T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
INTRODUCTION
Description of Devices
The Q7300H Subbase is a LonMark® certified device that
provides networking capability for the T7300F Thermostat
in a LonWorks® system using a transformer-coupled Free
Topology Transceiver (FTT). See Fig. 1.
The T7300F/Q7300H communicates with all LonMark®
devices including the following:
Unit (CVAHU) Controller.
— Excel 15 W7760A Building Manager.
— Excel 10 W7761A Remote Input/Output (RIO)
Controller.
BUILDING MANAGER
NOTEBOOK PC
RS-232
SERIAL
PORT
SLTA
1 4 8 12 16
EXCEL 15
W7760
17 23
Control Application
The T7300F/Q7300H Series 2000 Commercial
Thermostats and Communicating Subbases control 24
Vac commercial single zone heating, ventilating and air
conditioning (HVAC) equipment. In addition, the Q7300H
can communicate schedule information and system
instructions to other devices in a LonWorks® network.
Fig. 2 shows a typical T7300F/Q7300H application in a
three-stage heat and two-stage cool heat pump system.
For additional T7300F/Q7300H hookups, see Fig. 13, 15,
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
g
g
g
g
SUBBASE
3
Y2
ASAS
DISCHARGE
AIR
SENSOR
1
2
3
4
X
COMPRESSOR
CONTACTOR 2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS.
USE A1 AND A2 WHEN CONTACTS ARE NORMALLY CLOSED IN OCCUPIED MODE.
CONNECT GND TO EARTH GROUND.
Y1OG
COMPRESSOR
CONTACTOR 1
COOL
CHANGEOVER
VALVE
E
EM. HT.
RELAY
FAN
RELAY
W1
AUX.
HEAT
HEAT
CHANGEOVER
VALVE
R
B
ECONOMIZER
Fig. 2. Typical T7300F/Q7300H application.
A2A1
C4C3C5
CA4 CA3CA5
T7147 REMOTE COMFORT ADJUST MODULE
2
TRANSFORMER
C2
CA2
L1
(HOT)
L2
C1T
CA1
1
T
GND
4
TEBEB
T
M16056
LonWorks®
BUS
LonWorks®
BUS
Communicating subbases for T7300F Thermostats add
value by allowing remote-site access—via telephone
lines—for diagnostics, maintenance and monitoring. In
addition, the T7300F can act as the user interface for onsite Excel 10 Controllers (after initial installation with Excel
LonSpec™) without the need for a personal computer
workstation. Through the T7300F/Q7300H
Thermostat/Communicating Subbase, a building operator
can control Excel 10 devices by setting occupancy
schedules, setpoints and additional features.
Control Provided
The Q7300H communicates with other network devices, or
nodes, for the purpose of sharing data. Through the
network, the T7300F/Q7300H sets and deletes schedules.
Schedules can be bypassed by selecting Continuous
Unoccupied or Temporary Override. By using network
messaging, the Q7300H sets fan operation (ON, AUTO)
and system mode (HEAT, COOL, AUTO, OFF, EM HEAT)
designated by a remote T7300F. Schedules can be
programmed for seven days with four designated periods
per day; Occupied 1, Occupied 2, Unoccupied 1 and
Unoccupied 2. In external schedule mode, the T7300F
changes occupancy through a network-based scheduler.
In local schedule mode, the T7300F changes occupancy
through an internal scheduler. If the external schedule is
not periodically updated, the T7300F defaults to the local
schedule.
The T7300F/Q7300H is also able to provide time of day,
temporary setpoint, bypass status and additional
information to multiple Excel 10 devices by sending
instructions from one T7300F/Q7300H to the Excel 10
devices. When the T7300F is configured to schedule
temporary setpoint and effective bypass information for
other devices, certain restrictions apply such as:
— When the T7300F is scheduling temporary setpoints
for Excel 10 devices, the Excel 10 cannot adjust
setpoints using the T7770 wall module.
— When the T7300F is providing effective bypass
information to Excel 10 devices, the Excel 10 cannot
change the bypass status using the T7770 wall
module.
63-43654
Product Names
When combined with the T7300F Series 2000 Commercial
Thermostat, the Q7300H Communicating Subbase
communicates with other devices in a LonWorks®
network. The thermostat and subbase are available in the
following models:
Part NumberProduct Description
Q7300H2003Communicating subbase with O and B
terminals for three-sta
cool heat pump system.
Q7300H2011Communicating subbase without O and
B terminals for three-sta
stage cool heat pump system.
Q7300H2029Communicating subbase for three-stage
heat, three-sta
e cool conventional
system.
Q7300H2037Communicating subbase for two-stage
heat, one-sta
e cool conventional
system with valve two-position heat
output.
T7300F2002Series 2000 Commercial Electronic
Thermostat without system and fan
switching.
T7300F2010Series 2000 Commercial Electronic
Thermostat with system and fan
switching.
e heat, two-stage
e heat, two-
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
Products Covered
This System Engineering manual describes how to apply
the T7300F Thermostat and Q7300H Communicating
Subbase and related accessories to typical applications.
Devices include:
T7300F Series 2000 Commercial Thermostat.
Q7300H Series 2000 Communicating Subbase.
Excel 15 W7760A Building Manager.
Excel 10 Controllers, as follows:
W7750A,B Constant Volume Air Handler Unit (CVAHU)
Controller.
W7761 Remote Input/Output (RIO) Controller.
Other products:
Q7751A,B Bus Router.
Q7760A Serial LonTalk Adapter.
Q7740A,B FTT Repeaters.
209541B FTT Termination Module.
See Table 1 for additional products.
Table 1. Additional Products.
Part NumberProduct DescriptionComments
R8242AContactor, 24 Vac coil, DPDT.—
AT72D, AT88A, etc.Transformers.—
4074EYDWallplate for T7770 Wall Modules.For covering an existing hole in a
—Serial Interface Cable, male DB-9 to female DB-9 or
Outputs/Power: 14 to 18 AWG (2.0 to 1.0 sq mm).NEC Class 2, 140°F (60°C) rating.
