK3797 (1 pair)
AK3799 (2 pair) Twisted pair stranded conductor, nonshielded.
1000 feet.
500 feet.
1000 feet.
500 feet.
1000 feet.
1000 feet.
Limited by line-loss effects on power consumption.
Guidelines Users Guide 74-2865 for maximum length and generic cable specifications.
NOTE: 1. The X, RH and RC terminals will accept 14 to 22 AWG. 14 and 16 AWG should be avoided since the stiff cable
interferes with the cover to subbase installation.
15 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 9. Honeywell Cable Details.
Honeywell Part
Number Size (AWG) Number of wires Jacket Plenum Rated Description
AK3798 22 2 Yes No E-bus cable.
AK3797 22 2 Yes Yes E-bus cable.
AK3799 22 4 Yes Yes E-bus cable.
AK4606ABE 22 2 Yes No Beige jacket.
AK4628AWH 22 2 Yes Yes White jacket.
AK3702x 18 2 No No
AK3741A 18 2 Yes No
AK3744C 18 2 Yes Yes Red jacket.
AK3757C 18 2 Yes Yes White jacket.
AK3703x 18 3 No No
AK3724 18 3 Yes No Tan jacket.
AK3746C 18 3 Yes Yes Tan jacket.
AK3726 18 5 Yes No Tan jacket.
AK3712x 16 2 No No TFN
AK3754 14 2 No No TFN
63-4368 16
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

Step 5. Order Equipment

After compiling a bill of materials through completion of the previous application steps, refer to Table 10, Ordering Information.
Table 10. Ordering Information.
Part Number Product Description Comments
T7350H1009 Communicating Thermostat with three heating and
three cooling digital outputs.
T7350H1017 Communicating Thermostat with two modulating
outputs, one heating and one cooling digital output.
T7771A Remote Temperature Sensor. • Pushbutton setpoint adjustment with LED indicators.
T7770A1006 Remote Wall Module. • Basic model with room temperature sensor.
T7770B1046 Remote Wall Module. • ± setpoint change.
T7770C1044 Remote Wall Module. • ± setpoint change.
T7770D1000 Remote Wall Module. • OCC button and LED.
AK3798 L
AK3797 L
AK3799 L
ONWORKS
ONWORKS
ONWORKS
®
Bus (Non-Plenum), 1 pair.
®
Bus (Plenum rated), 1 pair.
®
Bus (Plenum rated), 2 pair.
209541B FTT Network Termination Module.
H7625
Remote Humidity Sensors
H7635
C7089A
Outdoor Air Sensors. — C7170A, C7031G2014
Duct Discharge Air Sensors: C7041B C7041C C7041J C7770A
50000452-
6 inch probe.
18 inch probe.
150 inch averaging.
6 inch probe.
Troubleshooting Cable. One Troubleshooting Cable required for each 001
50000083-
Thermostat Interface Module (TIM). One TIM required for each installation technician. Note 001
PDA Qualified Palm OS PDA. One PDA required for each installation technician.
50000314-
PDA Configuration Software. One Configuration software package can be used to 001
• Optional heat pump control.
• Isolated auxiliary digital output.
• Isolated auxiliary digital output.
• Occupied/unoccupied override (bypass) with LED.
•L
ONWORKS
®
Bus jack.
• OCC button and LED.
installation technician.
that a network tool such as L
ONSPEC™ eliminates the
need for a TIM.
Refer to the PDA Configuration Software for an up-to­date list of qualified PDA hardware. Note that a network tool such as L
ONSPEC™ eliminates the need for a PDA.
program multiple PDAs. Note that a network tool such
ONSPEC™ eliminates the need for a PDA.
as L

Step 6. Configure T7350

Use Excel LONSPEC™ Software to configure the T7350H Thermostat for specific applications. The Excel L User’s Guide, form 74-2937, provides software operation instructions for this personal computer based application.
ONSPEC
17 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

Step 7. Troubleshooting

Table 11. Troubleshooting Information.
Symptom Possible Cause Action
Display will not come on.
Temperature display is incorrect.
Temperature settings will not change. (Example: Cannot set heating higher or cooling lower.)
Room temperature is out of control.
Heat will not come on.
Thermostat is not being powered. Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and RH terminals. If missing 24 Vac:
Check if circuit breaker is tripped; if so, reset circuit breaker.
Check if system fuse is blown; if so, replace fuse.
Check if the HVAC equipment power switch is in the Off position; if
so, set to the On position.
Check wiring between thermostat and HVAC equipment. Replace
broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
Room temperature display has been recalibrated.
Thermostat is configured for °F or °C
Use PDA or L
ONSPEC™ configuration software to recalibrate as
desired.
Press both Run Schedule and Copy, then reconfigure the display.
display.
Bad thermostat location. Relocate the thermostat.
Display shows three dashes and a degree sign (all systems shut down).
Upper or lower temperature limits were reached.
T7350 is set for remote sensing and sensor is missing or circuit is either open or shorted.
Check the temperature setpoints:
Heating limits are 40 to 90°F (7 to 31°C)
Cooling limits are 45 to 99°F (9 to 37°C)
Occupied setpoint temperature range stops were configured.
Keypad is locked. When a locked key is pressed, LOCKED appears momentarily on the LCD.
Remote temperature sensing is not
Using a PDA or L
ONSPEC™, check setpoint stops. If necessary,
reconfigure the stop(s).
Use PDA or L
ONSPEC™ (Set, Display) to unlock keypad.
Press both Run Schedule and Copy, then change keypad lock
level.
Check all remote sensors.
working.
No power to the thermostat. Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and RH terminals. If missing 24 Vac:
Check if circuit breaker is tripped; if so, reset circuit breaker.
Check if system fuse is blown; if so, replace fuse.
Check if the HVAC equipment power switch is in the Off position; if
so, set to the On position.
Check wiring between thermostat and HVAC equipment. Replace
broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
Thermostat minimum off time is activated.
System selection is set to Off or
Wait up to five minutes for the system to respond.
Use PDA or L
ONSPEC™ to configure heating response.
Set system selection to Heat or Auto.
Cool.
63-4368 18
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 11. Troubleshooting Information. (Continued)
Symptom Possible Cause Action
Cooling will not come on.
No power to the thermostat. Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and RH terminals. If missing 24 Vac:
Check if circuit breaker is tripped; if so, reset circuit breaker.
Check if system fuse is blown; if so, replace fuse.
Check if the HVAC equipment power switch is in the Off position; if
so, set to the On position.
Check wiring between thermostat and HVAC equipment. Replace
broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
Thermostat minimum off time is activated.
System selection is set to Off or
Wait up to five minutes for the system to respond.
Use PDA or L
ONSPEC™ to configure cooling response.
Set system selection to Cool or Auto.
Heat.
System indicator (flame: heat, snowflake: cool) is displayed, but no warm or cool air is coming from the registers.
The call for heat or cool is not yet given.
Conventional heating equipment turns the fan on only after the
Check if any stage indicators (dots next to the system indicator) are displayed. With no display of stage indicators, no call for cool/heat is yet given. For the modulating T7350H1017 only: Check the information screens. MODHEAT or MODCOOL percentages of zero and 100 indicate an extreme signal from the given terminal.
Wait one minute after seeing the on indicator and then check the registers.
furnace has warmed to a setpoint.
Heating or cooling equipment is not
Verify operation of heating or cooling equipment in self-test.
operating.
19 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

