Honeywell T7200, T7300, Q7300 User Manual

T7200, T7300 and Q7300
63-4038-7
Programmable Commer cial
Thermostats and Subbases
The T7200, T7300 Thermostats and Q7300 Sub­bases control commerical single zone heating, ven­tilating and air conditioning (HVAC) equipment.
stage applications.
7-day programming—two occupied/unoccupied
periods per day.
Individual temperature setpoints for:
—Occupied heat and cool.
—Unoccupied heat and cool.
Proportional plus integral control—eliminates temp-
erature fluctuations and thermostat tampering.
Intelligent Recovery™—automatically optimizes
start time depending on building load.
Intelligent Fan™—energizes fan on call for heating
or cooling only. Fan can be configured to run cont-
inuously in occupied mode.
Automatic heat/cool changeover.
Universal Versaguard™ Thermostat Guard avail-
able for T7200 and T7300/Q7300.
Locking setpoints and schedules eliminate tamp-
ering (use keyboard security).
One thermostat can be used for heat pump or con-
ventional control.
Optional remote sensors.
Configurable to vary fan and reversing valve operation.
Use with Q7300 to interface with C7400/W7459
Economizer System for total integration of rooftop control.
Convenient overrides allow temporary changes.
Battery backup saves program and maintains clock
time during power failure.
Auxiliary contacts available for use with economizer.
CONTENTS
Specifications ................................................ 2
Ordering Information.................................... 2
Recycling Notice............................................ 4
Installation .................................................... 4
Temperature Averaging Networks
(See Fig. 5-9) ........................................ 5
Set Q7300 Subbase DIP Switches............. 6
Set Thermostat DIP Switches.................... 9
Set Thermostat Mini-Jumper .................. 11
Program the Thermostat ............................. 12
Checkout...................................................... 13
Test Mode................................................ 13
Operation .................................................... 15
Cross Reference .......................................... 18
Wiring Diagrams......................................... 22
Troubleshooting .......................................... 45
J. A. • Rev. 12-95 • • ©Honeywell Inc. 1995
M3375
1 63-4038—7
T7200/T7300/Q7300 SPECIFICATIONS • ORDERING INFORMATION
Specifications
IMPORTANT: The specifications given in this publication
do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. This product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.
• T7300A is a fully configurable programmable commer­cial thermostat to be used with a Q7300 Subbase.
• T7300B is a fully configurable programmable commer­cial thermostat with the 3-HOUR OVERRIDE key in the cover, to be used with a Q7300 Subbase. (See Fig. 2).
• T7300C is a fully configurable programmable commer­cial thermostat with limited access cover for easy pro­gramming. Cover includes Set Heat, Set Cool, Warmer,
T7200 AND T7300 THERMOSTATS
• T7200A is an autochangeover programmable commer-
Cooler and Occupied/Unoccupied keys. Use with Q7300 Subbase. (See Fig. 3).
cial thermostat to be used with a single stage conventional heat/cool system.
•T7200B is an autochangeov er programmable commercial
Q7300 SUBBASE
Q7300 Subbases provide features listed in Table 1.
thermostat to be used w ith a sing le stage heat pump system .
TABLE 1—Q7300 SUBBASE FEATURES.
Model System Switch
Q7300A Q7300B Heat-Off-Cool-Auto Auto-On 2 heat-1 cool; 2 heat-2 cool Q7300C Em. Ht.-Heat-Off-
Q7300D None 1 stage heat pump compressor with
Q7300E None Conventional 1 heat-1 cool; 2 heat-2 cool Q7300F None Aux. Ht. 1 stage heat pump compressor with
Q7300G Heat-Off-Cool-Auto None Conventional 1 stage heat with
Q7300L None Auto-On Heat Cool 2 stage heat (ML984 actuator/
a
a,b
None None None Conventional 1 heat-1 cool; 1 heat-2 cool
Cool-Auto
Select models do not have auxiliary relay output. The auxiliary relay output is used with an ecomonomizer for minimum
Fan
Switch LEDs Application Selectable Output
Em. Ht.,
Aux. Ht.
1 stage heat pump compressor with auxiliary heat
2 stage heat pump compressor with auxiliary heat
auxiliary heat 2 stage heat pump compressor with
auxiliary heat
auxiliary heat 2 stage heat pump compressor with
auxiliary heat
3-stage cool
V5013 Valve) 1 stage cool
c
1 heat-1 cool; 2 heat-1 cool
1 heat-1 cool; 2 heat-1 cool; 3 heat-1 cool
1 heat-1 cool; 2 heat-1 cool
1 heat-1 cool; 2 heat-1 cool; 3 heat-1 cool
1 heat-1 cool; 2 heat-1 cool
1 heat-1 cool; 2 heat-1 cool; 3 heat-1 cool
1 heat-3 cool (fixed)
1 heat-1 cool; 2 heat-1 cool
position control based on programmed time schedule. Can also be used for switching other external equipment.
b
Q7300A1000 model configures for 1 heat-1 cool only (fixed).
c
Uses conventional terminal designations. Compressor changeover is controlled by the heat pump equipment.
