Abbreviations and Definitions .................................................................................................................................. 4
Bus Layout ...................................................................................... 11
Appendix D - Network Access to Local Sensor Data ............................................................................................................. 25
Appendix E - Scheduling Network Devices ............................................................................................................................ 25
Appendix F - Network Master Clock ........................................................................................................................................ 25
Appendix G - Network Connections to Other LCBS Devices ................................................................................................ 26
Appendix H - T7350H Network Variable Summary ................................................................................................................. 34
Subbase.
— Excel 15 S7760A Command Display.
— Excel 10 W7750A,B,C Constant Volume Air Handler Unit
(CVAHU) Controller.
— Excel 15 W7760A, B, C Building & Plant Managers.
— Excel 10 W7751B, D, F, H, J Variable Air Volume Terminal
Unit Controllers.
— Excel 10 W7752D, E, F, G Fan Coil Unitcontrollers.
— Excel 10 W7753A Unit Ventilator Controller.
— Excel 10 W7762A,B Hydronic Controllers.
— Excel 10 W7763C, D, E Chilled Ceiling Controllers.
NOTEBOOK PC
®
system using a
ONMARK
RS-232
SERIAL
PORT
SLTA
®
devices
BUILDING MANAGER
1481216
EXCEL 15
W7760
30 31
17 23
37
Control Application
The T7350H programmable communicating Thermostat
controls commercial single zone heating, ventilating and air
conditioning (HVAC) equipment through staged and
modulating outputs. The T7350H consists of a two piece
assembly with a thermostat cover and subbase. The
thermostat cover includes the keypad and display for 7-day
programming. Calendar programming is available through a
direct connect PDA (Configuration Tool) or network
(L
ONSPEC™ with model T7350H) tool configuration. The
subbase includes equipment control, inputs and network
connections. The subbase mounts on the wall and the
thermostat cover mounts to the subbase. In addition, the
T7350H model can communicate local sensor data, schedule
information, master clock operations and accept configuration
and override instructions to or from other devices/tools in a
L
ONWORKS
application in a three-stage heat and two-stage cool heat
pump system. For additional hookups, see Fig. 10 through 12.
44
S7760
®
network. Fig. 9 shows a typical T7350H
WALL MODULE
EXCEL 10
CVAHU
LonWorks BUS
T7350H
MODEM
Select
Back
MODEM
BUILDING MANAGER
1481216
RS-232
SERIAL
PORT
SLTA
EXCEL 15
W7760
17 23
30 31
44
37
S7760
Select
Back
EXCEL 10
CVAHU
LonWorks BUS
Fig. 1. Typical T7350H LONWORKS® network diagram.
WALL MODULE
T7350H
M22490
63-43682
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Network Control Provided
The T7350H communicates with other network devices, or
nodes, for sharing data such as local inputs. Through the
network, a Command Display (S7760) is used to view or
modify T7350H operational modes including:
• Weekly Schedule.
• Holiday Schedule.
• Room Temperature SetPoints (Occupied, Unoccupied,
Standby).
• Manual Occupancy Override.
• Temperature Setpoints.
• Update Time Clock.
Network connected Workstations and Configuration Tools are
used to view and modify additional T7350 operational modes:
By using network messaging, the T7350H may share the
following local inputs with other T7350, T7300/Q7300, XL15
or XL10 network connected devices:
• Room Humidity and Temperature.
• Outdoor Air Temperature.
• Occupancy Sensor.
• Unoccupied Bypass User Input.
Network messaging also supports distribution of local user
commands and operational states from a single T7350H. That
is, network connected T7350H and XL10 devices can be
configured to follow the local user commands and states from
a single (master) T7350H. These local T7350 commands
include the following:
• Time synchronization from a T7350H designated as
network master clock.
• Master Time Scheduling of Occupied, Unoccupied and
Standby states.
MODELS
Table 1. T7350 Communicating Thermostat Models.
Maximum
a
Stages
ModelApplications
T7350H1009Conventional
or
Heat Pump
T7350H1017Modulating
a
All models are down-selectable and can be configured to
control fewer stages than the maximum allowed.
b
Heat pump applications for these models have a maximum
of two heat stages and two cool stages.
c
One extra stage (of either heat or cool) can be configured
using the auxiliary relay.
3 (2)b3 (4)
2 modulating, 2
relay
b
c
FeaturesHeatCool
Humidity, Occupancy,
Outdoor, Discharge Air
Capability
Humidity, Occupancy,
Outdoor, Discharge Air
Capability, 4-20 mA
output (2-10 Vdc with
500 ohm resistor)
Products Covered
This System Engineering manual describes how to apply the
T7350H Communicating Thermostat and related accessories
to typical applications. Devices include:
The following list of documents contains general information
related to the T7350H Communicating Commercial
Thermostats.
Table 3. Applicable Literature
Form No.Title
63-1299T7350 Commercial Programmable
Thermostat Spec Data
62-0195T7350 Commercial Programmable
Thermostat Installation Instructions
63-2605T7350 Commercial Programmable
Thermostat Product Data
74-2976Excel L
ONSPEC™ ZL7760A Specification
Data
74-2937Excel LONSPEC™ ZL7760A User’s Guide
74-3123Light Commercial Building Solution System
Communication Guide
74-2697T7770A, B, C, D, E, F, G Wall Module
Specification Data
95-7538T7770A, B, C, D, E, F, G Wall Module
Installation Instructions
63-2617T7771 Wall Module Product Data
74-2972S7760A Command Display Specification
Data.
74-2858Q7740A,B FTT Repeater Specification
Data.
95-7555Q7740A,B FTT Repeater Installation
Instructions.
®
74-2954Q7760A SLTA-10 Serial LonTalk
Adapter
Specification Data.
®
95-7511Q7760A SLTA-10 Serial LonTalk
Adapter
Installation Instructions.
95-7554209541B Termination Module Installation
Instructions
ABBREVIATIONS AND DEFINITIONS
Application—A special use Building Control function.
Binding—The process of logically connecting network
variables in one node to network variable(s) in other node(s).
Binding is performed by a network management Tool (such as
L
ONSPEC™) that writes the binding information into the
EEPROM memory of all the neuron’s involved. The binding
information is saved in the network image of each neuron.
Building Manager—A LONMARK® certified device that can be
used to monitor and control HVAC equipment and other
miscellaneous loads in a distributed network.
Command Display—A device that can be used to monitor
data and change parameters of network connected devices.
CVAHU—Excel 10 Constant Volume Air Handler Unit
Controller.
Excel 10s—A family of application - specific HVAC controllers
such as the Excel 10 CVAHU and Excel 10 VAV.
HVAC—Heating, Ventilating and Air Conditioning.
I/O—Input/Output.
LCBS—Light Commercial Building Solution. These systems
are configured with the L
monitored with a Workstation such as LonStation
ONSPEC™ network tool and
®. Many
LCBS networks include the W7760B & C plant managers.
Routers (including Q7751A) are not supported by the LCBS
network configuration L
ONSPEC™-ZL7760A—A network connected tool which
L
ONSPEC™ tool.
configures, commissions, calibrates and monitors the
Honeywell Light Commercial Building Solution Q7300,
T7350H, Excel 10 and Excel 15 family of controllers.
Building Solution workstation that provides advanced building
control capabilities for small to medium-size buildings.
ONWORKS
L
communicating with each other using the LonTalk
®
Network—A data network based on neurons
®
protocol.
Mandatory Mechanisms/Objects/Network Variables—
Mandatory mechanisms and network variables that are
implemented in all the Excel 10 devices.
NamedObjects—These objects are visible on the network as
functional independent entities and are accessed by name.
Typical examples of NamedObjects are Controllers,
ControlLoops and LogicFunction blocks contained in devices
such as the XL5a or XL15b.
Network Management Node—A L
ONWORKS
®
node that is
responsible for configuring the network, installing the nodes,
binding the network variables between nodes, and general
network diagnostics.
63-43684
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Network Variables—A class of variables defined in Neuron C
that allows communication over the L
ONWORKS
®
network to
other nodes on the network. An output network variable in one
node can be bound to a corresponding input network
variable(s) in other node(s). Changing the value of the output
network variable in one node causes the new value to be
automatically communicated to the bound input network
variable(s) in other node(s). When an input network variable is
updated, a nv_update_occurs and the event is posted at the
receiving node(s) so that the application program can take
action based on the change. A network management node
(for example XL15A or XL15C) that explicitly reads and/or
writes the network variable can also poll network variables.
Network variables can contain one data field (one or two
bytes) or multiple data fields (a structure).
Neuron—Refers to the Echelon
implements the L
ONWORKS
®
semiconductor device which
®
protocol on a network connected
device such as the T7350H Honeywell controller.
Node—A device implementing layers one through six of the
LonTalk
®
protocol including a Neuron® Chip, transceiver,
memory, and support hardware.
Notebook PC—Portable personal computer.
PDA—Personal Digital Assistant. In the case of the T7350
product this is a hand held electronic device operating with the
Palm OS. A Honeywell provided PDA application program is
used to configure the T7350 thermostat using a direct RS232
connection. Before purchasing a PDA, check the latest
Configuration software release note for a list of qualified PDA
models. Network connected T7350H models can be
configured without a PDA using L
ONSPEC™.
