Honeywell T7270B2009 INSTALLATION AND OPERATING INSTRUCTIONS

Honeywell T7270B2009 INSTALLATION AND OPERATING INSTRUCTIONS

T7270B2009

WIRELESS WALL MODULE

HONEYWELL EXCEL 5000 OPEN SYSTEM

Fig. 1. T7270B2009

APPLICATION

The T7270B2009 Wireless Wall Module is designed for use in wireless systems, and is suitable for use in conjunction with the W7070A2000 ZAPP Wireless Receiver.

FEATURES

Easy mounting, no wiring;

All functions combined in a single, easy-to-use wall module;

Up to eight separate T7270B2009 wall modules can simultaneously communicate with the W7070A2000 over distances of approx. 30 meters and through two walls;

Permits not only HVAC, but also light and sunblind control;

Fits seamlessly into XL10 / XL12 individual room control systems.

® U.S. Registered Trademark

Copyright © 2007 Honeywell Inc. • All rights reserved

INSTALLATION AND OPERATING INSTRUCTIONS

STANDARDS AND NORMS

The ZAPP System complies with CE and EN 300 220-1 and EN 301 489-1.

IMPORTANT!

It is recommended that devices be kept at room temperature for at least 24 hours before applying power to allow any condensation resulting from low shipping/storage temperatures to evaporate.

Use in Combination with Legacy Devices

The T7270B2009 ZAPP Wireless Wall Module is suitable for use only with the W7070A2000 ZAPP Wireless Receiver. It cannot communicate with (but is likewise unaffected by) legacy devices (e.g. the W7070A1000).

NOTE: Do not attempt to teach-in both an RT7070A2008 and a T7270B2009 to the same room.

TECHNICAL DATA

Batteries

1.5 V, type LR06, AA

Frequency

868.3 MHz (transmitter)

OVERVIEW

Functions

In the operating mode, the T7270B2009 features the following six basic functions:

LIGHT (this is the default function),

SUNBLINDS,

OCCUPANCY,

FAN,

SETPOINT OFFSET and

TEMPERATURE DISPLAY/TRANSMIT function.

Controls

The T7270B2009 features three control buttons and a large setpoint wheel used (in the operating mode) to select individual functions and to adjust their respective settings:

the "function" button ("F"),

the UP ("") and DOWN ("") buttons, and

the setpoint wheel (for adjusting e.g. the value of the temperature setpoint offset, etc.).

EN1B-0398GE51 R1207A

T7270B2009 WALL MODULE

LCD Symbols and Printed Symbols

function

light

sunblind

occupancy

indication bar

symbol

symbol

symbol

fan

 

 

unit

symbol

 

 

 

 

 

 

MANU

 

 

fan

 

 

thermometer

mode

F

 

symbol

 

 

 

room temperature

Fig. 2. Default Display

The function in effect at any particular moment is indicated by the presence in the LCD of the function indication bar (see Fig. 2), and a corresponding symbol; e.g. the fan symbol.

OPERATING MODE

Selecting Functions / Adjusting Settings

The user can select the LIGHT, SUNBLINDS, OCCUPANCY, or FAN functions by pressing the "F" button, whereupon the current room temperature will disappear from the LCD and be replaced by the corresponding function symbol. The setting of the selected function can then be adjusted as desired using the UP button and the DOWN button.

To adjust a setting, press, as often as necessary (referred to as "cycling"), the "F" button until the symbol representing the desired function appears in the LCD. Once selected, this symbol will be displayed for 4 sec. During this time, the user can use the UP or DOWN buttons to adjust the setting. If there is no user action for more than 4 sec, the function symbol will disappear, and the T7270B2009 will revert to the default display and the default function.

The SETPOINT OFFSET function is selected and its settings adjusted using the large setpoint wheel located on the right side of the T7270B2009 (see section "SETPOINT OFFSET Function" below).

SETPOINT OFFSET Function

If the SETPOINT OFFSET function is selected (by rotating the setpoint wheel), the current temperature setpoint offset, accompanied by the degree symbol and corresponding temperature unit (°C or °F), will appear in the LCD.

NOTE: The SETPOINT OFFSET function can be configured so as to be disabled whenever the user has used the OCCUPANCY function to manually force the controller into the "unoccupied" state and parameter P8 (see page 6) has been set to 2 or 4. In this case, the setpoint offset is fixed to 0.0 °.

Adjusting the Setting

The SETPOINT OFFSET function setting can be adjusted by rotating the setpoint wheel clockwise or counterclockwise, thus increasing or decreasing (respectively) the setpoint offset over a range of max. -5...+5 K in steps of 0.5 K.

The setpoint offset range may be adjusted via parameter P4 (see page 6).

NOTE: A snowflake displayed in the lower right corner of the LCD indicates that the T7270B2009 is transmitting data. During transmission, the function keys are disabled; you will thus have to wait approx. 1 sec between e.g. switching a light ON and then OFF.

LIGHT Function

The LIGHT function is the default function (see section “Default Function” page 4). The LIGHT function can be selected by pressing the "F" button until the letters “”LI” are displayed in the LCD and the function indication bar appears underneath the light symbol imprinted on the housing.

NOTE: See also section "Default Function" on page 4.

Controlling a Single Light Group (P6:1)

If the T7270B2009 has been configured to control only a single group of lights (see section "P6: Light Groups" on page 5), the LIGHT function settings are performed as described in the following sections.

Pressing the UP Button

Briefly pressing the UP button once turns the light group ON and causes the word "ON" to appear in the LCD.

Pressing the UP button for more than 2 sec turns the light ON and starts dimming the light group. Once 0% is reached, it starts brightening from 0% to 100% (100%…0%…100%….). In the LCD, a vertical bar next to the word "ON" moves continuously from the left to the right. Releasing the UP button stops the process and causes the LCD to revert to the default display mode.

