Honeywell T7300D User Manual

Commercial Microelectronic
APPLICATION
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
not
place your old
T7300D Series 2000
Thermostat
INSTALLATION INSTRUCTIONS
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Mounting Thermostat on Subbase
The thermostat mounts on the subbase after it is installed.
1. Engage tabs at the top of thermostat and subbase.
See Fig. 1.
2. Press lower edge of case to latch.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; then remove the top.
®U.S. Registered Trademark Copyright © 1999 Honeywell Inc. • • All Rights Reserved
M4824A
Fig. 1. Mounting thermostat on subbase.
SETTINGS
Using Thermostat Keys
The thermostat keys are used to:
• set current time and day,
• program times and setpoints for heating and cooling,
• override the program temperatures,
• display present setting,
• set system and fan operation,
• configure Installer Setup,
• check Installer System Test. See Fig. 2 for key information.
X-XX UL
62-0132
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
ENTER UNOCCUPIED
ENTER OCCUPIED PROGRAM MODE
RETURNS TO NORMAL OPERATIONS
SET OVERRIDE TEMPERATURE OFFSET AND ACTIVATE TEMPORARY OVERRIDE
ENTER HOLD MODE
Program
Temporary
Occupied
Continuous
Unoccupied
PROGRAM MODE
Occupied
Run
Start Time
Set Current
Day/Time
SET CURRENT DAY AND TIME
CLEAR PROGRAM PERIOD
SET CURRENT DAY OR PROGRAM DAY
Mon
Occupied
System Fan
Heat
Set Program Set Temperature Change
Unoccupied
Start Time Day
Clear
Start Time
AM
Copy
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
Fig. 2. Thermostat key locations and descriptions.
Setting System and Fan (select models)
The system default setting is Heat. The fan default is set so the fan operates continuously in Occupied and Recovery mode and with the heating or cooling equipment in Unoccupied mode. Use the System and Fan keys to change the settings.
The system settings are: Heat: Thermostat controls the heating. Off: Both the heating and cooling are off. Cool: Thermostat controls the cooling. Auto: Thermostat automatically changes between heating
and cooling operation depending on the indoor temperature.
The fan settings are: On: Fan operates continuously. Auto: Equipment controls fan.
Setting Temperature
Refer to Table 1 for the default temperature setpoints. See Owners Guide form number 63-4356 for complete instructions on changing the setpoints.
Table 1. Default Temperature Setpoints.
Control Occupied Unoccupied
Heating 70°F (21°C) 55°F (13°C) Cooling 78°F (25.5°C) 90°F (32°C)
SET OCCUPIED TEMPERATURE SETPOINTS
Room
Auto
Occupied
Unoccupied
Temp
System Fan
SELECT SYSTEM OPERATION
Temp
Heat/Cool
Settings
SELECT FAN OPERATION
SET UNOCCUPIED TEMPERATURE SETPOINTS AND SCROLLS THROUGH INSTALLER SETUP AND SYSTEM TEST
Time/Temp
CHANGE BETWEEN HEATING AND COOLING SETPOINTS AND SCROLLS BACKWARDS THROUGH INSTALLER SETUP NUMBERS AND SYSTEM TEST
INCREASE TEMPERATURE OR TIME SETTING
DECREASE TEMPERATURE OR TIME SETTING
M10233A
INSTALLER SETUP
NOTE: For most applications, the thermostat factory-
settings do not need to be changed. Review the factory-settings in Table 2 and if no changes are necessary, go to the Installer Self-Test section.
The Installer Setup is used by the installer to customize the thermostat to specific systems. Installer Setup numbers are listed in Table 2. The table includes all the configuration options available.
A combination of key presses are required to use the Installer Setup feature. — To enter the Installer Setup, press and hold the Heat/
Cool Settings key with both the increaseand decrease keys until the first number is displayed. All display segments appear for approximately three seconds before the number is displayed. See Fig. 3 and 4.
62-0132
2
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Em Ht
Set Program
Set Day/Time
— To advance to the next Installer Setup number, press
the Unoccupied Temp key.
— To return to a previous Installer Setup number, press
the Heat/Cool Settings key.