Programmable Controller—A controller that has a variable
number of control loops of different types and is user
programmed to execute an application. The user can select
the number and type of control loops. The user also has the
capability of generating new types of control loops. Some
examples of Honeywell programmable controllers include the
XL15A and XL15B.
Recovery Mode or Recovery Period—The time in
unoccupied periods when the temperature control is adjusting
the control setpoint so that the space temperature reaches the
occupied setpoint when the schedule change occurs.
RIO—Excel 10 Remote Input/Output device.
RTC—Real Time Clock.
Schedule—The structure that defines the occupancy states
and the time of the changes between these states. In the case
of the T7350, schedules are organized around a eight day
weekly structure including an extra day for designated
holidays. Holidays are scheduled by yearly calendar events.
SGPU—Significant Event Notification and Guaranteed
Periodic Update.
SGPUC—Significant Event Notification and Guaranteed
Periodic Update with Change Field.
SLTA—Serial LonTalk
coupled LonTalk
®
Adapter. Adapts the transformer
®
messages to the RS-232 Serial Port.
SNVT—Standard Network Variable Type.
SCPT—Standard Configuration Parameter Type.
XL15A—W7760A Honeywell building level controller.
XL15B—W7760B Honeywell building level controller.
XL15C—W7760C Honeywell plant level controller.
Performance Specifications
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit might not exactly match listed specifications.
This product is tested and calibrated under closely
controlled conditions; minor performance differences
can be expected if those conditions are changed.
Models: See Table 4.
Dimensions: See Fig. 2.
Finish (color): Trident White.
Batteries: No batteries required.
Table 4. T7350 Thermostat Features.
a
b
Humidity, Occupancy,
Outdoor, Discharge Air Capability
Features
ModelApplications
T7350H1009 Conventional
or
Maximum Stages
b
3 (2)
3 (4)
Heat Pump
T7350H1017 Modulating
2 modulating, 2
c
Humidity, Occupancy,
relay
Outdoor, Discharge Air Capability,
4-20 mA output (2-10 Vdc with 500 ohm resistor)
a
All models are down-selectable and can be configured to control fewer stages than the maximum allowed.
b
Heat pump applications for these models have a maximum of two heat stages and two cool stages.
c
One extra stage (of either heat or cool) can be configured using the auxiliary relay.
563-4368
Auxiliary
Relay
Isolated
Normally
Open
ONWORKS®
L
Capability?HeatCool
Yes
Yes
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Mounting Means:
Mounts on subbase.
Subbase Mounts On:
Wall: Using two 5/8 in. long #6-32 screws (included).
Outlet Box: Using sheet metal screws.
Throttling Range for Modulating Outputs:
Automatically adjusts based on heat/cool stages. Manually
Fig. 2. Dimensions of thermostat and subbase in in. (mm).
Communications
The T7350H provides networking capability in a LONWORKS®
system using a Free Topology Transceiver (FTT) transformercoupled communications port running at 78 kilobits per
second (kbs). The transformer-coupled communications
interface offers a much higher degree of common-mode noise
rejection while ensuring dc isolation. L
ONWORKS
networks are very flexible and convenient to install and
maintain, but it is imperative that the network layout be
carefully planned and accurate documentation created and
maintained. This aids in compliance verification and future
expansion of the network. It also minimizes unknown or
inaccurate wire run lengths, node-to-node (device-to-device)
distances, node counts, total wire length, inaccurate repeater/
router locations, and misplaced or missing terminations.
L
ONWORKS
®
networks can be configured in a variety of ways;
refer to the E-Bus FTT Network Wiring Guidelines, form 742865, for a complete description of network topology rules and
maximum network wire length. If longer runs are required, add
a Q7740A 2-way or Q7740B 4-way repeater to extend the
L
ONWORKS
on LCBS L
types for L
®
Bus length. Q7751A routers are not supported
ONSPEC™ configured systems. Approved cable
ONWORKS
®
Bus communications wiring are Level
IV, 22 AWG (0.34 sq mm) plenum or non-plenum rated
unshielded, twisted pair, solid or stranded conductor wire.
Refer to Table 2 for a list of Honeywell network cable part
numbers. Other Echelon® approved cable may also be used.
Run communications wiring in a conduit, if needed, with nonswitched 24 Vac or sensor wiring. The Free Topology
Transceiver (FTT) communications L
ONWORKS
a polarity insensitive, free topology wiring scheme that, in turn,
supports star, loop, and/or bus wiring.
Fig. 3. T7350H LONMARK® Space Comfort Controller Rooftop Object (8504) with Node Object.
63-43688
nviBypass
nv30
SNVT_switch
nviFanAuto
nv31
SNVT_switch
nviManValue
nv32
UNVT_manValue
nviDlcShed
nv34
UNVT_dlcShed
Manufacturer
Defined
Section
Hardware Input
nvoBypass
nv43
SNVT_switch
nvoOccSchedule
nv44
SNVT_tod_event
nvoOccSensor
nv45
SNVT_occupancy
nvoData1
nv46
UNVT_data1
nvoData2
nv47
UNVT_data2
M22431
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
NETWORK CONFIGURATIONS
The T7350H can be configured to perform a variety of
activities in which data is sent to and/or received from other
nodes on the L
ONWORKS
shared with other network devices includes:
— Current year, month, day, hour, minute, second.
— System mode (HEAT, COOL, AUTO, OFF, EM HEAT).
— Current fan setting (ON, AUTO).
— Space temperature.
— Space relative humidity.
— Discharge air temperature.
— Outdoor air temperature.
— Occupancy sensor status.
— Terminal load.
— Current setpoint.
— Occupied/Unoccupied schedule commands.
— Current occupancy status.
— Occupancy schedule including current occupancy state,
next state and time in minutes until next scheduled
change of occupancy state.
— Relay status (heat/cool stages and fan).
— Alarm status.
— Alarm log including the last five alarms.
— Device Error status.
— Bypass state (multiple XL10 devices follow the bypass
operation of a master device).
A network configuration tool is used to configure the T7350H
Thermostats and other nodes with which the T7350H
interacts. The following is a brief description of the
configurable features that can be commanded over the
network:
•Time Master:
When a T7350H is designated as the network time master,
the current time of day and date is synchronized across the
network every minute. The L
Screen can be used to configure a T7350H as the Network
Time Master. Whenever the time of day or date of the time
master is changed, it automatically adjusts all the other
network devices (T7350H, Q7300 & XL15A) bound to the
time master. When a T7350H is controlled by a time
master, the local day light saving schedule is disabled. The
Day Light Saving option on all time master recipients
should be disabled. This prevents erroneous time changes
(local daylight savings switchover) during temporary
network outages.
Source Destination
T7350H.nvoTime
or
XL15a.nvoTimeOut
Q7300.nvoTime
®
network. Information that can be
ONSPEC™ T7350H General
T7350H.nviTimeSet
or
XL15a.nviTimeIn
Q7300.nviTime
the user is not prevented from making local schedule
changes at the recipient thermostat. Local schedule
changes (at a recipient device) have no effect on the
scheduling commands received from the master device.
When a T7350H is designated as a master schedule
device, it sends its schedule information (current state,
next state, time until next change of state) to the
appropriate T7350H(s) which, in turn, overrides any
existing internal time schedule. The T7350H Thermostat
can provide master scheduling information to multiple
Excel 10 devices. One T7350H shares the schedule
information (current state, next state, time until next
change of state) with the designated Excel 10 devices.
Source Destination
T7350H.nvoOccSchedule
or
XL15a.nvoTodEventCmd[i]
Q7300.nvoOccSchedulei
T7350H.nviOccSchedule
or
XL10.nviTodEvent
XL15c.nviTodEventIn[i]
• System Mode Settings:
System mode settings (HEAT, COOL, AUTO, OFF, EM
HEAT) can be commanded by a remote T7350H or other
compatible XL10 device. A one to many network binding
can be used to command multiple devices from a single
unit. In addition, a network connected Workstation can be
used to change the System Mode.
Command SourceCommand Destination
T7350H.nvoHeatCool
T7350H.nviApplicMode
or Workstation
• Fan Settings:
Fan settings (ON, AUTO) can be changed from a network
connected Workstation.
Source Destination
Workstation
T7350H.nviFanAuto
or Network Tool
• Outdoor Air Temperature Sharing:
If a valid outdoor air temperature value is received at the
T7350H OAT network variable input, that value will be used
in the T7350H. The local OAT sensor of the T7350H is
ignored until the network sensor fails.
Source Destination
T7350H.nviOutdoorTemp
or
XL10.nvoOdTemp
XL15c.nvoOdTemp
T7350H.nvoOutdoorTemp
or
XL10.nviOdTemp
XL15c.nviOdTemp
• Time Schedule:
The occupancy schedule used by a T7350H may reside
locally in that device or remotely in another schedule
device (T7350H, XL15a, XL15b or T7300/Q7300). Local
schedules can be created and modified using the T7350H
keypad, a direct connected PDA, a network connected
configuration tool (L
ONSPEC™) or Command Display.
