Legacy Building Systems
Q667 Switching Subbase
|
|
|
Provide manual switching for T7067 Thermostat/Transmitters. |
||
|
|
|
• Mount directly on wall or on vertical 2 x 4 in. outlet box |
||
|
|
|
• T7067 mounts on subbase with mounting screws which also complete |
||
|
|
|
electrical connections between thermostat/transmitter and subbase |
||
|
|
|
• When fan switch is set to AUTO, the fan is intermittent in HEAT and |
||
|
|
|
continuous in system AUTO or COOL |
|
|
|
|
|
Dimensions, Approximate: 4 3/4 in. high x 3 15/16 in. wide x 15/16 in. |
||
|
|
|
deep (121 mm high x 100 mm wide x 24 mm deep) |
|
|
|
|
|
Power Consumption: 1A at 24 Vac Full Load |
|
|
|
|
|
Description: Switching Subbase used with T7067 |
|
|
|
|
|
|
|
|
|
|
Switch Positions |
|
|
|
|
|
|
|
|
|
Product Number |
Application |
System |
Fan |
Comments |
Used With |
|
|
|
|
|
|
Q667A1005/U |
Heat Pump Systems, |
HEAT-OFF-COOL- |
AUTO/ON |
Number of stages of heating and cooling |
T7067 |
|
Split Systems |
AUTO |
|
depends on the chosen Logic Panel |
|
|
|
|
|
|
|
Q667B1004/U |
Heat Pump Systems, |
HEAT-OFF-COOL- |
AUTO/ON |
Number of stages of heating and cooling |
T7067 |
|
Split Systems |
AUTO |
|
depends on the chosen Logic Panel |
|
|
|
|
|
|
|
Q667B1020/U |
Heat Pump Systems, |
HEAT-OFF-COOL- |
AUTO/ON |
Provides intermittent fan operation |
T7067 |
|
Split Systems |
AUTO |
|
in cooling when used with W974B |
|
|
|
|
|
|
|
Q667C1003/U |
Single Stage Subbase |
COOL/AUTO/HEAT/ |
AUTO/OFF; OFF |
— |
T7067 |
|
|
EM.HT. |
position shuts off |
|
|
|
|
|
entire system |
|
|
|
|
|
|
|
|
T7067 Thermostat and Transmitter
Application Size: Depends on Logic Panel (W973)
Dimensions, Approximate: 4 5/8 in. high x 2 13/16 in. wide x 1 1/4 in. deep (118 mm high x 71 mm wide x 32 mm deep)
Output Type: Voltage Ramp
Voltage: 20 Vdc from W973 panel
Setpoint Temperature Range: 55 F to 85 F (13 C to 29 C) Shipping Temperature Range: -40 F to +150 F (-40 C to +65 C)
T7067A Thermostat and T7067B Transmitter control space temperature when used with W973 Logic Panel.
•Separate heat and cool adjustable set point levers provide adjustable deadband from 3 F to 30 F (2 C to 17 C)
•Separate 1-16 Vdc voltage ramps provide independent heating and cooling signals to W973 Single Zone Logic Panel
•Two light-emitting diodes (LEDs) under T7067 cover for system checkout
•C7046A Discharge Air Sensor provides temperature anticipation
•One T7067 can control up to 6 W973 panels in parallel
•Mount on standard 2 x 4 in. vertical outlet box or on a non-conductive flat surface
•All models include wiring plate and locking cover
Approvals
ASHRAE Guidelines: Meets ASHRAE 90-75
Department of Defense Guidelines: Meets
Accessories:
S963D1001-2 Potentiometers that simulate the ramp signals of a T7067 Thermostat
|
|
|
|
|
|
Control |
|
|
|
Product Number |
System |
Compatible with |
Description |
Comments |
|
|
|
|
|
T7067A1008/U |
W973 single |
Q667 subbase, |
Solid State Thermostat designed to be used with |
Integral temperature sensor without thermometer; |
|
zone |
W973 Logic Panel |
the W973 logic panel to control the operation of |
Number of stages of heating and cooling depends |
|
|
|
single zone packaged air conditioning equipment |
on the chosen Logic Panel |
|
|
|
|
|
T7067B1006/U |
W973 single |
Q667 subbase, |
Transmitter designed for use with a T7047C1025 |
Must order T7047C,G remote temperature sensor or |
|
zone |
W973 Logic Panel |
or T7022A1010 remote temperature sensor |
T7022A remote duct temperature sensor separately |
|
|
|
|
|
334 |
customer.honeywell.com |
70-6910 |