APPENDIX A - NETWORK TOOLS & WORKSTATIONS

Table 12. T7350H Operational Support.
Network Tools & Workstations
T7350H Operational Support
Device Configuration X X X
View & Modify Weekly Schedule X X X X X
View & Modify Holiday Schedule X X X X X
Data Monitoring XXXXXX
Command Outputs to Manual Value X X X X
Override System Delays X X X X
Room Temperature Calibration X X X
Command Occupancy Override XXXXXX
Command Fan Operation (On Auto) X X X X
Command System Mode (off, auto, heat, cool) X X X X
View & Modify Temperature Setpoints XXXXXX
Report T7350 alarm data XXXX
Network Time Scheduler for T7350 Devices X
Generate Trend & Log files with T7350 data X
User defined T7350 analog & digital alarms X
Update T7350 Time Clock XXXXXX
Set T7350 as network Time Master X
View T7350 Cover Firmware Version X X X
Update T7350 Cover Firmware X
View T7350H SubBase Firmware Version X X X
Update T7350H SubBase Firmware X
Summary of
LONSPEC
LONSTATION
XL15B
W7760B -
Cmd Display -
CARE
S7760
LNS Plugin
DataMon
63-4368 20
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

APPENDIX B - NETWORK ALARM REPORTING

Table 13. T7350H Alarm Change of State Event.
A T7350H alarm change of state event is reported by the manufacturer defined output network variable nvoAlarmH.
nvoAlarmH Field Description
subnet
The L
ONWORKS
bound, it reports domain index 0.
0: Invalid subnet (power up value) 1-255: Subnet number
node
The L
ONWORKS
bound, it reports domain index 0.
0: Invalid entry (power up value) 1-127: Node number
type The alarm type being issued.
0: AT_NO_ALARM (power up value) 1: AT_INVALID_SUBBASE_TYPE 2: AT_NETWORK_COMM_FAIL 3: AT_SENSOR_FAIL 4: AT_INVALID_IO_CONFIG 5: AT_COVER_COMM_FAIL 6: AT_COVER_SUBBASE_MISMATCH
Return to Normal Codes
-127: AT_rtnINVALID_SUBBASE_TYPE
-126: AT_rtnNETWORK_COMM_FAIL
-125: AT_rtnSENSOR_FAIL
-124: AT_rtnINVALID_IO_CONFIG
-123: AT_rtnCOVER_COMM_FAIL
-122: AT_rtnCOVER_SUBBASE_MISMATCH
-1: AT_ALARM_NOTIFY_DISABLED
®
subnet number in the domain entry to which nvoAlarmH is bound. If nvoAlarmH is not
®
node number in the domain entry to which nvoAlarmH is bound. If nvoAlarmH is not
Table 14. T7350 Current Alarm Status.
The T7350 current alarm status is reported by the manufacturer defined output network variable nvoAlarmStatus.
nvoAlarmStatus
Field
Description
coverCommFail Communications between the cover and sub-base.
0: No alarm (power up value). 1: The communications between the thermostat cover assembly and the sub-base has failed in one or both directions. The data from the cover to the sub-base has not been received for at least 90 seconds, or data from the sub-base is not updating the cover assembly.
invalidIOConfig Output configuration error.
0: No alarm (power up value). 1: The number of outputs configured exceeds the capability of the sub-base to support them. Considers sub-base type, heat pump/conventional application, maxCoolStgs, maxHeatStgs.
sensorFail Sensor failure.
0: No alarm (power up value). 1: One of the analog sensors on the cover assembly has failed or is out of range (high or low).
networkCommFail Network Communications Failure.
0: No alarm (power up value). 1: One of the bound network input network variables is not being updated periodically. This alarm may be caused by a failed node or a damaged L
ONWORKS NETWORK cable.
invidSubBaseTyp Sub-base type error.
0: No alarm (power up value). 1: The detected sub-base type is not supported by the firmware version of the cover assembly.
21 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 15. Identifying Five Most Recent T7350 Alarms.
The five most recent T7350 alarms are identified in the manufacturer defined output network variable nvoAlarmLog.
nvoAlarmLog Field Description
alarm1 Alarm log: Most recent alarm.
Alarm Codes
0: AT_NO_ALARM (power up value) 1: AT_INVALID_SUBBASE_TYPE 2: AT_NETWORK_COMM_FAIL 3: AT_SENSOR_FAIL 4: AT_INVALID_IO_CONFIG 5: AT_COVER_COMM_FAIL 6: AT_COVER_SUBBASE_MISMATCH
Return to Normal Codes
-127: AT_rtnINVALID_SUBBASE_TYPE
-126: AT_rtnNETWORK_COMM_FAIL
-125: AT_rtnSENSOR_FAIL
-124: AT_rtnINVALID_IO_CONFIG
-123: AT_rtnCOVER_COMM_FAIL
-122: AT_rtnCOVER_SUBBASE_MISMATCH
-1: AT_ALARM_NOTIFY_DISABLED
alarm2
Alarm log: 2
nd
most recent alarm.
0: No alarm (power up value).
alarm3
Alarm log: 3
rd
most recent alarm.
0: No alarm (power up value).
alarm4
Alarm log: 4
th
most recent alarm.
0: No alarm (power up value).
alarm5 Alarm log: Oldest alarm.
0: No alarm (power up value).
63-4368 22
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

