Honeywell T7300D User Manual

Commercial Microelectronic
APPLICATION
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
not
place your old
T7300D Series 2000
Thermostat
INSTALLATION INSTRUCTIONS
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Mounting Thermostat on Subbase
The thermostat mounts on the subbase after it is installed.
1. Engage tabs at the top of thermostat and subbase.
See Fig. 1.
2. Press lower edge of case to latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; then remove the top.
®U.S. Registered Trademark Copyright © 1999 Honeywell Inc. • • All Rights Reserved
M4824A
Fig. 1. Mounting thermostat on subbase.
SETTINGS
Using Thermostat Keys
The thermostat keys are used to:
• set current time and day,
• program times and setpoints for heating and cooling,
• override the program temperatures,
• display present setting,
• set system and fan operation,
• configure Installer Setup,
• check Installer System Test. See Fig. 2 for key information.
X-XX UL
62-0132
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
ENTER UNOCCUPIED
ENTER OCCUPIED PROGRAM MODE
RETURNS TO NORMAL OPERATIONS
SET OVERRIDE TEMPERATURE OFFSET AND ACTIVATE TEMPORARY OVERRIDE
ENTER HOLD MODE
Program
Temporary
Occupied
Continuous
Unoccupied
PROGRAM MODE
Occupied
Run
Start Time
Set Current
Day/Time
SET CURRENT DAY AND TIME
CLEAR PROGRAM PERIOD
SET CURRENT DAY OR PROGRAM DAY
Mon
Occupied
System Fan
Heat
Set Program Set Temperature Change
Unoccupied
Start Time Day
Clear
Start Time
AM
Copy
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
Fig. 2. Thermostat key locations and descriptions.
Setting System and Fan (select models)
The system default setting is Heat. The fan default is set so the fan operates continuously in Occupied and Recovery mode and with the heating or cooling equipment in Unoccupied mode. Use the System and Fan keys to change the settings.
The system settings are: Heat: Thermostat controls the heating. Off: Both the heating and cooling are off. Cool: Thermostat controls the cooling. Auto: Thermostat automatically changes between heating
and cooling operation depending on the indoor temperature.
The fan settings are: On: Fan operates continuously. Auto: Equipment controls fan.
Setting Temperature
Refer to Table 1 for the default temperature setpoints. See Owners Guide form number 63-4356 for complete instructions on changing the setpoints.
Table 1. Default Temperature Setpoints.
Control Occupied Unoccupied
Heating 70°F (21°C) 55°F (13°C) Cooling 78°F (25.5°C) 90°F (32°C)
SET OCCUPIED TEMPERATURE SETPOINTS
Room
Auto
Occupied
Unoccupied
Temp
System Fan
SELECT SYSTEM OPERATION
Temp
Heat/Cool
Settings
SELECT FAN OPERATION
SET UNOCCUPIED TEMPERATURE SETPOINTS AND SCROLLS THROUGH INSTALLER SETUP AND SYSTEM TEST
Time/Temp
CHANGE BETWEEN HEATING AND COOLING SETPOINTS AND SCROLLS BACKWARDS THROUGH INSTALLER SETUP NUMBERS AND SYSTEM TEST
INCREASE TEMPERATURE OR TIME SETTING
DECREASE TEMPERATURE OR TIME SETTING
M10233A
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the factory-settings in Table 2 and if no changes are necessary, go to the Installer Self-Test section.
The Installer Setup is used by the installer to customize the thermostat to specific systems. Installer Setup numbers are listed in Table 2. The table includes all the configuration options available.
A combination of key presses are required to use the Installer Setup feature. — To enter the Installer Setup, press and hold the Heat/
Cool Settings key with both the increaseand decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 3 and 4.
62-0132
2
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Em Ht
Set Program
Set Day/Time
— To advance to the next Installer Setup number, press
the Unoccupied Temp key.
— To return to a previous Installer Setup number, press
the Heat/Cool Settings key.
— To change a setting, use the increaseor
decrease key.
— To exit the Installer Setup, press the Run Program
M4916
key. The Installer Setup is automatically exited if no key presses are made for four minutes.