Ordering Information
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the Tradeline Catalog or price sheets for complete ordering number, or specify—
1. Order number. 3. Order additional system components and system accessories
2. Accessories, if desired. separately.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
2. Home and Building Control Customer Relations Honeywell, 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-4038—7 2
THERMOSTAT
ELECTRICAL RATING: 24 to 30 Vac, 50/60 Hz. SYSTEM CURRENT DRAW: 6 VA maximum at 30 Vac,
50 or 60 Hz.
OUTPUT RELAY DRAW: See Table 2.
TABLE 2—MAXIMUM AMPS AT 30 VAC.
Relay Running (A) Inrush (A)
Fan 1.6 3.5 Heat 1.6 3.5 Cool 1.6 7.5
Auxillary (Economizer) 1.6 3.5
TEMPERATURE:
Ratings:
Ambient: 40°F to 110°F (4°C to 43°C). Shipping: -30°F to +150°F (-34°C to +65°C).
Display Accuracy: ±1°F (±1°C). Setpoint:
Range: 45°F to 95°F (7°C to 35°C). Differential: 2°F (1°C). Default Settings: See Table 3.
TABLE 3—DEFAULT SETPOINTS.
Control Occupied Unoccupied
Heating 68°F (20°C) 55°F (13°C) Cooling 78°F (26°C) 90°F (32°C)
T7200/T7300/Q7300
SPECIFICATIONS
Fig. 1—Thermostat and subbase dimensions in in. (mm).
8 (204)
4
(102)
FAN
1
EM. HEAT AUX. HEAT
ONAUTO COOLOFFHEATEM. HEAT
T7300/Q7300 ONLY.
Fig. 2—T7300B door.
OCCUPIED •
UNOCCUPIED •
CONT UNOC •
3 HR OCCUPIED •
ENVIRONMENTAL CONTROL
4-5/8 (118)
3 HOUR
OCCUPIED
1-3/4
1
(41)
M4404
M4421
REMOTE SENSOR WIRING TEMPERATURE OFFSET:
Temperature offset occurs with 500 ft (157m) to 1000 ft (305m) of 2-wire cable. See Table 4.
TABLE 4—TEMPERATURE OFFSET.
Temperature
Range 18 AWG 20 AWG 22 AWG
50-90°F -0.4°F -0.7°F -1.0°F 10-32°C -0.3°C -0.4°C -0.6°C
MINIMUM STAGE OPERATION TIME:
Conventional Heat: Two minutes On or Off. Compressor: Two minutes On and four minutes Off.
HUMIDITY RATINGS: 5% to 90% RH, noncondensing. CLOCK ACCURACY: ±1 minute per month. BATTERY BACKUP: Up to 60 hours with fresh 9-volt
alkaline battery. Mallory MN11604™ or equivalent.
FINISH: Beige thermostats with brown subbases or Premier
White™ thermostats with light gray subbases. DIMENSIONS: See Fig. 1. T7300 Doors: See Fig. 2. MOUNTING MEANS: T7200 Thermostat mounts on a
wallplate. The T7300 mounts on the Q7300 Subbase. The
Q7300 and wallplate mount horizontally on a wall or
outlet box with two no. 6 x 32 screws (included).
Fig. 3—T7300C door.
OCCUPIED •
UNOCCUPIED •
TO ADJUST HEAT PRESS SET HEAT THEN PRESS WARMER OR COOLER
TO ADJUST COOLING PRESS SET COOL THEN PRESS WARMER OR COOLER
FOR AFTER HOURS PRESS OCCUPIED UNOCCUPIED FOR BUSINESS HOURS PRESS OCCUPIED UNOCCUPIED AGAIN
SET SET
HEAT COOL
TO ACCESS FULLY PROGRAMMABLE TIME AND TEMPERATURE FEATURES LIFT COVER
ENVIRONMENTAL CONTROL
WARMER
COOLER
OCCUPIED
UNOCCUPIED
M4422
ACCESSORIES:
— 229997BU T7300B Conversion Kit. (See Fig. 2). — 229997BY T7300A Conversion Kit. (See cover photo). — 229997CE T7300C Conversion Kit. (See Fig. 3). — 231054AA White Door Assembly for T7300C. (See
Fig. 3.
— 231055AA White Door Assembly for T7300B. (See
Fig. 2).
— 231056AA White Door Assembly for T7300A. (See
cover photo).
— 4074EEP Hardware for door and hinge pin assembly.
3 63-4038—7
T7200/T7300/Q7300 SPECIFICATIONS • RECYCLING • INSTALLATION
— 4074EFS Bag Assembly (two sheet metal screws and
two machine screws).
— 4074EKA Bag Assembly (Allen wrench and four
Allen head screws). — 4074ENE Hinge Pin Assembly. — C7400 Enthalpy Sensor. —M7415 Damper Actuator. — T675A Temperature Control. — T7022A1010 Remote Temperature Sensor. — T7047C1025 Remote Temperature Sensor. — T7047G1000 Remote Temperature Sensor.
If this control is replacing a control that contains mer-
cury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for
instructions regarding recycling and the proper disposal of
— T7147A1002 Remote Temperature Sensor and Over-
ride Module.
— T7147A1010 Remote Temperature Sensor and Over-
ride Module.
