The T7100F Microelectronic Thermostat provides
electronic control of 24 Vac commercial single
zone heating, ventilating and air conditioning
(HVAC) equipment. It is designed for use with the
Q7100A Subbases for conventional heat/cool
applications and the Q7100C Subbases for heat
pump applications. The T7100F is field
configurable for automatic or manual changeover
between heating and cooling. All T7100F
Thermostats require a common wire to supply
power.
NOTE: When Q7100C Subbases are used, Installer
Setup Option must be set to 01 (heat pump).
RECYCLING NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do
control in the trash.
Contact your local waste management authority for
instructions on recycling and the proper disposal of
the old thermostat.
not
place your old
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
the instructions can damage the product or cause a
hazardous condition.
2. Check ratings given in instructions and on product to
make sure product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions
to check out the product operation.
Mounting and Wiring Q7100 Subbase
Refer to the subbase installation instructions for mounting
and wiring information.
Setting Keypad Lockout Switch
The T7100F can be configured for keypad lockout to
prevent changes to the temperature or system settings.
DIP switch number 1, on the back of the thermostat,
activates the lockout feature. See Fig. 1. The DIP switch
must be set to the ON position (up) to activate the lockout
feature. The factory setting is off (down). Be sure to set the
switch before mounting the thermostat on the subbase.
When the DIP switch is set to the ON position it disables
all of the keys on the thermostat.
ON
1
1
2
DIP 1 IS ON
1
BACK OF THERMOSTAT
Fig. 1. Setting keypad lockout DIP switch
Mounting Thermostat
Mount the thermostat on the Q7100 Subbase after the
Q7100 is installed:
1. Engage tabs at the top of the thermostat and
subbase. Fig. 2.
2. Press lower edge of the case to close and latch.
(back of thermostat).
M10108
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before installation.
X-XX UL
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
A.
ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE.
B.
PRESS LOWER EDGE OF CASE TO LATCH.
M6799A
Fig. 2. Mounting thermostat on subbase.
NOTE: To remove the thermostat from the wall, first pull
out at the bottom of the thermostat; then remove
the top.
Using Thermostat Keys
The thermostat keys are used to:
• Set temperature,
•Display present setting,
• Configure Installer Setup,
• Check Self-Test.
Select models have keys to:
• Temporarily override the temperature,
• Set the system operation,
• Set the fan operation.
See Fig. 3 for key information.
DISPLAY PRESENT SETTINGS
AND SCROLL THROUGH
INSTALLER SETUP
(INFORMATION KEY)
CHANGE TEMPERATURE
SETTING TEMPORARILY
(SELECT MODELS)
i
INCREASE TEMPERATURE
SETTING
DECREASE TEMPERATURE
SETTING
SELECT
FAN OPERATION
SELECT SYSTEM
OPERATION
M6800B
Fig. 3. Thermostat key locations and descriptions.
SETTINGS
System and Fan Settings
System settings control the thermostat operation as
follows:
Em Heat (Q7100C only): Emergency heat relay is on
continuously. Thermostat cycles highest stage of
heat. Cooling system is off. Compressor is de-
energized.
Heat: Thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: Thermostat controls the cooling.
Auto: Thermostat automatically changes between
heating and cooling operation, depending on the
indoor temperature.
Fan settings control the system fan as follows:
On: Fan operates continuously.
Auto: Equipment controls fan.
The system default setting is Heat and the Fan default
setting is Auto. Use the keys to change to the desired
settings.
Temperature Settings
The default setpoint for heat is 70°F (21°C) and for cool is
78°F (25.5°C). Press the increase ▲ or decrease ▼ key to
change the setting. To change between heat and cool
settings, press the Information i key until the setting to
be changed appears.
Override Temperature Settings
(Select Models)
The T7100 temperature settings can be overridden in
three ways:
— Using the T7100 Override key, acting as a toggle.
— Using a remote setback timer.
— Using an occupancy sensor.
The temperature settings change based on Installer
Setup 27.
NOTE: Installer Setup 27 is factory set at zero degrees
so this setting must be changed for the temperature to change.