APPENDIX C - NETWORK ERROR REPORTING

Table 16. Reporting T7350H Errors.
T7350H errors are reported through the manufacturer defined output network variable, nvoError.
nvoError Field Description
errLoclSpaceSensr Local space temperature sensor not working.
0: Sensor value is OK. (power up value) 1: Sensor is configured to function and is out of range or disconnected.
errRemtSpaceSensr Remote space temperature sensor not working.
0: Sensor value is OK. (power up value) 1: Sensor is configured to function and is out of range or disconnected.
errNetSpaceSensr Network space temperature sensor not working.
0: Sensor value is OK. (power up value) 1: Sensor is configured by the thermostat to function but is not being updated by either the bound network sensor or by the subbase (faulty subbase).
errLoclHumSensr Local Humidity sensor not working.
0: Sensor value is OK. (power up value) 1: Sensor is configured to function and is out of range or disconnected.
errRemtHumSensr Remote Humidity sensor not working.
0: Sensor value is OK. (power up value) 1: Sensor is configured to function and is out of range or disconnected.
errNetHumSensr Network Humidity sensor not working.
errRemtOdSensr Remote Outdoor air sensor not working.
errNetOdSensr Network Outdoor air sensor not working.
errRemtSetPt Remote wall module set point is out of range or disconnected.
errDischSensr Discharge sensor out of range or disconnected.
errIOConfig Output configuration error. Considers sub-base type, heat pump / conventional application.
errSubBaseType Sub-base type error.
errUnused1 Not currently used
errSelfTest Self test failure. Upon factory test power up, a self test of memory is performed. If external RAM,
errCoverCommFail Communications between the cover and sub-base
0: Sensor value is OK. (power up value) 1: Sensor is configured by the thermostat to function but is not being updated by either the bound network sensor or by the subbase (faulty subbase).
0: Sensor value is OK. (power up value) 1: Sensor is configured to function and is out of range or disconnected.
0: Sensor value is OK. (power up value) 1: Sensor is configured by the thermostat to function but is not being updated by either the bound network sensor or by the subbase (faulty subbase).
0: Value is OK. (power up value) 1: Remote wall module set point is configured to function and is out of range or disconnected.
0: Sensor value is OK. (power up value) 1: Sensor is configured to function and is out of range or disconnected.
maxCoolStgs, maxHeatStgs.
0: The outputs configuration is consistent with the sub-base type selected (power up value) 1: The number of outputs configured exceeds the capability of the sub-base to support them.
0: The sub-base is a valid sub-base type (power up value) 1: The detected sub-base type is not supported by the firmware version of the cover assembly.
EEPROM, or application FLASH memory fails the test, nvoError.errSelfTest is set. This bit is intended for use in production testing. Field devices should ignore this bit.
0: Passed the test 1: Failed the test
0: No error (power up value) 1: The communications between the thermostat cover assembly and the sub-base has failed in one or both directions. The data from the cover to the sub-base has not been received for at least 90 seconds, or data from the sub-base is not updating the cover assembly.
23 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 16.
Reporting T7350H Errors. (Continued)
T7350H errors are reported through the manufacturer defined output network variable, nvoError.
nvoError Field Description
errSubBaseVerMisMatch Sub-base/cover firmware mismatch.
0: Sub-base and cover firmware are compatible. (power up value) 1: The firmware version in the sub-base is unable to communicate correctly with the firmware version of the cover assembly. The cover assembly Public Interface number of the sub-base is not compatible with the Public Interface number of the sub-base. That is nroT7350Ver.commVer does not match the version supported by the sub-base. Communications with the sub-base is turned off.
errNviSpaceTemp nviSpaceTemp network variable is:
0: either not bound or is bound and being updated periodically (power up value) 1: bound and not being updated periodically (communications or source node failure)
errNviOccSchedule nviOccSchedule network variable is:
0: either not bound or is bound and being updated periodically (power up value) 1: bound and not being updated periodically (communications or source node failure).
errNviOccSensor nviOccSensor network variable is:
0: either not bound or is bound and being updated periodically (power up value) 1: bound and not being updated periodically (communications or source node failure)
errNviApplicMode nviApplicMode network variable is:
0: either not bound or is bound and being updated periodically (power up value) 1: bound and not being updated periodically (communications or source node failure)
errNviOutdoorTemp nviOutdoorTemp network variable is:
0: either not bound or is bound and being updated periodically (power up value) 1: bound and not being updated periodically (communications or source node failure)
errNviSpaceRH nviSpaceRH network variable is:
0: either not bound or is bound and being updated periodically (power up value) 1: bound and not being updated periodically (communications or source node failure)
errNviBypass nviBypass network variable is:
0: either not bound or is bound and being updated periodically (power up value) 1: bound and not being updated periodically (communications or source node failure)
errNviDlcShed nviDlcShed (Demand Limit Control Shed signal) network variable is:
0: either not bound or is bound and being updated periodically (power up value) 1: bound and not being updated periodically (communications or source node failure)
63-4368 24
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

APPENDIX D - NETWORK ACCESS TO LOCAL SENSOR DATA

Table 17. T7350H Reports Local Sensor Data.
The T7350H reports local sensor data using the following output network variables.
Nv Name
nvoDischAirTemp Discharge Temperature
nvoOccSensor Occupancy Sensor Out Status of occupancy sensor
nvoOutdoorTemp Outdoor Temperature Out The current outdoor temperature. The sensor value source is specified by
nvoSpaceRH Space Humidity Out The current space humidity. The sensor value source is specified by
nvoSpaceTemp Space Temperature Out The current space temperature. The sensor value source is specified by
LonSpec Reference
Name Description
Out
The current discharge air temperature. The sensor value source is configured by nciConfig.dischAirSensor. A value of 327.67 means the sensor is not functioning correctly or is out of range.
327.67: Power up value
0: OC_OCCUPIED 1: OC_UNOCCUPIED
-1: OC_NUL (not configured and power up value)
nciConfig.oDAirSensor. A value of 327.67 means the sensor is not functioning correctly or is out of range.
327.67: Power up value
nciConfig.humiditySensor. A value of 163.84 means the sensor is not functioning correctly or is out of range.
163.84: Power up value
nciConfig.spaceSensor. A value 327.67 means the sensor is not functioning correctly or is out of range.
327.67: power up value

APPENDIX E - SCHEDULING NETWORK DEVICES

A T7350H can be used to time schedule the following Honeywell controllers:
• Another T7350H.
• T7300/Q7300.
• XL15C application objects (Control loops/StartStop loops).
• XL10 controllers.
A single T7350 can be configured to schedule all (up to 119) of the compatible controllers connected to the same network. This is accomplished by a one to many binding from the source T7350 to the destination controller or object.
T7350.nvoOccSchedule > XL10.nviOccSchedule.
L
ONSPEC™ automatically implements these NV bindings
based on the selection of Unscheduled Objects (XL10(s), Q7300(s), T7300H(s) and XL15cAP(s) located on the L
ONSPEC™ T7350 Scheduling Screen.