18 AWG (1.0 sq mm) twisted pair.Non-plenum.
16 AWG (1.3 sq mm) twisted pair.Non-plenum.
14 AWG (2.0 sq mm) two conductor.Non-plenum.
Organization of Manual
This manual is divided into four basic sections:
Introduction
1.
T7300F/Q7300H, discusses related devices, lists
additional literature, and provides a glossary of
abbreviation and terms.
Construction
2.
network connections and dimensions.
Application Steps
3.
provides the information necessary to plan and lay
out the T7300F/Q7300H application and accurately
order materials.
Appendix
4.
operations for configuring network controllers.
The organization of the manual assumes a project is being
engineered from start to finish. If you are changing an
existing system, refer to the Table of Contents for relevant
sections.
. Provides an overview of the
. Describes T7300F/Q7300H features,
. A step-by-step procedure that
. Appendix A provides a sequence of
wall.
Obtain locally from any computer
hardware vendor.
Level IV, 140°F (60°C) rating.
Level IV, 140°F (60°C) rating.
563-4365
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
Applicable Literature
The following list of documents contains general
information related to the T7300F/Q7300H Series 2000
Commercial Thermostats and Communicating Subbases.
Form No.Title
62-0125T7300F Series 2000 Commercial
Microelectronic Conventional or Heat
Pump Thermostat Installation Instructions
variables in one node to network variable(s) in other
node(s). Binding is performed by a network management
node that writes the binding information into the EEPROM
memory of all the neuron's involved. The binding
information is saved in the network image of each neuron.
Building Manager
be used to monitor and control HVAC equipment and other
miscellaneous loads in a distributed network.
Command Display
and change parameters.
Control Loop
function in a node that includes processes, loops and
programs. A node can contain one or more control loops.
(In Excel 10 class devices, the control loop occupies the
entire node.)
CVAHU
Controller.
Excel 10s
controllers such as the Excel 10 CVAHU and Excel 10
RIO.
HVAC
I/O
—Input/Output.
LonWorks® Network
communicating with each other using the LonTalk®
protocol.
Mandatory Mechanisms/Objects/Network Variables
Mandatory mechanisms and network variables that are
implemented in all the Excel 10 devices.
NamedObject
NamedObjects. These objects are visible on the network
as functional independent entities and are accessed by
name. Typical examples of NamedObjects are Controllers,
ControlLoops and LogicFunction blocks.
Network Management Node
responsible for configuring the network, installing the
nodes, binding the network variables between nodes, and
general network diagnostics.
—A specific Building Control function.
—The process of logically connecting network
—A LonMark® certified device that can
—A device that can be used to monitor
—A primitive control function. A type of
—Excel 10 Constant Volume Air Handler Unit
—A family of application - specific HVAC
—Heating, Ventilating and Air Conditioning.
—A data network based on neurons
—
—Objects that have names are called
—A LonWorks® node that is
Agency Listings
European Community Mark (CE): Conforms to
requirements of European Consortium Standards.
63-43656
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
Network Variables
Neuron C that allows communication over the LonWorks®
network to other nodes on the network. An output network
variable in one node can be bound to corresponding input
network variable(s) in other node(s). Changing the value of
the output network variable in one node causes the new
value to be automatically communicated to the bound input
network variable(s) in other node(s). When an input
network variable is updated, an nv_update_occurs event is
posted at the receiving node(s) so that the application
program can take action based on the change. A network
management node that explicitly reads and/or writes the
network variable can also poll network variables. Network
variables can contain one data field (one or two bytes) or
multiple data fields (a structure).
Node
—A device implementing layers one through six of
the LonTalk® protocol including a Neuron® Chip,
transceiver, memory, and support hardware.
Notebook PC
Optional Mechanism/Object/Network Variables
Optional mechanisms and variables that shall be
implemented on an as-needed basis. However, a different
mechanism or network variable cannot be implemented if
an existing optional mechanism or network variable can
perform the same function.
Programmable Controller
variable number of control loops of different types and is
user-programmed to execute an application. The user can
select the number and type of control loops. The user also
has the capability of generating new types of control loops.
Recovery Mode or Recovery Period
unoccupied periods when the temperature control is
adjusting the control setpoint so that the space
temperature reaches the occupied setpoint when the
schedule change occurs.
—A class of variables defined in
—Portable personal computer.
—
—A controller that has a
—The time in
RIO
—Excel 10 Remote Input/Output device.
RTC
—Real Time Clock.
Schedule
states, setpoints and the time of the changes between
these states.
SGPU
Periodic Update.
SGPUC
Periodic Update with Change Field.
SLTA
coupled LonTalk® messages to the RS-232 Serial Port.
The T7300F Thermostat has a keypad for setting system
parameters, a corresponding LCD display and a flip-down
keypad cover. The T7300F Thermostat mounts on the
Q7300H Subbase.
The Q7300H Communicating Subbase includes
LonWorks® Bus terminals and a jack for temporary
network connections to a personal computer. A service pin
push button provides service messaging to physically
locate the device on the LonWorks® network. The
subbase mounts horizontally on the wall or on a
2 in. x 4 in. junction box.
Fig. 3 shows T7300F/Q7300H dimensions.
763-4365
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
6-11/16 (170)
7-5/16 (186)
3-3/16 (77)
1-3/8 (35)
1/16 (2)
1-7/8
(47)
4-1/8
(105)
7/8
(22)
1-11/16
(43)
Occupied
Start Time
Day/Time
Set Program
Unoccupied
Start Time
Clear
Start Time
Day
Copy
Run
Program
Temporary
Occupied
Continous
Unoccupied
Set Current
Fig. 3. T7300F/Q7300H dimensions in in. (mm).
Performance Specifications
Electrical Ratings:
Power: 20 to 30 Vac, 50/60 Hz.
System Current: 6 VA maximum at 30 Vac, 50 or 60 Hz.
Temperature Ratings:
Setpoint Range: Heating: 40°F to 90°F (4°C to 32°C;
Cooling: 45°F to 90°F (7°C to 32°C).