External schedules can also be modified using the keypad
of the master schedule device, or with a network
connected configuration tool or Workstation. When a
T7350H receives scheduling information over the network,
• Discharge Air Temperature Sharing:
The discharge air temperature value can be shared with
other devices on the network. Note that the T7350H does
not accept a network discharge air temperature input.
Source Destination
T7350H.nvoDischAirTempXL15c.nviDATemp
• Space Temperature Sharing:
If a valid space temperature value is received at the
T7350H Space Temperature network variable input, that
963-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
value will be used in the T7350H as the primary controlled
variable. The local space temperature sensor of the
T7350H is ignored until the network sensor fails.
Source Destination
T7350H.nvoSpaceTemp
or XL10.nvoSpaceTemp
• Space Humidity Sharing:
If a valid humidity value is received at the T7350H Space
Humidity network variable input, that value will be used in
the T7350H as the humidity control variable. The local
space humidity sensor of the T7350H is ignored until the
network sensor fails.
Source Destination
T7350H.nvoSpaceRHT7350H.nviSpaceRH
• Current Setpoint Sharing:
If a valid setpoint value is received at T7350H nviSetpoint,
that value will be used by the T7350H as the center
setpoint. The heat and cool setpoints are then calculated
from this value and are used in the T7350H as the
occupied setpoints. During unoccupied periods,
nviSetpoint is ignored.
Source Destination
T7350H.nvoEffectSetpt
or XL10.nvoEffectSetpt
T7350H.nviSpaceTemp
or XL15c.nviRARH
T7350H.nviSetpoint
• Occupancy Bypass:
Any internal or external scheduled unoccupied state in the
T7350H is overridden by a network occupancy bypass
command. Bypass is a method to command unoccupied
override over the network from another controller (typically
a T7350H or XL10). The source controller manages the
bypass timing.
Source Destination
T7350H.nvoBypass
or
XL10.nvoBypass
XL15a.nvoBypass[i]
XL15c.nvoBypass[i]
• Manual occupancy:
Provides a method to command the occupancy state from
a network workstation. Effective occupancy override works
on a “last in wins” basis. That is, the last occupancy
override command received from any source determines
the override state. The workstation can command
occupied, unoccupied, standby, bypass, or not active (null).
There are several ways to return the device to normal
schedule operation.
1. Power failure reset at the T7350H.
2. Workstation issues a “not active” (null) network com-
mand to T7350H.nviOccManCmd.
3. User activates “Temporary Occupied” button on the
local keyboard. This can be followed by a “Run Schedule” local command.
4. If manual occupancy is commanded to bypass and the
bypass timer times out.
T7350H.nviBypass
• Occupancy Sensor Sharing:
If a valid value is received at the T7350H occupancy
sensor network variable input, that value will be used in the
T7350H as the occupancy sensor. The local T7350H
occupancy sensor is ignored until the network sensor fails.
Source Destination
T7350H.nvoOccSensor
or XL10.nvoSensorOcc
NetworkSensor
NOTE: The occupancy or motion sensor is active whenever
The T7350H effective occupancy is determined in Table 6.
OccupiedOpenStandby
OccupiedClosedOccupied
StandbyNAStandby
UnoccupiedNAUnoccupied
the device is scheduled “Occupied” and a remote or
network occupancy sensor is configured.
Table 6. T7350H Effective Occupancy.
Schedule
Occupancy
Occupancy/Motion
Sensor Contact
T7350H.nviOccSensor
Effective
Occupancy
Source Destination
Workstation
Command Display
XL15b
T7350H.nviOccManCmd
APPLICATION STEPS
Overview
The application steps shown in Table 7 are guidelines for
configuring the T7350H in a L
explain the network role of the T7350H.
Table 7. Application Steps.
Step Description
1Plan the system.
2Determine required network devices.
3Lay out communications and power wiring.
4Prepare wiring diagrams.
5Order equipment.
6Configure T7350.
7Troubleshooting.
ONWORKS
®
Bus network and
63-436810
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Refer to the Light Commercial Building Solution System
Communication Guide form 71-3123 and the E-Bus Wiring
Guidelines, form 74-2865 for a complete description of
network topology rules. Prepare Wiring Diagrams, for wiring
details. Plan to configure each controller. Refer to the Excel
L
ONSPEC™ User Guide, form 74-2937, to configure the
T7350H, XL15 and XL10 Controllers.
Step 1. Plan the System
Plan the use of the T7350H Thermostat according to the job
requirements. Determine the location and functionality of each
device. Verify the sales estimate for the number of other
controllers and devices required. Check the number and type
of other required accessories. When planning the system
layout, consider potential expansion possibilities for future
growth. Planning is very important if HVAC systems and
controllers are to be added in future projects.
NOTEBOOK PC
SHIELDED
RS-232
SERIAL
PORT
INTERFACE
CABLE
Q7760
SLTA
CABLE
PART
NO. 205979
LonWorks
BUS PORT
T7350H
Step 2. Determine Required Network Devices
A maximum of 60 nodes can communicate on a single
L
ONWORKS
comprises one node. If more than 60 nodes are needed, a
Q7751A Router or Q7740 Repeater is necessary. A router or
repeater allows up to 120 controller nodes per network,
divided between two L
that routers are not supported by the LCBS L
system configuration tool. Refer to the Light Commercial
Building Solution System Communication Guide form 71-3123
for LCBS details. Refer to the E-Bus Wiring Guidelines, form
74-2865, for a complete description of network topology rules
and maximum wire lengths. A 209541B Termination Module
may be required. Refer to the Excel 10 FTT Termination
Module Installation Instructions form, 95-7554.
®
Bus segment. Each LONWORKS® Bus device
ONWORKS
®
Bus segments. Please note
ONSPEC™
Step 3. Layout Communications and Power
Wiring:
L
ONWORKS
The communications LONWORKS® Bus, is a 78-kilobit network
that uses transformer isolation and differential Manchester
encoding. The Free Topology Transceiver (FTT) LONWORKS®
communications Bus supports a polarity insensitive, free
topology wiring scheme, refer to the E-Bus Wiring Guidelines
form, 74-2865, for a complete description of L
network topology rules. Fig. 5 shows T7350H devices
connected in a typical free topology L
®
Bus Layout
ONWORKS
ONWORKS
®
network.
®
M22492
Fig. 4. Connecting personal computer to LonWorks® bus.
NOTEBOOK PC
T7350H
RS-232
SLTA
MODEM
T7350H
MODEM
RS-232
SLTA
T7350HT7350H
LonWorks BUS
MODEM
T7350HT7350H
LonWorks BUS
RS-232
SLTA
T7350H
T7350H
LonWorks BUS
T7350H
T7770
WITH NO
LonWorks
BUS ACCESS
T7770
LonWorks BUS
I/O CONNECTIONS
JACK FOR OPERATOR TERMINAL
Fig. 5. Typical topology for T7350 devices in LONWORKS® network.
1163-4368
M22493
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Cable Termination
The FTT network segment requires termination for proper
data transmission performance. Use a 209541B Termination
Module to connect two of the three termination module wires
to the L
ONWORKS
Wiring Guidelines form 74-2865 for details.
®
Bus terminals. Refer to LONWORKS® Bus
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
Singly Terminated Network Segment
In a singly terminated topology segment, only one termination
is required and can be placed anywhere on the segment.
Singly terminated segments use the yellow and brown wires.
If the network topology requires a singly terminated
termination module at a T7350H, connect the singly
terminated module wiring on the appropriate terminals as
shown in Fig. 6.
SUBBASE
BROWN
ORANGE
T5 T6 T7 T4
EB
YELLOW
T3
OSOSASAS
M
MHC HPHSEB
X
PART NO. 209541B
TERMINATION MODULE
W3/Y4 Y3 W2
AUX
RC
AUXRH
Y2
W1GY1
M22494
Fig. 6. Singly terminated LonWorks® bus termination
module.
Doubly Terminated Daisy-Chain Network Segment
In a doubly terminated daisy-chained topology segment, two
terminations are required, one at each end of the topology
segment. Doubly terminated segments use the orange and
brown wires. If the network topology requires a doubly
terminated module at a T7350H (T7350H is the first or last
device on the network cable) connect the termination module
wiring on the appropriate terminals as shown in Fig. 7. For
additional wiring information, refer to the E-Bus Wiring
Guidelines, form 74-2865, and the Excel 10 FTT Termination
Module Installation Instructions, form 95-7554.
SUBBASE
T5 T6 T7 T4
T3
OSOSASAS
W3/Y4 Y3 W2
AUX
Y2
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
1. Loosen subbase terminal screws and connect system
wires.
NOTE: Maximum (and recommended) wire size is 18-
gauge. Do not use wire smaller than 22-gauge. Follow equipment manufacturer wiring instructions
when available. Refer to the Wiring Diagram section
for typical hookups. A letter code is located near
each terminal for identification. Refer to the Specifications section, Tables 8 and 9 for terminal designations.
2. Securely tighten each terminal screw.
3. Push excess wire back into the hole in the wall.
4. Plug the hole with nonflammable insulation to prevent
drafts from affecting the thermostat.
Wiring Details
LONWORKS® network cable should be wired separately from
the power and I/O wires when installing T7350H models. If
this is not possible, use a minimum of 4 in. (102 mm)
separation between split ferrite cores (Fair-Rite 0443164151,
www.fair-rite.com) to ensure compliance with Class B limits
(does not apply to Class A limits). See Fig. 8 to apply ferrite
cores to L
ONWORKS
®
Bus input and output.