— To change a setting, use the increaseor
decrease key.
— To exit the Installer Setup, press the Run Program
M4916
key. The Installer Setup is automatically exited if no key presses are made for four minutes.
Installer Setup numbers are listed in Table 2.
CAUTION
Electric heat systems must be configured correct­ing in Installer Setup 2 to prevent equipment damage caused by the system running without the fan.
IMPORTANT
Only configurable numbers are shown on the device. Example: If thermostat does not have a system key, Installer Setup Number 12 will not be displayed. Review Table 2 factory-settings and mark any desired changes in the Actual Setting column. When Installer Setup is complete, review the settings to confirm that they match the system.
AM PM
Recovery
In Lo
Med
Wait
Temporary Setting Enrg
Room
%Humid
Cool
Auto
Remote
Only
On
Duct
Auto
Heat
Hi
Sav
Set Program Em Ht Aux Ht
Comm Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System Fan
Off Auto
Heat
Em
Start Time
Cool
Set Day/Time
Fig. 3. Display of all the segments of the LCD.
INSTALLER SETUP NUMBER DISPLAY (COLUMN 2 OF TABLE 2)
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 2)
M10238B
Fig. 4. Display of Installer Setup number and setting.
Table 2. Thermostat Installer Setup Options.
Installer Setup
Number
Select
(Press
Unoccupied
Temp key
to change)
Factory-Setting
Display Description Display Description
Other Choices
(Press or key to change)
Not used 1 — Fan operation 2 0 Conventional applica-
Output stages of heating
Heating cycle rate
3 Depends
on subbase
46Stage 1—4 cph 8 5 6 Stage 2—4 cph
tions where equipment controls fan operation in heat mode
Stages of heat 0, 1, 2,
1 Electric heat applications
or 3
where thermostat controls fan operation in heat mode
0—No heating 1—One stage of heat 2—Two stages of heat 3—Three stages of heat
3, 4, 8, 9 cph
6 6 Stage 3—4 cph Not used 7 — Output stages
of cooling
8 Depends
on subbase
Three stages of cool 0, 1, 2
or 3
0—No cooling 1—One stage of cool 2—Two stages of cool 3—Three stages of cool
(continued)
Actual Setting
3
62-0132
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
Installer Setup
Number
(Press
Unoccupied
Temp key
Select
Cooling cycle rate
System setting adjustment (models with System key)
Degree tempera­ture display
Clock format 16 0 12-hour clock format 1 24-hour clock format Intelligent Fan™
operation
Auxiliary Contact Operation
Fan key adjustment (models with Fan key only)
Remote sensing 22 0 Remote sensing not
Keypad lockout level (keypad lockout is enabled and disabled by DIP switch 1 on back of thermostat)
Duration of temporary override
Minimum off time for the compressor
to change)
9 4 Stage 1—4 cph 3 3—3 cph
10 4 Stage 2—4 cph
11 4 Stage 3—4 cph
12 Depends
14 0 Temperature is
17 2 Fan operates
18 0 0—Time of day
21 0 Fan setting key is
25 0 No lockout 1 or 2, 3 1—Lockout all keys on
26 3 3—Three hour
33 4 4 minute minimum off
Factory-Setting
Display Description Display Description
on model
System selection 0, 1 or 2 0—System setting key is
displayed in °F
continuously in Occupied and Recovery mode. Fan operates with call for heating or cooling in Unoccupied mode.
contacts
operational
activated
override
time for the compressor
1 Temperature is displayed in
0 or 1 0—Fan only operates with
1 1—Economizer contacts
1 Fan setting key is Auto only
1 Remote sensing activated
1, 8 or 12 1—One hour override
0, 1, 2, 3 or 5
Other Choices
(Press or key to change)
operational 1—Auto setting is disabled 2—Auto only setting
°C
calls for heating or cooling
in Occupied and
Unoccupied modes. 1—Fan operates
continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.
thermostat except system
and fan settings, temporary
setpoint, clock and day
adjustments 2—Lockout all keys except
Set Current Day/Time,
increase and decrease
keys.
