Honeywell T7200E, T7300D, T7300E User Manual

T7200D,E, T7300D,E,F and Q7300
Series 2000 Programmable Commercial
Thermostats and Subbases
PRODUCT DATA
T7200D,E Thermostats:
• Use on single-stage conventional (T7200D) or heat pump (T7200E) applications.
T7300D,E Thermostats:
• Use on multistage conve ntional (T7300D) or heat pump (T7300E) applications.
• Models available with remote sensor capability.
T7300F Thermostats:
• Use on single-stage or multistage system in conventional or heat pump applications.
• Auxiliary contacts on Q7300 can be used to interface with C7400/W7459 Economizer System for total integration of rooftop control.
• Remote temperature sensors available for use with all models.
• Different levels of keypad lockout available.

APPLICATION

ONWORKS
L
®
network.

FEATURES

All Models:
• 7-day programming.
• Two Occupied and two Unoccupied periods per day.
• Individual heat and cool setpoints available for Occupied and Unoccupied periods.
• Proportional plus Integral (P+I) control eliminates temperature fluctuations.
• Intelligent Recovery equipment start times based on building load.
• Intelligent Fan™ feature energizes fan continuously in the Occupied periods. Fan can also be configured for conventional heat or electric heat fan operation.
• Automatic or manual changeover models available.
• Universal Versaguard™ Thermostat guards available.
• Convenient overrides allow temporary setpoint changes.
• Keypad lockout available.
®
control automatically optimizes
Q7300 Subbase:
• Use with T7300D,E,F Thermostats.
• Auxiliary contacts can be used to interface with C7400/W7459 Economizer System for total integration of rooftop control .
• When used with the T7300F (revision 4 or later), the Q7300H communicates with other network devices .
• Q7300L two stages of heat control ML7984 and V5011/ V5013 valve: stage 1 opens valve 40%; stage 2 100%.
• Q7300L provides two-speed fan control: — Low: heat and occupied fan. — High: cooling.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 5
Wiring Subbase/Wallplate ................................................ 7
Settings ............................................................................ 9
Installer Setup .................................................................. 10
Installer System Test ........................................................ 13
Programming .................................................................... 16
Operation .......................................................................... 19
General Operation Information ......................................... 21
Troubleshooting Guide ..................................................... 22
Cross Reference .............................................................. 23
Wiring Diagrams (Fig. 20-34) ........................................... 29
® U.S. Registered Trademark Copyright © 2001 Honeywell • • All Rights Reserved
63-4355-4
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES

SPECIFICATIONS

IMPORTANT
T7200/T7300 Thermostats:
See Table 1.
The specifications given in this publication do not include normal manufacturing tolerances.
Q7300 Subbases:
See Table 2.
Therefore, this unit might not e xactly mat ch the lis ted specifications. This product is tested and calibrated
Dimensions:
See Fig. 1.
under closely controlled conditions, and some minor differences in performance can be expected if those
Finish (color):
Taupe.
conditions are changed.
Table 1. T7200 and T7300 Thermostat Features.
Maximum Stages
Heat Cool
Wiring Diagram Changeover
Model Applications
T7200D Conventional T7200E Heat Pump
Subbase
Required
None None
a a
1120Automatic or 1121
T7300D Conventional Q7300A,G,L 3 3 22-23, 28, 34 T7300E Heat Pump Q7300C,D 3 2 24-27 T7300F Conventional or
Heat Pump
a
Wallplate provided.
b
Configured in Installer Setup.
Q7300A,C,D,G,L 3 3 22-28,34 Q7300H 3 3 29-33
Table 2. Q7300 Subbase Features.
a,b
Wiring DiagramHeat Cool
Model Applications
Thermostat
Required
Maximum Stages
Q7300A Conventional T7300D,F 2 2 22-23 Q7300C Heat Pump T7300E,F 3 2 24-26 Q7300D Heat Pump T7300E,F 3 2 27 Q7300G Conventional T7300D,F 3 3 28
Q7300H Q7300H
c d
Heat Pump T7300F 3 2 29 Heat Pump T7300F 3 2 30
Q7300H Conventional T7300F 3 3 31 Q7300H Conventional T7300F 2 1 32 Q7300L
a
Depends on model (some specific models have fewer).
b
All subbases are down selectable and can be configured to
Conventional
e
control fewer stages than the maximum allowed.
T7300D,F 2 1 34
c
Without O/B terminals.
d
With O/B terminals.
e
Used with ML7984 Actuator and V5011 or V5013 Valve.
b
Manual
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1.
Your local Home and Building Control Sales Office (check white pages of your phone directory).
2.
Home and Building Control Customer Relations Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (800) 328-5111 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-4355—4 2
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
MERCURY NOTICE
Electrical Ratings:
24 Vac, 50/60 Hz. 20 to 30 Vac, 50/60 Hz.
Batteries: Auxiliary Heat and Emergency Heat Indication:
Thermostat display indicates when Auxiliary Heat or
Emergency Heat are activated.
Loss of Power:
and temperatures for the life of the product. The clock and day information is retained for a minimum of two hours.
Light Emitting Diodes (LED):
Two user-defined LED (not available on Q7300H). Two defined (CHECK and MAINTENANCE) LED on select
models.
System Current Draw: Output Relay Current Draw:
Fan 0.5 2.5 Heat (all stages) 1.5 3.5 Cool (all stages) 1.5 7.5 Auxiliary (Economizer) 1.5 3.5
Temperature:
Ratings:
Operating Ambient: 40°F to 110°F (4°C to 43°C). Shipping: -30°F to +150°F (-34°C to +65°C).
Display Accuracy: ±1°F (±0.5°C).
No batteries required.
The thermostat mai ntains pr ogrammed ti mes