Step 4. Prepare Wiring Diagrams
Fig. 9 through 12show T7350 terminal arrangements and
provide detailed wiring diagrams. Reference these diagrams
to prepare the site-specific job drawings.
1.
WIRES TO T7300H
COMMUNICATING SUBBASE
RC
W1GY1
AUXRH
M22495
®
bus termination
BROWN
YELLOW
EB
ORANGE
M
PART NO. 209541B
TERMINATION MODULE
Fig. 7. Doubly terminated L
MHC HPHSEB
X
ONWORKS
modules.
63-436812
M22496
WIRES TO ALL
INPUTS AND
OUTPUTS
2.
WIRES TO T7300H
COMMUNICATING SUBBASE
Fig. 8. Ferrite core wires from T7350H to L
inputs and outputs.
WIRES TO ALL
INPUTS AND
OUTPUTS
ONWORKS
®
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
DISCHARGE
AIR
SENSOR
OSOSASAS
MHC HPHSEB
4
ECONOMIZER
X
3
HEAT
RELAY 3
AUX
W3/Y4 Y3 W2
AUXRH
RC
HEAT
RELAY 2
W1G
Y1
HEAT
RELAY 1
COMPRESSOR
CONTACTOR 1
COMPRESSOR
CONTACTOR 2
Y2
COMPRESSOR
CONTACTOR 3
FAN
RELAY
M22499
LONWORKS
BUS
LONWORKS
BUS
OUTDOOR
123456789
T3
AIR
SENSOR
M
MOTION
SENSOR
T7770 REMOTE SENSOR
SUBBASE
T5 T6T7T4
EB
®
®
L2
2
1
L1
(HOT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
2
3
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
HUMIDITY
SENSOR
Fig. 9. Typical hookup of T7350H1009 in three-stage heat and three-stage cool conventional system with one
transformer.
LONWORKS
BUS
LONWORKS
BUS
2
1
OUTDOOR
T7770 REMOTE SENSOR
SUBBASE
T5 T6T7T4
EB
®
®
L2
L1
(HOT)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.
2
3
HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
L2
L1
(HOT)
HUMIDITY
SENSOR
AIR
SENSOR
123456789
T3
M
MOTION
SENSOR
AUXILIARY
TRANSFORMER
DISCHARGE
AIR
SENSOR
OSOSASAS
MHC HPHSEB
X
HEAT
RELAY 3
AUX
W3/Y4 Y3 W2
AUXRH
RC
3
4
ECONOMIZER
HEAT
RELAY 2
W1G
Y1
HEAT
RELAY 1
COMPRESSOR
CONTACTOR 1
COMPRESSOR
CONTACTOR 2
Y2
COMPRESSOR
CONTACTOR 3
FAN
RELAY
M22497
Fig. 10. Typical hookup of T7350H1009 with auxiliary transformer.
1363-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
LONWORKS
BUS
LONWORKS
BUS
1
OUTDOOR
123456789
T3
AIR
SENSOR
M
MOTION
SENSOR
DISCHARGE
AIR
SENSOR
OSOSAS AXAS
MHC HPHSEB
RCX
2
MODULATING
HEAT
–
(4-20 mA)
+
AC
AH
W1G
AUXRH
HEAT
RELAY 1
3
ECONOMIZER
T7770 REMOTE SENSOR
SUBBASE
T5 T6T7T4
EB
®
®
L2
L1
(HOT)
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
2
3
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
HUMIDITY
SENSOR
MODULATING
–
+
R
X
AUX
Y1
FAN
RELAY
COMPRESSOR
CONTACTOR 1
(4-20 mA)
COOL
R
X
COOLING
TRANSFORMER
L2
L1
(HOT)
M22498
1
Fig. 11. Typical hookup of T7350H1017 for system with two independent heat stages (one modulating), two independent
cool stages (one modulating), and two transformers.
OUTDOOR
T7770 REMOTE SENSOR
SUBBASE
T5 T6T7T4
HS
®
LONWORKS
BUS
®
ONWORKS
L
BUS
L2
1
L1
(HOT)
HEATING
TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.
2
3
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
L2
L1
(HOT)
HUMIDITY
SENSOR
AIR
SENSOR
123456789
T3
M
MOTION
SENSOR
AUXILIARY
TRANSFORMER
DISCHARGE
AIR
SENSOR
OSOSAS MXAS
MHC HP
RCX
2
ECONOMIZER
MODULATING
–
(4-20 mA)
+
MC
MH
W1G
AUXRH
HEAT
RELAY 1
3
R
HEAT
X
Y1
COMPRESSOR
CONTACTOR 1
FAN
RELAY
MODULATING
–
(4-20 mA)
+
AUX
COOL
R
X
L2
1
L1
COOLING
TRANSFORMER
(HOT)
M22491
Fig. 12. Typical hookup of T7350H1017 for system with two independent heat stages (one modulating), two independent
cool stages (one modulating), and three transformers.
63-436814
General Considerations
Table8 lists wiring types, sizes and distances for the T7350
and Excel 10 products. The T7350 terminal strip accepts 18
through 22 AWG (0.82 to 0.34 sq. mm) wire.
Table 8. Field Wiring Reference.
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Wire Function
Digital Outputs:
W Y G AUX X
Modulating Outputs:
MX MH MC
Remote Humidity
Sensor:
HS HC HP
Discharge Air
Temperature Sensor:
AS
Outdoor Air
Temperature Sensor:
OS
Motion Sensor:
M
Wall Module
connections:
T3-T7
Power Wiring to:
X RH RC
ONWORKS
L
®
Bus
(Non-Plenum).
LONWORKS® Bus
(Plenum Rated).
Recommended Wire
Size (Minimum)
18 AWG (0.82 sq mm)
five wire cable bundle.
Specification or
Requirement
Standard thermostat
wire.
Honeywell Part
Number Distance (Maximum)
AK37261000 feet.
18 AWG (0.82 sq mm)1 pair per output.AK3757C, AK3744C,
AK3741A, AK3702x
18 to 22 AWG
(0.82 to 0.34 sq mm)
18 to 22 AWG
(0.82 to 0.34 sq mm)
3 wires.AK3746C, AK3724,
AK3703x
1 pair.AK4606ABE,
AK4628AWH,
AK3702x, AK3741A,
AK3744C, AK3757C
18 AWG (0.82 sq mm)1 pair.AK3757C, AK3744C,
AK3741A, AK3702x
18 to 22 AWG
(0.82 to 0.34 sq mm)
1 pair.AK4606ABE,
AK4628AWH,
AK3702x, AK3741A,
AK3744C, AK3757C
18 to 22 AWG
(0.82 to 0.34 sq mm)
Twisted pair wire is
recommended for wire
runs longer than 100
ft. The number of pairs
depends on the model
Limited by line-loss
effects on power
consumption.
Guidelines Users
Guide 74-2865 for
maximum length and
generic cable
specifications.
—
NOTE: 1. The X, RH and RC terminals will accept 14 to 22 AWG. 14 and 16 AWG should be avoided since the stiff cable
interferes with the cover to subbase installation.
1563-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 9. Honeywell Cable Details.
Honeywell Part
Number Size (AWG)Number of wiresJacketPlenum Rated Description
AK3798222YesNoE-bus cable.
AK3797222YesYesE-bus cable.
AK3799224YesYesE-bus cable.
AK4606ABE222YesNoBeige jacket.
AK4628AWH222YesYesWhite jacket.
AK3702x182NoNo—
AK3741A182YesNo—
AK3744C182YesYesRed jacket.
AK3757C182YesYesWhite jacket.
AK3703x183NoNo—
AK3724183YesNoTan jacket.
AK3746C183YesYesTan jacket.
AK3726185YesNoTan jacket.
AK3712x162NoNoTFN
AK3754142NoNoTFN
63-436816
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Step 5. Order Equipment
After compiling a bill of materials through completion of the
previous application steps, refer to Table10, Ordering
Information.
Table 10. Ordering Information.
Part NumberProduct DescriptionComments
T7350H1009Communicating Thermostat with three heating and
three cooling digital outputs.
T7350H1017Communicating Thermostat with two modulating
outputs, one heating and one cooling digital output.
T7771ARemote Temperature Sensor.• Pushbutton setpoint adjustment with LED indicators.
T7770A1006Remote Wall Module.• Basic model with room temperature sensor.
T7770B1046Remote Wall Module.• ± setpoint change.
T7770C1044Remote Wall Module.• ± setpoint change.
T7770D1000Remote Wall Module.• OCC button and LED.
AK3798L
AK3797L
AK3799L
ONWORKS
ONWORKS
ONWORKS
®
Bus (Non-Plenum), 1 pair.—
®
Bus (Plenum rated), 1 pair.—
®
Bus (Plenum rated), 2 pair.—
209541BFTT Network Termination Module.—
H7625
Remote Humidity Sensors—
H7635
C7089A
Outdoor Air Sensors.—
C7170A,
C7031G2014
Duct Discharge Air Sensors:
C7041B
C7041C
C7041J
C7770A
50000452-
6 inch probe.