3—Lockout all keys except
Temporary Occupied, Set
Day and Clock keys
8—Eight hour override 12—Twelve hour override
Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor
Actual Setting
(continued)
62-0132
4
Select
Temperature display adjustment
Minimum off times in heating
Installer Setup lockout (keypad lockout is enabled and disabled by DIP switch 1 on back of thermostat)
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
Installer Setup
Number
(Press
Unoccupied
Temp key
to change)
37 0 No difference in
38 4 4—4 minute minimum
40 0 0—No Installer Setup
Factory-Setting
Display Description Display Description
displayed temperature and actual room temperature89
off time
lockout
Other Choices
(Press or key to change)
1 thru 6
0, 1, 2, 3, or 5
1 1—Installer Setup lockout
1—Display adjusts to 1°F
higher than actual room
temperature 2—Display adjusts to 2°F
higher than actual room
temperature 3—Display adjusts to 3°F
higher than actual room
temperature 4—Display adjusts to 1°F
lower than actual room
temperature 5—Display adjusts to 2°F
lower than actual room
temperature 6—Display adjusts to 3°F
lower than actual room
temperature Minimum number of minutes
(0 thru 5) the heating equipment will be off between calls for heat
activated
Actual Setting
IMPORTANT
Review the settings to confirm that they match the system. Press Run Program to exit the Installer Setup. Be sure to set the current day and time immediately.
Setting Current Day and Time
1. Press Set Current Day/Time.
NOTE: On initial power up or after an extended
power loss, 1:00 pm flashes on the LCD until a key is pressed.
Set Current
Day/Time
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous Unoccupied
Time/Temp
Occupied
Unoccupied
Unoccupied
Temp
Start Time Day
Temp
Clear
Start Time
Mon
Heat/Cool
Copy
Settings
System Fan
Set Day/Time
PM
M4951B
2. Press Day until the current day is displayed.
NOTE: Sun=Sunday, Mon=Monday,
Tue=Tuesday, Wed=Wednesday, Thu=Thursday, Fri=Friday, Sat=Saturday.
Day
3. Press increase or decrease until the current
time is displayed.
NOTE: Tapping the Set Current Day/Time will
5
Set Program Set Temperature Change
Time/Temp
Occupied
Unoccupied
Occupied
Run
Unoccupied
Temp
Start Time Day
Start Time
Program
Temp
Temporary
Set Current
Clear
Copy
Occupied
Day/Time
Start Time
Continous Unoccupied
Tue
Heat/Cool
Settings
System Fan
change the time in one hour increments.
Set Program Set Temperature Change
Time/Temp
Occupied
Unoccupied
Occupied
Run
Unoccupied
Temp
Start Time Day
Start Time
Program
Temp
Temporary
Set Current
Clear
Copy
Occupied
Day/Time
Start Time
Continous Unoccupied
Tue
Heat/Cool
Settings
System Fan
Set Day/Time
PM
Set Day/Time
PM
M4952B
M4953B
62-0132
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Em Ht
Set Program
Set Day/Time
4.. Press Run Program.
Run
Program
Set Program Set Temperature Change
Occupied
Run
Start Time
Program
Temporary
Set Current
Occupied
Day/Time
Continous Unoccupied
Time/Temp
Unoccupied
Occupied
Unoccupied
Temp
Temp
Start Time Day
Heat/Cool
Clear
Settings
Start Time
Copy
System Fan
AM
Mon
Occupied 1
System Fan
Heat
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat configurations and operation. Refer to Table 3 for a list of the available system tests.
Table 3. Tests Available in Installer System Test.
Test
Number System Test Description
Press and hold the increaseand ▼ decrease keys, at the same time, until 10 appears. All segments of the LCD are displayed for three seconds before 10 appears. See
Room
Fig. 5 and 6.
Auto
M4954A
Set Program Em Ht Aux Ht
Comm Mon Un
Occupied 12 Override
System Fan
Em
Fig. 5. Display of all the segments of the LCD.
