1.1Overview
The contractor shall furnish, install, and place in operating condition an HVAC control system described herein.
All units shall be located in accordance with the plans.
1.2Type of System
1.2.1System Requirements
Commercial Thermostat
GUIDE SPECIFICATION
a.Controls one heating and one cooling stages for heat pump applications.
b.Permit seven day programming.
c.Provide two occupied and two unoccupied periods per day.
d.Offer automatic heat/cool changeover with 2°F minimum deadband.
e.Provide override capability for a three hour period.
f.Include a comfort adjust feature to modify setpoints for a three hour period.
g.Provide Proportional plus Integral (P + I) temperature control.
h.Permit automatic or manual changeover between heating and cooling setpoints.
i.Display room temperature in °F or °C.
j.Display time in 12 or 24 hour clock format.
1.2.2System Components
a.Seven day programmable thermostat.
b.Wallplate.
1.3Codes and Standards
1.3.1The system shall comply with applicable provisions of ASHRAE 90-75.
1.3.2These specifications are based on equipment from Honeywell to set a standard for design and quality.
1.4Wiring
1.4.1All wiring meets National Electrical Codes and local electrical codes.
1.5Testing Guarantee Service
1.5.1Prior to installation, the contractor shall provide copies of submittals.
1.5.2The contractor is responsible for assuring that conduit and wire quantity, size, and type are suitable for
1.5.3Upon completion, the contractor shall conduct a total system test for the owner and engineer.
1.5.4All components, parts, and assemblies supplied by the manufacturer shall be guaranteed against
the equipment supplied.
defects in materials and workmanship for 12 months. Warranty service shall be performed by the
contractor.
SINGLE STAGE HEAT PUMP PROGRAMMABLE COMMERCIAL THERMOSTAT
2.0SEQUENCE OF OPERATIONS
The heating and cooling setpoints shall be individually adjustable for both the occupied and unoccupied periods. The
thermostat shall have a minimum deadband of 2°F (no mechanical heating or cooling shall operate within this
deadband). Space temperature deviation above the cooling setpoint or below the heating setpoint shall generate a
demand signal to control the system as follows.
2.1Heating
2.1.1The thermostat shall control the heating output based on the demand signal communicated from the
2.1.2The thermostat shall energize heating equipment when space temperature falls below heating
2.2Cooling
2.2.1The thermostat shall control the cooling output based on the demand signal communicated from the
2.2.2The thermostat shall energize cooling equipment when space temperature exceeds cooling setpoint.
2.3Heating Setback and Cooling Setup
Initiation of heating setback or cooling setup for each of 7 days shall be provided by a programmed time
schedule manually entered into the thermostat. When all or a portion of a manually programmed schedule is
unavailable, the thermostat shall control to the default program as follows:
2.4Setpoint Recovery from Unoccupied to Occupied
thermostat program, taking into account both space temperature deviation (proportional error) and the
duration of that temperature deviation (integral error).
setpoint.
thermostat program, taking into account both space temperature deviation (proportional error) and the
duration of that temperature deviation (integral error).
The thermostat shall employ Intelligent Recovery™. This shall select the optimum time to begin building warm
up or cool down based on setpoints and occupied program as follows:
2.4.1Heating: 5°F per hour.
2.4.2Cooling: 5°F per hour.
2.5Fan Operation
2.5.1Fan operation shall be energized with calls for cooling and calls for heating (optional).
2.6Heating and Cooling Operation Minimum On and Off Times
The thermostat shall incorporate a program to maintain minimum-stage operation in both the heating and
cooling:
2.6.1Cooling: 2 minutes on and 4 minutes off.
2.6.2Heating: 2 minutes on and 4 minutes off.
2.7Power Interruption
The system shall cycle off and provide timed restaging of heating or cooling equipment upon restoration of
power. The restaging operation shall occur according to minimum stage operation times incorporated in the
thermostat. A power interruption is annunciated by a blank LCD display.
2.7.1During a power interruption less than 2 hours, the thermostat retains all programmed occupied and
unoccupied start times and temperatures as well as the present time and day.
63-4361 2
SINGLE STAGE HEAT PUMP PROGRAMMABLE COMMERCIAL THERMOSTAT
2.7.2During a power interruption greater than 2 hours, the thermostat retains all programmed occupied and
2.8Calibration
2.8.1No calibration and no adjustment shall be required for mixed air temperature, throttling range, reset
2.8.2Temperature setting displayed on thermostat shall be adjustable within ±3°F of measured room
2.9Security
Two levels of security shall exist:
2.9.1A keypad lockout switch located on the back of the thermostat shall allow for three types of keypad
2.9.2Thermostat shall allow for door to be locked by use of two Allen head screws to lock the cover and not
2.10Overrides
Temperature setpoints can be overridden in three ways:
unoccupied start times and temperatures. Only the present time and day will need to be
reprogrammed.
ratio, band width, or discharge air temperature.
temperature (optional).
lockout.
a.Lock out all keys on the thermostat.
b.Lock out all keys on the thermostat except System and Fan settings, temporary setpoint
adjustments, and clock and day adjustments.
c.Lock out thermostat Installer Setup only.
allow access to the keypad.
2.10.1Thermostat shall allow for a 3 hour timed override from unoccupied setpoint to occupied setpoint from
the thermostat keypad.
2.10.2Thermostat shall allow for a 3 hour timed adjustment of the occupied setpoint from the thermostat
keypad.
2.10.3Thermostat shall allow for a continuous override to the unoccupied setpoint from the thermostat
keypad.
3.0MAJOR EQUIPMENT
Model
NumberDescriptionFeatures
T7200E2005Commercial programmable
thermostat, taupe color.
4.0OPTIONS
4.1System Accessories
4.1.1T675A—Remote Bulb Temperature Control, low ambient compressor lockout.
4.1.2R8222—Switching Relay.
•7-day programming
•2 occupied and 2 unoccupied periods per day
•System and fan setting key set to AUTO only
•Wallplate included
4.1.3W950—Status Panels.
363-4361
Home and Building ControlHome and Building ControlHelping You Control Your World
Honeywell Inc.Honeywell Limited-Honeywell Limitée
Honeywell Plaza155 Gordon Baker Road
P. O. Box 524North York, Ontario
Minneapolis, MN 55408-0524M2H 2C9
Printed in U.S.A. on recycled
63-4361 J.A. 2-97
paper containing at least 10%
post-consumer paper fibers.
®
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.