APPENDIX F - NETWORK MASTER CLOCK

A T7350H can be used as the network time master for the following network connected Honeywell controllers:
• Another T7350H.
• T7300/Q7300.
• XL15A.
This is accomplished by a one to many binding from the source T7350H to the destination controller. The following is an example NV binding of one T7350H as a time master to another.
T7350H.nvoTime > T7350H.nviTimeSet
ONSPEC™ automatically implements these NV bindings
L based on the selection of Network Time Master check box on the T7350 General configuration screen. The Day Light Saving Start and Stop Month on all time master recipients should be configured to None (invalid). This prevents erroneous time changes during temporary network outages.
25 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

APPENDIX G - NETWORK CONNECTIONS TO OTHER LCBS DEVICES

Table 18. Network Connections to XL15A AP Inputs.
T7350H Network Variable Outputs can be used as inputs to XL15A application objects.
XL15A
Application Object Application Input
Analog Alarm Selected Analog Value nvoSpaceTemp
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1 PercentCmdHeat
nvoData1 PercentCmdCool
Digital Alarm Selected Digital Value nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
Bypass Logs Select Bypass Object nvoEffectOccup
Source T7350H
Network Variable Network Variable Field
Run Times Select Point Name nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
Trends Trend Pt nvoSpaceTemp
nvoEffectSetpt
nvoEffectOccup
nvoHeatCool
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1 HeatStgsOn
nvoData1 CoolStgsOn
nvoData1 PercentCmdHeat
nvoData1 PercentCmdCool
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
63-4368 26
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 18. Network Connections to XL15A AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15A application objects.
XL15A
Application Object
Application Input Source T7350H
Network Variable
Network Variable Field
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
DLC Override If nvoSpaceTemp
Demand Limit Control nvoEffectSetpt
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1 PercentCmdHeat
nvoData1 PercentCmdCool
Analog Logic Function Analog Input nvoSpaceTemp
nvoEffectSetpt
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1 PercentCmdHeat
nvoData1 PercentCmdCool
Digital Logic Function Digital Input nvoAlarmStatus CoverCommFail
nvoAlarmStatus InvalidIOConfig
nvoAlarmStatus SensorFail
nvoAlarmStatus networkCommFail
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
nvoError ErrRemtHumSensr
nvoError errNetHumSensr
nvoError ErrRemtOdSensr
nvoError ErrNetOdSensr
nvoError ErrRemtSetPt
nvoError ErrDischSensr
nvoError errIOConfig
nvoError errSubBaseType
nvoError errSubBaseVerMisMatch
nvoError errNviSpaceTemp
nvoError errNviOccSchedule
nvoError errNviOccSensor
nvoError errnviApplicMode
nvoError errnviOutdoorTemp
27 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 18. Network Connections to XL15A AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15A application objects.
XL15A
Application Object
Application Input Source T7350H
Network Variable
Network Variable Field
nvoError errnviSpaceRH
nvoError errNviBypass
nvoError errNviDLCShed
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
Control Loop LoopDisable nvoAlarmStatus CoverCommFail
nvoAlarmStatus InvalidIOConfig
nvoAlarmStatus SensorFail
nvoAlarmStatus networkCommFail
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
nvoError ErrRemtHumSensr
nvoError errNetHumSensr
nvoError ErrRemtOdSensr
nvoError ErrNetOdSensr
nvoError ErrRemtSetPt
nvoError ErrDischSensr
nvoError errIOConfig
nvoError errSubBaseType
nvoError errSubBaseVerMisMatch
nvoError errNviSpaceTemp
nvoError errNviOccSchedule
nvoError errNviOccSensor
nvoError errnviApplicMode
nvoError errnviOutdoorTemp
nvoError errnviSpaceRH
nvoError errNviBypass
nvoError errNviDLCShed
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
63-4368 28
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 18. Network Connections to XL15A AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15A application objects.
XL15A
Application Object Application Input
Source T7350
Network Variable Network Variable Field
nvoData2 RelayFan
nvoData2 dehumidActive
Control Loop MainSensor nvoSpaceTemp nvoSpaceTemp
ResetSensor nvoEffectSetpt nvoEffectSetpt
nvoDischAirTemp nvoDischAirTemp
nvoTerminalLoad nvoTerminalLoad
nvoSpaceRH nvoSpaceRH
nvoOutdoorTemp nvoOutdoorTemp
nvoData1 PercentCmdHeat
nvoData1 PercentCmdCool
Start/Stop Loop LoopDisable nvoAlarmStatus CoverCommFail
nvoAlarmStatus InvalidIOConfig
nvoAlarmStatus SensorFail
nvoAlarmStatus networkCommFail
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
nvoError ErrRemtHumSensr
nvoError errNetHumSensr
nvoError ErrRemtOdSensr
nvoError ErrNetOdSensr
nvoError ErrRemtSetPt
nvoError ErrDischSensr
nvoError errIOConfig
nvoError errSubBaseType
nvoError errSubBaseVerMisMatch
nvoError errNviSpaceTemp
nvoError errNviOccSchedule
nvoError errNviOccSensor
nvoError errnviApplicMode