10 to 19 Heating equipment can be turned on and off 30 to 39 Cooling equipment can be turned on and off 40 to 49 Fan equipment can be turned on and off 60 0 to
60 19 70 to 79 Thermostat information including date code,
To start the system test:
Keyboard keys test
software versions and subbase identification are displayed
CAUTION
The minimum off time for compressors is bypassed during the Installer System Test. Equipment damage can occur if the compressor is cycled too quickly.
Refer to Table 4 and Thermostat Information section for directions and results of the specific system tests.
NOTE: Press Run Program to exit the system test. The
Table 4. Installer System Test Options.
Key to
Press
Test
Number Description
Heating Equipment System Test
Heat/Cool Settings 10 Enter heating equipment system test.
11 Stage-one heat comes on. When Installer Setup number 02 is 01, the system fan
is also energized.
12 Stage-two heat comes on. Stage-one heat and system fan remain on. 13 Stage-three heat comes on. Stage-one and stage-two heat with the system fan
are on.
12 Stage-three heat turns off. 11 Stage-two heat turns off. 10 Stage-one heat and system fan turn off.
AM PM
Recovery
In Lo
Med
Wait
Temporary Setting Enrg
%Humid
Cool
Auto
Remote
Only
On
Heat
Hi
Set Day/Time
Start Time
TueWedThuFriSatSun
Off Auto
Cool
Heat
TEST NUMBER
Fig. 6. Display of test number.
system test times out after four minutes without any key presses.
(continued)
Sav
Room
Duct
Auto
M4916
M10257A
62-0132
6
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Table 4. Installer Self-Test Options (Continued).
Key to
Press
Cooling Equipment System Test
Heat/Cool Settings 30 Change from heating to cooling equipment system test.
31 Stage-one cooling and system fan come on. 32 Stage-two cool comes on. Stage-one cool and system fan remain on. 33 Stage-three cool comes on (Q7300G only). Stage-one and stage-two cool with
32 Stage-three cool turns off. 31 Stage-two cool turns off. 30 Stage-one cool and system fan turn off.
Fan Equipment System Test
Heat/Cool Settings 40 Change from cooling to fan equipment system test.
41 Fan comes on. 40 Fan turns off.
Key Operation System Test
Heat/Cool Settings 60 2 Change from fan to key operation system test.
Unoccupied Temp 60 0 Unoccupied Temp test number is displayed.
Occupied Temp 60 1 Occupied Temp test number is displayed.
60 3 Increase test number is displayed. 60 5 Decrease test number is displayed.
Clear Start Time 60 7 Clear Start Time test number is displayed.
Day 60 8 Day test number is displayed.
Copy 60 9 Copy test number is displayed.
Unoccupied Start
TIme
System 60 11 System test number is displayed.
Fan 60 12 Fan test number is displayed.
Set Current
Day/Time
Run Program 60 15 Run Program test number is displayed.
Temporary
Occupied
Occupied Start Time 60 17 Occupied Start Time test number is displayed.
Continuous
Unoccupied
Test
Number Description
system fan remain on.
60 10 Unoccupied Start Time test number is displayed.
60 14 Set Current Day/Time test number is displayed.
60 16 Temporary Occupied test number is displayed.
60 19 Continuous Unoccupied test number is displayed.
Thermostat Information
1. Press the Heat/Cool Settings key to access the
thermostat information.
M4934
2. Press the increasekey to display the production
date code. The first two large digits are the month and the third digit is the last digit of the year. (Example: 036 = March 1996)
M4931
3. Press the increasekey again to display the
software identification code. (Example: 02 = software ID code 2)
4. Press the increasekey again to display the
software revision number. (Example: 001 = revision number 1)
7
M4932A
M10229
62-0132
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
5. Press the increasekey again to display the
EEPROM identification code. (Example: 314= EEPROM ID 314)
M4933A
6. Press the increasekey again to display the
subbase identification code. (Example: C= conventional subbase)
M10289
7. Press Run Program to exit the system test. The
system test times out after four minutes without any key presses.
The factory-setting is off (down). Remove the thermostat from the subbase and set the switch to ON if keypad lockout is desired. Setting DIP switch 1 to the ON position disables all of the keys on the thermostat.