Operating: 40°F to 110°F (4°C to 43°C).
Shipping: -20°F to +130°F (-29°C to +54°C).
Display Accuracy: ±1°F (+0.5°C).
Set Temperature
Occupied
Temp
System
Unoccupied
Temp
Heat/Cool
Settings
Fan
Change
Time/Temp
4-5/8
(117)
Differential:
2°F (1°C).
Humidity Ratings:
5% to 90% RH, noncondensing.
Input/Output Summary:
Table 2 summarizes the T7300F/Q7300H
Thermostat/Subbase inputs and outputs.
M16086A
63-43658
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
g
Table 2. Terminal descriptions and conditions.
Standard Terminal
DesignationsTypical ConnectionFunctionTerminal Type
A1, A3Damper control relay. See T7300F Installation Instructions, form
A2Dry auxiliary contact. (A2 is common to A1, A3.)Input—
AS,ASC7150B Discharge Air Sensor connection.Input—
BHeating changeover valve.Output24V powered
BMML7984 Actuator connection. No call for heat; valve closed
C1, C2, C3, C4, C5 Communication input for T7147.Input/OutputLow power
EEmergency heat relay.Output24V powered
EB, EBLonWorks® Bus connection to LonWorks® network.Input/outputCommunications
FCFan control transformer.Input—
GFan relay.Output—
GHHigh speed fan output. Activated during call for cooling.Output—
GLLow speed fan output. Activated on call for heat and fan On
OCooling changeover valve.Output—
P1, P2Pump interlock relay. Operates circulator pump in hydronic heat
R24V system transformer.Input—
RC24V cooling transformer.Input—
RH24V heating transformer.Input—
RMML7984 Actuator connection. No call for heat; valve closed. Call
69-1025-3, installer setup 18, for control parameters.
during occupied periods and open during unoccupied periods.
selection.
or energizes conventional heat system.
for sta
stage 2 heat; valve fully open.
compressor contactor (heat pump).
e 1 heat; valve approximately one-half open. Call for
OutputDry contract
contact
Output—
contact
Output—
Input, output—
Output—
Output—
Communications
The Q7300H provides networking capability in a
LonWorks® system when using a Free Topology
Transceiver (FTT) transformer-coupled communications
port running at 78 kilobits per second (kbs). The
transformer-coupled communications interface offers a
much higher degree of common-mode noise rejection
while ensuring dc isolation.
LonWorks® FTT networks are very flexible and convenient
to install and maintain, but it is imperative that the network
layout be carefully planned and accurate documentation
created and maintained. This aids in compliance
verification and future expansion of the network. It also
minimizes unknown or inaccurate wire run lengths, nodeto-node (device-to-device) distances, node counts, total
wire length, inaccurate repeater/router locations, and
misplaced or missing terminations. LonWorks® networks
can be configured in a variety of ways; refer to the E-Bus
FTT Network Wiring Guidelines, form 74-2865-1, for a
complete description of network topology rules and
maximum wire length. If longer runs are required, add a
Q7740A 2-way or Q7740B 4-way repeater to extend the
LonWorks® Bus length. Add a Q7751A to partition the
system into two segments to double the length of
LonWorks® Bus.
963-4365
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
Approved cable types for LonWorks® Bus
communications wiring are Level IV, 22 AWG (0.34 sq
mm) plenum or non-plenum rated unshielded, twisted pair,
solid conductor wire. For nonplenum areas, use US part
AK3781 (one pair) or US part AK3782 (two pair). In
plenum areas, use US part AK3791 (one pair) or US part
AK3792 (two pair). Other Echelon approved cable may
also be used. Run communications wiring in a conduit, if
needed, with
non-switched
24 Vac or sensor wiring. The
Free Topology Transceiver (FTT) communications
LonWorks® Bus supports a polarity insensitive, free
topology wiring scheme that, in turn, supports star, loop,
and/or bus wiring.
LonMark® Functional Profile
The Q7300H supports the LonMark® Functional Profile
Number 8060,Thermostat Object (Type 09). See Fig. 4.
Hardware
Output
Thermostat Object
Type Number 09.
nv1
nviSetpoint
SNVT_temp_p
Mandatory
Network
Variables
nvoHeatOutput
nv2
SNVT_ lev_percent
nvoCoolOutput
nv3
SNVT_ lev_percent
nvoSpaceTemp
nv4
SNVT_ temp_p
nvoUnitStatus
nv5
SNVT_hvac_status
NOTE: For additional information on the LonMark®
Functional Profile, see the LonMark® Application
Layer Interoperability Guidelines and the
LonMark® Functional Profile: Thermostat. Both
documents are available from LonMark® at
internet address: www.lonmark.org.
CONFIGURATIONS
General
The T7300F/Q7300H can be configured to perform a
variety of activities in which data is sent to and/or received
from other nodes on the LonWorks network.
Information that can be shared with other network devices
includes:
— Day-of-week and time-of-day
— System mode (HEAT, COOL, AUTO, OFF, EM HEAT)
— Current fan setting (ON, AUTO)
— Space temperature
— Current setpoint
— Occupied/Unoccupied schedule commands
— Current occupancy status
— Relay status (heat/cool stages and fan)
— Alarm status
— Alarm log
A network configuration tool is used to configure Q7300Hs
and other nodes with which the Q7300H interacts.
(Thermostat profile variables not used are grayed).
The following is a brief description of the configurable
features that can be commanded over the network:
•
Day-of-Week/Time-of-Day:
When a T7300F Thermostat is designated as the
network time master, the current time of day and day of
week is synchronized across the network every minute.
Whenever the time of day or day of week of the time
master is changed, it automatically adjusts all the other
T7300Fs on the network. When a T7300F is controlled
by a time master, its time cannot be changed using its
keypad. If an attempt is made to change its time, the
LOC
controlled T7300F LED displays
•
System Switch Settings:
.
System switch settings (HEAT, COOL, AUTO, OFF, EM
HEAT) can be designated by a remote T7300F, or if
configured to allow it, from the T7300F keypad.