nvoError errnviOutdoorTemp
nvoError errnviSpaceRH
nvoError errNviBypass
nvoError errNviDLCShed
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
29 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 19. Network Connections to XL15A AP Outputs.
T7350H Network Variable Inputs can be connected to XL15A application outputs.
XL15A
Application Object Application Output
Destination T7350H
Network Variable Network Variable Field
Network Time Schedule Scheduled Device List nviOccSchedule
DLC External Load Assignment nviDlcShed
Table 20. Network Connections to XL15C AP Inputs.
T7350H Network Variable Outputs can be used as inputs to XL15C application objects.
XL15C
Application Object Application Input
Source T7350H
Network Variable Network Variable Field
Math Functions: Analog Input nvoSpaceTemp
Min, Max, Avg, Sqrt Add, nvoEffectSetpt
Subt, Mult, Div nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1 PercentCmdHeat
nvoData1 PercentCmdCool
nvoData1 HeatStgsOn
nvoData1 CoolStgsOn
nvoData1 BypassTime
nvoOccSensor
nvoEffectOccup
nvoHeatCool
nvoData2 stagesActive
Math Functions: nvoSpaceTemp
Network Special nvoEffectSetpt
SNVT_temp_p nvoDischAirTemp
nvoOutdoorTemp
Math Functions: nvoSpaceRH
Network Special nvoTerminalLoad
SNVT_lev_percent
Logic Loop ACDO Analog Input nvoSpaceTemp
DCAO Analog Input nvoEffectSetpt
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1 PercentCmdHeat
nvoData1 PercentCmdCool
nvoData1 HeatStgsOn
nvoData1 CoolStgsOn
nvoData1 BypassTime
nvoOccSensor
nvoEffectOccup
nvoHeatCool
63-4368 30
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 20. Network Connections to XL15C AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15C application objects.
XL15C
Application Object Application Input
Source T7350H
Network Variable Network Variable Field
nvoData2 stagesActive
Logic Loop DCAO Digital Input nvoAlarmStatus CoverCommFail
OR Digital Input nvoAlarmStatus InvalidIOConfig
AND Digital Input nvoAlarmStatus SensorFail
nvoAlarmStatus networkCommFail
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
nvoError ErrRemtHumSensr
nvoError errNetHumSensr
nvoError ErrRemtOdSensr
nvoError ErrNetOdSensr
nvoError ErrRemtSetPt
nvoError ErrDischSensr
nvoError errIOConfig
nvoError errSubBaseType
nvoError errSubBaseVerMisMatch
nvoError errNviSpaceTemp
nvoError errNviOccSchedule
nvoError errNviOccSensor
nvoError errnviApplicMode
nvoError errnviOutdoorTemp
nvoError errnviSpaceRH
nvoError errNviBypass
nvoError errNviDLCShed
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 Relay Aux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
Control Loop SetPtOverride Digital Input nvoAlarmStatus CoverCommFail
LoopDisable nvoAlarmStatus InvalidIOConfig
Bypass Input nvoAlarmStatus SensorFail
OccupancySensor nvoAlarmStatus networkCommFail
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
31 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 20. Network Connections to XL15C AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15C application objects.
XL15C
Application Object Application Input
Source T7350H
Network Variable Network Variable Field
nvoError ErrRemtHumSensr
nvoError errNetHumSensr
nvoError ErrRemtOdSensr
nvoError ErrNetOdSensr
nvoError ErrRemtSetPt
nvoError ErrDischSensr
nvoError errIOConfig
nvoError errSubBaseType
nvoError errSubBaseVerMisMatch
nvoError errNviSpaceTemp
nvoError errNviOccSchedule
nvoError errNviOccSensor
nvoError errnviApplicMode
nvoError errnviOutdoorTemp
nvoError errnviSpaceRH
nvoError errNviBypass
nvoError errNviDLCShed
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
Control Loop MainSensor nvoSpaceTemp
ResetSensor nvoEffectSetpt
RecoverySensor nvoDischAirTemp
LimitAnalogInput nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1 PercentCmdHeat
nvoData1 PercentCmdCool
nvoData1 HeatStgsOn
nvoData1 CoolStgsOn
nvoData1 BypassTime
nvoOccSensor
nvoEffectOccup
nvoHeatCool
nvoData2 stagesActive
Start/Stop Loop LoopDisable nvoAlarmStatus CoverCommFail
Bypass nvoAlarmStatus InvalidIOConfig
nvoAlarmStatus SensorFail
nvoAlarmStatus networkCommFail
63-4368 32
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 20. Network Connections to XL15C AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15C application objects.
XL15C
Application Object Application Input
nvoAlarmStatus InvalidSubBaseType
nvoError errLoclSpaceSensr
nvoError ErrRemtSpaceSensr
nvoError ErrNetSpaceSensr
nvoError ErrLoclHumSensr
nvoError ErrRemtHumSensr
nvoError errNetHumSensr
nvoError ErrRemtOdSensr
nvoError ErrNetOdSensr
nvoError ErrRemtSetPt
nvoError ErrDischSensr
nvoError errIOConfig
nvoError errSubBaseType
nvoError errSubBaseVerMisMatch
nvoError errNviSpaceTemp
nvoError errNviOccSchedule
nvoError errNviOccSensor
nvoError errnviApplicMode
nvoError errnviOutdoorTemp
nvoError errnviSpaceRH
nvoError errNviBypass
nvoError errNviDLCShed
nvoData2 RelayHeat3
nvoData2 RelayCool3
nvoData2 RelayHeat2
nvoData2 RelayCool2
nvoData2 RelayAux
nvoData2 RelayHeat1
nvoData2 RelayCool1
nvoData2 RelayFan
nvoData2 dehumidActive
Source T7350H
Network Variable Network Variable Field