18 inch probe.
150 inch averaging.
6 inch probe.
Troubleshooting Cable.One Troubleshooting Cable required for each
001
50000083-
Thermostat Interface Module (TIM).One TIM required for each installation technician. Note
001
PDAQualified Palm OS PDA.One PDA required for each installation technician.
50000314-
PDA Configuration Software.One Configuration software package can be used to
001
• Optional heat pump control.
• Isolated auxiliary digital output.
• Isolated auxiliary digital output.
• Occupied/unoccupied override (bypass) with LED.
•L
ONWORKS
®
Bus jack.
• OCC button and LED.
—
installation technician.
that a network tool such as L
ONSPEC™ eliminates the
need for a TIM.
Refer to the PDA Configuration Software for an up-todate list of qualified PDA hardware. Note that a network
tool such as L
ONSPEC™ eliminates the need for a PDA.
program multiple PDAs. Note that a network tool such
ONSPEC™ eliminates the need for a PDA.
as L
Step 6. Configure T7350
Use Excel LONSPEC™ Software to configure the T7350H
Thermostat for specific applications. The Excel L
User’s Guide, form 74-2937, provides software operation
instructions for this personal computer based application.
ONSPEC™
1763-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Step 7. Troubleshooting
Table 11. Troubleshooting Information.
SymptomPossible CauseAction
Display will not
come on.
Temperature
display is
incorrect.
Temperature
settings will not
change.
(Example: Cannot
set heating higher
or cooling lower.)
Room
temperature is out
of control.
Heat will not come
on.
Thermostat is not being powered.Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and RH terminals.
If missing 24 Vac:
• Check if circuit breaker is tripped; if so, reset circuit breaker.
• Check if system fuse is blown; if so, replace fuse.
• Check if the HVAC equipment power switch is in the Off position; if
so, set to the On position.
• Check wiring between thermostat and HVAC equipment. Replace
broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
Room temperature display has been
recalibrated.
Thermostat is configured for °F or °C
Use PDA or L
ONSPEC™ configuration software to recalibrate as
desired.
Press both Run Schedule and Copy, then reconfigure the display.
display.
Bad thermostat location.Relocate the thermostat.
Display shows three dashes and a
degree sign (all systems shut down).
Upper or lower temperature limits
were reached.
T7350 is set for remote sensing and sensor is missing or circuit is
either open or shorted.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (7 to 31°C)
• Cooling limits are 45 to 99°F (9 to 37°C)
Occupied setpoint temperature
range stops were configured.
Keypad is locked. When a locked
key is pressed, LOCKED appears
momentarily on the LCD.
Remote temperature sensing is not
Using a PDA or L
ONSPEC™, check setpoint stops. If necessary,
reconfigure the stop(s).
• Use PDA or L
ONSPEC™ (Set, Display) to unlock keypad.
• Press both Run Schedule and Copy, then change keypad lock
level.
Check all remote sensors.
working.
No power to the thermostat.Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and RH terminals.
If missing 24 Vac:
• Check if circuit breaker is tripped; if so, reset circuit breaker.
• Check if system fuse is blown; if so, replace fuse.
• Check if the HVAC equipment power switch is in the Off position; if
so, set to the On position.
• Check wiring between thermostat and HVAC equipment. Replace
broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
Thermostat minimum off time is
activated.
System selection is set to Off or
• Wait up to five minutes for the system to respond.
No power to the thermostat.Check that X terminal is connected to the system transformer.
Check for 24 Vac between X and RH terminals.
If missing 24 Vac:
• Check if circuit breaker is tripped; if so, reset circuit breaker.
• Check if system fuse is blown; if so, replace fuse.
• Check if the HVAC equipment power switch is in the Off position; if
so, set to the On position.
• Check wiring between thermostat and HVAC equipment. Replace
broken wires and tighten loose connections.
If 24 Vac is present, proceed with troubleshooting.
Thermostat minimum off time is
activated.
System selection is set to Off or
• Wait up to five minutes for the system to respond.
• Use PDA or L
ONSPEC™ to configure cooling response.
Set system selection to Cool or Auto.
Heat.
System indicator
(flame: heat,
snowflake: cool) is
displayed, but no
warm or cool air is
coming from the
registers.
The call for heat or cool is not yet
given.
Conventional heating equipment
turns the fan on only after the
Check if any stage indicators (dots next to the system indicator) are
displayed. With no display of stage indicators, no call for cool/heat is
yet given.
For the modulating T7350H1017 only: Check the information
screens. MODHEAT or MODCOOL percentages of zero and 100
indicate an extreme signal from the given terminal.
Wait one minute after seeing the on indicator and then check the
registers.
furnace has warmed to a setpoint.
Heating or cooling equipment is not
Verify operation of heating or cooling equipment in self-test.
operating.
1963-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
APPENDIX A - NETWORK TOOLS & WORKSTATIONS
Table 12. T7350H Operational Support.
Network Tools & Workstations
T7350H Operational Support
Device ConfigurationXXX
View & Modify Weekly ScheduleXXXXX
View & Modify Holiday ScheduleXXXXX
Data MonitoringXXXXXX
Command Outputs to Manual ValueXXXX
Override System DelaysXXXX
Room Temperature CalibrationXXX
Command Occupancy OverrideXXXXXX
Command Fan Operation (On Auto)XXXX
Command System Mode (off, auto, heat, cool)XXXX
View & Modify Temperature SetpointsXXXXXX
Report T7350 alarm dataXXXX
Network Time Scheduler for T7350 DevicesX
Generate Trend & Log files with T7350 dataX
User defined T7350 analog & digital alarmsX
Update T7350 Time ClockXXXXXX
Set T7350 as network Time MasterX
View T7350 Cover Firmware VersionXXX
Update T7350 Cover FirmwareX
View T7350H SubBase Firmware VersionXXX
Update T7350H SubBase FirmwareX
Summary of
LONSPEC™
LONSTATION™
XL15B
W7760B -
Cmd Display -
CARE
S7760
LNS Plugin
DataMon
63-436820
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
APPENDIX B - NETWORK ALARM REPORTING
Table 13. T7350H Alarm Change of State Event.
A T7350H alarm change of state event is reported by the manufacturer defined output network variable nvoAlarmH.
nvoAlarmH FieldDescription
subnet
The L
ONWORKS
bound, it reports domain index 0.
0: Invalid subnet (power up value)
1-255: Subnet number
node
The L
ONWORKS
bound, it reports domain index 0.
0: Invalid entry (power up value)
1-127: Node number
subnet number in the domain entry to which nvoAlarmH is bound. If nvoAlarmH is not
®
node number in the domain entry to which nvoAlarmH is bound. If nvoAlarmH is not
Table 14. T7350 Current Alarm Status.
The T7350current alarm status is reported by the manufacturer defined output network variable nvoAlarmStatus.
nvoAlarmStatus
Field
Description
coverCommFailCommunications between the cover and sub-base.
0: No alarm (power up value).
1: The communications between the thermostat cover assembly and the sub-base has failed in one or
both directions. The data from the cover to the sub-base has not been received for at least 90
seconds, or data from the sub-base is not updating the cover assembly.
invalidIOConfigOutput configuration error.
0: No alarm (power up value).
1: The number of outputs configured exceeds the capability of the sub-base to support them.
Considers sub-base type, heat pump/conventional application, maxCoolStgs, maxHeatStgs.
sensorFailSensor failure.
0: No alarm (power up value).
1: One of the analog sensors on the cover assembly has failed or is out of range (high or low).
networkCommFailNetwork Communications Failure.
0: No alarm (power up value).
1: One of the bound network input network variables is not being updated periodically. This alarm may
be caused by a failed node or a damaged L
ONWORKSNETWORK cable.
invidSubBaseTypSub-base type error.
0: No alarm (power up value).
1: The detected sub-base type is not supported by the firmware version of the cover assembly.
2163-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 15. Identifying Five Most Recent T7350 Alarms.
The five most recent T7350 alarms are identified in the manufacturer defined output network variable nvoAlarmLog.
T7350H errors are reported through the manufacturer defined output network variable, nvoError.
nvoError FieldDescription
errLoclSpaceSensrLocal space temperature sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errRemtSpaceSensrRemote space temperature sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errNetSpaceSensrNetwork space temperature sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured by the thermostat to function but is not being updated by either the bound
network sensor or by the subbase (faulty subbase).
errLoclHumSensrLocal Humidity sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errRemtHumSensrRemote Humidity sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errNetHumSensrNetwork Humidity sensor not working.
errRemtOdSensrRemote Outdoor air sensor not working.
errNetOdSensrNetwork Outdoor air sensor not working.
errRemtSetPtRemote wall module set point is out of range or disconnected.
errDischSensrDischarge sensor out of range or disconnected.
errSelfTestSelf test failure. Upon factory test power up, a self test of memory is performed. If external RAM,
errCoverCommFailCommunications between the cover and sub-base
0: Sensor value is OK. (power up value)
1: Sensor is configured by the thermostat to function but is not being updated by either the bound
network sensor or by the subbase (faulty subbase).
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
0: Sensor value is OK. (power up value)
1: Sensor is configured by the thermostat to function but is not being updated by either the bound
network sensor or by the subbase (faulty subbase).