The Override key changes the current temperature
temporarily to a preset offset. The remote timer and
occupancy sensor open (temporary setpoint) or close
(comfort setpoint) contacts according to the settings. See
Table 1.
Always check the display to determine if the thermostat is
controlling the comfort, temporary or remote setpoints.
Temporary is displayed when the Override key is pressed
or the occupancy sensor or remote setback timer is
energized.
Table 1. Temperature override.
System
Setting
Comfort
Setpoint
Installer Setup
27 Setting
Heat68°F10°F58°F
Cool74°F10°F84°F
Temporary
Setpoint
69-0964–2
2
T7100F MICROELECTRONIC CONVENTIONAL OR HEAT PUMP THERMOSTAT
INSTALLER SETUP
NOTE: For most applications, the thermostat factory
settings do not need to be changed. Review the
factory settings in Table 2 and if no changes are
necessary go to the Installer Self-Test section.
The Installer Setup is used to customize the thermostat to
specific systems. Some of the options include temperature
display, remote sensing system, changeover, minimum
equipment On time and minimum Off time. Installer modes
are listed in numerical order in Table 2. It includes all the
configuration options and the factory-settings available for
the T7100F.
IMPORTANT
The Installer Setup must be set correctly for the
HVAC equipment, thermostat and subbase to
operate properly.
A combination of key presses are required to use the
Installer Setup feature:
— To enter the Installer Setup mode, press and hold the
Information i key with the increase ▲ and decrease
▼ keys until the first mode number is displayed. All
display segments appear for approximately three
seconds before the first mode number is displayed.
See Fig. 4 and 5.
— To advance to the next Installer Setup mode, press
the Information i key.
— To change a setting, use the increase ▲ or decrease
▼ key.
— To exit the Installer Setup mode, press and hold the
Information i key until the display returns to normal
(approximately three seconds). The display scrolls the
mode numbers backward to get to the normal display.
The Installer Setup mode is automatically exited if no
key presses are made for five minutes.
Em Ht Temporary Setting
Aux Ht
Repl
Wait
Batt
SystemFan
Em HeatOffCool Auto Only
Heat Cool
Fig. 4. Display of all LCD segments.
MODE NUMBER DISPLAY
(COLUMN 2 OF TABLE 2)
Fig. 5. Display of Installer Setup mode and setting.
CAUTION
Equipment Damage.
Damage can result when the system runs
without the fan.
Configure heat pump and electric heat systems
correctly in Installer Setup modes 01 and 02.
NOTE: Only configurable Mode Numbers are shown.
Remote
Room
%Humid
Outdoor
OnAuto
M4844
FACTORY SETTING OR
OTHER CHOICE DISPLAY
(COLUMN 3 OR 5 OF TABLE 2)
M10105
Table 2. Thermostat Installer Setup Options.
Mode Number
(Press i key
Select
to change)
Application.0100Conventional equipment
Fan operationa.0200Conventional applica-
Output stages of
heating.
03 Depends
Factory-Setting
DisplayDescriptionDisplayDescription
application (Q7100A).
tions where equipment
controls fan operation in
heat mode.
on
subbase.
Stages of heat.01, 02, or0301—One stage of heat.
01Heat pump application (Q7100C,D)
01Electric heat applications where
Other Choices
(Press ▲ or ▼ key to change)
(fan operation is automatically
selected so go to mode number
03).
thermostat controls fan operation
in heat mode.
02—Two stages of heat.
03—Three stages of heat.
Heating cycle 04Depends Stage 1.03, 04,03—3 cph used for hot water
rate.05 on model Stage 2.06, 08systems or high efficiency
06 Stage 3 (Q7100C only). or 09furnaces.
07Emergency heat
a
Mode 01 must be 00 to allow a selection in this mode.
(Q7100C only).
04—4 cph (factory setting for heat
pump systems).
06—6 cph used for conventional
systems.
08—8 cph (factory setting for
conventional systems).
09—9 cph used for electric heat
systems and is the factory setting
for the emergency heat stage.
(continued)
3
69-0964–2
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.