Installer Setup numbers are listed in Table 2.
CAUTION
Electric heat systems must be configured correct­ing in Installer Setup 2 to prevent equipment damage caused by the system running without the fan.
IMPORTANT
Only configurable numbers are shown on the device. Example: If thermostat does not have a system key, Installer Setup Number 12 will not be displayed. Review Table 2 factory-settings and mark any desired changes in the Actual Setting column. When Installer Setup is complete, review the settings to confirm that they match the system.
AM PM
Recovery
In Lo
Med
Wait
Temporary Setting Enrg
Room
%Humid
Cool
Auto
Remote
Only
On
Duct
Auto
Heat
Hi
Sav
Set Program Em Ht Aux Ht
Comm Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System Fan
Off Auto
Heat
Em
Start Time
Cool
Set Day/Time
Fig. 3. Display of all the segments of the LCD.
INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 2)
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 2)
M10238B
Fig. 4. Display of Installer Setup number and setting.
Table 2. Thermostat Installer Setup Options.
Installer Setup
Number
Select
(Press
Unoccupied
Temp key
to change)
Factory-Setting
Display Description Display Description
Other Choices
(Press or key to change)
Not used 1 — Fan operation 2 0 Conventional applica-
Output stages of heating
Heating cycle rate
3 Depends
on subbase
46Stage 1—4 cph 8 5 6 Stage 2—4 cph
tions where equipment controls fan operation in heat mode
Stages of heat 0, 1, 2,
1 Electric heat applications
or 3
where thermostat controls fan operation in heat mode
0—No heating 1—One stage of heat 2—Two stages of heat 3—Three stages of heat
3, 4, 8, 9 cph
6 6 Stage 3—4 cph Not used 7 — Output stages
of cooling
8 Depends
on subbase
Three stages of cool 0, 1, 2
or 3
0—No cooling 1—One stage of cool 2—Two stages of cool 3—Three stages of cool
(continued)
Actual Setting
3
62-0132
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
Installer Setup
Number
(Press
Unoccupied
Temp key
Select
Cooling cycle rate
System setting adjustment (models with System key)
Degree tempera­ture display
Clock format 16 0 12-hour clock format 1 24-hour clock format Intelligent Fan™
operation
Auxiliary Contact Operation
Fan key adjustment (models with Fan key only)
Remote sensing 22 0 Remote sensing not
Keypad lockout level (keypad lockout is enabled and disabled by DIP switch 1 on back of thermostat)
Duration of temporary override
Minimum off time for the compressor
to change)
9 4 Stage 1—4 cph 3 3—3 cph
10 4 Stage 2—4 cph
11 4 Stage 3—4 cph
12 Depends
14 0 Temperature is
17 2 Fan operates
18 0 0—Time of day
21 0 Fan setting key is
25 0 No lockout 1 or 2, 3 1—Lockout all keys on
26 3 3—Three hour
33 4 4 minute minimum off
Factory-Setting
Display Description Display Description
on model
System selection 0, 1 or 2 0—System setting key is
displayed in °F
continuously in Occupied and Recovery mode. Fan operates with call for heating or cooling in Unoccupied mode.
contacts
operational
activated
override
time for the compressor
1 Temperature is displayed in
0 or 1 0—Fan only operates with
1 1—Economizer contacts
1 Fan setting key is Auto only
1 Remote sensing activated
1, 8 or 12 1—One hour override
0, 1, 2, 3 or 5
Other Choices
(Press or key to change)
operational 1—Auto setting is disabled 2—Auto only setting
°C
calls for heating or cooling
in Occupied and
Unoccupied modes. 1—Fan operates
continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.
thermostat except system
and fan settings, temporary
setpoint, clock and day
adjustments 2—Lockout all keys except
Set Current Day/Time,
increase and decrease
keys.
3—Lockout all keys except
Temporary Occupied, Set
Day and Clock keys
8—Eight hour override 12—Twelve hour override
Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor
Actual Setting
(continued)
62-0132
4
Loading...
+ 8 hidden pages