6 VA maximum at 30 Vac, 50/60 Hz.
See Table 3.
Table 3. Maximum Amps at 30 Vac.
Relay Running (A) Inrush (A)
Table 5. Temperature Offset.
Temperature Range 18 AWG 20 AWG 22 AWG
50 to 90°F -0.4°F -0.7°F -1.0°F 10 to 32°C -0.3°C -0.4°C -0.6°C
Minimum Stage Operation Time:
Minimum On (Heat and Cool): factory setting 2 minutes;
option 0 minutes.
Minimum Off (Cool and Heat Pump): factory setting
4 minutes; option 0, 1, 3, 5 minutes.
Mounting Means:
T7200: Mounts on a wallplate. T7300: Mounts on a Q7300 Subbase.
NOTE: Wallplate and subbase mount horizontally on a wall
or outlet box with two no. 6 x 32 screws (included).
Accessories:
C7150B1004 Discharge Air Sensor: for checkout use
(form 63-2072). M7415 Damper Actuator (form 63-2100). ML7984 Valve Actuator (form 95C-10753). Q7760A Serial LonTalk® Adapter. R8222 Switching Relay (form 60-2056). T675A Temperature Control (form 60-2200). T7022A1010 Remote Temperature Sensor (form 60-0247). T7047C Remote Temperature Sensor (form 62-3050). T7047G Remote Temperature Sensor (form 62-3050). T7147A Remote Temperature Sensor and Override Module
(form 62-3049). W859F Packaged Economizer (form 63-2476). W950A Sys tem Supervisor (form 60-2351). W7459 Economizer Logic Module (form 63-2141). W6210/W7210 Economizer (form 63-2528). W6215/W7215 Economizer (form 63-2544).
only
Setpoint:
Range: 45°F to 95°F (7°C to 35°C). Deadband: 2°F (1°C). Default Settings: See Table 4.
Table 4. Default Setpoints.
Control Occupied Unoccupied
Heating 70°F (21°C) 55°F (13°C) Cooling 78°F (26°C) 90°F (32°C)
Remote Sensor Wiring Temperature Offset:
Temperature offset occurs with 500 ft (157m) to
1000 ft (305m) of 2-wire cable. See Table 5.
Humidity Ratings: Clock Accuracy:
5% to 90% RH, noncondensing.
±1 minute per month.
Approvals:
European Community Mark (CE) Listed. Q7300H
only
ONMARK
: L
Thermostat Object (type 09).
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control. If you have questions, call Honeywell Customer Response Center at 1-800-468-1502.
® Functional Profile No. 8060,
3 63-4355—4
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
6-3/4 (172)
3-1/4 (82)
1-3/8 (35)
1/16 (2)
1-7/8
(47)
4-1/8 (105)
4-3/4 (121)
1
Q7300A,C,D,G,L
6-11/16 (170)
3-3/16 (77)
1-3/8 (35)
1/16 (2)
1-7/8
(47)
M16292
Q7300H
7-5/16 (186)
Run
Program
Temporary
Occupied
Continous
Unoccupied
Occupied Start Time
Set Current
Day/Time
Set Program
Unoccupied
Start Time
Clear
Start Time
Day
Copy
Set Temperature
Occupied
Temp
System
Unoccupied
Temp
Heat/Cool
Settings
Fan
1
T7200D,E; T7300D,E,F
1 T7200 WALLPLATE DOES NOT HAVE THE LED EXTENSION
Change
Time/Temp
4-5/8 (117)
4-1/8 (105)
5 (127)
7/8
(22)
1-11/16
(43)
9/16 (14)
Fig. 1. Dimensions of T7200, T7300 and Q7300 in in. (mm).
63-4355—4 4
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
5 FEET
(1.5 METERS)
YES
NO
NO
NO
M4823A
M4839BB
TT
SUBBASE
TT
T7047C