S7760 - Command Display

A network connected Command display can be configured (by LonSpec) to implement the following T7350H functions: View and Modify Schedules:
• Occupied, Unoccupied and Standby setpoints
• weekly schedule
• holiday schedule
NOTE: If a T7350H is connected to a wall module with set-
point adjustment, the user will not be allowed to change occupied setpoints through Command Dis­play.
1
33 63-4368
Command manual occupancy, Annunciate T7350H alarms, Monitor T7350H data:
• Room Temperature
• Active Room Temperature SetPoint
• Occupancy Status
• Operating Mode
• Discharge Air Temperature
• Space Humidity
• Outdoor Temperature
• Heat Stages Active
• Cool Stages Active
• Heat Modulating Output Position
• Cool Modulating Output Position
• Bypass Minutes Remaining
• Auxiliary Relay Status
• Fan Status
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

APPENDIX H - T7350H NETWORK VARIABLE SUMMARY

Table 21. T7350H Network Variable Summary.
Nv Name L
nciApplVer Application version CONFIG Application type: identifies the current application number for this
nciBypassTime Bypass Time CONFIG Temporary Occupied Override duration in minutes.
nciConfig NA FTP
nciConfigPts NA FTP
nciDayLghtSav NA FTP
nciDaySchedule0 NA FTP
nciDaySchedule1 NA FTP
nciDaySchedule2 NA FTP
nciDaySchedule3 NA FTP
nciDaySchedule4 NA FTP
nciDaySchedule5 NA FTP
nciDaySchedule6 NA FTP
nciDaySchedule7 NA FTP
nciDeviceName Device Name CONFIG Device Name is an 18 character field used to identify the device
nciHolSched NA FTP
ONSPEC™ Ref Name Class Description
device given by a tool.
0: (Default).
Increment: increased by one whenever any configuration parameter changed by PDA or thermostat keyboard. L
ONSTATION™ does not change this field.
and L
0: (Default).
Time Stamp: indicates the last change to the device application configuration. The time stamp meets the ANSI C time stamp requirement specifying the number of seconds elapsed since midnight (0:00:00), January 1, 1970. It is represented in the Intel Format. If the T7350 keyboard or the PDA Config Tool updates any configuration parameters, the time is incremented.
0: (Default).
Version Number: identifies the version number of the application for this device. If the T7350 keyboard or the PDA Config Tool updates any configuration parameters, is incremented.
0: (Default).
180: (Default).
Thermostat configuration parameters.
CONFIG
Thermostat operating setpoint values for the control algorithms
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
contained in the Thermostat application code.
Daylight-saving start and end calendar schedule.
Event time schedule for Sunday.
Event time schedule for Monday.
Event time schedule for Tuesday.
Event time schedule for Wednesday.
Event time schedule for Thursday.
Event time schedule for Friday.
Event time schedule for Saturday.
Event time schedule for designated Holiday.
uniquely as one device at the site or project. The content of Device Name is maintained by a management node. If Device Name is all ASCII blanks, it is considered un-configured by Honeywell tools. ASCII blanks: (Default)
Holiday calendar schedule.
ONSPEC
63-4368 34
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nciRcvHrtBt Controller Receive Time CONFIG Receive heartbeat time (seconds) for all failure detect heartbeat
network variables in this node.
0: Disable failure (Default). 300: Typical value in Honeywell system.
nciSetpoints Setpoint Config CONFIG Heating and Cooling SetPoints in Celsius engineering units.
Occupied cool set-point.
23.9 C: (Default)
Standby cool set-point.
25.6 C: (Default).
Unoccupied cool set-point.
29.4 C: (Default).
Note: It is required that: UnoccCl>=OccCl>=OccHt+1.11 C. UnoccCl>=StdByCl>=StdByHt+1.11 C. If the above criteria is not met, then the nciSetpoints received over the L
ONWORKS network will not be accepted, and all the current
controlling set points will be restored from the thermostat.
Occupied heat set-point.
21.1 C: (Default).
Standby heat set-point.
19.4 C: (Default).
Unoccupied heat set-point.
12.8 C: (Default).
It is required that: UnoccHt<=OccHt<=OccCl-1.11 C. UnoccHt<=StdByHt<=StdByCl-1.11 C. If the above criteria is not met, then the nciSetpoints received over the L
ONWORKS network will not be accepted, and all the current
controlling set points will be restored from the thermostat.
nciSndHrtBt Controller Send Time CONFIG Send heartbeat time (seconds) for all Guaranteed periodic update
heartbeat network variables in this node.
0: Disable periodic update (Default). 55: Typical value in Honeywell system.
nroPgmVer Program Version CONST The Honeywell program identifier and subbase firmware version
number.
nroT7350Ver T7350 Version CONST Detailed T7350 cover assembly firmware version information.
nviApplicMode Application Mode In IN Thermostat System mode switch:
0: HVAC_AUTO 1: HVAC_HEAT 3: HVAC_COOL 6: HVAC_OFF 8: HVAC_EMERG_HEAT Others: Considered to be HVAC_AUTO.
Failure detect and mains power up value: HVAC_AUTO.
35 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nviBypass Bypass In IN Remote time bypass input from usually from another device.
Bypass is a method to command unoccupied override over the network from another controller. The other controller does the bypass timing. nviBypass can be used to place the T7350H into temporary occupied mode. This mode will bypass the time of day occupancy schedule in this device. Val ue
State Action 0 NA Do not bypass the time of day occupancy schedule.
NA 0 or -1 Do not bypass the time of day occupancy schedule.
0.5 - 100 1 or Bypass the time of day occupancy greater schedule.
0 0 Mains power up and fail detect value.
nviDlcShed DLC Shed In IN Demand limit duty cycle load shed command from a network
device. When a shed request is received, the thermostat “bumps” the control set point up for cooling and down for heating. The amount of the “bump is a user set point selection. The shed state remains until a DLC restore command is received or network communication is lost. When the unit transitions from shed to restore, the set point is ramped back to the original set point over a period of 60 minutes. The control only sheds when the thermostat is in the occupied mode.
Value:
0: No load shed being called (mains power up or failure detect value). 1 or other values: Call for load shedding.
nviFanAuto FanOnAuto In IN Auto Fan switch (last in wins).
value = 0, state = don’t care: Fan is On. value = Don’t care, state = 0 or -1: Fan is On. Value = 0.5 - 100: state = 1 or greater: Fan is On when there is a call for heat / cool. Failure detect and mains power up value: No change from previous value. Val ue
State Action 0 NA Fan is ON.
NA 0 or -1 Fan is ON.
0.5 - 100 1 or Fan is ON when there is a call for greater heat / cool.
no no Mains power up and fail detect value. change change
nviFilePos File Position In IN
Supports L
ONMARK
®
FTP file transfer. Random Access file Pointer
to first byte to be transferred and Number of bytes to transfer.
nviFileReq File Request In IN
Supports L
ONMARK
®
FTP file transfer. Message request
management is communicated through this input variable.
nviInUse InUse IN In use number is used by a management node to indicate to all
other management nodes that it is “logged on.”
63-4368 36
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nviManValue Manual Value In IN Manual override values for outputs:
Relays: Y1, Y2, Y3, Aux, G, W1, W2, W3 Analog Outputs: Mc, Mh