— T7147A1028 Remote Temperature Sensor and Over-
ride Module. — R8222 Switching Relay. —W950A System Supervisor. —W859D Packaged Economizer. —W7459 Economizer Logic Module.
Recycling Notice
M3375
this control, or of an old control containing mercury in a sealed tube.
Installation
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous con­dition.
2. Check the ratings given on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service tech­nician.
4. Allow thermostat to warm to room temperature before operating.
5. After installation is complete, check out product op­eration as provided in these instructions.
CA UTION
Disconnect power supply before beginning instal­lation to prevent electrical shock or equipment damage.
LOCATION Thermostat Without Remote-Mounted Temperature Sensor
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 4.
Do not mount the thermostat where it can be affected by:
— drafts or dead spots behind doors, in corners or under
cabinets. — hot or cold air from ducts. — radiant heat from the sun, fireplace, or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat.
Thermostat With Remote-Mounted Temperature Sensor(s)
Install the thermostat in an area that is accessible for
setting and adjusting the temperature and settings.
Install the remote-mounted sensor(s) about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 4.
Do not mount the sensor(s) where it can be affected by:
— drafts or dead spots behind doors, in corners or under
cabinets. — hot or cold air from ducts. — radiant heat from the sun, fireplace, or appliances. — concealed pipes and chimneys. — unheated (uncooled) areas such as an outside wall
behind the thermostat. If more than one remote sensor is required, they must be
arranged in a temperature averaging network consisting of two, three, four, five, or nine sensors. Instal as shown in Fig. 5-9.
REPLACE AN EXISTING THERMOSTAT OR NEW INSTALLATION Replace An Existing Thermostat
Turn off all sources of power for the thermostat. Re-
move any existing wallplate or subbase from the wall. To avoid miswiring later, label or write down each wire color with the letter or number on the wiring terminal as the wire is removed.
63-4038—7 4
Fig. 4—Location for installing thermostat or remote-mounted sensor.
YES
NO
5 FEET
[1.5 METERS]
NO
T7200/T7300/Q7300
INSTALLATION
NO
M4385
Fig. 5—Two T7047G1000 Sensors providing a temperature averaging network for a T7300/ Q7300 Thermostat/Subbase.
Q7300
TT
T7047G1000T7047G1000
T
T
T
T
M3421
Fig. 6—Two T7047C1025 and one T7047G1000 Sensors providing a temperature averaging network for a T7300/Q7300 Thermostat/Subbase.
Q7300
TT
T7047C
TT
T7047G1000
Fig. 7—Four T7047C1025 Sensors providing a temperature averaging network for a T7300/ Q7300 Thermostat /Subbase.
Q7300
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
M3420
T7047C
TT
TT
M3418
5 63-4038—7
T7200/T7300/Q7300 INSTALLATION
Fig. 8—Five T7047G1000 Sensors providing a temperature averaging network for a T7300/ Q7300 Thermostat/Subbase.
Q7300
TT
T7047G
T
T7047G
T
T7047G
T
T
T
T7047G
T
T
T7047G
T
T
M3422
Fig. 9—Nine T7047C1025 Sensors providing a temperature averaging network for a T7300/ Q7300 Thermostat/Subbase.
New Installation
Run cable to a hole at the selected wall location for the
thermostat and pull about 3 in. (76 mm) of wire through the opening. Color-coded, 18-gauge thermostat cable with at least one conductor for each wiring terminal is recom­mended. Good service practice recommends selecting a cable with one or two extra conductors than the immediate application requires.
If using remote temperature sensor(s) or LAN override
switch module, refer to the mounting instructions included with the device for wiring cable requirements. Route cable away from sources of electrical noise.
IMPORTANT: The remote sensor(s) or override switch
T
wires must be in a shielded cable if bundled or placed
in the same conduit with the cooling control wires.
Earth ground the shield at the thermostat.
SET Q7300 SUBBASE DIP SWITCHES
NOTE: Subbase dip switches are not available on the T7200
Wallplate. The Q7300 Subbase provides the T7300 Thermostat
with an interface to the single zone HVAC system. See Table 5 for DIP switch settings. The subbase DIP switches are located on the front and to the right of the wiring terminals. See Fig. 10. Set the DIP switches for the system being controlled.
T7047C
TT
T7047C
TT
T7047C
TT
Q7300
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
T7047C
TT
M3419
TABLE 5—SUBBASE DIP SWITCH SETTINGS.
Switch Setting Function
a
1
OFF 1 stage heat
ONb2 stage heat
a
2
OFF 1 stage cool
ONb2 stage cool
3 OFF Proportional control (allows droop)
ONbProportional plus integral (P+I)
control (droopless)
c
4
ONbEnergizes fan on cool only
OFF Energizes fan on heat and cool
5ONbUse internal sensor
OFF Use remote sensor
a
No effect on 1 heat/1 cool (Q7300A) or 1 heat/3 cool (Q7300G) models.
b
Factory setting.
c
No effect on heat pump systems.
MOUNT SUBBASE OR WALLPLATE
The subbase or wallplate can be mounted on a horizon-
tal outlet box or directly on the wall. For an outlet box installation, go to step 3.