BACK OF THERMOSTAT
Fig. 7. Setting the keypad lockout DIP switch 1
Setting Keypad Lockout Switch
The DIP switch 1 on the back of the thermostat activates the lockout feature. The switch must be set to the ON position (up) to activate the lockout feature. See Fig. 7.
NOTE: DIP switch 1 should be set to ON prior to entering
Installer setup. This only applies when changing Installer setup number 25 or 40.
TROUBLESHOOTING GUIDE
Symptom Possible Cause Action
Display will not come on.
Temperature display is incorrect.
Temperature settings will not change. (Example: Cannot set heating higher or cooling lower.)
Thermostat is not being powered.
Room temperature display has been reconfigured.
Thermostat is configured for °F or °C display.
• Check that X terminal is connected to the system transformer.
• Check for 24 Vac between X and R or RH terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker.
— check if the system fuse is blown—replace the
fuse.
— check if the power switch on the HVAC
equipment is in the Off position—set to the On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Enter Installer Setup number 37 and reconfigure the display.
Enter Installer Setup number 14 and reconfigure the display.
Bad thermostat location. Relocate the thermostat. Display shows two dashes
and a degree sign. Upper or lower temperature
limits were reached.
The setpoint temperature range stops were configured.
Keypad is locked. When a locked key is pressed, LOC will flash on the LCD.
Installer Setup 22 is set for remote sensing and the sensor is missing or the circuit is open or shorted.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (7 to 31°C)
• Cooling limits are 45 to 99°F (9 to 37°C)
Check Installer Setup number 34 and 35 and reconfigure the setpoint stops.
• Reset DIP switch 1 on back of thermostat to enable keypad.
ON
1
1
1
2
on the back of the thermostat.
2
2
DIP 1 IS ON
DIP 2 IS NOT USED.
M10235
(continued)
62-0132
8
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
TROUBLESHOOTING GUIDE (Continued).
Symptom Possible Cause Action
Temperature settings change from original setting.
Room temperature is out of control.
Heating will not come on.
Cooling will not come on.
System on indicator (flame=heat, snowflake=cool) is displayed, but no warm or cool air is coming from the registers.
Trying to set heating and cooling setpoints too close together. There is a deadband in automatic changeover thermostats. Example: cool setpoint=72, deadband=3, heat setpoint=68, changing heat setpoint to 70 will automatically change the cool setpoint to 73.
Remote temperature sensing is not working.
No power to the thermostat. • Check that X terminal is connected to the system
Thermostat minimum off time is activated and wait indicator is displayed.
System selection is not set to Heat.
No power to the thermostat. • Check that X terminal is connected to the system
Thermostat minimum off time is activated and wait indicator is displayed.
System selection is not set to Cool.
Fan operation set for 0 (conventional heat) when it should be set for 1 (electric heat).
Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint.
Heating or cooling equipment is not operating.
• Check that the heating setpoint is lower than the cooling setpoint.
Checkout all remote sensors.
transformer.
• Check for 24 Vac between X and R or RH terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker.
— check if the system fuse is blown—replace the
fuse.
— check if the system switch at the equipment is in
the Off position—set to On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
•Wait up to five minutes for the system to respond.
• Enter Installer Setup number 38. Reconfigure minimum off time (if required).
Set system selection to Heat.
transformer
• Check for 24 Vac between X and R or RC and Y terminals. — If missing 24 Vac:
— check if the circuit breaker is tripped—reset the
circuit breaker.
— check if the system fuse is blown—replace the
fuse.
— check if the system switch at the equipment is in
the Off position—set to the On position.
— check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
•Wait up to five minutes for the system to respond.
• Enter Installer Setup number 33. Reconfigure minimum off time (if required).
Set system selection to Cool.
Enter Installer Setup number 2 and reconfigure the fan operation.
Wait a minute after seeing the on indicator and then check the registers.
Verify operation of heating or cooling equipment in self-test.
9
62-0132
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
62-0132
10
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
11
62-0132
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Home and Building Control
Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis, MN 55408-0524
62-0132 D.A. 3-99
62-0132
Home and Building Control
Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7
12
www.honeywell.com/yourhome
Loading...