0: Value is OK. (power up value)
1: Remote wall module set point is configured to function and is out of range or disconnected.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
maxCoolStgs, maxHeatStgs.
0: The outputs configuration is consistent with the sub-base type selected (power up value)
1: The number of outputs configured exceeds the capability of the sub-base to support them.
0: The sub-base is a valid sub-base type (power up value)
1: The detected sub-base type is not supported by the firmware version of the cover assembly.
EEPROM, or application FLASH memory fails the test, nvoError.errSelfTest is set. This bit is intended
for use in production testing. Field devices should ignore this bit.
0: Passed the test
1: Failed the test
0: No error (power up value)
1: The communications between the thermostat cover assembly and the sub-base has failed in
one or both directions. The data from the cover to the sub-base has not been received for at least
90 seconds, or data from the sub-base is not updating the cover assembly.
2363-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 16.
Reporting T7350H Errors. (Continued)
T7350H errors are reported through the manufacturer defined output network variable, nvoError.
0: Sub-base and cover firmware are compatible. (power up value)
1: The firmware version in the sub-base is unable to communicate correctly with the firmware
version of the cover assembly. The cover assembly Public Interface number of the sub-base is not
compatible with the Public Interface number of the sub-base. That is nroT7350Ver.commVer does
not match the version supported by the sub-base. Communications with the sub-base is turned
off.
errNviSpaceTempnviSpaceTemp network variable is:
0: either not bound or is bound and being updated periodically (power up value)
1: bound and not being updated periodically (communications or source node failure)
errNviOccSchedulenviOccSchedule network variable is:
0: either not bound or is bound and being updated periodically (power up value)
1: bound and not being updated periodically (communications or source node failure).
errNviOccSensornviOccSensor network variable is:
0: either not bound or is bound and being updated periodically (power up value)
1: bound and not being updated periodically (communications or source node failure)
errNviApplicModenviApplicMode network variable is:
0: either not bound or is bound and being updated periodically (power up value)
1: bound and not being updated periodically (communications or source node failure)
errNviOutdoorTempnviOutdoorTemp network variable is:
0: either not bound or is bound and being updated periodically (power up value)
1: bound and not being updated periodically (communications or source node failure)
errNviSpaceRHnviSpaceRH network variable is:
0: either not bound or is bound and being updated periodically (power up value)
1: bound and not being updated periodically (communications or source node failure)
errNviBypassnviBypass network variable is:
0: either not bound or is bound and being updated periodically (power up value)
1: bound and not being updated periodically (communications or source node failure)
errNviDlcShednviDlcShed (Demand Limit Control Shed signal) network variable is:
0: either not bound or is bound and being updated periodically (power up value)
1: bound and not being updated periodically (communications or source node failure)
63-436824
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
APPENDIX D - NETWORK ACCESS TO LOCAL SENSOR DATA
Table 17. T7350H Reports Local Sensor Data.
The T7350H reports local sensor data using the following output network variables.
Nv Name
nvoDischAirTemp Discharge Temperature
nvoOccSensorOccupancy Sensor OutStatus of occupancy sensor
nvoOutdoorTemp Outdoor Temperature OutThe current outdoor temperature. The sensor value source is specified by
nvoSpaceRHSpace Humidity OutThe current space humidity. The sensor value source is specified by
nvoSpaceTempSpace Temperature OutThe current space temperature. The sensor value source is specified by
LonSpec Reference
NameDescription
Out
The current discharge air temperature. The sensor value source is configured
by nciConfig.dischAirSensor. A value of 327.67 means the sensor is not
functioning correctly or is out of range.
327.67: Power up value
0: OC_OCCUPIED
1: OC_UNOCCUPIED
-1: OC_NUL (not configured and power up value)
nciConfig.oDAirSensor. A value of 327.67 means the sensor is not functioning
correctly or is out of range.
327.67: Power up value
nciConfig.humiditySensor. A value of 163.84 means the sensor is not
functioning correctly or is out of range.
163.84: Power up value
nciConfig.spaceSensor. A value 327.67 means the sensor is not functioning
correctly or is out of range.
327.67: power up value
APPENDIX E - SCHEDULING
NETWORK DEVICES
A T7350H can be used to time schedule the following
Honeywell controllers:
A single T7350 can be configured to schedule all (up to 119)
of the compatible controllers connected to the same network.
This is accomplished by a one to many binding from the
source T7350 to the destination controller or object.
T7350.nvoOccSchedule > XL10.nviOccSchedule.
L
ONSPEC™ automatically implements these NV bindings
based on the selection of Unscheduled Objects (XL10(s),
Q7300(s), T7300H(s) and XL15cAP(s) located on the
L
ONSPEC™ T7350 Scheduling Screen.
APPENDIX F - NETWORK MASTER
CLOCK
A T7350H can be used as the network time master for the
following network connected Honeywell controllers:
• Another T7350H.
• T7300/Q7300.
• XL15A.
This is accomplished by a one to many binding from the
source T7350H to the destination controller. The following is
an example NV binding of one T7350H as a time master to
another.
T7350H.nvoTime > T7350H.nviTimeSet
ONSPEC™ automatically implements these NV bindings
L
based on the selection of Network Time Master check box on
the T7350 General configuration screen. The Day Light
Saving Start and Stop Month on all time master recipients
should be configured to None (invalid). This prevents
erroneous time changes during temporary network outages.
2563-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
APPENDIX G - NETWORK CONNECTIONS TO OTHER LCBS DEVICES
Table 18. Network Connections to XL15A AP Inputs.
T7350H Network Variable Outputs can be used as inputs to XL15A application objects.
XL15A
Application ObjectApplication Input
Analog AlarmSelected Analog ValuenvoSpaceTemp
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1PercentCmdHeat
nvoData1PercentCmdCool
Digital AlarmSelected Digital ValuenvoData2RelayHeat3
nvoData2RelayCool3
nvoData2RelayHeat2
nvoData2RelayCool2
nvoData2RelayAux
nvoData2RelayHeat1
nvoData2RelayCool1
nvoData2RelayFan
nvoData2dehumidActive
Bypass LogsSelect Bypass ObjectnvoEffectOccup
Source T7350H
Network VariableNetwork Variable Field
Run TimesSelect Point NamenvoData2RelayHeat3
nvoData2RelayCool3
nvoData2RelayHeat2
nvoData2RelayCool2
nvoData2RelayAux
nvoData2RelayHeat1
nvoData2RelayCool1
nvoData2RelayFan
TrendsTrend PtnvoSpaceTemp
nvoEffectSetpt
nvoEffectOccup
nvoHeatCool
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1HeatStgsOn
nvoData1CoolStgsOn
nvoData1PercentCmdHeat
nvoData1PercentCmdCool
nvoData2RelayHeat3
nvoData2RelayCool3
nvoData2RelayHeat2
63-436826
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 18. Network Connections to XL15A AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15A application objects.
XL15A
Application Object
Application InputSource T7350H
Network Variable
Network Variable Field
nvoData2RelayCool2
nvoData2RelayAux
nvoData2RelayHeat1
nvoData2RelayCool1
nvoData2RelayFan
nvoData2dehumidActive
DLC Override IfnvoSpaceTemp
Demand Limit ControlnvoEffectSetpt
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1PercentCmdHeat
nvoData1PercentCmdCool
Analog Logic FunctionAnalog InputnvoSpaceTemp
nvoEffectSetpt
nvoDischAirTemp
nvoTerminalLoad
nvoSpaceRH
nvoOutdoorTemp
nvoData1PercentCmdHeat
nvoData1PercentCmdCool
Digital Logic FunctionDigital InputnvoAlarmStatusCoverCommFail
nvoAlarmStatusInvalidIOConfig
nvoAlarmStatusSensorFail
nvoAlarmStatusnetworkCommFail
nvoAlarmStatusInvalidSubBaseType
nvoErrorerrLoclSpaceSensr
nvoErrorErrRemtSpaceSensr
nvoErrorErrNetSpaceSensr
nvoErrorErrLoclHumSensr
nvoErrorErrRemtHumSensr
nvoErrorerrNetHumSensr
nvoErrorErrRemtOdSensr
nvoErrorErrNetOdSensr
nvoErrorErrRemtSetPt
nvoErrorErrDischSensr
nvoErrorerrIOConfig
nvoErrorerrSubBaseType
nvoErrorerrSubBaseVerMisMatch
nvoErrorerrNviSpaceTemp
nvoErrorerrNviOccSchedule
nvoErrorerrNviOccSensor
nvoErrorerrnviApplicMode
nvoErrorerrnviOutdoorTemp
2763-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 18. Network Connections to XL15A AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15A application objects.