63-4038—7 6
T7200/T7300/Q7300
INSTALLATION
1. For a wall installation, hold subbase or wallplate in position and mark holes for the anchors. See Fig. 4. Wall anchors must be obtained locally. Be careful that the wires do not fall back into the wall opening. Set aside subbase or wallplate.
Fig. 10—Setting subbase DIP switches.
BA3A2W2Y2TA1 T
Y1
GRCRH
LED1
1
CONFIGURATION OF ILLUSTRATED SWITCH IS: 1 – ON 2 – OFF 3 – OFF 4 – ON 5 – ON
CA1
LED2 COM
CA2 CA3 CA4 CA5
2. Drill four 3/16 in. (4.8 mm) holes and gently tap
anchors into the holes until flush with the wall.
3. Pull wires through the cable opening. See Fig. 11.
1
O
N
1
234
5
M4401
Fig. 11—Installing subbase on outlet box or on wall.
BA3A2W2Y2TA1 T
Y1
GRCRH
SHEET METAL SCREWS
MOUNTING TO WALL BOARD
CA2 CA3 CA4 CA5
CA1
LED2 COM
LED1
MACHINE SCREWS
OR
BA3A2W2Y2TA1 T
Y1
GRCRH
MOUNTING TO HORIZONTAL 2 X 4 JUNCTION BOX
CA2 CA3 CA4 CA5
CA1
LED2 COM
LED1
M4410
7 63-4038—7
T7200/T7300/Q7300 INSTALLATION
4. Secure the subbase or wallplate with the screws pro­vided. Do not fully tighten the screws.
5. Level the subbase or wallplate for appearance only. Leveling is not required for operation. Securely tighten the screws.
WIRE SUBBASE OR WALLPLATE
CA UTION
Never install more than one wire per terminal unless using factory-supplied jumper with spade terminal.
IMPORTANT: Most equipment manufacturers size system
transformers for the equipment installed at the fac­tory. Before connection, be sure that the system trans­former can supply the T7200 OR T7300 and Q7300 with adequate power (6 VA). If less than 6 VA is available, install a separate 24 Vac transformer.
CA UTION
Disconnect power supply before beginning instal­lation to prevent electrical shock or equipment damage.
All wiring must comply with local electrical codes and
ordinances.
IMPORTANT: Use 18 gauge, solid-conductor wire when-
ever possible. If using 18 gauge stranded wire, no more than 10 wires can be used. Do not use larger than 18 gauge wire.
Follow equipment manufacturer’s wiring instructions when available. See Fig. 23-46 for wiring diagrams. To wire subbase, proceed as follows:
1. Connect the correct wires to the terminals as shown in applicable diagram; the terminal barrier allows straight or wraparound wiring connection. See Fig. 12. A letter code is located near each terminal for identification. Typical termi­nal designation and wiring connections are listed in Table
6. Connect remote temperature sensor or override switch module.
NOTE: If a remote sensor is used, be sure that the Q7300 DIP
switch 5 is placed in the OFF position.
Fig. 12—Barrier configuration. Keep wiring restricted to recessed area surrounding termi­nals.
FOR STRAIGHT INSERTION – STRIP 5/16 in. [8 mm]
FOR WRAPAROUND – RESTRICT WIRING TO THIS AREA
FRONT VIEW OF
TERMINAL AREA
WIRING TO BE BELOW THIS SURFACE
CROSS-SECTIONAL VIEW OF
TERMINAL AREA
STRIP 7/16 in. [11 mm]
TOP SURFACE OF SUBBASE
M3062
2. Firmly tighten each terminal screw. Loose or intermit­tent wire connections can cause inconsistent system opera­tion.
3. Fit wires as close as possible to the subbase. Push excess wire back into the hole.
4. Plug hole with nonflammable insulation to prevent drafts from affecting the thermostat.
Refer to Fig. 23-46 for typical hookups. When system installation is complete, perform the initial power up proce­dure in the Checkout section.
63-4038—7 8
T7200/T7300/Q7300
TABLE 6—TERMINAL DESIGNATIONS.
Standard Terminal
Designation
BHeating damper motor; changeover valve/relay Output 24 Vac powered contact EKEmergency heat relay Output 24 Vac powered contact GFFan relay coil Output 24 Vac powered contact ORCooling damper motor; changeover valve/relay Output 24 Vac powered contact RVPower connection to transformer (internally
RC Power connection to cooling transformer Input RH Power connection to heating transformer Input W1 H1, R3 Stage 1 heating control Output 24 Vac powered contact W2 H2, Y, R4 Stage 2 heating control Output 24 Vac powered contact W3 Stage 3 heating control Output 24 Vac powered contact
Y1 C1, M Stage 1 cooling control Output 24 Vac powered contact
Y2 C2 Stage 2 cooling control Output 24 Vac powered contact
a
Y3
XX1,X2,C Common connection Input T
LED1,
LED2, COM
YMCompressor contactor
A1, A2, A3 Auxiliary relay Output Dry contact
CA1-CA5
a
Q7300G only.
b
Shielded cable can be required in some installations where electrical interference (noise) can cause control problems.