Pressing the DOWN Button

Briefly pressing the DOWN button once turns the light group OFF and causes the word "OFF" to appear in the LCD.

Pressing the DOWN button for more than 2 sec turns the light OFF and starts brightening the light group. “ON” is displayed once the brightening starts. Brightening continues until 100% is reached. Then it starts dimming from 100% to 0% (0%…100%…0%….). In the LCD, a vertical bar next to the word "ON" moves continuously from the right to the left. Releasing the DOWN button stops the process and causes the LCD to revert to the default display mode.

NOTE: If, after dimming / brightening the light group, the user uses the DOWN button to turn it OFF and subsequently back ON, it will be turned back ON at a brightness level of 100%.

Controlling Two Light Groups (P6:2 and P6:3)

Dimming / brightening is not possible if the T7270B2009 has been configured to control two light groups (see section "P6: Light Groups" on page 5). In this case, it is possible only to turn each group of lights ON or OFF.

The UP and DOWN buttons can be configured by setting parameter P6 to 2 or 3.

EN1B-0389GE51 R1207A

2

T7270B2009 WALL MODULE

NOTE: The UP and DOWN buttons can also be configured by setting parameter P6 to 4 or 5 (special custom models, only).

“UP” = ON and “DOWN” = OFF usage (P6:2)

Pressing the UP Button

Pressing the UP button will turn ON the two light groups as follows:

Pressing the UP button once turns ON light group 1, and the characters "ON 1" appear in the LCD.

Pressing the UP button twice turns ON light group 2, and the characters "ON 2" appear in the LCD.

NOTE: The corresponding ON command is transmitted only after the UP button is finally released. Thus, only one light group can be turned ON/OFF at a time.

Pressing the DOWN Button

Pressing the DOWN button will turn OFF the two light groups as follows:

Pressing the DOWN button once turns OFF light group 1, and the characters "OFF 1" will appear in the LCD.

Pressing the DOWN button twice turns OFF light group 2, and the characters "OFF 2" will appear in the LCD.

NOTE: The corresponding OFF command is transmitted only after the DOWN button is finally released. Thus, only one light group can be turned ON/OFF at a time.

“UP” = Light 1 and “DOWN” = Light 2 usage (P6:3)

Pressing the UP Button for Light Group 1

Pressing the UP button the first time will turn ON light group 1, and the characters “ON 1” will appear in the LCD. Pressing the UP button again will turn OFF light group 1, and the characters “OFF 1” will appear in the LCD.

Pressing the DOWN Button for Light Group 2

The DOWN button has the same effect upon light group 2 as the UP button upon light group 1.

Disabling the Light Function (P6:6)

The LIGHT function can be completely disabled by setting parameter P6 to 6 (in this case, the SUNBLINDS function then becomes the default function).

SUNBLINDS Function

The SUNBLINDS function can be selected by pressing the "F" button until the corresponding function symbol – a stylized representation of sunblinds (= = = =) – appears in the LCD and the function indication bar appears underneath the sunblind symbol imprinted on the housing.

The SUNBLINDS function can be configured via parameter P5 ("sunblind runtime") as well as by setting parameter P9 to 1 ("no sunblind") or to 2 ("one sunblind").

NOTE: The value of the sunblind runtime must be the same in the T7270B2009, the W7070A2000, and in the connected controller (e.g. an XL12).

NOTE: The SUNBLINDS function can also be configured by setting parameter P9 to 3 or 4 (special custom models, only) as well as via parameter PB (special custom models, only).

Refer to section “Configuration Parameters" on page 5 for details.

Raising/Lowering One Set of Sunblinds (P9:2)

Pressing the UP Button

Briefly pressing the UP button will completely raise the sunblinds; in the LCD, the "sunblinds" symbol (= = = =) moves upwards. Briefly pressing either the UP or the DOWN button while the sunblinds are rising will stop the sunblinds, and the LCD will revert to the default display.

Pressing the UP button for more than 2 sec will raise the sunblinds only as long as it remains pressed; in the LCD, the "sunblinds" symbol (= = = =) moves upwards.

Pressing the DOWN Button

Briefly pressing the DOWN button will completely lower the sunblinds; in the LCD, the "sunblinds" symbol

(= = = =) moves downwards. Briefly pressing either the UP or the DOWN button while the sunblinds are descending will stop the sunblinds, and the LCD will revert to the default display.

Pressing the DOWN button for more than 2 sec will lower the sunblinds only as long as it remains pressed; in the LCD, the "sunblinds" symbol (= = = =) moves downwards.

When changing directions, the blinds will first stop, tilt, and then move.

OCCUPANCY Function

If the OCCUPANCY function is selected (by pressing the "F" button twice), one of the three following function symbols will appear in the LCD:

A crescent moon (" "), meaning that the user wishes to override the occupancy state automatically established by the controller and manually force it into the "unoccupied" state, in which it will remain until overruled by a central control unit or until the user himself changes this by again invoking the OCCUPANCY function.

A full sun (""), meaning that the user wishes to override the occupancy state automatically established by the controller and manually force it into the "occupied" state, in which it will remain until overruled by a central control unit or until the user himself changes this by again invoking the OCCUPANCY function.

A half-sun (" "), meaning that the user wishes to override the occupancy state automatically established by the controller and manually force it into the "occupied" state for a limited time (set using the controller's plug-in).

At the same time, the function indication bar will also appear underneath the printed occupancy symbol. Thereafter, the T7270B2009 will automatically revert to the default display, i.e. it will no longer be apparent that the OCCUPANCY function had been invoked.

3

EN1B-0398GE51 R1207A

Loading...
+ 5 hidden pages