Honeywell t7100f Installation Instructions Manual

Page 1
T7100F Microelectronic Conventional
69-0964-2
or Heat Pump Thermostat
INSTALLATION INSTRUCTIONS
APPLICATION
The T7100F Microelectronic Thermostat provides electronic control of 24 Vac commercial single zone heating, ventilating and air conditioning (HVAC) equipment. It is designed for use with the Q7100A Subbases for conventional heat/cool applications and the Q7100C Subbases for heat pump applications. The T7100F is field configurable for automatic or manual changeover between heating and cooling. All T7100F Thermostats require a common wire to supply power.
NOTE: When Q7100C Subbases are used, Installer
Setup Option must be set to 01 (heat pump).
RECYCLING NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do control in the trash.
Contact your local waste management authority for instructions on recycling and the proper disposal of the old thermostat.
not
place your old
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on product to
make sure product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Mounting and Wiring Q7100 Subbase
Refer to the subbase installation instructions for mounting and wiring information.
Setting Keypad Lockout Switch
The T7100F can be configured for keypad lockout to prevent changes to the temperature or system settings. DIP switch number 1, on the back of the thermostat, activates the lockout feature. See Fig. 1. The DIP switch must be set to the ON position (up) to activate the lockout feature. The factory setting is off (down). Be sure to set the switch before mounting the thermostat on the subbase. When the DIP switch is set to the ON position it disables all of the keys on the thermostat.
ON
1
1
2
DIP 1 IS ON
1
BACK OF THERMOSTAT
Fig. 1. Setting keypad lockout DIP switch
Mounting Thermostat
Mount the thermostat on the Q7100 Subbase after the Q7100 is installed:
1. Engage tabs at the top of the thermostat and
subbase. Fig. 2.
2. Press lower edge of the case to close and latch.
(back of thermostat).
M10108
CAUTION
Electrical Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before installation.
X-XX UL
Page 2
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
M6799A
Fig. 2. Mounting thermostat on subbase.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; then remove the top.
Using Thermostat Keys
The thermostat keys are used to:
• Set temperature,
•Display present setting,
• Configure Installer Setup,
• Check Self-Test.
Select models have keys to:
• Temporarily override the temperature,
• Set the system operation,
• Set the fan operation.
See Fig. 3 for key information.
DISPLAY PRESENT SETTINGS AND SCROLL THROUGH INSTALLER SETUP (INFORMATION KEY)
CHANGE TEMPERATURE SETTING TEMPORARILY (SELECT MODELS)
i
INCREASE TEMPERATURE SETTING
DECREASE TEMPERATURE SETTING
SELECT FAN OPERATION
SELECT SYSTEM OPERATION
M6800B
Fig. 3. Thermostat key locations and descriptions.
SETTINGS
System and Fan Settings
System settings control the thermostat operation as follows:
Em Heat (Q7100C only): Emergency heat relay is on
continuously. Thermostat cycles highest stage of heat. Cooling system is off. Compressor is de-
energized. Heat: Thermostat controls the heating. Off: Both the heating and cooling are off. Cool: Thermostat controls the cooling. Auto: Thermostat automatically changes between
heating and cooling operation, depending on the
indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously. Auto: Equipment controls fan.
The system default setting is Heat and the Fan default setting is Auto. Use the keys to change to the desired settings.
Temperature Settings
The default setpoint for heat is 70°F (21°C) and for cool is 78°F (25.5°C). Press the increase or decrease key to change the setting. To change between heat and cool settings, press the Information i key until the setting to be changed appears.
Override Temperature Settings (Select Models)
The T7100 temperature settings can be overridden in three ways: — Using the T7100 Override key, acting as a toggle. — Using a remote setback timer. — Using an occupancy sensor.
The temperature settings change based on Installer Setup 27.
NOTE: Installer Setup 27 is factory set at zero degrees
so this setting must be changed for the tempera­ture to change.
The Override key changes the current temperature temporarily to a preset offset. The remote timer and occupancy sensor open (temporary setpoint) or close (comfort setpoint) contacts according to the settings. See Table 1.
Always check the display to determine if the thermostat is controlling the comfort, temporary or remote setpoints. Temporary is displayed when the Override key is pressed or the occupancy sensor or remote setback timer is energized.
Table 1. Temperature override.
System
Setting
Comfort Setpoint
Installer Setup
27 Setting
Heat 68°F10°F58°F
Cool 74°F10°F84°F
Temporary
Setpoint
69-0964–2
2
Page 3
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
INSTALLER SETUP
NOTE: For most applications, the thermostat factory
settings do not need to be changed. Review the factory settings in Table 2 and if no changes are necessary go to the Installer Self-Test section.