XL15A
Application Object
Application InputSource T7350H
Network Variable
Network Variable Field
nvoErrorerrnviSpaceRH
nvoErrorerrNviBypass
nvoErrorerrNviDLCShed
nvoData2RelayHeat3
nvoData2RelayCool3
nvoData2RelayHeat2
nvoData2RelayCool2
nvoData2RelayAux
nvoData2RelayHeat1
nvoData2RelayCool1
nvoData2RelayFan
nvoData2dehumidActive
Control LoopLoopDisablenvoAlarmStatusCoverCommFail
nvoAlarmStatusInvalidIOConfig
nvoAlarmStatusSensorFail
nvoAlarmStatusnetworkCommFail
nvoAlarmStatusInvalidSubBaseType
nvoErrorerrLoclSpaceSensr
nvoErrorErrRemtSpaceSensr
nvoErrorErrNetSpaceSensr
nvoErrorErrLoclHumSensr
nvoErrorErrRemtHumSensr
nvoErrorerrNetHumSensr
nvoErrorErrRemtOdSensr
nvoErrorErrNetOdSensr
nvoErrorErrRemtSetPt
nvoErrorErrDischSensr
nvoErrorerrIOConfig
nvoErrorerrSubBaseType
nvoErrorerrSubBaseVerMisMatch
nvoErrorerrNviSpaceTemp
nvoErrorerrNviOccSchedule
nvoErrorerrNviOccSensor
nvoErrorerrnviApplicMode
nvoErrorerrnviOutdoorTemp
nvoErrorerrnviSpaceRH
nvoErrorerrNviBypass
nvoErrorerrNviDLCShed
nvoData2RelayHeat3
nvoData2RelayCool3
nvoData2RelayHeat2
nvoData2RelayCool2
nvoData2RelayAux
nvoData2RelayHeat1
nvoData2RelayCool1
63-436828
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Table 18. Network Connections to XL15A AP Inputs. (Continued)
T7350H Network Variable Outputs can be used as inputs to XL15A application objects.
nciApplVerApplication versionCONFIGApplication type: identifies the current application number for this
nciBypassTimeBypass TimeCONFIGTemporary Occupied Override duration in minutes.
nciConfigNAFTP
nciConfigPtsNAFTP
nciDayLghtSavNAFTP
nciDaySchedule0NAFTP
nciDaySchedule1NAFTP
nciDaySchedule2NAFTP
nciDaySchedule3NAFTP
nciDaySchedule4NAFTP
nciDaySchedule5NAFTP
nciDaySchedule6NAFTP
nciDaySchedule7NAFTP
nciDeviceNameDevice NameCONFIGDevice Name is an 18 character field used to identify the device
nciHolSchedNAFTP
ONSPEC™ Ref NameClassDescription
device given by a tool.
0: (Default).
Increment: increased by one whenever any configuration
parameter changed by PDA or thermostat keyboard. L
ONSTATION™ does not change this field.
and L
0: (Default).
Time Stamp: indicates the last change to the device application
configuration. The time stamp meets the ANSI C time stamp
requirement specifying the number of seconds elapsed since
midnight (0:00:00), January 1, 1970. It is represented in the Intel
Format. If the T7350 keyboard or the PDA Config Tool updates
any configuration parameters, the time is incremented.
0: (Default).
Version Number: identifies the version number of the application
for this device. If the T7350 keyboard or the PDA Config Tool
updates any configuration parameters, is incremented.
0: (Default).
180: (Default).
Thermostat configuration parameters.
CONFIG
Thermostat operating setpoint values for the control algorithms
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
CONFIG
contained in the Thermostat application code.
Daylight-saving start and end calendar schedule.
Event time schedule for Sunday.
Event time schedule for Monday.
Event time schedule for Tuesday.
Event time schedule for Wednesday.
Event time schedule for Thursday.
Event time schedule for Friday.
Event time schedule for Saturday.
Event time schedule for designated Holiday.
uniquely as one device at the site or project. The content of Device
Name is maintained by a management node. If Device Name is all
ASCII blanks, it is considered un-configured by Honeywell tools.
ASCII blanks: (Default)
nciRcvHrtBtController Receive TimeCONFIGReceive heartbeat time (seconds) for all failure detect heartbeat
network variables in this node.
0: Disable failure (Default).
300: Typical value in Honeywell system.
nciSetpointsSetpoint ConfigCONFIGHeating and Cooling SetPoints in Celsius engineering units.
Occupied cool set-point.
23.9 C: (Default)
Standby cool set-point.
25.6 C: (Default).
Unoccupied cool set-point.
29.4 C: (Default).
Note:
It is required that:
UnoccCl>=OccCl>=OccHt+1.11 C.
UnoccCl>=StdByCl>=StdByHt+1.11 C.
If the above criteria is not met, then the nciSetpoints received over
the L
ONWORKS network will not be accepted, and all the current
controlling set points will be restored from the thermostat.
Occupied heat set-point.
21.1 C: (Default).
Standby heat set-point.
19.4 C: (Default).
Unoccupied heat set-point.
12.8 C: (Default).
It is required that:
UnoccHt<=OccHt<=OccCl-1.11 C.
UnoccHt<=StdByHt<=StdByCl-1.11 C.
If the above criteria is not met, then the nciSetpoints received over
the L
ONWORKS network will not be accepted, and all the current
controlling set points will be restored from the thermostat.
nciSndHrtBtController Send TimeCONFIGSend heartbeat time (seconds) for all Guaranteed periodic update
heartbeat network variables in this node.
0: Disable periodic update (Default).
55: Typical value in Honeywell system.
nroPgmVerProgram VersionCONSTThe Honeywell program identifier and subbase firmware version
number.
nroT7350VerT7350 VersionCONSTDetailed T7350 cover assembly firmware version information.
nviApplicModeApplication Mode InINThermostat System mode switch:
0: HVAC_AUTO
1: HVAC_HEAT
3: HVAC_COOL
6: HVAC_OFF
8: HVAC_EMERG_HEAT
Others: Considered to be HVAC_AUTO.
Failure detect and mains power up value: HVAC_AUTO.
nviBypassBypass InINRemote time bypass input from usually from another device.
Bypass is a method to command unoccupied override over the
network from another controller. The other controller does the
bypass timing. nviBypass can be used to place the T7350H into
temporary occupied mode. This mode will bypass the time of day
occupancy schedule in this device.
Val ue
State Action
0 NA Do not bypass the time of day
occupancy schedule.
NA 0 or -1 Do not bypass the time of day
occupancy schedule.
0.5 - 100 1 or Bypass the time of day occupancy
greater schedule.
0 0 Mains power up and fail detect value.
nviDlcShedDLC Shed InINDemand limit duty cycle load shed command from a network
device.
When a shed request is received, the thermostat “bumps” the
control set point up for cooling and down for heating. The amount
of the “bump is a user set point selection. The shed state remains
until a DLC restore command is received or network
communication is lost. When the unit transitions from shed to
restore, the set point is ramped back to the original set point over a
period of 60 minutes. The control only sheds when the thermostat
is in the occupied mode.
Value:
0: No load shed being called (mains power up or failure detect
value).
1 or other values: Call for load shedding.
nviFanAutoFanOnAuto InINAuto Fan switch (last in wins).
value = 0, state = don’t care:
Fan is On.
value = Don’t care, state = 0 or -1:
Fan is On.
Value = 0.5 - 100: state = 1 or greater:
Fan is On when there is a call for heat / cool.
Failure detect and mains power up value: No change from
previous value.
Val ue
State Action
0 NA Fan is ON.
NA 0 or -1 Fan is ON.
0.5 - 100 1 or Fan is ON when there is a call for
greater heat / cool.
no no Mains power up and fail detect value.
change change
nviFilePosFile Position InIN
Supports L
ONMARK
®
FTP file transfer. Random Access file Pointer
to first byte to be transferred and Number of bytes to transfer.
nviFileReqFile Request InIN
Supports L
ONMARK
®
FTP file transfer. Message request
management is communicated through this input variable.
nviInUseInUseINIn use number is used by a management node to indicate to all
nviOccManCmdOccupancy Cmd InINManual occupancy is a method to command the occupancy state
from a network workstation. Effective occupancy override works
on a “last in wins” basis. That is, the last occupancy override
command received from any source determines the override state.
The workstation can command occupied, unoccupied, standby,
bypass, or not active (null).
nviOccManCmd is used to place the T7350H into manual
occupancy (note there is no timer associated with
nviOccManCmd).
Manual occupancy input from a network device:
-1: OC_NUL not connected (mains power up).
Others: same as OC_NUL.
NOTE: If nviOccManCmd is OC_BYPASS and the bypass timer
(nvoData1.bypassTime) times out, then nviOccManCmd
is set to OC_NUL.
nviOccScheduleOccupancy Schedule InINThere are 2 distinct modes of operation: local schedule and
network schedule. The local schedule mode causes the T7350H
to change set points by using the scheduler in the T7350H. The
network schedule mode causes the T7350H to change set points
from a network-based scheduler. The network schedule, when
valid, overrides the local schedule.
The network schedule input is nviOccSchedule. This input has
current state, next state and tuncos (Time Until Next Change of
State). It is bound from another scheduler such as the XL15A or
T7300/Q7300H. The XL15B or a workstation can also write to it in
an “unbound” relationship.
If the network schedule is not periodically updated the T7350H
resumes local scheduling. Periodically means at a rate greater
than the fail detect time. This rate is typically 55 seconds, 300
seconds maximum. (The actual rate and maximum depend on the
configured heartbeat and failure detect times.)
Current scheduled occupancy state:
0: OC_OCCUPIED
1: OC_UNOCCUPIED
3: OC_STANDBY
Others: same as OC_NUL.
-1: OC_NUL (mains power up and fail detect value).