INSTALLATION

When Installing this Product…

1.
Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.
2.
Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3.
Installer must be a trained, experienced service technician.
4.
After completing installation, use these instructions to check out the product operation.
Fig. 2. Typical location of thermostat

Location

Do not install the thermostat where it can be affected by:
drafts, or dead spots behind doors and in corners.hot or cold air from ducts.radiant heat from sun or appliances .concealed pipes and chimneys.unheated (uncoole d) a rea s s uc h a s a n outside wall behind
the thermostat.
T7200 Wallplate or Q7300 Subbase without Remote-Mounted Temperature Sensor
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 2.
IMPORTANT
or remote-mounted sensor.
To avoid electrical interference, which can cause erratic performances, keep wiring runs as short as possible and do not run thermostat wires a dja ce nt to the line voltage electrical distribution systems. Use shielded cable (Belden type 8762 or equivalent for 2-wire and Belden type 8772 or equivalent for 3-wire). The cable shield must be grounded only at the controlled equipment case.
Q7300 Subbase with Remote-Mounted Temperature Sensor(s)
If only the remote-mounted temperature sensor(s) is used to sense and control room temperature, then install the thermostat in an area that is accessible for setting and adjusting the temperature and settings.
If both the subbase and remote-mounted temperature sensor(s) are used to sense and control room temperature, then install the subbase about 5 ft above the floor in an area with good air circulation.
Install the remote-mounted sensor(s) about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 2.
If multiple remote sensors are required, they must be arranged in a temperature averaging network consisting of two, three, four, five or nine sensors. See Fig. 3 through 8.
NOTES:
When sensor averaging, the T7147A can be substituted
Up to four T7147As can be used in parallel to place the
for the T7047C. The T7147A includes OVERRIDE and WARMER/COOLER keys.
thermostat in Temporary Occupied.
Fig. 3. One T7047C Sensor providing temperature
sensing for T7300/Q7300 Thermostat/Subbase.
SUBBASE
TT
T7047GT7047G
T
T
T
T
M4838
Fig. 4. Two T7047G Sensors providing temperature
averaging network for T7300/Q7300 Thermostat/Subbase.
5 63-4355—4
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
SUBBASE
TT
T7047C
TT
T7047G
T7047C
TT
TT
M4839
Fig. 5. Two T7047C Sensors and one T7047G Sensor
providing temperature averaging network for
T7300/Q7300 Thermostat/Subbase.
SUBBASE
TT
T7047C
TT
T7047C
T7047C
TT
T7047C
SUBBASE
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
M4842
Fig. 8. Nine T7047C Sensors providing temperature
averaging network for T7300/Q7300 Thermostat/Subbase.
NOTE: With the thermostat configured for a temperature
averaging network (remo te and internal s ensing), the internal sensor has 50% authority of the averaged temperature.
TT
TT
M4840
Fig. 6. Four T7047C Sensors providing temperature
averaging network for T7300/Q7300 Thermostat/Subbase.
SUBBASE
TT
T7047G
T
T7047G
T
T7047G
T
T
T
T7047G
T
T
T7047G
T
T
T
M4841
Fig. 7. Five T7047G Sensors providing temperature
averaging network for T7300/Q7300 Thermostat/Subbase.