Alternate
Designations Or
Customer Specials Typical Connection Function Terminal Type
Input
connected for heating and cooling)
Stage 3 cooling control
Remote sensor
L, C, H HSII control panel
OMomentary circuit, changeover
A,A1,A2,Z,C,L LEDs Annunciation
TExternal temperature readout, T relay
R1, R2 LO and HI speed fan relays
RS Cooling contactor
Remote override
b
a
b
Output 24 Vac powered contact
Input
Input Low power
INSTALLATION
SET THERMOSTAT DIP SWITCHES
The thermostat DIP switches provide the thermostat with an interface to the single zone HVAC system. See Table 7 for DIP switch settings. The thermostat DIP switches are located on the back of the thermostat. See Fig. 13. Set the DIP switches for the desired thermostat features and the system being controlled.
IMPORTANT: The thermostat configuration must match
the application, or the control logic will not function properly.
TABLE 7—THERMOSTAT DIP SWITCH SETTINGS
Switch Setting Function
1ONa°F display
OFF °C display
2ONa12 hour clock display
OFF 24 hour clock display
3ON
a,b
Intermittent fan operation in occupied period
OFF Continuous fan operation in occupied
period 4 Nonfunctional switch 5ONaKeyboard is used for programming
OFF Keyboard disabled, but can be used to
review program, perform overrides
and make clock changes.
a
Factory setting.
b
Q7300B,C,D,E,L: fan switch will override this switch setting. Q7300A,F,G: no override is available.
9 63-4038—7
T7200/T7300/Q7300 INSTALLATION
Fig. 13—Setting thermostat DIP switches.
T7300 ONLY
HEAT PUMP CONV
12 HR. TIME
°F - TEMP
ON
1
°C
12 HR. TIME
INT - FAN
90
45
234
24
CON
ON - KEYBD
5
OFF
°F - TEMP
ON
45
1
234
24
°C
M4085A
Fig. 14—Setting thermostat mini-jumper for conventional or heat pump system.
T7300 ONLY
1 2
HEAT PUMP CONV
- KEYBD
INT - FAN
5
OFF
CON
ON - KEYBD
12 HR. TIME
INT - FAN
°F - TEMP
ON
90
45
1
234
5
24
°C
OFF
CON
ONLY PUT MINI-JUMPER IN THIS POSITION WHEN USING Q7300C,D, OR F SUBBASES.
1
2
ONLY PUT MINI-JUMPER IN THIS POSITION WHEN USING Q7300A,B,E, OR G SUBBASES.
63-4038—7 10
12 HR. TIME
INT - FAN
°F - TEMP
90
ON - KEYBD
M4086A
BATTERY SNAPS
STEP 1:
STEP 2: STEP 3:
CONNECT THERMOSTAT CABLES TO THE SUBBASE. FIRST CONNECT THE 12 PIN THEN THE 9 PIN.
SNAP BATTERY INTO PLACE. SLIDE BATTERY UP TO THE
BATTERY CONNECTOR UNTIL CONNECTED.
M4408
T7200/T7300/Q7300
INSTALLATION
SET THERMOSTAT MINI-JUMPER
NOTE: This operation must be done prior to installing the
batteries. If batteries are installed prior to this operation, remove battery for 15 minutes and begin.
The T7300 is factory-set for conventional system con­trol using the Q7300A,B,E,G. If using with a heat pump and Q7300C,D,F, locate the mini-jumper on the back of the T7300. See Fig. 14. Pull the mini-jumper off the two CONV pins and move to the two HEAT PUMP pins. This changes the thermostat to the heat pump algorithm.
If you wish to change the control of the thermostat because a new subbase has been purchased, remove battery for 15 minutes, change mini-jumper position, and re-install battery.
MOUNT THERMOSTAT
CA UTION
Always disconnect power supply and remove bat­tery from the T7300 before connecting the ribbon cables to prevent electrical shock and equipment damage.
Use the following procedure to connect the T7300 rib­bon cables to the Q7300.
1. Check that the 24 Vac power supply is disconnected
from the Q7300.
2. Check that the 9 Vdc battery is not installed in the
T7300.
INSTALL BATTERY (OPTIONAL)
The 9 volt battery is not necessary for the operation of the thermostat, but holds the program during power out­ages. When the power is restored, the system will resume normal operation. Without the battery, the system will follow the default setpoints. See Table 3. Use the following steps to install a battery:
1. Locate the battery holder on the back of the thermo-
stat.
2. Slide the battery up to the connector until it is firmly
seated. See Fig. 16. NOTE: Observe the polarity when snapping a 9 volt alkaline
battery into the holder. NOTE: The plugs must be firmly seated on the connectors
for the thermostat to work properly.
6. Hang the top edge of the thermostat on the subbase
hooks. See Fig. 17.
7. Swing down and press on the lower edge until the
thermostat snaps in place.
8. Insert and tighten three Allen head screws on the
bottom of the thermostat. See Fig. 17.
Fig. 16—Installing optional 9 volt battery.
IMPORTANT: First be sure to connect the 12 pin ribbon
cable to the Q7300.
3. Connect the 12 pin (larger) ribbon cable to the Q7300.
See Fig. 15.
4. Connect the 9 pin (smaller) ribbon cable to the Q7300.
5. If using a 9 Vdc battery, go to the Install Battery
Backup section for installation instructions.