•
Fan Settings:
Fan settings (ON, AUTO) are selected as designated by
a remote T7300F, or from the T7300F keypad.
•
Space Temperature:
If a valid space temperature value is received at the
Q7300H DestRmTemp network variable input, that
value will be used in the T7300F as the primary
controlled variable. In this case, the internal space
sensor of the T7300F is ignored.
•
Current Setpoint:
If a valid setpoint value is received at Q7300H
DestSetPoint, that value will be used by the Q7300H as
center
the
setpoint. The heat and cool setpoints are
then calculated from this value and are used in the
T7300F as the occupied setpoints. During unoccupied
periods, DestSetPoint is ignored.
63-436510
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
•
Schedule:
The occupancy schedule used by a T7300F may reside
locally in that device or remotely in another schedule
device (T7300F or Excel 15). Local schedules can be
created and modified using the T7300F keypad, or with
a configuration tool. External schedules can also be
modified using the keypad of the schedule device, or
with a configuration tool. When a T7300F receives
scheduling information over the network, the user is
locked out from making schedule changes at the
LOC
keypad, and the LCD displays
if attempted. When
a T7300F Thermostat is designated as a schedule
device, it sends its schedule file to the appropriate
Q7300H(s) which, in turn, overwrites any existing
internal schedule in their T7300F Thermostat. The
T7300F/Q7300H Thermostat/Subbase can provide
scheduling information to multiple Excel 10 devices by
taking instruction from one T7300F/Q7300H and
sharing the information with the desired Excel 10
devices.
•
Occupancy Bypass:
Any internal schedule in the T7300F is overridden if a
valid occupancy command is received by its Q7300H
(resulting from an existing external schedule on the
LonWorks network).
•
Continuous Unoccupied:
In this mode, the T7300F Thermostat sets the operating
setpoints to the unoccupied setpoints. The T7300F
remains in this mode until the Run Program key is
pressed.
•
Setpoint Changes:
Selecting a temporary setpoint modifies that setpoint for
the present schedule period. Pressing Run Program
terminates temporary setpoints. Temperature setpoint
range is 40°F to 90°F (4°C to 32°C).
•
Temporary Override:
Modifies the schedule to operate the thermostat in
occupied mode for a designated number of hours.
Temporary occupied time can be selected for 1, 3, 8 or
12 hours. If a change from occupied to unoccupied is
scheduled and the Temporary Override key is pressed,
the thermostat remains in occupied mode until the
designated override time expires. If the thermostat is in
the unoccupied mode when the Temporary Occupied
key is pressed, the thermostat operates at the occupied
setpoint until the override time expires.
APPLICATION STEPS
Overview
The application steps shown in Table 3 are guidelines for
configuring the T7300F/Q7300H Thermostat/Subbase in a
LonWorks® Bus network and explain the network role of
the T7300F/Q7300H.
Table 3. Application Steps.
StepDescription
1Plan the system.
2Determine required network devices.
3Lay out communications and power wiring.
4Prepare wiring diagrams.
5Order equipment.
6Configure T7300F/Q7300H.
7Troubleshooting.
Step 1. Plan the System
Plan the use of the T7300F/Q7300H Thermostat/Subbase
according to the job requirements. Determine the location
and functionality. Verify the sales estimate for the number
of other controllers and devices required. Check the
number and type of other required accessories.
When planning the system layout, consider potential
expansion possibilities for future growth. Planning is very
important if HVAC systems and controllers are to be added
in future projects.
NOTEBOOK PC
SHIELDED
INTERFACE
RS-232
SERIAL
PORT
CABLE
Q7760
SLTA
CABLE
PART
NO. 205979
Fig. 5. Connecting personal computer to LonWorks
Bus.
Refer to the E-Bus Wiring Guidelines, form 74-2865 for a
complete description of network topology rules. See
Application Step 3. Lay Out Communications and Power
Wiring, for more information on bus wiring layout and Fig.
6 through 10 in Application Step 4. Prepare Wiring
Diagrams, for wiring details.
Refer to the Excel LonSpec™ User Guide, form 74-2937,
to configure the W7760A Building Manager, W7750A,B
and W7761 Controllers and the Q7300H Subbase.
T7300
LonWorks
BUS PORT
®
M10102B
1163-4365
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
Step 2. Determine Required Network
Devices
A maximum of 60 nodes can communicate on a single
LonWorks Bus segment. Each LonWorks Bus device
comprises one node. If more than 60 nodes are needed, a
Q7751A Router or Q7740 Repeater is necessary. In a
network with Excel 15 devices, a router allows up to 120
controller nodes per network, divided between two
LonWorks Bus segments. A router or repeater allows up
to 120 controller nodes per network, divided between two
LonWorks Bus segments. The router comprises two
nodes (one node on each side of the router). Router and
operator access nodes are not counted in the maximum
controller node totals. All devices are able to talk to each
other through the router.
Multiple operator terminals can be connected to the
LonWorks Bus at the same time. Table 4 summarizes
the LonWorks Bus segment configuration rules.
Refer to the E-Bus Wiring Guidelines, form 74-2865, for a
complete description of network topology rules and
maximum wire lengths. If longer runs are required, use a
Q7740A 2-way or Q7740B 4-way repeater to extend the
length of the LonWorks Bus. Each network segment can
only have one repeater. If more nodes or longer distances
are required, add a router or repeater to limit bus traffic or
boost distance.
In addition, a 209541B Termination Module may be
required. Refer to the E-Bus Wiring Guidelines, form 742865, and the Excel 10 FTT Termination Module
Installation Instructions form, 95-7554, or if Excel 15s are
present, see Application Step 3. Lay Out Communications
and Power Wiring in the W7760A System Engineering
Guide, form 74-2969.
Step 3. Lay Out Communications and
Power Wiring
LonWorks® Bus Layout
The communications LonWorks Bus, is a 78-kilobit
network that uses transformer isolation and differential
Manchester encoding.