Mounting Subbase/Wallplate

The subbase/wallplate mounts horizontally on the wall or a 2 in. by 4 in. wiring box. Position the subbase/wallplate horizontally on the wall or on a 2 in. by 4 in. wiring box.
1.
Position and level the subbase/wallplate. NOTE: A level wallplate is only for appearance. The
2.
Use a pencil to mark the mounting holes. See Fig. 9.
3.
Remove the subbase/wallplate from the wall and drill two 3/16 inch holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/32 inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.
4.
Position the subbase/wallplate over the holes, pulling wires through the wiring opening.
5.
Loosely insert the mounting screws into the holes.
6.
Tighten mounting screws.
thermostat functions properly w hen not level.
63-435546
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
CAUTION
M4826
FOR WRAPAROUND INSERTION STRIP 7/16 IN. (11 MM).
FOR STRAIGHT INSERTION STRIP 5/16 IN. (8 MM).

WIRING SUBBASE/WALLPLATE

WALL
WIRES THROUGH WALL
WALL ANCHORS (2)
LEDS
Fig. 9. Mounting subbase or wallplate.
MOUNTING HOLES
MOUNTING SCREWS
M10237
IMPORTANT
All wiring must comply with local electrical codes and ordinances.
Follow equipment manufacturer wiring instructions when available. Refer to the Wiring section for typical hookups. A letter code is located near each terminal for identification. Refer to Table 6 for terminal designations.
Electrical Shock Hazard. Power supply can cause electrical shock.
Disconnect power before beginni ng installation.
1.
Loosen the terminal screws on the subbase/wallplate and connect the system wires. See Fig. 10.
IMPORTANT
Use 18-gauge, solid-conductor color-coded thermostat cable for proper wiri ng. If using 18- gauge stranded wire, no more than ten wires can be used. Do not use larger than 18-gauge wire.
2.
Securely tighten each terminal screw.
3.
Push excess wire back into the hole.
4.
Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.
Fig. 10. Proper wiring technique.
Table 6. Terminal Designations and Descriptions.
Terminal Designations
A1
A2
a
T ypic al Conne ction Function
Dry auxiliary contacts for economizer control; A1 is normally open during Unoccupied periods and closed during Occup ied periods.
Output Dry contact
Terminal
TypeStandard Alternate
A1, A2 Damper control relay (Q7300L only). Input, Output 24V powered
contact
A2
A1
a
A3 Dry auxiliary contacts for economizer control; A3 is normally open
Dry auxiliary contacts for economizer control (A2 is common). Input Dry contact
Output Dry contact
during Occupied periods and closed during Unoccupied periods. AS, AS C7150B Discharge Air Sensor connection. Input B Heating changeover valve. Output 24V powered
contact
C1, C2, C3,
Communication input for T7147. Input Low power
C4, C5 E K Emergency heat relay. Output 24V powered
contact
a
Some OEM models reverse the economizer terminal designations A1 and A2.
b
Some OEM models label the terminal for transformer common B.
c
Applies only to Q7300H2037.
7 63-4355—4
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
Table 6. Terminal Designations and Descriptions. (Continued)
Terminal Designations
EB, EB Q7300H LONW
T ypic al Conne ction Function
ORKS
® bus connection to LONW
ORKS
® network. Input, Output Communi-
Terminal
TypeStandard Alternate
cations
G F Fan relay. Output 24V powered
contact
O R Cooling changeover valve. Output 24V powered
contact R V 24V system transformer. Input RC 24V cooling transformer. Input RH 24V heating transformer. Input T, T Remote sensor input for T7047 or T7147. Input W1 H1, R3 Stage 1 heating relay (Q7300A,G,H) or auxiliary heat relay
(Q7300C,D,H).
Output 24V powered
contact W2 H2, R4, W3, Y Stage 2 heating relay. Output 24V powered
contact W3 Stage 3 heating relay. Output 24V powered
contact X
b
, C, X1, X2
B
X1, X3 A, A1, A2, C,
Common. Input User defined Light Emitting Diodes (LED). Annunciation
L, X, Z X4 LED comm on. Annunciation Y1 C1, M, Y Stage 1 compressor contactor (Q7300C,D,H). Output 24V powered
contact
Y1, Y RS, M
Stage 1 cooling compressor (Q7300A,G,H
Y2 C2 Stage 2 cooling compressor (conventional).
Stage 2 compressor contactor (heat pump).
c
,L).
Output 24V powered
contact
Output 24V powered
contact
Y3 Stage 3 cooling compressor. Output 24V powered
contact
BM
ML7984 Actuator connection (Q7300H
c
, L only); no call for heat,
Output
valve closed; call for stage 1 heat, valve approximately one-half open; call for stage 2 heat, valve fully open.
FC GH
GL
P1, P2
RM
c
Fan control transformer (Q7300H High-speed fan output (Q7300H
, L only).
c
, L only); activate during calls for
cooling.
c
Low-speed fan outpu t (Q730 0H
, L only); activated on call s for hea t
and fan On selection.
c
Pump interlock relay (Q730 0H
, L only); operates c irculator pump in
hydronic heat or energizes conventional heat system.
c
ML7984A Actuator connection (Q7300H
, L only); no call for heat,
Input Output 24V powered
contact
Output 24V powered
contact
Input, Output 24V powered
contact
Output
valve closed; call for stage 1 heat, valve approximately one-half open; call for stage 2 heat, valve fully open.
C, H, L HSII Control Panel. —— — O Momentary circuit changeover. —— PDefrost. —— R1, R2 Low- and high-speed fan relays. —— — T External temperature readout, T-relay; outdoor thermistor. ——
a
Some OEM models reverse the economizer terminal designations A1 and A2.
b
Some OEM models label the terminal for transformer common B.
c
Applies only to Q7300H2037.
63-435548
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES

Mounting Thermostat on Subbase/Wallplate

The thermostat mounts on the subbase/wallplate after it is installed:
1.
Engage the tabs at the top of the thermostat and subbase/wallplate. See Fig. 11.
2.
Press the lower edge of the case to latch.
NOTE: To remove the thermostat from the wall, first pull out
at the bottom of the thermostat; then remove the top.
A. ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE.
B. PRESS LOWER EDGE OF CASE TO LATCH.

SETTINGS

Using Thermostat Keys

The thermostat keys are used to:
set current time and day,
program times and setpoints for heating and cooling,
override the program temperatures,
display present setting,
set system and fan operation,
configure Installer Setup,
check Installer System Test.
See Fig. 12 for key information.