The Installer Setup is used to customize the thermostat to specific systems. Some of the options include temperature display, remote sensing system, changeover, minimum equipment On time and minimum Off time. Installer modes are listed in numerical order in Table 2. It includes all the configuration options and the factory-settings available for the T7100F.
IMPORTANT
The Installer Setup must be set correctly for the HVAC equipment, thermostat and subbase to operate properly.
A combination of key presses are required to use the Installer Setup feature: — To enter the Installer Setup mode, press and hold the
Information i key with the increase and decrease keys until the first mode number is displayed. All display segments appear for approximately three seconds before the first mode number is displayed. See Fig. 4 and 5.
— To advance to the next Installer Setup mode, press
the Information i key.
— To change a setting, use the increase or decrease
key.
— To exit the Installer Setup mode, press and hold the
Information i key until the display returns to normal (approximately three seconds). The display scrolls the mode numbers backward to get to the normal display. The Installer Setup mode is automatically exited if no key presses are made for five minutes.
Em Ht Temporary Setting Aux Ht
Repl
Wait
Batt
System Fan
Em HeatOffCool Auto Only
Heat Cool
Fig. 4. Display of all LCD segments.
MODE NUMBER DISPLAY (COLUMN 2 OF TABLE 2)
Fig. 5. Display of Installer Setup mode and setting.
CAUTION
Equipment Damage.
Damage can result when the system runs
without the fan.
Configure heat pump and electric heat systems
correctly in Installer Setup modes 01 and 02.
NOTE: Only configurable Mode Numbers are shown.
Remote
Room
%Humid
Outdoor
OnAuto
M4844
FACTORY SETTING OR OTHER CHOICE DISPLAY (COLUMN 3 OR 5 OF TABLE 2)
M10105
Table 2. Thermostat Installer Setup Options.
Mode Number (Press i key
Select
to change)
Application. 01 00 Conventional equipment
Fan operationa.0200Conventional applica-
Output stages of heating.
03 Depends
Factory-Setting
Display Description Display Description
application (Q7100A).
tions where equipment controls fan operation in heat mode.
on subbase.
Stages of heat. 01, 02, or0301—One stage of heat.
01 Heat pump application (Q7100C,D)
01 Electric heat applications where
Other Choices
(Press ▲ or ▼ key to change)
(fan operation is automatically selected so go to mode number
03).
thermostat controls fan operation in heat mode.
02—Two stages of heat. 03—Three stages of heat.
Heating cycle 04 Depends Stage 1. 03, 04, 03—3 cph used for hot water rate. 05 on model Stage 2. 06, 08 systems or high efficiency
06 Stage 3 (Q7100C only). or 09 furnaces. 07 Emergency heat
a
Mode 01 must be 00 to allow a selection in this mode.
(Q7100C only).
04—4 cph (factory setting for heat
pump systems).
06—6 cph used for conventional
systems.
08—8 cph (factory setting for
conventional systems).
09—9 cph used for electric heat
systems and is the factory setting for the emergency heat stage.
(continued)
3
69-0964–2
Page 4
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
Select
Output stages of cooling.
Mode Number (Press i key
to change)
08 02 Two stages of cool. 00 or 01 00—No cooling.
Factory-Setting
Display Description Display Description
Cooling cycle rate. 09 04 Stage 1. 03 3 cph.
10 04 Stage 2. Not used. 11 — Changeover
(T7100F only).
12 00 System setting key is
operational.
01 or 02 01—Manual changeover
Not used. 13 — Degree tempera-
ture display. Displaying
temperature.
14 00 Temperature is
15 00 Temperature is
displayed in °F.
displayed.
01 Temperature is displayed in °C.
01 Temperature is not displayed.
Not used. 16 - 18 — Extended fan
operation in
b
heating
.
Extended fan operation in cooling.
Fan key adjustment.
Remote sensing. 22 00 Remote sensing not
Temperature averaging
c
network
.
19 00 No extended fan
20 00 No extended fan
21 00 Fan setting key is
operation after the call for heat ends.
operation after the call for cool ends.
operational.
activated.
23 00 Temperature averaging
disabled.
01 Fan operation is extended
01 Fan operation is extended
01 Fan setting key is continuously in
01 Remote sensing activated.
01 Temperature averaging between
Not used. 24 — Keypad lockout
level.
25 0 No lockout. 01 - 02 01—View setpoint only.
Not used. 26 — Heating/cooling
override.
27 00 No temperature change
when override key is pressed.
01 - 15 °F the temperature setting is
Not used. 28 - 29 — Deadband. 30 02 Heating and cooling
Interstage control point (select models).
31 01
(Conven­tional) or 02 (Heat pump).
Minimum On time. 32 02 2-minute minimum On
Minimum Off time for the compressor.
b
Mode 01 or 02 must be 01 to extend fan operation.
c
Mode 22 must be set to 01 and remote sensor(s) must be installed.