nviOccManCmd Occupancy Cmd In IN Manual occupancy is a method to command the occupancy state
from a network workstation. Effective occupancy override works on a “last in wins” basis. That is, the last occupancy override command received from any source determines the override state. The workstation can command occupied, unoccupied, standby, bypass, or not active (null).
nviOccManCmd is used to place the T7350H into manual occupancy (note there is no timer associated with nviOccManCmd). Manual occupancy input from a network device:
0: OC_OCCUPIED 1: OC_UNOCCUPIED 2: OC_BYPASS 3: OC_STANDBY
-1: OC_NUL not connected (mains power up). Others: same as OC_NUL.
NOTE: If nviOccManCmd is OC_BYPASS and the bypass timer
(nvoData1.bypassTime) times out, then nviOccManCmd is set to OC_NUL.
nviOccSchedule Occupancy Schedule In IN There are 2 distinct modes of operation: local schedule and
network schedule. The local schedule mode causes the T7350H to change set points by using the scheduler in the T7350H. The network schedule mode causes the T7350H to change set points from a network-based scheduler. The network schedule, when valid, overrides the local schedule. The network schedule input is nviOccSchedule. This input has current state, next state and tuncos (Time Until Next Change of State). It is bound from another scheduler such as the XL15A or T7300/Q7300H. The XL15B or a workstation can also write to it in an “unbound” relationship. If the network schedule is not periodically updated the T7350H resumes local scheduling. Periodically means at a rate greater than the fail detect time. This rate is typically 55 seconds, 300 seconds maximum. (The actual rate and maximum depend on the configured heartbeat and failure detect times.)
Current scheduled occupancy state:
0: OC_OCCUPIED 1: OC_UNOCCUPIED 3: OC_STANDBY Others: same as OC_NUL.
-1: OC_NUL (mains power up and fail detect value).
Next scheduled occupancy state:
0: OC_OCCUPIED 1: OC_UNOCCUPIED 3: OC_STANDBY Others: same as OC_NUL.
-1: OC_NUL (mains power up and fail detect value).
Time in minutes until next scheduled change of occupancy state:
0: (mains power up and fail detect value).
37 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nviOccSensor Occupancy Sensor In IN There are 3 distinct modes of operation: local occupancy sensor,
network occupancy sensor, or none. The network occupancy input is nviOccSensor. It is bound from another sensor or controller with occupancy status.
Occupancy sensor input from a network device:
0: OC_OCCUPIED 1: OC_UNOCCUPIED
-1: OC_NUL not connected (mains power up and fail detect value). Others: same as OC_NUL.
NOTE: If nviOccSensor is not invalid (OC_NUL), nviOccSensor
is used as the occupancy sensor even if another sensor or no sensor is configured.
nviOutdoorTemp Outdoor Temperature In IN Outdoor temperature input from a network device. Ignored unless
nciConfig.oDAirSensor specifies a network configuration.
327.67: means to ignore comODTemp.
327.67: mains power up and failure detect value.
NOTE: If nviOutdoorTemp is not invalid (327.67), nviOutdoor-
Temp is used as the outdoor temperature even if another sensor or no sensor is configured.
nviPgm Program In IN Memory address and data being sent to cover assembly flash
memory.
nviRequest Request IN Input variable for managing network requests for status.
nviSetpoint Setpoint In IN Desired space temperature (Celsius) set by remote network
device.
327.67: means to ignore nviSetPoint.
327.67: mains power up value.
nviSpaceRH Space Humidity In IN Space humidity input (percent) from a network device. Ignored
unless nciConfig.humiditySensor specifies a network configuration.
163.83: mains power up and failure detect value.
NOTE: If nviSpaceRH is not invalid (163.83), nviSpaceRH is
used as the space relative humidity even if another sen­sor or no sensor is configured.
nviSpaceTemp Space Temperature In IN When configured for a network sensor and periodically updated,
the network space temperature sensor will override both the local and remote sensors. Space temperature input (Celsius) from a network device. Values less than -2.2 will be clipped to -2.2. Values greater than 60 will be clipped to 60.
327.67: means to ignore nviSpaceTemp.
327.67: mains power up and failure detect value.
NOTE: If nviSpaceTemp is not invalid (327.67), nviSpaceTemp is
used as the space temperature even if another sensor or no sensor is configured.
nviTimeSet Time In IN Set current month, day, year, hour, minute, second
Time synchronization will be to a network device that has been designated as the “time master.” Time synchronization will occur at the Guaranteed Periodic Update rate (typically every 55 seconds).
63-4368 38
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nvoAlarmH Alarm Out OUT Alarm subnet, node and type.
Alarm subnet is the LonWorks subnet number in domain entry to which nvoAlarmH is bound. If nvoAlarmH is not bound reports domain index 0.
0: Invalid subnet (power up value). 1-255: Subnet number.
Alarm node is the LonWorks node number (in domain entry to which nvoAlarmH is bound. If nvoAlarmH is not bound reports domain index 0).
0: Invalid entry (power up value). 1-127: Node number.
Alarm type is the alarm type being issued:
0: AT_NO_ALARM (power up value). 1: AT_INVALID_SUBBASE_TYPE 2: AT_NETWORK_COMM_FAIL 3: AT_SENSOR_FAIL 4: AT_INVALID_IO_CONFIG 5: AT_COVER_COMM_FAIL 6: AT_COVER_SUBBASE_MISMATCH
-127: AT_rtnINVALID_SUBBASE_TYPE
-126: AT_rtnNETWORK_COMM_FAIL
-125: AT_rtnSENSOR_FAIL
-124: AT_rtnINVALID_IO_CONFIG
-123: AT_rtnCOVER_COMM_FAIL
-122: AT_rtnCOVER_SUBBASE_MISMATCH
-1: AT_ALARM_NOTIFY_DISABLED
nvoAlarmLog Alarm Log Out OUT Reports the last five alarms.
nvoAlarmStatus Alarm Status Out OUT Status of the following alarms states:
Communications between the cover and sub-base.
0: No alarm (power up value). 1: The communications between the thermostat cover assembly and the sub-base has failed in one or both directions. The data from the cover to the sub-base has not been received for at least 90 seconds, or data from the sub-base is not updating the cover assembly.
Output configuration error:
0: No alarm (power up value). 1: The number of outputs configured exceeds the capability of the sub-base to support them. Considers sub-base type, heat pump / conventional application, maxCoolStgs, maxHeatStgs.
Sub-base type error:
0: No alarm (power up value). 1: The sub-base is not a valid sub-base type for the firmware in the cover assembly.
Network Communications Failure:
0: No alarm (power up value). 1: One of the bound network input variables is not being updated periodically. This alarm may be caused by a failed node or a damaged LonWorks network cable.
Sensor failure:
0: No alarm (power up value). 1: One of the analog sensors on the cover assembly has failed or is out of range (high or low).
39 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nvoBypass Bypass Out OUT The T7350H uses nvoBypass to command bypass to other XL10
nodes. When the T7350 is in bypass, it commands nvoBypass. This is a one to many bound relationship. “Many” means one T7350H can command bypass on all XL10s connected on the subnet. Reports whether this device is in timed bypass of the scheduled occupancy state. Used by other devices to also bypass the time of day schedule. Val ue
State Action 0 0 This device is not in bypass Power up value
1 100 This device is in bypass
nvoData1 nvoData1 OUT Reports Manufacturer Specific Device Data including:
bypassTime, coolStgsOn, DaysLeftKeypadHoliday, dischTemp, effMode, effOccCurrentState, effSetPt, fan, heatStgsOn, oDTemp, percentCmd,Cool, percentCmdHeat, spaceHumidity, spaceTemp, subBaseType, sysMode, terminalLoad.
nvoData2 nvoData2 OUT Reports Manufacturer Specific Device Data including: auxRelay,
DALimit, dehumidActive, ESR, holiday, noAuxHeat1, noAuxHeat2, occSensor, relayAux, relayCool1, relayCool2, relayCool3, relayFan, relayHeat1, relayHeat2, relayHeat3, remoteStPtOffset, schedNextState, scheduledState, scheduledTuncos, stagesActive, T7350CommWorks, temporarySetPt, totalError.
nvoDischAirTemp Discharge Temperature
Out
OUT The current discharge air temperature (Celsius). The sensor is
configured by nciConfig.dischAirSensor. A value of 327.67 means the sensor is not functioning correctly or is out of range.
327.67: Power up value.
nvoEffectOccup Effective Occ Out OUT Current effective occupancy state:
0: OC_OCCUPIED (power up value). 1: OC_UNOCCUPIED 2: OC_BYPASS 3: OC_STANDBY
-1: OC_NUL
nvoEffectSetpt Effective Stpt Out OUT Effective room temperature control set point (Celsius).
327.67: Power up value.
nvoError nvoError OUT Device error status. Refer to Appendix C - Network Error
Reporting for details.
nvoFileStat File Status Out OUT File transfer status.
nvoHeatCool Application Mode out OUT Effective operating mode:
0: HVAC_AUTO 1: HVAC_HEAT (heat or re-heat). 3: HVAC_COOL 6: HVAC_OFF (power up value). 7: HVAC_TEST (manual mode or cover in factory test mode). 8: HVAC_EMERG_HEAT
63-4368 40
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nvoOccSchedule Time Of Day Out OUT This output has current state, next state and tuncos (Time Until
Change of State). This output is typically bound to other controller(s) that need a schedule command. This output is the combination of the local schedule and the network schedule command. It doesn’t include any bypass, override, or manual occupancy commands that affect this T7350H. There is no TOD assignment table in the T7350H. The T7350H allows a one to many binding of nvoOccSchedule. This means one T7350H can command all of the XL10s on the subnet – up to 119 controllers.
Current scheduled occupancy state:
0: OC_OCCUPIED 1: OC_UNOCCUPIED 3: OC_STANDBY
-1: OC_NUL (power up value).
Next scheduled occupancy state:
0: OC_OCCUPIED (power up value). 1: OC_UNOCCUPIED 3: OC_STANDBY
-1: OC_NUL (power up value).
Time in minutes until next scheduled change of occupancy state: 2880: Means there is not a next change of occupancy state or it is longer than 2 days from now (Power up value).
nvoOccSensor Occupancy Sensor Out OUT Status of occupancy sensor:
0: OC_OCCUPIED 1: OC_UNOCCUPIED
-1: OC_NUL (not configured and power up value).
nvoOutdoorTemp Outdoor Temperature Out OUT The current outdoor temperature (Celsius). The sensor source is
specified by nciConfig.oDAirSensor. A value of 327.67 means the sensor is not functioning correctly or is out of range.
327.67: Power up value.
nvoPgm Program Out OUT Cover assembly flash memory programming data.
nvoSpaceRH Space Humidity Out OUT The current space humidity (percent). The sensor source is
specified by nciConfig.humiditySensor. A value of 163.84 means the sensor is not functioning correctly or is out of range.
163.84: Power up value.
nvoSpaceTemp Space Temperature Out OUT The current space temperature (Celsius). The sensor source is
specified by nciConfig.spaceSensor. A value 327.67 means the sensor is not functioning correctly or is out of range.
327.67: power up value.
41 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nvoStatus Status OUT Status:
Alarm notify disabled:
0: Alarm notification is turned on (power up value). 1: Alarm notification via nvoAlarmH, nvoAlarmLog, nvoUnitStatus, and nvoStatus has been turned off.
Alarm
0: no alarm (power up value). 1: there is an alarm.
Override the delays associated with automatic control:
0: Delays turned on (power up value). 1: Delays turned off (Useful for troubleshooting).
Invalid ID:
0: The request was for a valid ID (Power up value). 1: The request was not for a valid ID.
Invalid Request:
0: The request was for a valid operation (Power up value). 1: Invalid request for an operation.
Manual control:
0: The function block is in automatic operation (power up value). 1: The function is in manual operation and outputs respond to nviManValue.
Status report. Function block number being in status report:
0: Node function block. 1: Space comfort controller function block.
Programming Mode:
0: Normal operating mode (power up value). 1: The node is in the “programming the cover flash memory” mode, and is not automatically controlling temperature.
Report mask:
0: Normal operation (power up value). 1: RQ_REPORT_MASK received. The status bits that are set have been implemented.
nvoTerminalLoad Terminal Load Out OUT Terminal load (percent): Reports the demand for supply energy.
Positive numbers are cooling demand and negative numbers are heating demand. 100 percent is full capacity. Terminal loads greater than 100 percent or less than -100 percent indicate that the equipment is not able to supply the required heating or cooling energy. The valid range is between 163 and minus 163 percent. Terminal load is used by supervisory level control applications to reset Boiler or Chiller discharge water temperatures.
163.84: Power up condition.
nvoTime Time Out OUT Current year, month, day, hour, minute, second.
The T7350H can be a time master to other T7350Hs, XL15As, and Q7300s.
63-4368 42
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 21. T7350H Network Variable Summary. (Continued)
Nv Name L
ONSPEC™ Ref Name Class Description
nvoUnitStatus Unit Status OUT Unit Status:
Percentage of cooling capability currently being supplied to the controlled space.
163.84: Power up value.
Fan turned on or off:
0: Fan not running. 100: Fan running.
163.84: (power up value).
Percentage of auxiliary heating capability currently being supplied to the controlled space (Applies to heat pump application only):
163.84: Power up value.
Alarm report:
0: No alarms reported in the unit (power up value). 1: One or more alarms reported in the unit.
-1: The Alarms have been suppressed by alarm notified disabled command.
Effective operating mode:
0: HVAC_AUTO (power up value). 1: HVAC_HEAT 3: HVAC_COOL 6: HVAC_OFF (power up value). 7: HVAC_TEST (manual mode or cover in factory test mode). 8: HVAC_EMERG_HEAT
43 63-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

Class Description

CONFIG: LonMark network configuration parameters
FTP CONFIG: Configuration parameters implemented with the LonMark file transfer protocol
IN: Network variable inputs.
OUT: Network variable outputs.
ZIRE and TUNGSTEN are trademarks of palmOne, Inc.
HotSync and Palm OS are registered trademarks of PalmSource, Inc.
Palm is a trademark of PalmSource, Inc.
TRGPro is a trademark of HandEra, Inc.
ONMARK
L
®
, LONTALK®, and LONWORKS® are registered trademarks of Echelon® Corporation.
LonSpec™, and LonStation™ are trademarks of Echelon® Corporation.
Automation and Control Solutions Honeywell International Honeywell Europe S.A. Honeywell Latin American
Honeywell Inter natio nal In c. Honeywell Limited-Honeywell Limitée Control Products 3 Avenue du Bourget 1985 Douglas Drive North 35 Dynamic Drive Honeywell Building 1140 Brussels 480 Sawgrass Corporate Parkway Golden Valley, MN 55422 Scarborough, Ontario 17 Changi Business Park Central 1 Belgium Suite 200
M1V 4Z9 Singapore 486073 Sunrise FL 33325
63-4368 B.B. 11-04 www.honeywell.com
Region
Loading...