Setting System and Fan (select models)

The system default setting is Heat. The fan default is set so the fan operates continuously in Occupied periods, Unoccupied period recovery times and with the heating and cooling equipment in Unoccupied periods. Use the System and Fan keys to change the settings. Fan and system operation are configured in the Installer Setup options.
The system settings are: Em Heat (T7200E, T7300/Q7300C,D,H): Emergency heat
relay is on continuously. Thermostat cycles highest stage of heat. Cooling sys tem is o f f. Comp resso r is de -energi zed.
Heat: Thermostat controls the heating.Off: Both the heating and cooling are off.Cool: Thermostat controls the cooling.Auto: Thermostat automatically changes between heating
and cooling depending on the indoor temperature.
M4824A
Fig. 11. Mounting thermostat on subbase/wallplate.
The fan settings are:
On: Fan operates continuously in occupied period.Auto: Equipment controls the fan in the Unoccupied
periods. The Intelligent Fan operation (Installer Setup number 17) offers three choices for the fan operation in Occupied periods:
fan turns on only when there is a call for heat or cool.fan oper ates continuously in Occu pied periods.fan is on continuously in Occupied periods and
Unoccupied period recovery times.

Setting Temperature

Refer to Table 4 for the default temperature setpoints. See Programming section for complete instructions on changing the setpoints.
9 63-4355—4
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
ENTER OCCUPIED PROGRAM MODE
RETURNS TO NORMAL OPERATIONS
SET OVERRIDE TEMPERATURE OFFSET AND ACTIVATE TEMPORARY OVERRIDE
ENTER HOLD MODE
Run
Program
Temporary
Occupied
Continuous Unoccupied
SET CURRENT DAY AND TIME
CLEAR PROGRAM PERIOD
ENTER UNOCCUPIED PROGRAM MODE
SET CURRENT DAY OR PROGRAM DAY
AM
Mon
Occupied
System Fan
Heat
Set Program Set Temperature Change
Occupied Start Time
Set Current
Day/Time
Unoccupied
Start Time Day
Clear
Start Time
Copy
COPY ONE PROGRAMMED DAY TO ANOTHER DAY
SET OCCUPIED TEMPERATURE SETPOINTS
Room
Auto
Occupied
Temp
System Fan
SELECT SYSTEM OPERATION
Unoccupied
Temp
Heat/Cool
Settings
Time/Temp
SELECT FAN OPERATION
SET UNOCCUPIED TEMPERATURE SETPOINTS AND SCROLLS THROUGH INSTALLER SETUP AND SYSTEM TEST
INCREASE TEMPERATURE OR TIME SETTING
DECREASE TEMPERATURE OR TIME SETTING
CHANGE BETWEEN HEATING AND COOLING SETPOINTS AND SCROLLS BACKWARDS THROUGH INSTALLER SETUP NUMBERS AND SYSTEM TEST
M10233A
Fig. 12. Thermostat key locations and descriptions.