Fig. 15—Connecting the pin ribbon cables to the subbase connectors.
9-PIN SUBBASE CONNECTOR
12-PIN SUBBASE CONNECTOR
M4403
Fig. 17—Mounting thermostat on subbase.
1
1
DO NOT OVERTIGHTEN SCREWS
M4391
11 63-4038—7
T7200/T7300/Q7300 PROGRAM THE THERMOSTAT
Program the Thermostat
OVERVIEW
The keyboard is located behind the thermostat flip-up cover. See Fig. 18. There are 16 keys to set, review and modify programmed times and temperatures. The liquid crystal display (LCD) shows day, time or temperature and which programming period is operating.
The thermostat can be set for two occupied and two unoccupied time and temperatures for each day of the week (28 independent settings). The two override keys provide quick temporary programming changes for increased occu­pant comfort.
IMPORTANT: To program the thermostat, 24 Vac is re-
quired (turn on system power) and the keyboard lock­out switch (see Fig. 27) must be in the ON-KEYBD position.
Fig. 18—Thermostat programming keys and
LCD display.
OCCUPIED •
UNOCCUPIED •
3 HR OCCUPIED •
SET SET START TIME
CLOCK
DAY
CONT UNOC •
SELECT
DAY
COPY
11:32
OCCUPIED
START TIME
START TIME
HEAT
AM
SET TEMPERATURE DATA CHANGE
OCCUPIED
OCCUPIED
COOL
HEAT
UNOC
UNOC
UNOC
HEAT
COOL
DISPLAY
CLEAR
START TIME
OVERRIDE
3 HOUR
+
OCCUPIED
CONT
UNOC
NOTE: The programming times are in intervals of ten
minutes; i.e., 8:00, 8:10, 8:20.
1. Press the SELECT DAY key. The display shows the
abbreviation for a day.
2. Press and hold the + or - key until the desired day
appears.
3. Press the OCCUPIED START TIME key. The pro-
gram indicator will point to OCCUPIED.
4. Press and hold the + or - key until the desired start time
appears. NOTE: Anytime a start time is not required, press the
CLEAR START TIME key.
5. Press the UNOC START TIME key. The program
indicator will point to UNOCCUPIED.
6. Press and hold the + or - key until the desired start time
appears.
7. To program a second occupied start time for the selected day, repeat Step 3 until four dashes (----) are dis­played or the second start time (if previously programmed) is displayed. Then repeat Step 4.
8. To program a second unoccupied start time for the selected day, repeat Step 5 until four dashes (----) are dis­played or the second start time (if previously programmed) is displayed. Then repeat Step 6.
9. Repeat Steps 1 through 8 for each remaining day of the week or refer to the following section, COPY A DAY.
M4384
SET CURRENT TIME/DAY
1. Set the current time by pressing and releasing the
CLOCK key once.
2. Press the + or - key until the current time appears on the
LCD.
3. Set the current day by pressing and releasing the DAY
key once.
4. Press the + or - key until the current day appears on the
LCD. NOTE: Su=Sunday; Mo=Monday; Tu=Tuesday; We=
Wednesday; Th=Thursday; Fr=Friday; Sa=Saturday.
SET PROGRAM TIMES IMPORTANT: The thermostat will remain in occupied
mode from the point of initial programming until it encounters the first unoccupied start time. To avoid the unnecessary occupied period following initial pro­gramming, set a 12:00 AM unoccupied start time on the thermostat when programmed.
COPY A DAY
1. Press the SELECT DAY key. The display shows the abbreviation for a day.
2. Press and hold the + or - key until the day to be copied from appears.
3. Press the COPY key.
4. Press and hold the + or - key until the day to be copied to appears.
NOTE: The day to be copied from will remain on the display.
5. Press the COPY key a second time to perform the copy.
6. Repeat Steps 3 to 5 to copy to another day.
SET PROGRAM TEMPERATURE SETPOINTS
NOTE: The setpoint temperature range is 45°F (unoccupied
heat) to 95°F (unoccupied cool). The occupied heat setpoint must be at least 2°F less than the occupied cool setpoint.
1. Press the SET TEMPERATURE key (OCCUPIED
HEAT, OCCUPIED COOL, UNOC HEAT, or UNOC COOL). The program indicator will point to OCCUPIED or
UNOCCUPIED and the LCD will indicate HEAT or COOL.
63-4038—7 12
T7200/T7300/Q7300
PROGRAM THE THERMOSTAT • CHECKOUT
2. Press and hold the + or - key until the desired tempera-
ture appears.
3. Repeat Steps 1 and 2 until all four temperatures are set.
SET OPERATING DISPLAY
The LCD can show time or temperature. To change the
current display, press the DISPLAY key until the desired operating display appears.
CLEAR START TIME
1. Press the SELECT DAY key.
2. Press and hold the + or - key until the desired day
appears.
3. Press and hold the OCCUPIED START TIME or
the UNOC START TIME key until the time to clear appears.
4. Press and hold the CLEAR START TIME key until
the display shows four dashes (----). NOTE: If there is a second OCCUPIED setting, the start for
time this setting will appear instead of four dashes (----).