The Free Topology Transceiver (FTT) LonWorks
communications Bus supports a polarity insensitive, free
topology wiring scheme, refer to the E-Bus Wiring
Guidelines form, 74-2865, for a complete description of
LonWorks network topology rules.
Fig. 6 shows a typical wiring diagram for the
T7300F/Q7300H in a LonWorks® network. Fig. 7 and 8
show wiring layouts for two doubly daisy-chained
LonWorks Bus segments.
Table 4. LonWorks Bus Configuration Rules and Device Node Numbers.
One LonWorks Bus SegmentMaximum Number of Controller Nodes 60
Maximum number of Excel 10s60 nodes (minus number of Excel 15s)
Maximum number of Excel 15s4 nodes
Total 60 nodes maximum
Two LonWorks Bus Segments;
Controllers, more than 60 devices
One Q7751A,B Router2 nodes
Maximum number of Excel 15s8 nodes
Maximum number of Excel 10 RIO devices24 nodes
Maximum number of Excel 10s (20 per each Excel 15)112 nodes (minus number of RIOs)
Two LonWorks Bus Segments;
Controllers, more than 60 devices
One Q7751A,B Router2 nodes
Maximum number of Excel 10s (60 per segment)120 nodes
with
without
Excel 15
Excel 15
Maximum Number of Controller Nodes 112, plus two
nodes for router access.
Total122 nodes maximum
Maximum Number of Controller Nodes 120, plus two
nodes for router access.
Total122 nodes maximum
63-436512
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
NOTEBOOK PC
MODEM
209541B
TERMINATION
MODULE
T7300
T7300T7300T7300
RS-232
SLTA
LonWorks® BUS
T7300
MODEM
MODEM
RS-232
SLTA
LonWorks® BUS
T7300T7300T7300T7300
RS-232
SLTA
LonWorks® BUS
Fig. 6. Typical topology for T7300F/Q7300H devices in LonWorks network.
LonWorks® BUS SEGMENT NUMBER 1
EXCEL 10
EXCEL 10
CVAHU
T7770
CVAHU
T7300
M16063A
EXCEL 10
CVAHU
209541B
TERMINATION
MODULE
®
LonWorks
LonWorks® BUS
SEGMENT NUMBER 2
BUILDING MANAGER
1 4 8 12 16
EXCEL 15
W7760
30 31
17 23
44
37
T7300T7300
BUS ACCESS
LonWorks® BUS SEGMENT NUMBER 2
EXCEL 10
CVAHU
EXCEL 10
CVAHU
Fig. 7. Wiring layout for two doubly terminated LonWorks Bus segments.
Q7751A
FTT
E-BUS
ROUTER
209541B
TERMINATION
MODULE
209541B
TERMINATION
MODULE
EXCEL 10
CVAHU
M16084C
1363-4365
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
LonWorks® BUS
EXCEL 10
CVAHU
T7770
EXCEL 10
RI0
EXCEL 10
RI0
EXCEL 10
CVAHU
BUILDING MANAGER
1 4 8 12 16
EXCEL 15
W7760
30 31
17 23
37
EXCEL 10
RI0
EXCEL 10
RI0
LonWorks® BUS
I/O CONNECTIONS
T7770
WITH NO
LonWorks®
BUS ACCESS
T7770
WITH NO
LonWorks®
BUS ACCESS
M16085B
T7300
T7300
T7300
EXCEL 10
CVAHU
T7770
209541B TERMINATION
MODULES (AT ENDS OF
LonWorks® BUS
DAISY-CHAIN)
T7300T7300
EXCEL 10
RI0
T7770
T7770
JACK FOR
OPERATOR
TERMINAL
T7300
T7300
T7300
EXCEL 10
RI0
BUS
®
LonWorks
44
LonWorks®
BUS
EXCEL 10
RI0
T7770
Fig. 8. Wiring layout for one doubly terminated daisy-chain LonWorks segment.
Cable Termination
The FTT network segment requires termination for proper
data transmission performance. Use a 209541B
Termination Module to connect two of the three termination
module wires to the LonWorks Bus terminals.
Singly Terminated Network Segment
In a singly terminated topology segment, only one
termination is required and can be placed anywhere on the
segment. Singly terminated segments use the yellow and
brown wires. Mount the termination modules on the
appropriate terminals as shown in Fig. 9.
C1 C2 C3 C4 C5
BROWN
ORANGE
EB EB
YELLOW
XTTASAS
PART NO. 209541B
TERMINATION MODULE
M16202
Fig. 9. Singly terminated LonWorks Bus termination
module.
63-436514
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
Doubly Terminated Daisy-Chain Network Segment
In a doubly terminated daisy-chained topology segment,
two terminations are required, one at each end of the
topology segment. Doubly terminated segments use the
orange and brown wires. Mount the termination modules
on the appropriate terminals as shown in Fig. 10. For
additional wiring information, refer to the E-Bus Wiring
Guidelines, form 74-2865, and the Excel 10 FTT
Termination Module Installation Instructions, form 95-7554.
2.
Securely tighten each terminal screw.
3.
Push excess wire back into the hole.
4.
Plug the hole with nonflammable insulation to
prevent drafts from affecting the thermostat.
NOTE: After wiring, check that all connections are tight
and secure. See Fig. 11. Loose or intermittent
wire connections can cause inconsistent system
operation.
C1 C2 C3 C4 C5
EB EB
ORANGEBROWN
YELLOW
EB EB
ORANGEBROWN
YELLOW
XTTASAS
PART NO. 209541B
TERMINATION MODULE
C1 C2 C3 C4 C5
XTTASAS
PART NO. 209541B
TERMINATION MODULE
Fig. 10. Doubly terminated LonWorks Bus
termination modules.
M16122
FOR STRAIGHT
FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).
INSERTION STRIP
5/16 IN. (8 MM).
M4826
Fig. 11. Proper wiring technique.