INSTALLER SETUP

NOTE: For mos t applicati ons, the th ermostat factory settings
The installer uses the Installer Setup to custo mi ze the thermostat to specific systems. (See Table 7.) The table includes all the configuration options available.
A combination of key p r esses are required to use th e Ins ta ller Setup feature:
To enter the Installer Setup, press and hold
To advance to the next Installer Setup number, press To return to an Installer Setup number, press To change a setting, use the increase
To exit the Installer Setup, press
NOTES:
do not need to be changed. Review the factory settings in Table 7 and if no changes are necessary, go to the Installer System Test section.
Heat/Cool
Settings
and both the increase
and decrease
keys until the first number is displayed. All display segments appear for approxi mately three secon ds before the numb er is displayed. See Fig. 13 and 14.
Unoccupied Temp
.
Heat/Cool
Settings
.
▲ or
Run Program
decrease ▼ key.
.
Installer Setup is automatically exited after four
minutes with no key pressed.
Be sure to set thermostat time after exiting
Installer Setup.
Installer Setup numbers are listed in Table 7.
Set Program
Start Time
Em Ht Aux Ht
Comm Mon
TueWedThuFriSatSun
Occupied 12 Override
Un
Set Day/Time
AM
PM
System Fan
Off Auto
Em
Heat
Cool
Temporary Setting Enrg
Heat
Recovery
In Lo
Med
Hi
Wait
Cool
Auto
Room
%Humid
Remote
Only
On
Sav
Duct
Auto
M4916
Fig. 13. LED display of all segments.
MODE NUMBER DISPLAY (COLUMN 2 OF TABLE 8)
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 8)
M10227
Fig. 14. Installer Setup number and setting display.
63-4355410
T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
IMPORTANT
CAUTION
Possible Equipment Damage. Fan must be running when system is operating.
Heat pump and electric heat systems must be configured correctly in Installer Setup 2 to prevent equipment damage caused by the system running without the fan.
Table 7. Thermostat Installer Setup Options.
Installer Setup
Number
Select
Not used 1 — Fan operation
Output stages of heating
Heating cycle rate 4 4 Stage 1: 4 cph. 3, 6, 8 or 93: 3 cph (hot water systems or high
Cooling output stages
Cooling cycle rate 9 4 Stage 1: 4 cph. 3 3: 3 cph.
System setting adjustment (models with System key)
Not used 13 — Degree
temperature display
Displaying temperature (T7300F only).
Clock format. 16 0 12-hour clock format. 1 24-hour clock format. Intelligent Fan™
operation.
Auxiliar y co ntact operation.
a
Number 2 must be set to 1 to extend fan operation.
b
Number 22 must be set to 1 and remote sensor(s) must be installed.
(Press Unoccupied
Temp to change)
a
2 0 Conventional applications where
3 Subbase
5 4 Stage 2: 4 cph. 6 4 Stage 3: 4 cph. 7 4 Emergency heat relay is on
8 Subbase
10 4 Stage 2: 4 cph. 11 4 Stage 3: 4 cph. 12 Model
14 0 Temperature displayed in °F. 1 Temperature displayed in °C.
15 0 Temperature displayed. 1 Temperature not displayed.
17 2 Fan operates continuously in
18 0 0: Time of day contact. 1 1: Economizer contacts.
dependant
dependant
dependant
Factory Setting
equipment controls fan operation in heat mode.
Stages of heat. 0, 1, 2,
continuously. Highest stage of heat cycles at 4 cph (Q7300C or D only).
Stages of cooling. 0, 1, 2 or 30: No cooling.
System selection. 0, 1 or 2 0: System setting key is operational.
Occupied and recovery modes. Fan operates with call for heat or cool in Unoccupied mode.
Only configurable numbers are shown on the devic e. Example: If the thermostat does not have a system key, Installer Setup number 12 will not be displayed. Review Table 7 factory settings and mark any desired changes in the Act ual Setting column. When the Installer Setup is comp lete, review the s etting s to confirm that they match the system.
Other Choices
(Press ▲ or ▼ to change)
1 Electric heat applications where thermostat
or 3
0 or 1 0: Fan operates only with call for heat or
controls fan operation in heat mode.
0: No heating. 1: One stage of heat. 2: Two stages of heat. 3: Three stages of heat.
efficiency furnaces). 6: 6 cph (conventional systems). 8: 8 cph (conventional systems). 9: 9 cph (electric heat systems).
1: One cooling stage. 2: Two cooling stages. 3: Three cooling stages.
1: Auto setting disabled. 2: Auto only setting.
cool (Occupied and Unoccupied modes). 1: Fan operates continuously in Occupied
mode. Fan operates with call for heat or
cool in Unoccupied mode.
Actual
SettingDisplay Description Display Description
11 63-4355—4
Loading...
+ 25 hidden pages