Honeywell T7079A, T7079B Product Data

Put UPC Code Here
T7079A,B Solid State Remote Temperature Controllers
PRODUCT DATA

FEATURES

• Switch selection of heat or cool mode.
• Temperature sensing up to 400 feet.
• Does not require field calibration.
• 10K NTC temperature sensor.
• Wide setpoint temperature range.
• LED annunciation for both power on and relay state.
• Dual setpoint scale (°F and °C).
• Isolation transformer for 24 Vac input.
• Single- or Dual-stage output.
• Dual-stage output models can be configured as two-heat, two-cool, or one-heat/one-cool.

APPLICATION

Contents
Application ........................................................................1
Features ...........................................................................1
Specifications ....................................................................2
Ordering Information .........................................................2
Installation ........................................................................3
Wiring ...............................................................................4
Operation ..........................................................................5
Checkout ..........................................................................6
63-2572—04
T7079A,B SOLID STATE REMOTE TEMPERATURE CONTROLLERS

SPECIFICATIONS

Models:
T7079: On-off wall-mount control with one temperature input
and one or two relay output stages. Differential range of 1 to 30°F. Includes one sensor. See Table 1.
Table 1. T7079 models.
Voltage (in Vac) Setpoint Range in °F (°C)
-25 to 105
24 120/230
(-32 to 40)
T7079A1004 X X
T7079A1012 X X
T7079A1046 X X
T7079A1053 X X
T7079B1028 X X
T7079B1036 X X
T7079B1044 X X
T7079B1051 X X
Dimensions: See Fig. 1.
2 (50)
1 (25)
2-7/16 (61)
2 (50)
2-7/16 (61)
STAGE1 STAGE2 POWER
100 to 240 (38 to 116)
Power Consumption: See Table 2.
Table 2. Power consumption ratings.
Vol tage Hz No m i n a l VA M a x imum VA
24 50 5.6 6.2
60 5.5 6.1
120 50 7.7 8.5
60 5.6 6.2
230 50 5.0 6.1
60 2.9 4.7
Contact Ratings:
At 120 Vac: 1/2 hp, 9.8 FLA, 58.8 LRA. At 230 Vac: 1/4 hp, 4.9 FLA, 29.4 LRA. At 120/230 Vac: 125 VA pilot duty. At 24 Vac (resistive): 8A.
Ambient Ratings:
Operating Temperature: -40° to 140°F (-40° to 60°C). Storage Temperature: -40° to 180°F (-40° to 82°C). Operating Humidity: 5% to 95% RH non-condensing.
Temperature Accuracy (at nominal voltage): In 77°F (25°C) ambient, nominal sensor value: ±2°F.
NOTE: Accuracy can vary based on deviation from nominal
values of input voltage, operating ambient and sensor ambient.
Sensor: 10k NTC, 400 ft maximum distance between sensor and electronic controller. See Table 3 for thermistor output.
Approvals:
Underwriters Laboratories, Inc. Canadian Underwriters Laboratories. CE.
4-1/2 (114)
7-3/16
(183)
Accessories:
107048 Heat Conduction Compound, 4 once. 107324A Bulb Holder, duct insertion.
M17560
Fig. 1. Dimensions of T7079 in in. (mm).
121371A Copper Immersion Well. 121371E Stainless Steel Well. 32004800-001 10K NTC Sensor. T7047C1090 Wall Mounted Sensor Case.
Electrical Ratings:
Voltage Input: 24 Vac, 50/60 Hz (+10%, -15%), Class 2 only.
120/230 Vac, 50/60 Hz (+10%, -15%).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2572—04 2
T7079A,B SOLID STATE REMOTE TEMPERATURE CONTROLLERS
CAUTION
Table 3. 10K thermistor output.
Resistance °C °F
97820 -20 -4
32740 0 32
19920 10 50
12500 20 68
10000 25 77
8056 30 86
5326 40 104
3604 50 122
2491 60 140
1756 70 158
1261 80 176
920.9 90 194

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
Sensor Location
The sensor can be located up to 400 feet (122 meters) from the T7079 using standard AWG 18/2 unshielded wire. The sensor may be attached to pipes, in an immersion well, in a wall-mounted case or on a bulb holder.
NOTES:
For cable runs greater than 25 feet, shielded cable
is recommended.
Multiple sensors can be parallel-series wired to
sense average temperatures in large spaces. See Fig. 2.
To maintain control accuracy, the number of
sensors wired parallel-series must be n
2
(examples: 4, 9, 16).
SENSORS
TO T7079
M13129
Fig. 2. Parallel-series wiring of sensors.
Sensor Mounting
IMPORTANT
The T7079 is an operation control, not a limit or safety control. If used in applications requiring safety or limit controls, use a separate safety or limit control device in conjunction with the T7079.
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.

Location and Mounting

Mount the controller on a convenient interior location using the three mounting holes provided on the back of the enclosure (mounting screws are not provided and must be obtained separately). Use controller dimensions in Fig. 1 as a guide.
Mount the sensor(s) in one of the following manners: — Hot/cold water sensing: Strap sensor to a pipe or insert in a
well (see Fig. 3).
— Space temperature sensing: Mount on a wall or panel
(see Fig. 4).
— Duct air sensing: Tape to a standard cap or bulb holder.
COVER SENSOR LEADS WITH HEAT CONDUCTIVE COMPOUND
SENSOR PLACED IN WELL
1/2 NPT
IMMERSION WELL
M5249
Fig. 3. Sensor inserted in an immersion well.
3 63-2572—04