Wiring Details
LonWorks® network cable should be wired separately
from the power and I/O wires when installing Q7300s. If
this is not possible, use a minimum of 4 in. (102 mm)
separation between split ferrite cores (Fair-Rite
0443164151, or equivalent Honeywell part no. 229997CB,
containing five split ferrite cores) to ensure compliance
with Class B limits (does not apply to Class A limits). See
Fig. 12. to apply ferrite cores to LonWorks® Bus input and
output.
1.
WIRES TO ALL
INPUTS AND
OUTPUTS
WIRES TO Q7300H
COMMUNICATING SUBBASE
2.
WIRES TO ALL
INPUTS AND
OUTPUTS
CAUTION
Electrical Shock Hazard.
Power supply can cause electrical shock.
Disconnect power supply before beginning
installation.
1.
Loosen the terminal screws on the subbase and
connect the system wires. See Fig. 11.
IMPORTANT
Use 18-gauge, solid-conductor color-coded
thermostat cable for proper wiring. If using 18gauge stranded wire, do not use more than two
wires. Do not use larger than 18-gauge wire.
M10886A
WIRES TO Q7300H
COMMUNICATING SUBBASE
Fig. 12. Ferrite core wires from Q7300H to LonWorks®
inputs and outputs.
Step 4. Prepare Wiring Diagrams
Fig. 13 through 16 show T7300F/Q7300H terminal
arrangements and provide detailed wiring diagrams.
Reference these diagrams to prepare the site-specific job
drawings.
1563-4365
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
SUBBASE
ASAS
DISCHARGE
AIR
SENSOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
1
PROTECTION AS REQUIRED.
2
USE A1 AND A2 WHEN CONTACTS ARE NORMALLY CLOSED IN OCCUPIED MODE.
USE A2 AND A3 WHEN CONTACTS ARE NORMALLY OPEN IN OCCUPIED MODE.
3
CONNECT GND TO EARTH GROUND.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
Y1G
XR
COMPRESSOR
CONTACTOR 1
Y2
FAN
RELAY
COMPRESSOR
CONTACTOR 2
EM. HT.
RELAY
W3E
HEAT
RELAY 3
W2
HEAT
RELAY 2
W1
HEAT
RELAY 1
ECONOMIZER
2
A2 A3A1
4
C4C3C5
CA4 CA3CA5
T7147 REMOTE COMFORT ADJUST MODULE
TRANSFORMER
C2
CA2
C1T
CA1
1
L1
(HOT)
L2
T
T
T
GND
3
Fig. 13. Typical hookup of T7300F/Q7300H in three-stage heat, two-stage cool heat pump system
(without O/B terminals).
SUBBASE
3
ASAS
Y2
X
Y1OG
E
W1
R
B
A2A1
C4C3C5
C1T
C2
EB EB
LonWorks® BUS
LonWorks® BUS
M16057
TEBEB
AUX.
FAN
RELAY
HEAT
HEAT
CHANGEOVER
VALVE
ECONOMIZER
CA1
CA4 CA3CA5
T7147 REMOTE COMFORT ADJUST MODULE
2
TRANSFORMER
CA2
L1
(HOT)
L2
T
GND
4
1
T
M16056
LonWorks®
BUS
LonWorks®
BUS
DISCHARGE
AIR
SENSOR
1
2
3
4
COMPRESSOR
CONTACTOR 2
COMPRESSOR
CONTACTOR 1
COOL
CHANGEOVER
VALVE
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS.
USE A1 AND A2 WHEN CONTACTS ARE NORMALLY CLOSED IN OCCUPIED MODE.
CONNECT GND TO EARTH GROUND.
EM. HT.
RELAY
Fig. 14. Typical hookup of T7300F/Q7300H in three-stage heat, two-stage cool heat pump system (with O/B terminals).
63-436516
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
SUBBASE
Y1GX
ASAS
DISCHARGE
AIR
SENSOR
RCRH
2
COMPRESSOR
CONTACTOR 1
FAN
RELAY
L1
(HOT)
L2
1
COOLING
TRANSFORMER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A
SYSTEM WITH ONE TRANSFORMER.
3
USE A1 AND A2 WHEN CONTACTS ARE NORMALLY CLOSED
IN OCCUPIED MODE. USE A2 AND A3 WHEN CONTACTS
ARE NORMALLY OPEN IN OCCUPIED MODE.
Y2
COMPRESSOR
CONTACTOR 2
COMPRESSOR
CONTACTOR 3
HEAT
RELAY 3
W3Y3
W2
HEAT
RELAY 2
W1
HEAT
RELAY 1
3
A2 A3A1
ECONOMIZER
5
4
5
CONNECT GND TO EARTH GROUND.
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.
C4C3C5
CA4CA3CA5
T7147 REMOTE COMFORT ADJUST MODULE
1
L1
(HOT)
L2
HEATING
TRANSFORMER
C2
CA2
C1T
CA1
T
4
GND
Fig. 15. Typical hookup of T7300F/Q7300H in three-stage heat, three-stage cool conventional system.
SUBBASE
EB EB
T
LonWorks®
BUS
T
LonWorks®
BUS
M16058
GND
EB EB
T
LonWorks® BUS
T
LonWorks® BUS
2
M16059
GLGHR
ASAS
DISCHARGE
AIR
SENSOR
FCY
LOW
SPEED
FAN
RELAY
1
L1
(HOT)
L2
FAN TRANSFORMER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
CONNECT GND TO EARTH GROUND.
2
SEE TABLE 2 FOR VALVE AND VALVE ACTUATOR MODELS.
3
HIGH
SPEED
FAN
RELAY
X
RM
ML7984
VALVE
ACTUATOR
COOLING
RELAY
3
PUMP
INTERLOCK
RELAY
A2A1P1 P2BM
DAMPER
CONTROL
RELAY
C4 C3C5
CA4 CA3CA5
T7147 REMOTE COMFORT
ADJUST MODULE
TRANSFORMER
C2
L1
(HOT)
L2
C1 T
CA1 TCA2
1
Fig. 16. Typical hookup of T7300F/Q7300H in two-stage heat, one-stage cool conventional system.