33 04 4-minute minimum Off
setpoints can be set no closer than 2°F.
Temperature has to change 1°F or 2°F before the system calls for the next stage.
time for heating and cooling.
time for the compressor.
03 - 10 Heating and cooling setpoints can
00 - 12 Temperature has to change the
00 or 01 No minimum On time or 1 minute
00, 01, 02, 03 or 05
Other Choices
(Press ▲ or ▼ key to change)
01—One stage of cool.
02—Auto only.
90 seconds after the call for heat ends.
90 seconds after the call for cool ends.
the Auto position.
local sensor and remote sensor(s) activated.
02—Lockout all keys.
changed when the override key is pressed. Temporary is displayed.
be set no closer than the chosen value.
chosen value before the system calls for the next stage.
minimum On time for heating and cooling.
Minimum number of minutes (0 thru 5) the compressor will be off between calls for the compressor.
(continued)
69-0964–2
4
Page 5
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Table 2. Thermostat Installer Setup Options (Continued).
Mode Number
(Press i key
Select
Temperature range stops in heating (T7100F only).
Temperature range stops in cooling (T7100F only).
to change)
34 90 Highest heating setpoint
35 45 Lowest cooling setpoint
Not used. 36 — Temperature
display adjustment.
Minimum Off times in heating.
37 00 No difference in
38 02 2-minute minimum Off
Factory-Setting
(Press ▲ or ▼ key to change)
Display Description Display Description
allowed.
allowed.
displayed temperature and actual room temperature.
time.
40 - 89 Temperature range for (1°F
46 - 99 Temperature range for (1°F
01 - 06
00, 01, 03, 04 or 05
Other Choices
increments) heating setpoint.
increments) cooling setpoint.
01—Display adjusts to 1°F higher
than actual room temperature.
02—Display adjusts to 2°F higher
than actual room temperature.
03—Display adjusts to 3°F higher
than actual room temperature.
04—Display adjusts to 1°F lower
than actual room temperature.
05—Display adjusts to 2°F lower
than actual room temperature.
06—Display adjusts to 3°F lower
than actual room temperature.
Minimum number of minutes (0 thru 5) the heating equipment is off between calls for heat.
INSTALLER SELF-TEST
Use the Installer Self-Test to check the thermostat configurations and operation. Refer to Table 3 for a list of the available Self-Tests.
NOTE: The minimum Off time for compressors is
bypassed during the Installer Self-Test.
To start the Self-Test:
Press and hold the increase and decrease ▼ keys, at the same time, until two zeros appear. All segments of the LCD are displayed for three seconds before the two zeros appear. Refer to Fig. 6 and 7.
Em Ht Temporary Setting Aux Ht
Repl
Wait
Batt
System Fan
Em HeatOffCool Auto Only
Heat Cool
Fig. 6. Display of all LCD segments.
Remote
Room
%Humid
Outdoor
OnAuto
M4844
TEST MODE NUMBER
Fig. 7. Display of Test Mode number.
Table 3. Installer Self-Test Mode Tests.
Test
Number Self-Test Description
10-19 Heating equipment can be turned on and off. 20-29 Emergency heat (Q7100C only) equipment
can be turned on and off. 30-39 Cooling equipment can be turned on and off. 40-49 Fan equipment can be turned on and off. 60-69 Keyboard keys test. 70-79 Thermostat information including date code
and software versions is displayed.
Refer to Table 4 for the directions and results of the specific tests.
NOTE: Press and hold the increase and decrease
keys for three seconds to exit the Self-Test mode. Self-Test times out after five minutes without any key presses.
5
M6792
69-0964–2
Page 6
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
Table 4. Installer Self-Test Options.
Key to
Press
Heating Equipment Self-Test
11 Stage-one heat comes on. When Installer Setup mode number 01 is 01 or mode number 02
12 Stage-two heat comes on. Stage-one heat and system fan remain on. 13 Stage-three heat comes on (heat pump configuration). Stage-one and stage-two heat remain
12 Stage-three heat turns off. 11 Stage-two heat turns off. 10 Stage-one heat and system fan turn off.
Emergency Heating Equipment Self-Test (with select Q7100C Subbase models)
21 Emergency heat comes on. 20 Emergency heat turns off.
Cooling Equipment Self-Test
31 Stage-one cooling and system fan come on. 32 Stage-two cool comes on. Stage-one cool and system fan remain on. 31 Stage-two cool turns off. 30 Stage-one cool and system fan turn off.
Fan Equipment Self-Test
41 Fan comes on. 40 Fan turns off.
KEY TEST
60 Displays 4. 60 Displays 3.
Override 60 Displays 5. System
Fan
a
Available on select models.