TEMPORARILY OVERRIDE PROGRAM
There are three overrides available. The 3 hour occupied
overrides can be initiated from a remote location or the thermostat. The 3 hour occupied override without + or - keys can also be initiated from the T7300B cover.
NOTE: Pressing the DISPLAY key at anytime will return
the thermostat to the program.
3 Hour Occupied
The 3 HOUR OCCUPIED key is used to override the
unoccupied program when people need to use the area temporarily (working late, weekends or holidays).
1. Press the 3 HOUR OCCUPIED key to change the
unoccupied temperature setting to the occupied setpoint for three hours.
NOTE: The program indicator will point to 3 HR OCCU-
PIED while the override is in effect.
3 Hour Occupied with + or - Key
SET + OR - KEY VALUE
When using the + or - key with the 3 HOUR OCCU-
PIED key, the + or - key has a preassigned value of 0 to 5°F (default is 0). Use the following steps to check or change the value:
1. Press the 3 HOUR OCCUPIED key. The program indicator will point to 3 HR OCCUPIED.
2. Press the DISPLAY key. The LCD will show a number from 0 to 5.
3. Press the + or - key to change the value.
4. Press the DISPLAY key to return to the program.
Set 3 Hour Occupied Override With + or - Key
The 3 HOUR OCCUPIED key with the + or - key will
override the unoccupied program for three hours with the occupied temperature setpoint + the preassigned key value (see Set + or - Key Value section).
1. Press the 3 HOUR OCCUPIED key to change the unoccupied temperature setting to the occupied setpoint for three hours.
2. Press the + key to increase or press the - key to decrease the occupied setpoint by the key value.
EXAMPLE: Unoccupied setpoint is 62°F, occupied
setpoint is 70°F and key value is 3°F. Pressing the 3 HOUR OCCUPIED key and the + key will change the setpoint from 62°F to 70°F plus 3°F or 73°F. Pressing the - key would change the setpoint to 70°F minus 3°F or 67°F.
NOTE: The program indicator will point to 3 HR OCCU-
PIED while the override is in effect. The LCD will not reflect the key value.
Cont Unoc
The continuous unoccupied override feature holds the setpoint at the unoccupied temperature setpoint until the DISPLAY or CONT UNOC key is pressed. This override is used when the area will be closed for a temporary closing such as a long holiday.
1. Press the CONT UNOC key to hold the temperature
at the unoccupied setpoint.
2. Press the CONT UNOC key again to return to the
program.
OVERVIEW
Check that all wiring is correctly completed and all sensors are installed. The thermostat should be mounted on the wallplate or subbase. If the thermostat has not been programmed, when the power is first turned on, the LCD will show four dashes (----). Without programming, the thermostat will operate from default temperature setpoints (see OPERATION section).
NOTE: It is helpful to program the thermostat before using
the Checkout procedure. Refer to the Programming sec-
tion to set a program.
Checkout
If the display has two dashes and a degree sign (--°), wait
sixty seconds and press the DISPLAY key twice. If the display does not change or is blank, refer to the Trouble­shooting section.
TEST MODE
The thermostat has a test mode that aids the installer in performing the checkout. The test mode overrides the minimum on and off times so the checkout can be quickly performed. Press the CLOCK and DAY keys at the same time to start the test mode. All the display segments will appear. See Fig. 19
13 63-4038—7
T7200/T7300/Q7300 CHECKOUT
CA UTION
Do not use the test mode for longer than 10 min­utes. The test mode overrides the minimum on and off times that protect the system. Equipment dam­age can result if the thermostat remains in the test mode.
COOL
Move switch to auto.
CA UTION
Do not operate cooling if outdoor temperature is below 50°F (10°C). Refer to the manufacturer recommendations.
Fig. 19—All segments on display.
TEST MODE INDICATOR
M4415
S
U
M
O
TUWETHFRS
AM
PM
A
COMM
HEAT
● ● ●
COOL BATT
To discontinue the test mode at any time, press the
CLOCK and DAY keys at the same time. The Test Mode Indicators will no longer show on the screen.
HEAT
NOTE: When the thermostat is used with a subbase with
subbase and fan switches, set the switches to AUTO.
1. Press the CLOCK and DAY keys at the same time.
This starts the test mode.
2. Press the DISPLAY key. See Fig. 20.
Fig. 20—Display when starting test sequence.
COMM
HEAT
AM
● ● ●
COOL
S
U
BATT
M4418
NOTE: When cooling setting changes, thermostat will wait
up to five minutes before turning on the cooling equip-
ment. This delay is to protect the compressor.
1. Press the OCCUPIED COOL key.
2. Press the - key to lower the setpoint 5°F (3°C) below
the room temperature. The cooling should start (both stages if multistage), and the fan should run.
NOTE: It can be necessary to change the OCCUPIED
HEAT setpoint. However, be aware that the OCCUPIED
HEAT and OCCUPIED COOL setpoints must have a
2°F difference.
3. Press the OCCUPIED COOL key.
4. Press the + key to raise the setpoint 5°F (3°C) above
the room temperature. The cooling and fan should shut off.
When the thermostat has a system switch, move the switch to the COOL position and repeat Steps 1 through 4.
