T7022A
Remote Temperature Sensor
INSTALLATION INSTRUCTIONS
APPLICATION
The T7022 Remote Temperature Sensor is a nonadjustable thermistor sensor. Its primary use is with the
T7300 Programmable Commercial Thermostat (only in
return air) to control heating or cooling equipment.
NOTE: The T7022 can also be used with a T7100F,
provided the proper Q7100 subbase√one
capable of handling more than one stage of
heat√is used.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Erratic System Operation Hazard.
Failure to follow proper wiring practices can
introduce disruptive electrical interference
(noise).
Keep wiring at least one foot away from large
inductive loads such as motors line starters,
lighting ballasts, and large power distribution
panels.
Shielded cable is required in installations where
these guidelines cannot be met.
Ground shield only to grounded controller case.
CAUTION
Electrical Shock or Equipment Damage
Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
All wiring must agree with applicable codes,
ordinances and regulations.
Wiring (Fig. 1)
Wiring for the T7022 Remote Temperature Sensor can
be run with class 2 wire in accordance with the National
Electrical Codes. Conduit and/or shielding are not
necessary for satisfactory operation, but conduit may be
required by local codes or practices.
Q7300
T T
T7022
M1784
Fig. 1. Typical wiring diagram.
Location
The T7022 Thermostat must be mounted in the return-air
flow in ducts (see Fig. 2 and 3) or light troffers (see Fig. 4
and 5). All mounting locations must be where the sensor
is not affected by heat from the lights or other sources.
Mounting
The T7022 can be mounted in a duct with the furnished
bracket, or in a light troffer as shown in Fig. 4 and 5 with
two rubber grommets (not supplied) if proper spacing
is available. Mounting can be directly in the return-air
passage or in an air-sampling box. The rubber grommets
can be used to wedge the sensor in slot openings of
approximately 3/8 in. to 1/2 in. wide.
When using the mounting bracket, the maximum duct
insertion length for the T7022 is approximately 2-3/4 in.
NOTE: A piece of 3/8 in. diameter conduit can be
used to extend the sensor further inside a duct
(see Fig. 3). The use of such an extension can
increase the maximum insertion length to
approximately 9-1/2 in.
® U.S. Registered Trademark
Copyright © 2001 Honeywell • All Rights Reserved
60- 0247- 2
T7022A REMOTE TEMPERATURE SENSOR
Duct Mounting
RILL 5/16 INCH
OLE FOR SENSOR
DRILL 3/8 INCH
OLE IF EXTENSION
UBE IS USED).
RETURN
AIR DUC
BOX MOUNTING
SHEET METAL
SCREWS
OPTIONAL
EXTENSION TUBE
MOUNTING
BRACKET
BRACKET
SETSCREW
Fig. 2. Duct mounting with mounting bracket.
M17818
OUTLET BOX
Fig. 3. Duct or light troffer mounting
where wiring must be run in conduit.
M17819
Light Troffer Mounting
NOTE: Fig. 4 and 5 illustrate T7022 mounting for individual zone control. This type of application requires the use of
an M7034 Electronic Modutrol® Motor. In applications with an M7034, an S963 can be used to provide remote
setpoint adjustment, if desired.
DUCT
AIR
CHAMBER
T7022
M1782
Fig. 4. Cross section of light troffer showing a typical
mounting location of the side of the light troffer.
T7022
Fig. 5. Cross section of light troffer showing a typical
mounting location at the end of the light troffer.
SHIELD
TO
DUCT OR
PLENUM
M1782
CHECKOUT
Move set point above and below room temperature to
make sure controlled equipment operates properly. See
other system component instructions for additional
checkout procedures.
Home and Building Control Home and Building Control
Honeywell Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario
M1V 4Z9
60-0247√2 B.B. Rev. 2-01
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
www.honeywell.com/building/components