Test
Mode
Number Description
i
10 Enter heating equipment Self-Test.
is 01, the system fan is also energized.
on.
i
i
i
i
20 Change from heating to emergency heating equipment Self-Test.
30 Change from heating or emergency heating to cooling equipment self-test.
40 Change from cooling to fan equipment Self-Test.
a
60 Displays 2.
a
60 Displays 0.
a
60
Displays 1.
Thermostat Information
1. Press the Information i key to access the thermo-
stat information.
M4864
69-0964–2
2. Press the increase key to display the production
date code. The first two large digits are the month and the third digit is the last digit of the year. (Example: 026 = February 1996)
6
M4865
Page 7
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
3. Press the increase ▲ key again to display the
software identification code. (Example: 02 = software ID code 2)
M4866
4. Press the increase ▲ key again to display the
software revision number. (Example: 001 = revision number 1)
M6787
5. Press the increase ▲ key again to display the
EEPROM identification code. (Example: 222 = EEPROM ID 222)
6. Press and hold both the increase ▲ and the
decrease keys, until the room temperature is displayed, to exit the Self-Test. The Self-Test times out after five minutes without any key presses.
TROUBLESHOOTING GUIDE
Symptom Possible Cause Action
Display does not come on.
Temperature display is incorrect.
Temperature settings will not change. (Example: Cannot set higher or cooling lower.)
Thermostat is not powered. • Check that X terminal is connected to the system
Thermostat microprocessor is locked up.
Room temperature display has been reconfigured.
Thermostat is configured for °F or °C display (select models).
transformer.
• Check for 24 Vac between X and R or RH terminals. — If missing 24 Vac:
— Check if the circuit breaker is tripped—reset the
circuit breaker.
— Check if the system fuse is blown—replace the
fuse.
— Check if the power switch on the HVAC equipment
is in the Off position—set to the On position.
— Check the wiring between the thermostat and the
HVAC equipment—replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
Remove the thermostat from the subbase for 2 minutes. After 2 minutes, replace the thermostat on the subbase.
Enter Installer Setup 37 and reconfigure the display.
Enter Installer Setup 14 and reconfigure the display.
Bad thermostat location. Relocate the thermostat. Display shows two dashes and
a degree sign. Upper or lower temperature
limits were reached.
heating
Installer Setup 22 is set for remote sensing and the sensor is missing or the circuit is open or shorted.
Check the temperature setpoints:
• Heating limits are 40 to 90°F (7 to 31°C).
• Cooling limits are 45 to 99°F (9 to 37°C).
M6788
(continued)
7
69-0964–2
Page 8
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
TROUBLESHOOTING GUIDE (Continued)
Symptom Possible Cause Action
Heating does not come on.
Cooling does not come on.
Cooling does not come on (continued)
System On indicator is lit, but no heat is being delivered.
24V is present on all terminals.
No power to the thermostat. • Check that X terminal is connected to the system
Thermostat minimum Off time is activated and wait indicator is displayed.
System selection is not set to Heat.
No power to the thermostat. • Check that the X terminal is connected to the system
Thermostat minimum Off time is activated and wait indicator is displayed.
System selection is not set to Cool.
Fan operation set to 00 (conventional heat) when it should be set to 01 (electric heat).
Conventional heating equipment turns on the fan when the furnace has warmed up to a setpoint.
Heating equipment is not operating.
When thermostat is powered but is not connected to heating/cooling equipment, arc suppression will be present (24V ghost voltage)
transformer.
• Check for 24 Vac between X and R or RH terminals. — If missing 24 Vac:
— Check if the circuit breaker is tripped—reset the
circuit breaker.
— Check if the system fuse is blown—replace the
fuse.
— Check if the system switch at the equipment is in
the Off position—set to On position.
— Check wiring between the thermostat and the
HVAC equipment—replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
• Wait up to five minutes for the system to respond.
• Enter Installer Setup 38. Reconfigure minimum On time (if required).
Set system selection to Heat.
transformer.
• Check for 24 Vac between X and R or RC and Y terminals. — If missing 24 Vac:
— Check if the circuit breaker is tripped—reset the
circuit breaker.
— Check if the system fuse is blown—replace the
fuse.
— Check if the system switch at the equipment is in
the Off position—set to the On position.
— Check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any loose connections.
— If 24 Vac is present, proceed with troubleshooting.
• Wait up to five minutes for the system to respond.
• Enter Installer Setup 33. Reconfigure minimum Off time (if required).
Set system selection to Cool.
Enter Installer Setup mode number 02 and reconfigure the fan operation.
Wait a minute after seeing the On indicator and then check the registers.
Verify operation of heating equipment in Self-Test.
Connect heating/cooling equipment to the thermostat. Voltage will drop to zero.
69-0964–2
69-0964–2 D.S. Rev. 12-98 Printed in Taiwan R.O.C. www.honeywell.com/building/components
8
Loading...