Move the system switch to the OFF position. All heating or cooling should stop.
FAN Thermostat
Fan Switch (located on the back of the thermostat):
— CON: Fan operates continuously in the occupied
mode.
— INT-FAN: Fan operates directly with the thermo-
stat call for heating or cooling in the occupied mode.
Subbase
3. Press the OCCUPIED HEAT key.
4. Press the + key to raise the setpoint 5°F (3°C) above
the room temperature. The heating should start (both stages if multistage), and the fan should run (may be a short delay on forced air systems).
NOTE: It can be necessary to change the OCCUPIED
COOL setpoint. However, be aware that OCCUPIED HEAT and OCCUPIED COOL setpoints must have a 2°F difference.
5. Press the OCCUPIED HEAT key.
6. Press the - key to lower the setpoint 5°F (3°C) below
the room temperature. The heating should shut off, followed by the fan shutoff.
When the thermostat has a system switch, move the
switch to the HEAT position and repeat steps 3 through 6.
63-4038—7 14
NOTE: Subbase fan switch overrides the thermostat fan
switch.
Subbase Dip Switch No. 4:
— ON: Fan operates only with cool. — OFF: Fan operates with heat and cool.
Q7300E Fan Switch:
— ON: Fan operates continuously. — AUTO: Fan operates directly with the thermostat
call for heating or cooling.
IMPORTANT: Press the CLOCK and DAY keys at the same
time to discontinue the test mode. The Test Mode Indi­cators will no longer show on the screen. See Fig. 19.
T7200/T7300/Q7300
OPERATION
Operation
T7200/T7300 RELAY LOGIC
The T7300 contains three switching relays. When the mini-jumper is set for conventional applications, the relays control first stage cooling, first stage heating, and fan. When the mini-jumper is set for heat pump applications, the relays control the heat pump compressor, auxiliary heat, and fan. Because of this change in switching logic, it is important to use Q7300C,D, or F subbases when the T7300 is set for heat pump applications and use Q7300A,B,E,G subbases when the T7300 is set for conventional applica­tions.
The T7200A Relay Logic is for conventional applica­tions. The T7300B Relay Logic is for heat pump applica­tions.
T7200/T7300 AND CONVENTIONAL THERMOSTATS P+I Control
The T7200/T7300 microprocessor based control requires that the user understands temperature control and thermo­stat performance. A conventional electromechanical or elec­tronic thermostat does not control temperature precisely at setpoint. Typically, there is an offset (droop) in the control point as the system load changes. This is a phenomenon that most people in the industry know and accept. Many factors contribute to offset including switch differential, thermal lag, overshoot, cycle rates and system load.
The thermostat microprocessor simultaneously gathers, compares and computes data. Using this data, it controls a wide variety of functions. The special proprietary algo­rithm (program) in the thermostat eliminates the factors causing offset. This makes temperature control more accu­rate than the conventional electromechanical or electronic thermostats. The temperature control algorithm is called proportional plus integral (P+I) control.
The thermostat sensor, located on the thermostat or remote, senses the current space temperature. The propor­tional error is calculated by comparing the sensed tempera­ture to the programmed setpoint. The deviation from the setpoint is the proportional error.
The thermostat also determines integral error, which is a deviation based on the length of error time. The sum of the two errors is the (P+I) error. The cycle rate used to reach and maintain the setpoint temperature is computed using the P+I. The addition of the integral error is what differen­tiates the thermostat from many other electronic and elec­tromechanical thermostats. See Fig. 21.
Fig. 21—Proportional temperature control versus P+I temperature control.
THERMOSTAT COOL SETPOINT
PROPORTIONAL COOL CONTROL POINT
P+I CONTROL POINT
P+I CONTROL POINT
TEMPERATURE
100 50 0 50 100
PROPORTIONAL HEAT CONTROL POINT
THERMOSTAT HEAT SETPOINT
HEATING
PERCENT LOAD
COOLING
M4414
While the thermostat is designed to eliminate droop, allowing droop can be desirable in applications where building visitors are dressed for the weather and their stays are brief. Examples of these applications include fast food restaurants and convenience stores. The droopless feature of the thermostat can be overridden by placing the droop/ droopless select switch located on the subbase in the OFF position. This removes the integral calculation from the thermostat control scheme, allowing only the proportional control to occur.
EQUIPMENT PROTECTION
As part of the operational sequence, the T7200/T7300 microprocessor also incorporates minimum On and Off times for all heating and cooling stages. Minimum On and Off times assure that rapid cycling of equipment will not occur, extending equipment life. Minimum On/Off times for compressor stages are two minutes On and four minutes Off. Minimum On/Off times for heat (electric resistive or gas) are two minutes.
T7200/T7300 THERMOSTAT OPERATION Startup
When power to the thermostat is turned on, a startup and initialization program begins. The startup takes place after total loss of power (24 Vac and battery backup). At this time, the system default values are put into memory (re­placing the user program that was lost). Default values are heating 68°F (20°C) and cooling 78°F (26°C) for the occu­pied modes. Unoccupied default values are heating 55°F (13°C) and cooling 90°F (32°C).
15 63-4038—7
Loading...
+ 33 hidden pages