1763-4365
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
g g
g
General Considerations
Table 5 lists wiring types, sizes and distances for the T7300F/Q7300H and Excel 10 products. The Q73000H accepts 14
through 22 AWG (2.0 to 0.34 sq. mm wire).
Table 5. Field Wiring Reference Table.
Wire
Function
Thermostat
wire.
Thermostat
wire.
LonWorks
Bus (NonPlenum).
Power
Wiring.
Recommended
Wire Size
(Minimum)Construction
Inputs: 18 AWG
(1.0 sq mm) five
wire cable bundle.
Outputs/Power:
14 to 18 AWG
(2.0 to
1.0 sq mm).
22 AWG
(0.34 sq mm)
14 AWG
(2.0 sq mm)
Standard thermostat
wire.
NEC Class 2, 140°F
(60°C) rating.
Twisted pair solid
conductor,
nonshielded or
Echelon® approved
cable.
Any pair nonshielded
(use heavier wire for
longer runs).
Specification
or RequirementVendor Wire Type
Level IV, 140°F
(60°C) rating.
Level IV, 140°F
(60°C) rating.
NEC Class II,
140°F (60°C)
rating.
Honeywell AK3725
(US only), typical or
equivalent.
Honeywell AK3752
(US only), typical or
equivalent.
LonWorks Bus (nonplenum): 22 AWG
(0.325 sq mm) twisted pair solid conductor,
nonshielded or Echelon approved shielded
cable.
Inputs: 18 AWG (1.0 sq mm) five wire cable
bundle.
Outputs/Power: 14 to 18 AWG
(2.0 to 1.0 sq mm).
18 AWG (1.0 sq mm) twisted pair.Non-plenum.
16 AWG (1.3 sq mm) twisted pair.Non-plenum.
14 AWG (2.0 sq mm) two conductor.Non-plenum.
e cool conventional system with
e heat, two-stage cool
e heat, two-stage cool
Includes AS terminals for optional dischar
sensin
economizer.
Includes AS terminals for optional dischar
sensin
economizer.
Includes AS terminals for optional discharge air
sensin
economizer.
Includes AS terminals for optional dischar
sensin
economizer.
Use with Q7300H Communicatin
network communications.
Use with Q7300H Communicating Subbase for
network communications.
to designated area.
location of specific Excel 10s on network.
Obtain locally from any computer hardware
vendor.
Level IV, 140°F (60°C) rating.
Level IV, 140°F (60°C) rating.
Standard thermostat wire.
NEC Class 2, 140°F (60°C) rating.
; A1, A2, A3 terminals for optional
; A1, A2, A3 terminals for optional
; A1, A2, A3 terminals for optional
; A1, A2, A3 terminals for optional
Subbase for
e air
e air
e air
1963-4365
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
Step 6. Configure T7300F/Q7300H
Use Excel LonSpec™ Software to configure the
T7300F/Q7300H Thermostat/Subbase for specific
applications. The Excel LonSpec™ User’s Guide, form 742937, provides software operation instructions for the
personal computer.
Step 7. Troubleshooting
1.
Check for 24 Vac power.
a. Turn on power.
b. Use a meter to check for 24 Vac power at the
subbase.
c. If 24 Vac is not present, check the transformer
for secure connections and proper operation.
d. If 24 Vac is present at the subbase, turn off the
power.
2.
Check wiring.
a. Inspect all wiring connections at the Q7300H
terminals and verify compliance with the job
site engineering drawings.
b. If any wiring changes are required,
sure to remove power from the device
starting work.
c.Pay particular attention to:
Terminal connections. Connect GND to
earth ground.
Device Wiring. In hookups with A1 and A2
terminals, use A1 and A2 when contacts
are normally closed in Occupied mode. In
hookups with A2, A3 terminals, use A2
and A3 when contacts are normally open
in Occupied mode.
O/B Terminals. The Q7300H2003
provides O/B terminals for cool/heat
changeover.
NOTE: All wiring must comply with applicable electrical
codes and ordinances or as specified in
installation wiring diagrams.
first
be
before
APPENDIX A: SEQUENCE OF
OPERATIONS
This appendix provides the network related control
sequences of operation for the T7300F/Q7300H. For
temperature control related sequences, refer to the
T7200D,E, T7300D,E,F and Q7300 Series 2000
Programmable Commercial Thermostat and Subbase
Product Data, form no. 63-4355.
Network Operations
Room Temperature Sensor (DestRmTemp)
This is the room space temperature sensor. This sensor
can be local (contained internally within the T7300F),
remote (external but hard-wired back to the Q7300H
subbase), or network (physical sensor is located
elsewhere on the LonWorks Bus, and its value is
communicated to the Q7300H). The Room Temperature
sensor provides the temperature input for the temperature
control loop of the T7300F. If both local and remote
sensors are available, the two values can be
the resulting value supplied to the temperature control
routine.
NOTE: A physical sensor (either local or remote)
be averaged with a network sensor. A valid value
for the network sensor input gives the network
sensor priority over any locally-wired sensors.
If a valid room temperature value is not available to the
T7300F/Q7300H, the temperature control algorithm in the
T7300F is disabled, causing the heating and cooling
control outputs to be turned off.
averaged
cannot
and
Network Setpoint (DestSetPoint)
This is a center-setpoint signal sent from another
LonWorks Bus device. When received, it is used to
calculate the actual cooling or heating occupied setpoint.
The DestSetPoint value becomes the center of the Zero
Energy Band (ZEB) between the cooling and heating
occupied setpoints. The size of the ZEB is found by taking
the difference between the programmed heating and
cooling occupied setpoints (CoolOccSpt and HeatOccSpt);
therefore, the actual setpoints are found as follows:
ActualCoolSpt = DestSetPoint + (CoolOccSpt -
HeatOccSpt) / 2
ActualHeatSpt = DestSetPoint - (CoolOccSpt -
HeatOccSpt) / 2
During unoccupied times, the network setpoint value is not
referenced, and the programmed setpoints are used
instead (CoolUnoccSpt and HeatUnoccSpt). During
occupied times, if DestSetPoint is valid, it will be used to
override any internal setpoints.