Next scheduled occupancy state:
0: OC_OCCUPIED
1: OC_UNOCCUPIED
3: OC_STANDBY
Others: same as OC_NUL.
-1: OC_NUL (mains power up and fail detect value).
Time in minutes until next scheduled change of occupancy state:
nviOccSensorOccupancy Sensor InINThere are 3 distinct modes of operation: local occupancy sensor,
network occupancy sensor, or none.
The network occupancy input is nviOccSensor. It is bound from
another sensor or controller with occupancy status.
Occupancy sensor input from a network device:
0: OC_OCCUPIED
1: OC_UNOCCUPIED
-1: OC_NUL not connected (mains power up and fail detect
value).
Others: same as OC_NUL.
NOTE: If nviOccSensor is not invalid (OC_NUL), nviOccSensor
is used as the occupancy sensor even if another sensor
or no sensor is configured.
nviOutdoorTempOutdoor Temperature InINOutdoor temperature input from a network device. Ignored unless
nciConfig.oDAirSensor specifies a network configuration.
327.67: means to ignore comODTemp.
327.67: mains power up and failure detect value.
NOTE: If nviOutdoorTemp is not invalid (327.67), nviOutdoor-
Temp is used as the outdoor temperature even if another
sensor or no sensor is configured.
nviPgmProgram InINMemory address and data being sent to cover assembly flash
memory.
nviRequestRequestINInput variable for managing network requests for status.
nviSetpointSetpoint InINDesired space temperature (Celsius) set by remote network
device.
327.67: means to ignore nviSetPoint.
327.67: mains power up value.
nviSpaceRHSpace Humidity InINSpace humidity input (percent) from a network device. Ignored
unless nciConfig.humiditySensor specifies a network
configuration.
163.83: mains power up and failure detect value.
NOTE: If nviSpaceRH is not invalid (163.83), nviSpaceRH is
used as the space relative humidity even if another sensor or no sensor is configured.
nviSpaceTempSpace Temperature InINWhen configured for a network sensor and periodically updated,
the network space temperature sensor will override both the local
and remote sensors.
Space temperature input (Celsius) from a network device. Values
less than -2.2 will be clipped to -2.2. Values greater than 60 will be
clipped to 60.
327.67: means to ignore nviSpaceTemp.
327.67: mains power up and failure detect value.
NOTE: If nviSpaceTemp is not invalid (327.67), nviSpaceTemp is
used as the space temperature even if another sensor or
no sensor is configured.
nviTimeSetTime InINSet current month, day, year, hour, minute, second
Time synchronization will be to a network device that has been
designated as the “time master.” Time synchronization will occur at
the Guaranteed Periodic Update rate (typically every 55 seconds).
nvoAlarmLogAlarm Log OutOUTReports the last five alarms.
nvoAlarmStatusAlarm Status OutOUTStatus of the following alarms states:
Communications between the cover and sub-base.
0: No alarm (power up value).
1: The communications between the thermostat cover
assembly and the sub-base has failed in one or both directions.
The data from the cover to the sub-base has not been received
for at least 90 seconds, or data from the sub-base is not
updating the cover assembly.
Output configuration error:
0: No alarm (power up value).
1: The number of outputs configured exceeds the capability of
the sub-base to support them. Considers sub-base type, heat
pump / conventional application, maxCoolStgs, maxHeatStgs.
Sub-base type error:
0: No alarm (power up value).
1: The sub-base is not a valid sub-base type for the firmware in
the cover assembly.
Network Communications Failure:
0: No alarm (power up value).
1: One of the bound network input variables is not being
updated periodically. This alarm may be caused by a failed
node or a damaged LonWorks network cable.
Sensor failure:
0: No alarm (power up value).
1: One of the analog sensors on the cover assembly has failed
or is out of range (high or low).
nvoBypassBypass OutOUTThe T7350H uses nvoBypass to command bypass to other XL10
nodes. When the T7350 is in bypass, it commands nvoBypass.
This is a one to many bound relationship. “Many” means one
T7350H can command bypass on all XL10s connected on the
subnet.
Reports whether this device is in timed bypass of the scheduled
occupancy state. Used by other devices to also bypass the time of
day schedule.
Val ue
State Action
0 0 This device is not in bypass
Power up value
1 100 This device is in bypass
nvoData1nvoData1OUTReports Manufacturer Specific Device Data including:
nvoOccScheduleTime Of Day OutOUTThis output has current state, next state and tuncos (Time Until
Change of State). This output is typically bound to other
controller(s) that need a schedule command.
This output is the combination of the local schedule and the
network schedule command. It doesn’t include any bypass,
override, or manual occupancy commands that affect this T7350H.
There is no TOD assignment table in the T7350H. The T7350H
allows a one to many binding of nvoOccSchedule. This means
one T7350H can command all of the XL10s on the subnet – up to
119 controllers.
Current scheduled occupancy state:
0: OC_OCCUPIED
1: OC_UNOCCUPIED
3: OC_STANDBY
-1: OC_NUL (power up value).
Next scheduled occupancy state:
0: OC_OCCUPIED (power up value).
1: OC_UNOCCUPIED
3: OC_STANDBY
-1: OC_NUL (power up value).
Time in minutes until next scheduled change of occupancy state:
2880: Means there is not a next change of occupancy state or it is
longer than 2 days from now (Power up value).
nvoOccSensorOccupancy Sensor OutOUTStatus of occupancy sensor:
0: OC_OCCUPIED
1: OC_UNOCCUPIED
-1: OC_NUL (not configured and power up value).
nvoOutdoorTempOutdoor Temperature Out OUTThe current outdoor temperature (Celsius). The sensor source is
specified by nciConfig.oDAirSensor. A value of 327.67 means the
sensor is not functioning correctly or is out of range.
0: Alarm notification is turned on (power up value).
1: Alarm notification via nvoAlarmH, nvoAlarmLog,
nvoUnitStatus, and nvoStatus has been turned off.
Alarm
0: no alarm (power up value).
1: there is an alarm.
Override the delays associated with automatic control:
0: Delays turned on (power up value).
1: Delays turned off (Useful for troubleshooting).
Invalid ID:
0: The request was for a valid ID (Power up value).
1: The request was not for a valid ID.
Invalid Request:
0: The request was for a valid operation (Power up value).
1: Invalid request for an operation.
Manual control:
0: The function block is in automatic operation (power up
value).
1: The function is in manual operation and outputs respond to
nviManValue.
Status report. Function block number being in status report:
0: Node function block.
1: Space comfort controller function block.
Programming Mode:
0: Normal operating mode (power up value).
1: The node is in the “programming the cover flash memory”
mode, and is not automatically controlling temperature.
Report mask:
0: Normal operation (power up value).
1: RQ_REPORT_MASK received. The status bits that are set
have been implemented.
nvoTerminalLoadTerminal Load OutOUTTerminal load (percent): Reports the demand for supply energy.
Positive numbers are cooling demand and negative numbers are
heating demand. 100 percent is full capacity. Terminal loads
greater than 100 percent or less than -100 percent indicate that
the equipment is not able to supply the required heating or cooling
energy. The valid range is between 163 and minus 163 percent.
Terminal load is used by supervisory level control applications to
reset Boiler or Chiller discharge water temperatures.
Percentage of cooling capability currently being supplied to the
controlled space.
163.84: Power up value.
Fan turned on or off:
0: Fan not running.
100: Fan running.
163.84: (power up value).
Percentage of auxiliary heating capability currently being supplied
to the controlled space (Applies to heat pump application only):
163.84: Power up value.
Alarm report:
0: No alarms reported in the unit (power up value).
1: One or more alarms reported in the unit.
-1: The Alarms have been suppressed by alarm notified
disabled command.
Effective operating mode:
0: HVAC_AUTO (power up value).
1: HVAC_HEAT
3: HVAC_COOL
6: HVAC_OFF (power up value).
7: HVAC_TEST (manual mode or cover in factory test mode).
8: HVAC_EMERG_HEAT
4363-4368
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
Class Description
CONFIG: LonMark network configuration parameters
FTP CONFIG: Configuration parameters implemented with
the LonMark file transfer protocol
IN: Network variable inputs.
OUT: Network variable outputs.
ZIRE and TUNGSTEN are trademarks of palmOne, Inc.
HotSync and Palm OS are registered trademarks of PalmSource, Inc.
Palm is a trademark of PalmSource, Inc.
TRGPro is a trademark of HandEra, Inc.
ONMARK
L
®
, LONTALK®, and LONWORKS® are registered trademarks of Echelon® Corporation.
LonSpec™, and LonStation™ are trademarks of Echelon® Corporation.
Automation and Control SolutionsHoneywell InternationalHoneywell Europe S.A. Honeywell Latin American
Honeywell Inter natio nal In c.Honeywell Limited-Honeywell LimitéeControl Products3 Avenue du Bourget
1985 Douglas Drive North35 Dynamic DriveHoneywell Building1140 Brussels480 Sawgrass Corporate Parkway
Golden Valley, MN 55422Scarborough, Ontario17 Changi Business Park Central 1 BelgiumSuite 200
M1V 4Z9Singapore 486073Sunrise FL 33325
63-4368 B.B. 11-04 www.honeywell.com
Region
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.