Network Setpoint Offset (DestSptOffset)
This is a setpoint adjustment signal sent from another
LonWorks device. When received, it is used to
current setpoint value up or down. The amount of the
bump is the value of DestSptOffset itself. The actual
setpoints are found as follows:
ActualSetpoint = CurrentSetPoint + DestSptOffset
During unoccupied times, the network setpoint offset value
is not referenced, and the programmed setpoints are used
instead (CoolUnoccSpt and HeatUnoccSpt).
bump
the
Setpoint Limits (MinCoolSetPt and MaxHeatSetPt)
User-entered setpoint limits are provided by MinCoolSetPt
and MaxHeatSetPt. The occupied setpoints used in the
control algorithms are limited by these parameters. The
lowest actual setpoint allowed in cool mode is equal to
MinCoolSetPt, and the highest actual setpoint allowed in
heat mode is equal to MaxHeatSetPt.
63-436520
T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
Bypass Operation (StatusOcc, DestManOcc and
DestBypass)
During unoccupied periods, the facility occupant can
request that the occupied temperature control setpoints be
observed by doing any one of the following:
— Depressing the Temporary Occupied button on the
T7300F, or
— Setting the DestManOcc network point to Bypass, or
— Setting the DestBypass network point to ON.
When activated, the thermostat remains in Bypass mode
until:
— Bypass duration setting has timed out (BypTime), or
— User presses the Run button on the T7300F to switch
off the Bypass mode, or
— Occupancy schedule switches the mode to occupied,
or
— User sets the DestManOcc network point to occupied,
or unoccupied.
BypassTime
BypassTime is the time between the pressing of the
override button at the wall module (or initiating bypass
mode via DestManOcc) and the return to the original
occupancy state. When the bypass state has been
activated, the bypass timer is set to BypTime (default of
180 min.).
NOTE: A Bypass mode initiated via DestBypass does
cause the bypass timer to run. The DestBypass
signal source is assumed to be tracking the
duration peiod using its internal bypass timer.
not
Override Priority
A network bypass signal always has priority over local
pushbutton induced overrides. When DestManOcc is not
OC_NUL, then the effective occupancy is DestManOcc,
regardless of the T7300F keypad-initiated override state.
Continuous Unoccupied Mode
This mode is entered when the Continuous Unoccupied
button on the T7300F is pressed. This mode can also be
entered via a network command (DestManOcc set to
Unoccupied). If the controller is in this mode, it reverts to
the unoccupied setpoints for temperature control. The
thermostat remains in this mode indefinitely until the Run
button is pressed to exit the mode, or a network command
is sent to clear the mode.
Occupancy Mode Arbitration (StatusOcc)
The T7300F/Q7300H has multiple sources for occupancy
schedule information and, therefore, it employs an
arbitration scheme to determine the current actual mode.
Time-of-day (TOD) schedule status comes from either one
of two sources:
— Internal schedule contained in the T7300F, or
— DestOccSchedule network input received from
another LonWorks device.
If DestOccSchedule is valid, it has highest priority and
determines the occupancy mode; otherwise, the status is
determined by the internal schedule of the T7300F.
StatusOcc has two possible states: occupied, or
unoccupied.
not
NOTE: The T7300F/Q7300H does
mode.
Manual Override of occupancy mode can occur from three
sources and is governed by two selectable arbitration
schemes. The two schemes are: Network Wins or Last-in
Wins, (as set in OvrdPriority).
The three sources of manual override status are:
— DestManOccPossible states: Occupied,
Unoccupied, Bypass, Standby and Null (not active). If
Standby is received, it is ignored. This input source
has the highest priority in determining manual override
status for a Network Wins arbitration scheme, or in the
event there is more than one source change at a time
in the Last-in Wins arbitration scheme. Bypass
initiates a self-timed bypass of the control unit and
expires upon completion of the defined timed period.
The controller then treats the bypass status of this
input as Null until the next change in status.
— DestBypassPossible states: Bypass On, Bypass Off
or Not Assigned (not active). This input places the
controller in an untimed bypass state or turns off the
bypass mode. This source is second in priority to
DestManOcc under the same arbitration schemes
mentioned above.
— The T7300F keypad (Temporary Occupied and
Continuous Unoccupied keys).
support Standby
Demand Limit Control (DestDlcShed)
When the Q7300H receives a high-electrical-demand
signal, the controller applies a DlcBumpTemp amount to
the current actual space temperature setpoint value. The
setpoint is always adjusted in the energy-saving direction.
This means that if the T7300F is in cooling mode, the DLC
offset bumps the control point up and when in heating
mode, bumps the control point down.
When returning from a DLC Shed event, the setpoint is
gradually ramped back to its original (unbumped) value
over a 30-minute period.
Start-Up
START_UP_WAIT is the first mode after application restart
or power-up. During START_UP_WAIT, no control
algorithms are active.
NOTES:
After a controller commission via Excel LonSpec™,
the Q7300 is reset and an application restart occurs.
Not all network inputs can be received during the
START_UP_WAIT period because many network
variables are updated at a slower rate; therefore some
control decisions can be considered temporarily
inappropriate during START_UP_WAIT.
2163-4365
63-436522
2363-4365
Home and Building ControlHome and Building ControlHoneywell Asia Pacific Inc.
Honeywell Inc.Honeywell Limited-Honeywell LimiteeRoom 3213-3225
Honeywell Plaza155 Gordon Baker RoadSun Hung Kai Centre
P.O. Box 524North York, OntarioNo. 30 Harbour Road
Minneapolis, MN 55408-0524M2H 3N7Wanchai
Hong Kong
Honeywell Latin American RegionHoneywell Europe S.A.
480 Sawgrass Corporate Parkway3 Avenue du Bourget
Suite 2001140 Brussels
Sunrise, FL 33325Belgium
Printed in U.S.A. on recycled
paper containing at least 10%
63-4365 J.S. 12-98
post-consumer paper fibers.
www.honeywell.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.